Murphy M5081FS, M2582-P, M5180-P Installation And Operation Instructions Manual

M2582, M5081, and M5180 Series Electromechanical and Pneumatic, Fuel Gas Shut­off Valves Installation and Operation Instructions
M2582 and M5081Series
Tripping Power From Engine Ignition System or Battery (Models available for magneto, CD ignition or 12/24 V battery)
These fuel shut-off valves are semi-automatic devices for shutdown of natural gas fueled engines. The standard valve opens by manual operation of the reset handle. A latch in the upper body of the valve will set and hold the valve open. At this point no electric power is used. The electromagnetic coil is de-energized, the snap-switch(es) is SET.
If a SWICHGAGE®contact closes, a circuit is completed from power through the snap-switch and coil. Now energized, the electromagnet trips the latch, (latch can be tripped manually), the valve closes, and the snap-switch resets. Power switches from the coil circuit to your choice of an open line, an electrical ground, or an alarm. After tripping, the vent seal opens, and on the M50 models, the open/close indicator (green button) retracts to indicate that the valve is closed. Valve body is sandcast aluminum. Optional cast steel for M5081 models.
M2582-P and M5180-P
MURPHY-NUMATIC
Pneumatic Version for Pressure
The M2582-P and M5180 pneumatically controlled valves can operate from pressure, and are designed to open and close automatically or semi­automatically (the supply can be air, oil or gas).
NOTE: If using oil as a pressure source, use a lightweight oil.
These valves will open on rising control pressure and close on decreasing control pressure. M2582-P and M5180-P automatically open at 2 psi (14 kPa) [0.14 bar] and fully open at 3 psi (21 kPa) [0.21 bar].
All models include a built-in lever to aid in opening the valve manually. The M2582-P can be manually opened against inlet pressure of 80 psi (552 kPa) [5.52 bar]. The M5180-P valve can be opened against inlet pressure of 100 psi (689 kPa) [6.89 bar].
Standard models include an escape vent for gas trapped forward in the line after shut-off.
M5081FS
Normally Energized Circuit
The M5081FS is manually opened, electrically latched open and tripped by interrupting the coil power circuit.
Magnetic Switch Adapter
As ignition systems wear from usage, their power output becomes less and less. Ignition may not have the capacity to reliably trip the Fuel Valve. Therefore, the use of a Magnetic Switch Adapter for CD ignition systems is recommended. The Magnetic Switch Adapter is a device that stores energy from the CD ignition to trip the Fuel Valve. Three models are available:
65700053 (was 65020126): For use with negative ground ignitions up to 240 VDC.
65700054 (was 65020127): For use with positive ground ignitions up to 450 VDC.
65700055 (was 65020155): For use with negative ground ignitions up to 450 VDC.
100 ohm, 2 watt Resistor
For Capacitor Discharge Ignitions that are specified to be grounded when the valve closes, and a Magnetic Switch Adapter is in use. The resistor must be connected in the system to prevent damage to the snap-switches in the fuel shut-off valve (see typical wiring diagrams).
Diode Package
The Murphy diode package (65010065) is designed to allow the fuel shut­off valve to be used with dual Magneto Ignition systems.
NOTE: All aluminum versions of the M5081 Series Fuel Valve carry Canadian Registartion Number OC1476.2.
*
M5081 model is CSA approved for Class I, Division 1, Groups C and D. See Specifications on page 12.
GENERAL INFORMATION
Please read the following instructions before installing. A visual inspection of this product for damage during shipping is recommended before mounting. It is your responsibility to have a qualified person install the unit and make sure installation conforms with NEC and local codes.
M-7980N
Revised 11-02
Section 55
(00-02-0206)
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT
Disconnect all electrical power to the machine.Make sure the machine cannot operate during installation.Follow all safety warnings of the machine manufacturer.Read and follow all installation instructions.
Model M5081
Approved
*
Installation M-7980N page 1 of 12
WARNING
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
VALVE CUT-OUT
A.
Main Stem
B.
Pressure Disc/seal (in run/open)
C.
Pressure Disc/seal (in trip/closed)
D.
Vent Seal Gland
E.
Reset Knob (latches valve open)
F.
Manual Trip Knob (not available for M5081FS)
G.
Indicator Button (out with valve open)
H.
Pipe Plug
A
B
D
E
F
Understanding the Basic Operation
of the Fuel Shut-off Valve
The valve below is shown in the run (open) position. Pressure is equalized, seat (B) is open, allowing the fuel to flow. When valve is in the tripped position (closed), seat closes (C). The vent (D) opens to relieve trapped downstream fuel to vent to a non-hazardous area.
C
NOTE:
If the vent-after-tripping feature is not used, remove O-ring (D), to avoid condensation accumulation that can hamper trip action. Be sure to replace Pipe Plug (H) and to clean vent periodically.
Vent to relieve trapped fuel outside the hazardous area.
Terminal Block is within this case.
G
Pipe Plug (remove to install vent tube).
TYPICAL MODEL (M5081) SHOWN
H
FLOW CHARACTERISTICS
250
[7.08]
500
[14.16]
1000
[28.32]
1250
[35.40]
1500
[42.48]
1750
[4956]
2000
[56.64]
2250
[63.72]
2500
[70.80]
3000
[84.96]
2750
[77.88]
750
[21.24]
0
1.0
[25.4]
2.0
[50.8]
3.0
[76.2]
4.0
[101.6]
5.0
[127.0]
6.0
[152.4]
7.0
[177.8]
8.0
[203.2]
9.0
[228.6]
10.0
[254.0]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (.11 kg.)
