Murphy M5081FS, M2582-P, M5180-P Installation And Operation Instructions Manual

M2582, M5081, and M5180 Series Electromechanical and Pneumatic, Fuel Gas Shut­off Valves Installation and Operation Instructions
M2582 and M5081Series
Tripping Power From Engine Ignition System or Battery (Models available for magneto, CD ignition or 12/24 V battery)
These fuel shut-off valves are semi-automatic devices for shutdown of natural gas fueled engines. The standard valve opens by manual operation of the reset handle. A latch in the upper body of the valve will set and hold the valve open. At this point no electric power is used. The electromagnetic coil is de-energized, the snap-switch(es) is SET.
If a SWICHGAGE®contact closes, a circuit is completed from power through the snap-switch and coil. Now energized, the electromagnet trips the latch, (latch can be tripped manually), the valve closes, and the snap-switch resets. Power switches from the coil circuit to your choice of an open line, an electrical ground, or an alarm. After tripping, the vent seal opens, and on the M50 models, the open/close indicator (green button) retracts to indicate that the valve is closed. Valve body is sandcast aluminum. Optional cast steel for M5081 models.
M2582-P and M5180-P
MURPHY-NUMATIC
Pneumatic Version for Pressure
The M2582-P and M5180 pneumatically controlled valves can operate from pressure, and are designed to open and close automatically or semi­automatically (the supply can be air, oil or gas).
NOTE: If using oil as a pressure source, use a lightweight oil.
These valves will open on rising control pressure and close on decreasing control pressure. M2582-P and M5180-P automatically open at 2 psi (14 kPa) [0.14 bar] and fully open at 3 psi (21 kPa) [0.21 bar].
All models include a built-in lever to aid in opening the valve manually. The M2582-P can be manually opened against inlet pressure of 80 psi (552 kPa) [5.52 bar]. The M5180-P valve can be opened against inlet pressure of 100 psi (689 kPa) [6.89 bar].
Standard models include an escape vent for gas trapped forward in the line after shut-off.
M5081FS
Normally Energized Circuit
The M5081FS is manually opened, electrically latched open and tripped by interrupting the coil power circuit.
Magnetic Switch Adapter
As ignition systems wear from usage, their power output becomes less and less. Ignition may not have the capacity to reliably trip the Fuel Valve. Therefore, the use of a Magnetic Switch Adapter for CD ignition systems is recommended. The Magnetic Switch Adapter is a device that stores energy from the CD ignition to trip the Fuel Valve. Three models are available:
65700053 (was 65020126): For use with negative ground ignitions up to 240 VDC.
65700054 (was 65020127): For use with positive ground ignitions up to 450 VDC.
65700055 (was 65020155): For use with negative ground ignitions up to 450 VDC.
100 ohm, 2 watt Resistor
For Capacitor Discharge Ignitions that are specified to be grounded when the valve closes, and a Magnetic Switch Adapter is in use. The resistor must be connected in the system to prevent damage to the snap-switches in the fuel shut-off valve (see typical wiring diagrams).
Diode Package
The Murphy diode package (65010065) is designed to allow the fuel shut­off valve to be used with dual Magneto Ignition systems.
NOTE: All aluminum versions of the M5081 Series Fuel Valve carry Canadian Registartion Number OC1476.2.
*
M5081 model is CSA approved for Class I, Division 1, Groups C and D. See Specifications on page 12.
GENERAL INFORMATION
Please read the following instructions before installing. A visual inspection of this product for damage during shipping is recommended before mounting. It is your responsibility to have a qualified person install the unit and make sure installation conforms with NEC and local codes.
M-7980N
Revised 11-02
Section 55
(00-02-0206)
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT
Disconnect all electrical power to the machine.Make sure the machine cannot operate during installation.Follow all safety warnings of the machine manufacturer.Read and follow all installation instructions.
Model M5081
Approved
*
Installation M-7980N page 1 of 12
WARNING
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
VALVE CUT-OUT
A.
Main Stem
B.
Pressure Disc/seal (in run/open)
C.
Pressure Disc/seal (in trip/closed)
D.
Vent Seal Gland
E.
Reset Knob (latches valve open)
F.
Manual Trip Knob (not available for M5081FS)
G.
Indicator Button (out with valve open)
H.
Pipe Plug
A
B
D
E
F
Understanding the Basic Operation
of the Fuel Shut-off Valve
The valve below is shown in the run (open) position. Pressure is equalized, seat (B) is open, allowing the fuel to flow. When valve is in the tripped position (closed), seat closes (C). The vent (D) opens to relieve trapped downstream fuel to vent to a non-hazardous area.
C
NOTE:
If the vent-after-tripping feature is not used, remove O-ring (D), to avoid condensation accumulation that can hamper trip action. Be sure to replace Pipe Plug (H) and to clean vent periodically.
Vent to relieve trapped fuel outside the hazardous area.
Terminal Block is within this case.
G
Pipe Plug (remove to install vent tube).
