Murphy TDXM User Manual

Description
The innovative new TDXM now gives you a unique con­figurable temperature scanner/pyrometer with a built-in power supply. A new design features a 7-character, 7-seg­ment Liquid Crystal Display window with 1/2 inch (13 mm), easy-to-read characters. Also located on the face­plate are membrane keys for easy configuring.
Highly reliable and versatile, the TDXM accepts up to 24 type “J” or “K” grounded or ungrounded
*
thermo­couples. Each channel has three (3) adjustable set­points SP1, SP2 and SP3. The SP1, SP2 and SP3 Setpoints correspond to the SP1, SP2 and SP3 outputs. Additionally it has the selectable feature to monitor and alarm or shutdown on deviation from an average from up to two groups of temperatures (GRP/DEV; deviation from average). One group could be exhaust temperatures and another group could be bearing temperatures.
The TDXM is capable of communicating with controllers, PLC’s, computers or SCADA (Supervisory Control & Data Acquisition) systems by a built-in RS485 serial com­munications port. The TDXM-DC is available for 10 - 32 VDC systems.
User Interface (Faceplate)
The User Interface includes a numeric LCD display and a 5-button membrane keypad for readout and channel configuration. Thermocouple types can be selected and setpoints entered through a series of setup menus, see “Setup Menus” section.
Thermocouple Types
Each of the 24 channels on the TDXM can be con­figured as either “J” or “K” type thermocouples
and temperature units can be selected as °F or °C readout for each channel. Unused channels can be set to “Ignore” and will not be seen in the display and will not cause fault trips.
Control Options
Each TDXM model features three outputs: 2 Field Effect Transistor (FET) outputs and 1 Form-C Relay output. Each channel has 3 setpoints, one for each of the outputs. This allows for greater system flexibility by grouping sets of channels through one output.
Setpoint History
The TDXM stores the last setpoint trip for each output in non-volatile memory. For instance, if SP1of channel 1 was the last SP1 tripped, the LCD display will read: SP1 1 when the Setpoint History is accessed for SP1.
Sensor Inputs and Terminals
The TDXM accepts up to 24, either “J” or “K” type grounded or ungrounded
*
thermocouples using 24 pairs of screw type connections. Each pair has a jumper from the factory. Any tripped setpoint is detected within 2 seconds after the set point is exceeded.
RS485 Serial Port
The RS485 serial port (MODBUS
®
RTU slave) on the back of the module is provided for communicating with micro-controllers, PC’s, PLC’s and SCADAsys­tems (see “Typical Wiring Diagrams”). It is recom­mended that a termination
resistor (customer supplied) be used when the TDXM is the last device connected in a daisy-chain configuration. The Baud rate, number
of stop bits, and slave node number can be set using the keypad. Communication is half-duplex. Modbus
®
RTU function codes 3 and 6 are supported.
Specifications
Power Input (Operating Voltages): 10- 32VDC, 750 mW max.
Sensor Inputs: Up to 24 type “J” or “K” grounded or
ungrounded
*
thermocouples.
Outputs: Two (2) Outputs 0.5 A, 350 VDC, FET-sink
to ground to trip. One (1) Form “C” Solid State Relay Output 0.125 A, 350 VDC/240 VAC.
NOTE: The form “C” relay output is de-energized for a trip condition. The NC terminal is closed and the NO terminal is open for trip.
Communications: RS485 Serial Port, MODBUS
®
RTU slave.
Operating, Storage, and Display Temperature: -40 to
85°C (-40 to 185F).
Sensor Scan Rate: Scans all channels in 2 seconds. Range: Type K: 0 - 1999°F (0 - 1093°C); Type J: 0 -
1538°F (0 - 837°C).
Display Type: Custom 7-segment, 7-character, back-
lit type with temperature units indication and set­point trip indication.
Accuracy: Cold junction: Better than ±0.5°C (1.0°F).
Type “J” or “K”: ±1°C (2°F); 38 - 1093°C (100 - 1999°F).
Cold Junction Compensation: -40 to 85°C (-40 to 185F). Open Thermocouple Detection: Drives channel reading high.
TDXM-00064B
Revised 06-06
Catalog Section 10
Temperature Scanner/Pyrometer
TDXM Model
Scans Up To 24 Channels
Three (3) Adjustable Trip Points Per Channel
Accepts Any Combination of “J” or “K” Type Grounded or Ungrounded Thermocouples
2 Separate Groups with Deviation Trip Functions Selectable
Powered By 10 to 32 VDC Systems
RS485 Serial Communications Port
Uses MConfigTMConfiguration and Monitoring Software
CSA Certified for Use in Class I, Division 2, Groups “C & D” Hazardous Locations
*
We recommend the use of ungrounded thermocouples. Errors in readings with grounded thermocouples can be the result of differences in grounding between different devices.
