Murphy Modex S10 Specifications

S10 series
AUTOMATIC BATTERY CHARGERS RATINGS TO 10 AMPS
The S10 is a constant potential, open-chassis battery charger, suitable for use with either 12V DC or 24V DC, lead acid or Ni-Cd systems. Although primarily designed for the diesel generator market, the charger may be configured for use in a wide range of unattended industrial applications where standby power is required at all times.
Each unit consists of a transformer, rectifier and control circuitry. The charger monitors the battery voltage and delivers as much current as the cells require up to the current limited maximum, giving a rapid recovery of charge. Once the battery is fully charged, the charger provides a low trickle charge to maintain the cells for an indefinite period at a pre-set float voltage, without overcharging, plus any additional current required to support a static load.
Also included is a range of on-board fault monitors complete with volt free relay contacts for remote alarm signalling.
Standard Features
Boost function, operated by remote link.
Indication by amber LED.
Adjustable float and boost voltage levels to meet with
a range of battery types, static loads and operating conditions. Standard calibrations are:-
BATTERY TYPE FLOAT
VOLTAGE
(V DC)
BOOST
VOLTAGE
(VDC)
Lead acid (6 cells) 13.6 14.1
12 V Ni-Cd (9 cells) 12.8 14.0
Ni-Cd (10 cells) 14.2 15.6 Lead acid (12 cells) 27.2 28.4
24 V Ni-Cd (18 cells) 25.6 28.1
Ni-Cd (20 cells) 28.4 31.2
Adjustable current limit. Standard versions have a
10 Amp limit, but this may be adjusted downwards where required (e.g. for lower capacity batteries).
Output short circuit protection.
Protection against reverse polarity battery connection
via fuse and red warning LED.
3 alarm monitoring circuits: 'charge fail', 'low battery
voltage' and 'high battery voltage', complete with volt-free relay outputs and LED indicators. The low battery voltage alarm features a fixed time delay of approx. 60 secs. to inhibit the signalling of a fault during normal battery loading (e.g. engine cranking).
Electrical connection of the battery, boost and charge monitoring relays is via ¼" blade terminals. The AC supply is connected through separately mounted screw terminals.
When ordering, please specify:-
a) Product type (S10 series) b) Nominal output voltage (12 or 24 V DC) c) AC supply voltage (240 or 110 V) d) Battery type (Lead-acid, or Ni-Cd and number of cells,
or special calibration requirements).
The Generator Controls Division of
R
M020301
Issue 5, revised 07/98
Catalogue section 75
Dimensions (mm)
Overall Fixing Base
Connection
L
42
5
6
7
8
31
F1
S1012, 240V: 1.5A 110V: 3.15A S1024, 240V: 3.15A 110V: 6.3A
F1, fuse type T, rating:
AC
supply
N
Boost switch/timer
E
10
9
BCS
battery
charge
fail
high
battery
volts
low
battery
volts
+ –
Product Specification
Power supply:
operating voltages 240 V AC or 110 V AC (specify),
+/– 10%, 50/60 Hz.
Charging output:
nominal output voltage see chart left voltage stability +/– 1% of nominal current limit 1 – 10 Amps, factory set current stability +/– 2% of nominal
Relay outputs:
(ratings for resistive load)
charge fail and low battery volts high battery volts
volt free SPNC contacts volt free SPNO contacts all rated 5 A @ 30 V DC
General:
operating temperature –10 to +55 oC overall dimensions (h x l x d) 185 x 145 x 155 mm weight approx. 8.0 Kg EMC emission/immunity to EN50081-2/EN50082-2
Since 1939
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 email: sales@fwmurphy.com
web: http://www.fwmurphy.com
Frank W. Murphy Southern Division
PO Box 1819, Rosenberg, Texas 77471, USA Tel: + 1 281 342 0297 Fax: + 1 281 341 6006 email: sales@fwmurphy.com
Frank W. Murphy Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K. Tel: + 44 1722 410055 Fax + 44 1722 410088 Pour service en Français, tél: + 44 1722 410697 email: sales@fwmurphy.co.uk web: http://www.fwmurphy.co.uk
Murphek Pty. Ltd.
1620 Hume Highway, Campbellfield, Vic. 3061 Australia Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558 email: murphy@macquarrie.com.au
Murphy Switch of California
PO Box 900788, Palmdale, California 93590, USA Tel: + 1 805 272 4700 Fax: + 1 805 947 7570 email: sales@murphyswitch.com web: http://www.murphyswitch.com
Murphy de Mexico S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P. México 78384 Tel: + 52 48 206264 Fax: + 52 48 206336 email: murmexsl@sanluis.podernet.com.mx
Frank W. Murphy Pte, Ltd.
No. 2 Tuas South Street 2, Sprintecs Building 02-01/02, Singapore 637895 Tel: + 65 863 1398 Fax: + 65 863 0208 email: fwmsales@fwmurphy.com.sg
Frank W. Murphy Ltd. en France
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 Direct usine Tel: + 44 1722 410697 email: sales@fwmurphy.co.uk