Murphy Selectronic Micro-Controller 1500 Specifications

S15-95063B
®
FRANK W.
MFR.
DISCONTINUED
Effective 10-95
Catalog Section 50
(00-02-0119)
SELECTRONIC®Micro-Controller
Series 1500
Alarm/Shutdown for 32 N.O. and/or N.C. Sensors
Operating Sequence Selection
Completely Field Adjustable
Selectable Sensor Lockouts Class A, B, C or P
Built-In Tachometer/Overspeed Function
Clearly Visible Alphanumeric Display
RS232 Communications Capability
Two Start/Run Timers
®
Description
The Series 1500 is a microprocessor based alarm and/or shutdown system. It tells in alphanumeric characters which protective device has signaled an alarm or caused equipment shutdown. Basic config­uration for each application is programmed at Murphy and can be configured in the field. Information is called up and adjustments are made on a six-button keypad on the face of the unit.
The S1500 system consists of a monitor, a sensor input terminal strip (rail mount type), a 36 inch (914 mm) flat ribbon cable for connecting the ter­minal strip to the monitor, and a power supply which includes the control Inputs/Outputs and intrinsically safe barrier with cable assembly.
Four SPDT relays are available for alarm and/or shutdown functions. A built-in RS232 communica­tion port allows interfacing with IBM patible computer systems and micro-controllers.
The S1500 is powered from a 120 VAC or 12 or 24 VDC, Class I, Division 1 explosion-proof power supply. The monitor is rated intrinsically safe.
®
PC and com-
Intrinsically Safe Barrier
Murphy’s LCDT-ISB intrinsically safe barrier for hazardous applications, is designed for use with two Normally Open sensors. This external barrier accepts non-intrinsically safe, normally open inputs and converts them to intrinsically safe outputs.
Applications
The Series 1500 can be configured to monitor applications such as:■Generators
Air compressors
Gas compressors■Water treatment
Fire pumps
Sewage pumps
Features
32 sensor inputs (N.O. and/or N.C.) for alarm or shutdown.
Six-button keypad for easy operation and adjustments.
RS232 output for interface with computers and micro-controllers (modem required).
Engine Automatic.
Two Start-Run Timers.
Four Control Relay Outputs.
Pre/Postlube Time Delay.
Typical standard program or customized*.
*
Murphy provides various standard preprogrammed configurations. If a customer sensor input configura­tion is needed, Murphy will custom program your unit at the time you order. Call Murphy for quote.
Warranty
A two-year limited warranty on materials and workmanship is given with this Murphy product. Details are available on request and are packed with each unit.
Elapsed Time Meter
Process control
Burner systems
Natural gas refueling
NRTL/C
Approved for Class I,
Division 1 Groups C & D
How to Order
To order the Complete S1500 System: Monitor, Terminal Block, Cable Assembly and Power Supply), just specify the part number:
S1500
To order individual components and accessories specify model number:
Specify: To Order:
S1500H S1500TB32 S1500CA36 S1500PS LCDT-ISB
Shipping Weights and Dimensions
Complete S1500 System: 28 lb. [12.7 kg.]; 20 x
S1500 H: 2 lb. (0.907 kg.); 6 x 6 x 6 in. (152 x
S1500 TB32: 2 lb. (0.907 kg.); 12 x 7 x 4 in.
S1500CA36: 2 lb. (0.907 kg.); 6 x 6 x 6 in.
S1500PS: 22 lb. (9.98 kg.); 17 x 10 x 9-
LCDT-ISB: 3 lb. (1.3 kg.); 9 x 10 x 6 in. (229 x
*
For Normally Closed sensor the use an intrinsically
safe (approved) barrier is required.
Monitor (Head) only Terminal Block only Cable Assembly only Power Supply only Intrinsically Safe Barrier (for Normally Open Sensors*)
1
14 x 12-
152 x 152 mm).
(305 x 178 x 102 mm).
( 152 x 152 x 152 mm).
(431 x 254 x 248 mm).
254 x 152 mm).
/2 in. [508 x 356 x 318 mm]).
3
/4 in.
6 in.
(152 mm)
10-1/2 in. (267 mm)
8-3/4 in.
(222 mm)
15 in. (381 mm) clearance for conduit
4-1/2 in.
(114 mm)
3 in.
(76 mm)
TOP VIEW
SIDE VIEW
9 in.
(229 mm)
3/4 NPT
conduit fittings
(2) places
1/2 NPT conduit fitting
3-1/2 in. (89 mm)
3-3/4 in. (95 mm)
3-1/2 in. (89 mm)
4-3/8 in.
(111 mm)
4-5/8 in.
(117 mm)
3-3/4 in.
(95 mm)
BACK VIEW
SIDE VIEW
3-9/16 in.
(90 mm)
3-9/16 in.
(90 mm)
MOUNTING HOLE
6-3/4 in.
(171 mm)
clearance for plug
Mounting
Clamp
7 in.
(178 mm)
3-1/32 in.
