MEF EMC-FILTER 3-PHASE 1-STAGE WITH NEUTRAL
I:6A U:4x440 VAC snap on
Current: 6 A DIN-rail mountable with neutral Attenuation curves on request.
Illustration
The information in this broch ure h as b een compiled with th e u tmost ca re. Liab ility for the correctn ess co mplete ness a nd topica lity of t he in formation is restricted to gross n eglige nce. Version : 10 /20
Approvals
General data
Produ ct may d iffer fro m Image
Climatic category 25/085/21 (EN 60068-1)
Test isolatio n voltage
2.7 kV (L - N), 2 s; 2.1 kV (L - L), 2 s (EN 60939-2)
Connection Screw connection, touch protected
INTERNET DATA SHEET for Article Number 10511
The information in this broch ure h as b een compiled with th e u tmost ca re. Liab ility for the correctn ess co mplete ness a nd topica lity of t he in formation is restricted to gross n eglige nce. Version : 10 /20
Mounting method DIN-rail mountable TH35 (EN 60715)
Dimensions H×W×D 107×65×39 mm
Technical Data
Operating voltage max. 3× 440 V AC
Operating frequency 50...60 Hz
Overload current 18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour)
Consumption max. 3 mA (250 V AC)
Connection cross section 0.2...6 mm² single core (AWG 24...9); 0.2...4 mm² multiple core (AWG 24...11)
Description
Functional description
The 3-phase and one-stage EMC filters MEF 3/1 are used in the ran ge 0.1...30 MHz and dampen interferences found in cabl es from the mains, supply units and control systems. They are suitable for TN-S, TN-C-S, and TT networks. The best results are obtained
Commercial data
country of origin IT
customs tariff numbe r 85363010
EAN 4048879029285
eClass 27130806
Packaging unit 1
INTERNET DATA SHEET for Article Number 10511