Murphy MGC447, MGC547 User Manual

MGC-96079B Revised 08-02
Catalog Section 75
(00-02-0766)
Digital Generator Panels
MGC447 and MGC547 Series
Microprocessor-Based Controller
Pre-Programmed, Full Featured
Built-In Advanced Communications
Compact Design, NEMA 1 Drip Proof
FWMurphy
Description
The MGC447 and MGC547 generator panels provide inexpensive engine and generator monitoring and control with digital accuracy.
These microprocessor-based controllers include all basic industry requirements plus many value added features such as: remote communications and control capabilities; on­board real time clock; shutdown history dis­play of last 5 shutdowns; service reminders.
Operating parameters are configured through a three-button interface. Data is displayed on a 32-character, back lit alphanumeric liquid crystal display. Access to the system memory is controlled by entry codes, and the program is stored in EPROM.
These panels accept a variety of sensor inputs such as from Murphy electric gage type resis­tive sending units and digital inputs such as from SWICHGAGE®instruments.
The MGC447 and MGC547 feature open col­lector transistor type and relay type outputs.
These compact panels measure only 13-1/4 x 8-1/2 x 12-1/2 inches (337 x 216 x 318 mm), and are shock mounted and rated NEMA 1 drip-proof.
The MGC547 Series models incorporate built­in serial ports for advanced communication capabilities. They can communicate with remote terminals, such as a computer via modem or can automatically dial your pager to inform you of the status of the generator.
The user is able to start or stop the engine, view operating parameters and reset or acknowledge abnormal conditions from a computer.
Features
Pre-programmed generator panels for typical gen-set operations: warm-up, transfer to load, run time, engine unload, cooldown.
For 3-phase, 4-wire or 1-phase, 3-wire generators.
Digital readout of all engine and generator functions: pressure, temperature, rpm, amps and volts. Monitored with first-out shutdown annunciation.
Built-in communication for remote start/stop and monitoring engine and generator func­tions (MGC547 models).
Optically-isolated noise resistant inputs.
Open collector transistor outputs.
Crank and Rest cycle timers, 1 to 300 seconds each (adjustable).
Shutdown time delay, 2 to 2000 seconds (adjustable), locks out low oil pressure and high temperature on start-up.
Crank disconnect and overspeed sensing operates from a magnetic pickup signal (requires 2 Vrms minimum) or alternator tachometer terminal.
Important: Off-panel items such as senders, mag­netic sensors and CT’s must be ordered separately.
Specifications
NOTE: These specification apply to all models unless otherwise indicated.
MGC447 models: EMS447 controller. MGC547 models: EMS547 controller. Power Requirements:
12 VDC battery for 12 V models. 24 VDC battery for 24 V models.
Operating Temperature: -4 to 149°F (-20 to 65°C). Storage Temperature: -4 to 149°F (-20 to 65°C). Relative Humidity: 95%RH @ 60°C (140°F). Communications:
MGC447: 1-RS485 serial port. MGC547: 2-RS485 and 2-RS232 serial ports.
Digital Inputs: 3optically-isolated, (positive voltage or ground) such as from Murphy SWICHGAGE
®
s.
Input 1: Auto position on toggle switch* Input 2: Test position on toggle switch*
Input 3: Spare 1 Input
Analog Inputs: 7
Analog 1: Water Temperature Sender Analog 2: Engine Oil Pressure Sender Analog 3: Low Coolant Input (closed on fault) Analog 4: Oil Level Input (closed on fault) Analog 5: AC Volts (0-5 VDC)* Analog 6: AC Amps (0-5 VDC)* Analog 7: Remote Start/Stop
Frequency Input: 1 optically-isolated for speed reference from magnetic sensor (pickup).
Outputs: 7
Output 1: Fuel Solenoid
Output 2: Starter
Output 3: Common Fail
Output 4: Glow Plug** Output 5: Generator Regulator Control** Output 6: Phase 2 Selection* Output 7: Phase 3 Selection*
NOTE: I/O’s and comm. ports are program specific and will vary depending upon the software program used. Custom programming is available.
*
Internal, not for customer connection.
** Open collector transistor type, 300 mA maximum.
To drive customer supplied relay.
Auxiliary relay, customer connection is
form “A” relay contact, 12 V, 40 A; 24 V, 16 A.
MGC547
Bulletin MGC-96079B page 2 of 2
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA (281) 342-0297 fax (281) 341-6006
e-mail sales@fwmurphy.com
MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 +52-444-8206264 fax +52-444-8206336 e-mail ventas@murphymex.com.mx www.murphymex.com.mx
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. +44 1722 410055 fax +44 1722 410088 e-mail sales@fwmurphy.co.uk www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West Palmdale, California 93551-1442; USA (661) 272-4700 fax (661) 947-7570 e-mail sales@murphyswitch.com www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
MACQUARRIE CORPORATION
1620 Hume Highway Campbellfield, Vic 3061; Australia +61 3 9358-5555 fax +61 3 9358-5558 e-mail murphy@macquarrie.com.au
FWMurphy
P.O. Box 470248 Tulsa, Oklahoma 74147 USA (918) 317-4100
fax (918) 317-4266 e-mail sales@fwmurphy.com
www.fwmurphy.com
R
E
G
I
S
T
E
R
E
D
Printed in U.S.A.
Warranty
A two-year limited warranty on materials and workmanship is given with this Murphy product. Details are available on
request and are packed with each unit.
Explore Murphy on the web:
http://www.fwmurphy.com and http://www.murphyswitch.com
Dimensions
How to Order
Phase
MGC447-1 = 1-phase MGC447-3 = 3-phase
MGC547-1 = 1-phase MGC547-3 = 3-phase
DC Power Supply
12 = 12 VDC 24 = 24 VDC
Front View
Note: Dimensions apply to all MGC447 and MGC547 Series Models
To order your MGC447 or MGC547 Series Model, just fill in the spaces.
Side View
8-1/2 in.
(216 mm)
13-1/4 in. (337 mm)
®
EMS
Controller
BACK
INCREMENTENTER
NO
SCROLL TO EXIT
YES
DECREMENTNEXTEXIT
OFF
AUTO
TEST
®
12-1/2 in. (318 mm)