(77 mm)
FRONT VIEW
Specifications
DISCONTINUED
Series 1500 System
Power Consumption: 120 VAC (8 watts), 12 or 24 VDC (2.5 or 7.2 watts).
®
Sensor Inputs: 32 N.O. and/or N.C., such as Murphy SWICHGAGE
instru­ments. Inputs are factory-programmed as a Class A, B, C or P for shutdown, alarm, or control function (specify).
Opto-Isolated Input: 12-120 VDC or 24-120 VAC, the opto-isolated input is
typically used as a run input, magnetic pickup and ignition.
Outputs: 4-SPDT relays, 4 A, 1/20 HP, 125/250 VAC/3A, 30 VDC.
NOTE: An approved isolation barrier must be used between the sensor switch and input terminals if the sensor output comes from any energy stor­ing device such as a relay or transistor. (See LCDT-ISB
Barrier, at right).
Tachometer Sensing: From either CD Ignition or Magnetic Pickup. Operating Temperatures: 32 to 122°F (0 to 50°C). Storage Temperatures: -4 to 158°F (-20 to 70°C). Case: ABS plastic, 1/4 DIN (90 x 90 mm). Interface Output: RS232 communication port. Alphanumeric Display: 2 lines, each line with 16 characters (32 total). Laboratory Approvals: CSA and NRTL/C for Cl. I, Div. 1, Grps. C & D. Power Supply Enclosure: Explosion-proof, Class I, Division 1. Intrinsically
safe barrier built into power supply, 120 VAC and 12 or 24 VDC power supply barrier with dry contact relay functions such as:
Timers: 12 adjustable timers for:
Two Start-up lockouts•Test
Postlube
Crank
Process delay
Load delay
Rest
Ignition ground
Time Delay: Delay before ignition ground or electric motor stop, for
up to 59 seconds.
Terminal Block: Rail mount DIN type; 32 positions (screw type). Backup Battery: Rechargeable during normal operation.
Provides up to 5 hours backup time.
Dimensions
Prelube
Idle
Run delay
LCDT-ISB Intrisically Safe Barrier
External barrier explosion-proof design for hazardous locations, according to NEC requirements for Class 1, Division 1 Group D areas. The LCDT-ISB accepts Normally Open sensor inputs (2 inputs per barrier). For Normally
Closed sensors, an intrinsically safe (approved) barrier is required.
Module, Terminal Block, Power Supply
Fuel valve
Shutdown
Control (Pre/Postlube)
Engine Cranking
Alarm
Ignition
Compressor Loading
:
Terminal Block
Module (Head)
Power Supply
Relays, Timers, and Sensor Input Class
DISCONTINUED
Ordering Your Configuration
Use the listings below to specify sensor input Class, Function and Nomenclature; the S1500 sensor inputs are factory-configured as follows:
Class A: Armed at all times for alarm or shutdown (specify). Class P: Locked out by the Compressor Load lockout timer. Class B1: Locked out by first lockout timer (First Start/Run timer). ESD: Overrides the Test lockout timer (for Remote/Emergency Stop input). Class B2: Locked out by second lockout timer (Second Start/Run timer). SD:S1500 System Shutdown Function. Class C: Armed after fault condition has been cleared for 2 seconds. AL:Alarm Relay Function (no shutdown).
Sensor Input Specify Class Specify Function Default Nomenclature User Specified Nomenclature
Example: Class B2 SD Compressor Oil Pressure Compressor #1 Oil Pressure
Input 1 ____________ _________________ Compressor Oil Pressure ________________________ Input 2 ____________ _________________ Compressor Oil Level ________________________ Input 3 ____________ _________________ Lubrication No-Flow ________________________ Input 4 ____________ _________________ Low Suction Pressure ________________________ Input 5 ____________ _________________ Interstage Pressure #1 ________________________ Input 6 ____________ _________________ Interstage Pressure #2 ________________________ Input 7 ____________ _________________ Interstage Pressure #3 ________________________ Input 8 ____________ _________________ Discharge Pressure ________________________ Input 9 ____________ _________________ Discharge Temperature #1 ________________________ Input 10 ____________ _________________ Discharge Temperature #2 ________________________ Input 11 ____________ _________________ Discharge Temperature #3 ________________________ Input 12 ____________ _________________ Discharge Temperature #4 ________________________ Input 13 ____________ _________________ Suction Liquid Level ________________________ Input 14 ____________ _________________ Interstage Liquid Level #1 ________________________ Input 15 ____________ _________________ Interstage Liquid Level #2 ________________________ Input 16 ____________ _________________ Interstage Liquid Level #3 ________________________ Input 17 ____________ _________________ Inlet Scrubber Liquid Level ________________________ Input 18 ____________ _________________ Engine Oil Pressure ________________________ Input 19 ____________ _________________ Engine Oil Level ________________________ Input 20 ____________ _________________ Engine Oil Vibration ________________________ Input 21 ____________ _________________ Engine Jacket Water Temp. ________________________ Input 22 ____________ _________________ Engine Jacket Water Level ________________________ Input 23 ____________ _________________ Engine Jacket Water Press. ________________________ Input 24 ____________ _________________ Engine Vacuum Right Bank ________________________ Input 25 ____________ _________________ Engine Vacuum Left Bank ________________________ Input 26 ____________ _________________ Compressor Vibration ________________________ Input 27 ____________ _________________ Cooler Vibration ________________________ Input 28 ____________ _________________ Cooler Water Level ________________________ Input 29 ____________ _________________ Auxiliary Pump Shutdown ________________________ Input 30 ____________ _________________ Emergency Shutdown ________________________ Input 31 ____________ _________________ PLC Shutdown ________________________ Input 32 ____________ _________________ Prelube Permissive ________________________
Select your Relay Logic Mode (see page 4):
MODE No. ____________________
Select your Timing and range; (default values)
TACHOMETER
Pulses/Rev.: _____________________ (60) Crank Disconnect: _______________ (100)
Underspeed: ____________________ (150) Overspeed: _____________________ (400)
TIMERS
Prelube: ___________________ (0:30) Run Delay: _________________ (0:30) Class B1: ___________________ (1:00) Class B2: ___________________ (1:00) Load Delay: _________________ (1:00) Process Delay: _______________ (1:30) Idle/Cooldown: _______________(5:00)
Ignition Ground: _______________ (0:10) Postlube: ______________________ (0:30)
CRANKING
Attempts: ______________________ (5) Crank Period: __________________ (0:15) Rest Period: ____________________ (0:15)
Mode Chart
®
FRANK W.