MODBUS®is a registered trademark of AEG Schneider
Automation Inc.
C US
TDXM Module Dimensions
Front
5.50 in.
(140 mm)
0.156 in. (4 mm) dia. 4 places
5.50 in. (140 mm)
Panel
Mounting
Hole
Keps Nut
Lock washer
Screw
3-3/8 in. (86 mm) minimum mounting clearence.
NOTE: Ground stud connection is only for single wire to equipment ground. Do NOT use for more than one wire.
49/64 in. (19 mm)
5-1/4 in.
(133 mm)
TDXM
6.0 in.
(152.3 mm)
3.0 in.
(76 mm)
3.0 in.
(76 mm)
6.0 in. (152.3 mm)
Mounting Hole
SP
HISTORY
CHANNEL
SP1 - 3
TC TYPE/UNITS (SETUP 1) 0 = IGNORE 1 = TYPE J TC. DEG F 2 = TYPE K TC. DEG F 3 = TYPE J TC. DEG C 4 = TYPE K TC. DEG C
RTU/BAUD (SETUP 7) BAUD SETUP 0 = 9600 (N, 8, 1) 1 = 19.2K (N, 8, 1) 2 = 38.4K (N, 8, 1) 3 = 9600 (N, 8, 2) 4 = 19.2K (N, 8, 2) 5 = 38.4K (N, 8, 2)
SETUP NUMBERS 0 = EXIT 1 = TC TYPE UNIT 2 = OFFSET 3 = SETPOINTS 4 = GRP/DEV A (SP1 OUT) GRP/DEV B (SP2 OUT) 5 = CH SCAN DELAY 6 = CJ DISPLAY 7 = RTU/BAUD 8 = UNIT ID
CJ DISPLAY (SETUP 6) 0 = DISABLE 1 = ENABLE, DEG F 2 = ENABLE, DEG C
TDXM-DC
POWER INPUT: 10-32 VDC
OUTPUT TYPE AND RATING:
SP1: FET, OPEN DRAIN, 350 VDC, 0.5A MAX. SP2: FET, OPEN DRAIN, 350 VDC, 0.5A MAX.
SP3: SSR, FORM C,
350 VDC/240 VAC, 0.12A MAX.
NON-INCENDIVE FIELD
WIRING CONNECTIONS
FOR USE IN CLASS I
DIV. 2, GROUPS C & D
LOCATIONS WHEN INSTALLED PER
MURPHY DRAWING 10-08-0006
THERMOCOUPLE INPUTS
(WHITE / YELLOW)
SCROLL
ENTER
®
V
OLT
AG
E:
10V
DCM
I
N
,32V
DCM
A
X
,500mW,
NE
GG
ND
,
C
S
A
CE
R
T
I
F
I
ED
F
O
R
CL
I,
D
IV2, G
RPS
C
&
D
W
H
EN
I
N
S
T
A
LLED
P
E
R
M
U
RP
HY
D
R
AWI
N
G10
-
0
8
-
000
6
X
M
U
RP
HY
X
M
U
RP
HY
6-1/2 in. (165 mm)
6-1/2 in.
(165 mm)
(SETUP) (SETUP)
C US
Head/Module
TDXM-DC
: 24-channel model, 10-32 VDC powered.
TDXM-DC W/SP3 Latch
: Same as TDXM-DC but
with SP3 latch feature.
Configuration Software
MConfig
: TDXM configuration software available.
Replacement Parts
Plug, kit, TDXM:
Terminal Plug replacement kit-P/N
10-00-7848.
Shipping Weights and Dimensions
Shipping Weight (all Models): 3 lb. (1.36 kg) approximately. Shipping Dimensions (all Models): 5-1/2 x 9 x 9-1/2 in.
(140 x 229 x 241 mm) approximately.
Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
Side
Back
How to Order Your TDXM
Specify the following part number:
For Outdoor Use, the TDXM should be mounted in a weatherproof enclosure
TDXM-00064B page 2 of 2
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time. MURPHY, the Murphy logo are registered and/or common law trademarks of Murphy Industries, Inc. This document, including textual matter and illustrations, is copyright protected by Murphy Industries, Inc., with all rights reserved. (c) 2006 Murphy Industries, Inc.