MWS TS-010V Datasheet

Project Catalog # Type
Prepared by Notes Date
MWS
TS-010V
T SO Cord with 0-10V Dimming Modular Wiring System
Typical Applications
Oce • Education • Healthcare • Hospitality • Retail • Industrial
• Manufacturing • Sports Venues
Interactive Menu
Product Certication
Order Information page 2
Product Specications page 2
• System View page 2
• Product Warranty
Top Product Features
• UL Listed under Standard 183 for make or break under load
• Meets requirements of Article 604 of the National Electrical Code
• Rated at 20 amperes with full-size ground wire
Powers xture as it allows circuit to feed through to next luminaire
Dimensional and Mounting Details
Side
Right
5-5/16"
[136mm]
To p
2-1/4"
[57mm]
additional product diagrams
PS519406EN page 1
May 14, 2020 3:44 PM
Order Information
Extender Cabl
SAMPLE ORDER NUMBER: 12TS10/2G03-010V
TS-010V
Voltage
Voltage Component Conductors and Size Cable Length (Feet) Dimming
12=120V 20=208V 24=240V 27=277V 34=347V 48=480V
Component Conductors and Size Cable Length (Feet) Dimming
TS=T SO Cord 10/2G=#10, 2 Conductors Plus Ground
12/2G=#12, 2 Conductors Plus Ground
03=3' 6=6' 11=11' 15=15'
010V=0-10V Dimming
Product Specications
• UL Listed under Standard 183 for make or break under load
• MWS components assembled with 12 AWG/10 AWG conductors rated at 20 amperes with full size ground wire
• 0-10V Dimming wires 16AWG
• Galvanized steel exterior with integral keying for voltage and amperage
Powers xture and allows circuit to feed through to next luminaire
• Pre-stripped 16AWG SO Cord for easy termination
at xture
• All unused outlets require a MWS dust cover. MWS ST, SP, SD, CT and TC are shipped with one dust cover attached
System View (not to scale)
e
T SO Cord
Extender Cable
T SO Cord (TS)
Feeds power to fixture and allows circuits to be carried through to other fixture. Provided with 2 conductor 16 gauge SO Cord. For use with HID and industrial fluorescents.
Typical MWS Wiring System Application shown utilizing T SO Cord (TS).
Consult MWS Installation, Application and Specification Manual for additional comprehensive System information.
Shipping Data
T SO Cord
Extender CableExtender Cable
Cord
Length Unit Wt.
Qty./Carton
3' 1.1 lbs. N/A
6' 1.7 lbs. N/A
11' 2.7 lbs. N/A
15' N/A
MWS Autocad Drafting
Please reach out to your local representative for MWS layout design assistance.
Standard
All electrical boxes, conduit, connections and switches by others.
Install dust covers on unused open ends.
Scale is exaggerated on xtures and MWS
system applications.
Cooper Lighting Solutions
1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com
© 2020 Cooper Lighting Solutions All Rights Reserved.
Specifications and dimensions subject to change without notice.
PS519406EN page 2
May 14, 2020 3:44 PM