TYPICAL MODEL (M5081) SHOWN
H
FLOW CHARACTERISTICS
250
[7.08]
500
[14.16]
1000
[28.32]
1250
[35.40]
1500
[42.48]
1750
[4956]
2000
[56.64]
2250
[63.72]
2500
[70.80]
3000
[84.96]
2750
[77.88]
750
[21.24]
0
1.0
[25.4]
2.0
[50.8]
3.0
[76.2]
4.0
[101.6]
5.0
[127.0]
6.0
[152.4]
7.0
[177.8]
8.0
[203.2]
9.0
[228.6]
10.0
[254.0]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (.11 kg.)
M2582 Series
M5081 and M5180 Series
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Installation M-7980N page 2 of 12
3.0
[76.2]
2.0
[50.8]
4 oz. (.11 kg.)
4 oz. (.11 kg.)
10 oz. (.28 kg.)
10 oz. (.28 kg.)
10 psig (69 kPa) [.69 bar]
1.0
[25.4]
500
0
[14.16]
1000
1500
[28.32]
[42.48]
2000
2500
[56.64]
[70.80]
10 psig (69 kPa) [.69 bar]
20 psig (138 kPa) [1.38 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
30 psig (207 kPa) [2.07 bar]
3000
3500
4000
[84.96]
[99.12]
[113.28]
4500
[127.44]
5000
[141.60]
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
DIMENSIONS
M2582
M5180-P
Magnetic Switch Adapters
65700053
(was 65020126); 65700054 (was 65020127); 65700055 (was 65020155)
M2582-P
CAUTION: THE ARROW ON THE SIDE OF THE FUEL VALVE MUST POINT TO THE CORRECT DIRECTION OF THE
FLOW, FROM FUEL SOURCE TO THE ENGINE. APPLY PIPE DOPE ONL
Y TO FUEL PIPE, NOT TO THE FUEL VALVE.
Installation M-7980N page 3 of 12
Manual Trip
Knob
1/4 NPT Vent and Plug
Reset Knob
3-3/32 in. (79 mm)
5-1/2 in. (140 mm)
Latch Arm (see NOTE 2)
Breather Vent (see NOTE 1)
2 NPT (2 places)
Vent and Plug 1/2 NPT
1/2 NPT Conduit Connection
1 NPT (2 places)
7-5/16 in. (186 mm)
9-3/8 in. (238 mm)
10-7/16 in. (265 mm)
1/4 in. (6 mm) tube connection; control pressure 3 psi (21 kPa) [0.21 bar] minimum,
Latch Arm (see NOTE)
Breather/Vent
1/16 in. (2 mm)
1 NPT (2 places)
1/4 NPT
Vent and
Plug
3-3/32 in. (79 mm)
5-1/2 in. (140 mm)
NOTE: Thumb operated opening latch (2.5 psi [17 kPa]
[0.17 bar] required to release cocking latch)
1/4 in. (6 mm) connection; control pressure 3 psi (21 kPa) [0.21 bar] minimum, 80 psi (552 kPa) [5.52 bar] maximum (see NOTE 1)
75 psi (517 kPa) [5.17 bar] maximum.
6-9/16 in. (167 mm)
6-1/8 in.
(156 mm)
4-3/8 in.
(111 mm)
4-1/4 in.
(108 mm)
NOTE 1: Control pressure connection fitting and breather vent fitting can be swapped to convert to vacuum control. NOTE 2: Thumb operated opening latch (2.5 psi [17 kPa] [0.17 bar] required to release cocking latch).
Panel Mount screws
10-24 N.C. x
5/16 in. (8 mm) long
2-5/16 in. (59 mm)
1-15/32 in.
(37 mm)
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
3/8 in. (10 mm)
31/32 in. (25 mm)
15/32 in. (12 mm)
Terminal screws
8-32 N.C. x
1/4 in. (6 mm) long
2-5/8 in. (67 mm)
GND ALT1 ALT2 SW
1-23/32 in. (44 mm)
2-7/16 in. (62 mm)
DIMENSIONS
continued
M5081 and M5081FS
M5081-3 Steel Flanged Option
CAUTION: THE ARROW ON THE SIDE OF THE FUEL VALVE MUST POINT TO THE CORRECT DIRECTION OF THE
FLOW, FROM FUEL SOURCE TO THE ENGINE. APPLY PIPE DOPE ONL
Y TO FUEL PIPE, NOT TO THE FUEL VALVE.
Installation M-7980N page 4 of 12
Manual Trip Knob
Inlet Breather
Vent and Plug 1/2 NPT
(M5081 only)
9-3/8 in. (238 mm)
1/2 NPT Conduit
Reset Knob
Connection (2 plcs.)
10-5/16 in. (262 mm)
Indicator
Button
2 NPT
(2 places)
3 in. (76 mm)
7-3/4 in. (197 mm)
1-3/8 in. (35 mm)
3-7/16 in.
(87 mm)
4-1/16 in. (103 mm)
14-25/64 to 14-29/64 in.
(366/367 mm)
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
3-5/8 in. (92 mm) dia.
2 in. (51 mm) dia. 2 places
150# RF (raised face) pipe flange
45°
3/4 in. (19 mm) dia. (4 places) each end equally spaced on a 15/32 in. (121 mm) b.c. (bolt circle)