Murphy TDX6 User Manual

TDX-9106B
Revised 11-02
Catalog Section 10
(00-02-0049)
Temperature Scanner/Pyrometer SWICHGAGE
®
Scans 6 Channels
Adjustable Trip Points
Powered by CD Ignition,
24 VDC, or 120 VAC
Rated for Class I, Division 2,
Group D Hazardous Areas
Start-up Time Delay
Easy to Read Digital Display
*
When used with approved ignition. Contact Murphy for details.
**
When used with
power
requirements
described below.
Description
The TDX6 is an advanced design 6-point temperature scanner and pyrometer. It continually scans up to six thermocouples and sequentially displays the thermocouple number and its reading. Each sensor input has a field settable trip point for alarm, shut­down or control. A read/scan selector allows the operator to set and view each trip point. With the selector in the scan mode, a “thermocouple read” push button provides a means to manually toggle through the six channels and to lock in on a specific chan­nel. Normal scanning will resume approximately three seconds after releasing the push button. All trip points are continually armed and active during the scanning process.
Type “J” or “K”, grounded
or ungrounded thermocouples are
accommodated. Other types are available upon request. The TDX6 can interface with other Murphy SELECTRONIC
®
TATTLETALE®annunciators and Micro-controllers. It is rated for Class I, Division 2, Group D, hazardous areas*and is available for operation from CD ignition, 120 VAC, or 24 VDC
.
Applications
Gas Compressor Process Temperatures
Suction/Discharge Temp.
Generators
Engine/Compressor Jacket Pumps
Water Temperature
Engine Exhaust Temperature
Features
Monitors six (6) input sensors
Accepts type “J” or “K” thermocouples grounded†or ungrounded
Field adjustable trip points
LCD display in either °F or °C (specify)
One thermocouple maybe selected for continuous display
CD ignition, 24 VDC, or 120 VAC powered
No special training or programming required
Scans all 6 sensors in 30 seconds
Specifications
Power Requirements (Operating Voltages): 120 VAC or
80-250 VDC, CD ignition or 24 VDC.
Outputs:
Models TDX6-A and TDX6-C:
Six (6) isolated Silicon Controlled Rectifier (S.C.R.) outputs; 0.5 A @ 250 VDC; switches on (applies ground) above trip point and switches off (removes ground) when power is switched off.
Models TDX6-B and TDX6-D:
Six (6) isolated Field-Effect Transistor (F.E.T.) outputs; 0.1 A @ 250 VDC; switches on (applies ground) above trip point and switches off (removes ground) below trip point.
Operating Temperature: -4 to 158°F (-20 to 70°C).
Storage Temperature: -40 to 300°F (-40 to 150°C).
Case: ABS 1/4 DIN (90 x 90 mm).
Scanning Speed: Complete scan in 30 seconds.
Reset Differential: F.E.T. models:
Decreases 3 Degrees (°F or
°C)
. S.C.R. models:
Turn input power off to reset.
Display Update Time: Updates temperature every 0.3 seconds.
Start-up Time Delay: Unit is locked out for 10 seconds after
ignition voltage is sensed.
Ambient Cold Junction Compensation Range:
2°F from 32°F to 122°F (1°C from 0°C to 50°C).
Measurement Range: Monitor Range 0-1999°F or °C (specify °F
or °C in part number).
Accuracy:
With J-type thermocouple:
from 50-150°F (10-66°C) +3°F (+2°C),
from 150-1200°F (66-649°C) ±1.0% of reading.
With K-type thermocouple:
from 400-2000°F (204-1076°C)
±1.0% of reading.
Trip Point Accuracy: ±3°F (±2°C) of reading.
Trip Point Adjustment Range: 0-1999 Degrees.
Open Thermocouple Input: A number 1 appears in the display
to the right of the channel number and the trip point operates.
Approved
**
Approved
*
Model TDX6
Using grounded thermocouples introduces the risk of odd currents or voltages
being imposed on the thermocouple signal which can affect the accuracy of the reading. This is an inherent problem of grounded thermocouples, the reason why we prefer ungrounded thermocouples.
Easy to Read
Digital Display
Thermocouple
Read
Trip Point
Read/Scan
Trip Point
Adjustment
TDX-9106B page 2 of 2
How to Order
To order the TDX6 use the part number designation diagram below.
