Wiring Instructions for
No Connection
Terminal location may differ from shown.
Alternator
Battery Cable
Battery
Starter
Motor
Voltmeter
(rear view†)
To Electrical System
Lamp
ON–OFF Switch
Light Switch
VM-94137N
Revised 09-96
Section 65
(00-02-0209)
®
VM-12 and VM-24 Voltmeter
1. Disconnect battery ground cable.
2. Connect an 18 AWG (1.0 mm2) wire, minimum, from
the ground terminal on the back of the voltmeter to ground (see wiring diagram). For an above ground system connect the wire from the “–” voltmeter to the negative (–) terminal on the battery
3. Connect an 18 AWG (1.0 mm2) wire, minimum,
from the “IGN” terminal on the ignition switch to the “+” terminal on back of the voltmeter.
4. Connect an 18 AWG (1.0 mm2) wire, minimum,
from the instrument panel’s lighting circuit to the illuminating lamp on back of the voltmeter (if applicable).
5. Reconnect battery ground cable.
terminal on the
.
B
Frank W. Murphy Manufacturer
P.O. Box 470248; Tulsa, Oklahoma 74147; USA
tel. (918) 627-3550 fax (918) 664-6146 e-mail fwmurphy@ionet.net
Frank W. Murphy Southern Division
P.O. Box 1819; Rosenberg, Texas 77471; USA tel. (713) 342-0297 fax (713) 341-6006
Frank W. Murphy, Ltd.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
tel. +44 1722 410055 fax +44 1722 410088 tlx 477088 e-mail sales@fwmurphy.co.uk
Frank W. Murphy Pte., Ltd.
26 Siglap Drive; Republic of Singapore 456153 tel. +65 241-3166 fax +65 241-8382
Murphek Pty., Ltd.
1620 Hume Highway; Campbellfield, Vic 3061; Australia tel. +61 3 9358-5555 fax +61 3 9358-5556
Murphy de México, S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 tel. +52-48-206264 fax +52-48-206336
Murphy Switch of California
P.O. Box 900788; Palmdale, California 93590; USA
tel. (805) 272-4700 fax (805) 947-7570 e-mail sales@murphyswitch.com
Frank W. Murphy France
tel. +33 1 30 762626 fax +33 1 30 763989
Loading...