Murphy S14E-92229N User Manual

yellow
brown
green
orange
L1 (black)
120 VAC Supply
12/24 VDC Supply
SAFETY BARRIER
Customer Wiring
S1400-PS (120 VAC, 12 or 24 VDC Power Supply)
red clear
blue
Power and Control Cable (to module)
white
1 2
3 4
5 6 7 8
9
10 11
13 14 15 16 17 18
12
N (white)
DC(+) DC(-)
K-1 Lube
*
K-2 Ign.
*
K-3 F.V.
*
K-4 Alarm
*
1 2 3
4 5
6 7 8
LED lights L1= power “ON” L2= K1 L3= K2 L4= K3 L5= K4
L2 L3 L4 L5
L1
Ground or Green
(on 120 VAC)
FB barrier
Backup
Battery pack
*
K-1 thru K-4 are relay outputs, form “C” dry contacts 250 VAC @ 3A maximum.
**
Optically-isolated input (for run indication) 24-120 VAC maximum.
Output
**
clear= black and violet wires with clear shield.
+
lube
100
2W
S14RSA92
black
S
Ignition
red
Lube Ign. F.V. Alarm
F.V.
NC
NO
COM
Alarm
Contacts
ATTACHMENT
Information for Four Stage ENGINE Driven Compressor Applications
S14E-92229N
Attachment to Installation and Operation Manual for SELECTRONIC
TYPICAL WIRING DIAGRAM
®
Annunciator Series 1400
S14E-92229N
®
B
WARNING:
Perform the wiring operation with the power source OFF and the area made NON–HAZARDOUS. Voltage and current requirements should be
within the S1400 ratings. Use hard conduit with seal to protect the wiring from damage. DO NOT route sensor leads and power leads in the same conduit.
STANDARD PROGRAM
CHANNEL DISPLAY* CONDITION LOCKOUT CLASS FUNCTION
01 COMPRESSOR OIL PRESSURE (LOW) B SHUTDOWN 02 COMPRESSOR OIL LEVEL (LOW) A SHUTDOWN 03 LUBRICATION NO–FLOW B SHUTDOWN 04 LOW SUCTION PRESSURE (LOW/HIGH) B SHUTDOWN 05 INTERSTAGE PRESSURE #1 (LOW/HIGH) B SHUTDOWN 06 INTERSTAGE PRESSURE #2 (LOW/HIGH) B SHUTDOWN 07 INTERSTAGE PRESSURE #3 (LOW/HIGH) B SHUTDOWN 08 DISCHARGE PRESSURE (LOW/HIGH) B SHUTDOWN 09 ENGINE OVERSPEED A SHUTDOWN 10 DISCHARGE TEMPERATURE #1 (HIGH) A SHUTDOWN 11 DISCHARGE TEMPERATURE #2 (HIGH) A SHUTDOWN 12 DISCHARGE TEMPERATURE #3 (HIGH) A SHUTDOWN 13 DISCHARGE TEMPERATURE #4 (HIGH) A SHUTDOWN 14 SUCTION LIQUID LEVEL (HIGH) A SHUTDOWN 15 INTERSTAGE LIQUID LEVEL #1 (HIGH) A SHUTDOWN 16 INTERSTAGE LIQUID LEVEL #2 (HIGH) A SHUTDOWN 17 INTERSTAGE LIQUID LEVEL #3 (HIGH) A SHUTDOWN 18 INLET SCRUBB. LIQUID LEVEL #1 (HIGH) A SHUTDOWN 19 ENGINE OIL PRESSURE (LOW) B SHUTDOWN 20 ENGINE OIL LEVEL (LOW) A SHUTDOWN 21 ENGINE VIBRATION (HIGH) A SHUTDOWN 22 ENGINE JACKET/WATER TEMP. (HIGH) B SHUTDOWN 23 ENGINE JACKET/WATER LEVEL. (LOW) A SHUTDOWN 24 ENGINE JACKET/WATER PRESS. (LOW) B SHUTDOWN 25 ENGINE VACUUM RIGHT BANK (LOW) B SHUTDOWN 26 ENGINE VACUUM LEFT BANK (LOW) B SHUTDOWN 27 COMPRESSOR VIBRATION (HIGH) A SHUTDOWN 28 COOLER VIBRATION (HIGH) A SHUTDOWN 29 COOLER WATER LEVEL (LOW) A SHUTDOWN 30 AUXILIARY PUMP PRESSURE (LOW) B SHUTDOWN 31 EMERGENCY SHUTDOWN A SHUTDOWN 32 PRELUBE PERMISSIVE SHUTDOWN
*Actual Display will be arranged into 2–lines, 16 characters each.