Display
F = Fahrenheit C = Celsius
Models
TDX6 = Square hole mounting TDXF6 = Round hole mounting
Power Supply/Output
A = CD ignition, 80-250 VDC Positive or Negative Ground or
120 VAC 50-60 Hz Inputs—S.C.R. Outputs.
B = CD ignition, 80-250 VDC Positive or Negative Ground
or 120 VAC 50-60 Hz Inputs—F.E.T. Pulsed Outputs.
††
C = 24 VDC Inputs—S.C.R. Outputs.
D = 24 VDC Inputs—F.E.T. Pulsed Outputs.
††
For use with electromechanical TATTLETALE
®
annunciators.
††
For use with SELECTRONIC
®
or similar solid-state annunciators.
Thermocouple Type
J = Type J K = Type K
Dimensions Typical Wiring Diagram
TDX6 Interface Capabilities
Model
Power Source Rating
LCDT CD Ign., 120 VAC, 12/24 VDC Cl.I, Div.1, Gr.D, Haz. areas*
S1501 120 VAC or 12/24 VDC Cl.I, Div.1, Gr.D, Haz. areas*
MARK II CD Ignition, pos. or neg. grnd Cl.I, Div.2, Gr.D, Haz. areas*
TATTLETALE
®
CD Ign., 120 VAC, 12/24 VDC Non-Hazardous areas
PLC’s, various non-Murphy annunciators–contact factory.
*Note: An isolation barrier is needed between the TDX6 and an Annunciator rated
for Class I, Division 1, Group D, Hazardous Areas.
**Note: When used with approved ignition. Contact Murphy for details.
Shipping Weight: 2 lb. (0.91 kg).
Shipping Dimensions: 5-1/2 x 9 x 6 in. (140 x 229 x 152 mm).
TDX6
– A – F – J
Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA +1 281 633 4500 fax +1 281 633 4588
e-mail sales@fwmurphy.com
MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 +52 444 8206264 fax +52 444 8206336 Villahermosa Office +52 993 3162117 e-mail ventas@murphymex.com.mx www.murphymex.com.mx
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. +44 1722 410055 fax +44 1722 410088 e-mail sales@fwmurphy.co.uk www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West Palmdale, California 93551-1442; USA +1 661 272 4700 fax +1 661 947 7570 e-mail sales@murphyswitch.com www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
MACQUARRIE CORPORATION
1620 Hume Highway Campbellfield, Vic 3061; Australia +61 3 9358 5555 fax +61 3 9358 5558
e-mail murphy@macquarrie.com.au
FW Murphy
P.O. Box 470248 Tulsa, Oklahoma 74147 USA +1 918 317 4100
fax +1 918 317 4266 e-mail sales@fwmurphy.com
www.fwmurphy.com
R
E
G
I
S
T
E
R
E
D
USA–ISO 9001:2000 FM 28221
UK–ISO 9001:2000 FM 29422
Printed in U.S.A. 0591127
Side View
4-5/8 in.
(117 mm)
Mounting Clamp
4-3/8 in.
(111 mm)
6-3/4 in.
(171 mm)
clearance for plug
Square Hole Mounting
3-9/16 in.
(90 mm)
3-9/16 in.
(90 mm)
3-3/4 in. (95 mm)
Round Hole Mounting (TDXF6)
Mounting Hole 4-3/4 in. (121 mm) diameter
120
1/4 in. (6 mm) dia. holes (3 places)
Back View
3-1/2 in. (89 mm)
3-3/4 in. (95 mm)
120
120
-
-
-
-
-
-
TC 1
TC 2
TC 3
TC 4
TC 5
TC 6
3
PWR
INPUT
TDX6
+
-
TP 1 COM TP 2
TP 3 COM
TP 4
TP 5 COM
TP 6 COM
5
Load
+
­+ +
-
TATTLETALE etc. + +
­+
-
+
MARK II,
S1400,
INPUT
1
2
TC 1
TC 2
TC 3
TC 4
TC 5
TC 6
NOTES:
1
Remove input jumper when the thermocouple is
POWER INPUT
JUMPER
+
+
+
+
+
+
connected to input.
2
Thermocouple Input
3
Power input 120 VAC, 80-250 VDC, CD ignition or 24 VDC, positive or negative ground.
4
Interfaced components must meet area classification requirements.
5
When using the TDX6 with inductive loads, we recommend installing a suppression diode across all coils.
4
LCDT,
®