MFR.
DISCONTINUED
Relay / Logic Mode Configurations Available
Logic Modes
Mode 01 Mode 02 Mode 03 Mode 04 Mode 05 Mode 06 Mode 07 Mode 08 Mode 09 Mode 10 Mode 11 Mode 12 Mode 13 Mode 14 Mode 15 Mode 16 Mode 17 Mode 18 Mode 19 Mode 20 Mode 21 Mode 22 Mode 23 Mode 24 Mode 25 Mode 26 Mode 27 Mode 28 Mode 29 Mode 30 Mode 31 Mode 32 Mode 33 Mode 34 Mode 35 Mode 36 Mode 37 Mode 38 Mode 39 Mode 40 Mode 41 Mode 42 Mode 43 Mode 44 Mode 45
Motor Ignition Cooler Load Shutdown Lube Crank Alarm Fuel
K4 K3 K2 K1 K4 K3 K2 K1 K4 K3 K2 K1 K4 K3 K1 K2 K4 K2 K3 K1 K4 K2 K3 K1 K4 K2 K1 K3 K4 K3 K2 K1 K4 K1 K3 K2 K4 K1 K3 K2 K4 K3 K2 K1 K4 K3 K2 K1 K4 K3 K2 K1 K4 K2 K3 K1 K4 K3 K2 K1 K4 K3 K2 K1 K4 K3 K2 K1 K4 K2 K3 K1
K4 K2 K3 K1 K4 K3 K2 K1 K4 K2 K1 K3
K4 K2 K1 K3 K4 K2 K1 K3 K4 K2 K1 K3
K4 K1 K2 K3
K4 K1 K2 K3
K4 K2 K1 K3
K4 K1 K2 K3 K4 K1 K2 K3 K4 K1 K2 K3 K4 K2 K1 K3 K4 K2 K1 K3 K4 K2 K1 K3 K4 K2 K1 K3 K4 K2 K1 K3
K4 K3 K1 K2 K4 K2 K1 K3 K4 K1 K3 K2 K4 K1 K3 K2 K4 K3 K2 K1 K4 K3 K2 K1 K4 K3 K2 K1 K4 K2 K3 K1 K4 K2 K3 K1 K4 K3 K2 K1
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Since 1939
Frank W. Murphy Manufacturer
P.O. Box 470248; Tulsa, Oklahoma 74147; USA
tel. (918) 627-3550 fax (918) 664-6146 e-mail fwmurphy@ionet.net
Frank W. Murphy Southern Division
P.O. Box 1819; Rosenberg, Texas 77471; USA
tel. (281) 342-0297 fax (281) 341-6006 e-mail murphysd@intertex.net
Printed in U.S.A.
Frank W. Murphy, Ltd.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
tel. +44 1722 410055 fax +44 1722 410088 tlx 477088 e-mail sales@fwmurphy.co.uk
Frank W. Murphy Pte., Ltd.
26 Siglap Drive; Republic of Singapore 456153
tel. +65 241-3166 fax +65 241-8382 e-mail fwmsales@fwmurphy.com.sg
Murphek Pty., Ltd.
1620 Hume Highway; Campbellfield, Vic 3061; Australia tel. +61 3 9358-5555 fax +61 3 9358-5558
Murphy de México, S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384
tel. +52-48-206264 fax +52-48-206336 e-mail murmexsl@infosel.net.mx
Murphy Switch of California
P.O. Box 900788; Palmdale, California 93590; USA
tel. (805) 272-4700 fax (805) 947-7570 e-mail sales@murphyswitch.com
Frank W. Murphy France
tel. +33 1 30 762626 fax +33 1 30 763989
Loading...