1
SEQUENCE OF OPERATIONS FOR ENGINE DRIVEN COMPRESSOR
POWER UP THE SYSTEM: Make sure the D-sub miniature connector from power and control cable is secured to the back of the S1400 module. The display will show: SYSTEM READY. Anytime primary power input signal is lost, the PRIMARY POWER FAILURE message will be displayed.
(S1400 will resume operations if no key is pressed within 30 sec.)
SYSTEM READY
If functions are okay, the display will show:
PRE/POST-LUBE
5.0 MIN. REMAIN
OK
By pressing the START/STOP
key the S1400 will scan all Class
“A” functions for shutdown.
The time will count down to zero. The keys YES (up) and NO (down) can be used to speed up or slow down the countdown. At the end of the prelube time the lube relay will de-energize. The display will show:
PERMISSIVE START
Run signal is seen at the opto-isolator input. If engine
FAULT
is running or cranking the display will show:
CLASS-B TIMER
5.0 MIN. REMAIN
The time will count down to zero. The keys YES up) and NO (down) can be used to speed up or slow down the countdown. Display will show:
RUN
FAULT
If the run signal is lost
the display will show:
FAULT
If permissive function is being used and at the end of the prelube time, sufficient lube pres­sure is not reached, the display will show:
UNACCEPTABLE LUBE PRESSURE
LOSS OF RUN SIGNAL
The alarm relay picks up and the fuel valve and
ignition relays de-energize. Display will show:
If a shutdown occurs the display will show:
SHUTDOWN SEQUENCE INIT.
PRE/POST-LUBE
5.0 MIN. REMAIN
To stop the compressor, while in the run mode press START/STOP key. The display will show:
MANUAL STOP GROUNDING IGNIT.
TEST TIMER PRESETTING PARAMETERS
While in SYSTEM READY or RUN, press the MODE key and the display will show:
TEST TIMER INITIALIZE ? (NO)
If the YES (up) key is pressed the test timer will begin and sen­sor inputs can be tested without shutting down.
Pressing NO (down) or MODE keys will take you into the PRE­SETTING PARAMETERS mode.
Test the sensor input (by tripping the end device), then the name and number for the sensor will be displayed. Clear the sensor, then press the RESET key, the display will show:
TEST TIMER X.X MIN. REMAIN
The display will show the remaining time. At the end of the test or to cancel press the MODE key, this will take you into the PRESETTING PARAMETERS, to return to RUN or SYSTEM READY press the MODE key again.
2
The time will count down to zero. The keys YES (up) and NO (down) can be used to speed up or slow down the countdown. When time expires the cause of shutdown is displayed. To clear, press the RESET key.
While in the TEST TIMER mode, press the MODE key and the display will show:
PRESET CLASS-B TIMER 5.0 MIN.
Press YES (up) or NO (down) keys to increase or decrease the values . Press ENTER key to accept new values. Press MODE to display the next parameter to be set. Repeat the above for each value to be preset. Preset displays will be shown in the following sequence every time MODE is pressed while in PRESETTING PARAMETERS mode.
PRESET - 0.1 MIN. IGN. GND.
PRESET - 5.0 MIN. PRELUBE
PRESET - 5.0 MIN. POST LUBE
CLASS - B TIMER INITIALIZE [NO]
Press the MODE key again to return to SYSTEM READY or RUN display.
Loading...