M2582 Series
M5081 and M5180 Series
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Installation M-7980N page 2 of 12
3.0
[76.2]
2.0
[50.8]
4 oz. (.11 kg.)
4 oz. (.11 kg.)
10 oz. (.28 kg.)
10 oz. (.28 kg.)
10 psig (69 kPa) [.69 bar]
1.0
[25.4]
500
0
[14.16]
1000
1500
[28.32]
[42.48]
2000
2500
[56.64]
[70.80]
10 psig (69 kPa) [.69 bar]
20 psig (138 kPa) [1.38 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
30 psig (207 kPa) [2.07 bar]
3000
3500
4000
[84.96]
[99.12]
[113.28]
4500
[127.44]
5000
[141.60]
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
DIMENSIONS
M2582
M5180-P
Magnetic Switch Adapters
65700053
(was 65020126); 65700054 (was 65020127); 65700055 (was 65020155)
M2582-P
CAUTION: THE ARROW ON THE SIDE OF THE FUEL VALVE MUST POINT TO THE CORRECT DIRECTION OF THE
FLOW, FROM FUEL SOURCE TO THE ENGINE. APPLY PIPE DOPE ONL
Y TO FUEL PIPE, NOT TO THE FUEL VALVE.
Installation M-7980N page 3 of 12
Manual Trip
Knob
1/4 NPT Vent and Plug
Reset Knob
3-3/32 in. (79 mm)
5-1/2 in. (140 mm)
Latch Arm (see NOTE 2)
Breather Vent (see NOTE 1)
2 NPT (2 places)
Vent and Plug 1/2 NPT
1/2 NPT Conduit Connection
1 NPT (2 places)
7-5/16 in. (186 mm)
9-3/8 in. (238 mm)
10-7/16 in. (265 mm)
1/4 in. (6 mm) tube connection; control pressure 3 psi (21 kPa) [0.21 bar] minimum,
Latch Arm (see NOTE)
Breather/Vent
1/16 in. (2 mm)
1 NPT (2 places)
1/4 NPT
Vent and
Plug
3-3/32 in. (79 mm)
5-1/2 in. (140 mm)
NOTE: Thumb operated opening latch (2.5 psi [17 kPa]
[0.17 bar] required to release cocking latch)
1/4 in. (6 mm) connection; control pressure 3 psi (21 kPa) [0.21 bar] minimum, 80 psi (552 kPa) [5.52 bar] maximum (see NOTE 1)
75 psi (517 kPa) [5.17 bar] maximum.
6-9/16 in. (167 mm)
6-1/8 in.
(156 mm)
4-3/8 in.
(111 mm)
4-1/4 in.
(108 mm)
NOTE 1: Control pressure connection fitting and breather vent fitting can be swapped to convert to vacuum control. NOTE 2: Thumb operated opening latch (2.5 psi [17 kPa] [0.17 bar] required to release cocking latch).
Panel Mount screws
10-24 N.C. x
5/16 in. (8 mm) long
2-5/16 in. (59 mm)
1-15/32 in.
(37 mm)
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
3/8 in. (10 mm)
31/32 in. (25 mm)
15/32 in. (12 mm)
Terminal screws
8-32 N.C. x
1/4 in. (6 mm) long
2-5/8 in. (67 mm)
GND ALT1 ALT2 SW
1-23/32 in. (44 mm)
2-7/16 in. (62 mm)
DIMENSIONS
continued
M5081 and M5081FS
M5081-3 Steel Flanged Option
CAUTION: THE ARROW ON THE SIDE OF THE FUEL VALVE MUST POINT TO THE CORRECT DIRECTION OF THE
FLOW, FROM FUEL SOURCE TO THE ENGINE. APPLY PIPE DOPE ONL
Y TO FUEL PIPE, NOT TO THE FUEL VALVE.
Installation M-7980N page 4 of 12
Manual Trip Knob
Inlet Breather
Vent and Plug 1/2 NPT
(M5081 only)
9-3/8 in. (238 mm)
1/2 NPT Conduit
Reset Knob
Connection (2 plcs.)
10-5/16 in. (262 mm)
Indicator
Button
2 NPT
(2 places)
3 in. (76 mm)
7-3/4 in. (197 mm)
1-3/8 in. (35 mm)
3-7/16 in.
(87 mm)
4-1/16 in. (103 mm)
14-25/64 to 14-29/64 in.
(366/367 mm)
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
3-5/8 in. (92 mm) dia.
2 in. (51 mm) dia. 2 places
150# RF (raised face) pipe flange
45°
3/4 in. (19 mm) dia. (4 places) each end equally spaced on a 15/32 in. (121 mm) b.c. (bolt circle)
INSTALLATION
Connecting the Fuel Shut-off Valve
1. Before connecting the unit, apply pipe dope to plumbing male threads that will be inserted into the valve. Do not apply pipe dope to the valve.
2. Make sure that the arrow on the side of the valve indicates the correct direction of the flow.
3. Fuel shut-off valves can be installed in all three planes. However, mounting the valve horizontally (with vent pointing down) is recommended. Do not install valve with top down. (Refer to Figure 1.)
4. Hold valve in position, (use a tool on valve wrench flats) and tighten plumbing into inlet and outlet ends. (Refer to dimensions on pages 3-4.)
5. To mount flanged models, follow the appropriate installation codes and ordinances for the application. (For dimensions see page 4.)
6. A vent line (to allow gas trapped forward between fuel valve and the carburetor to escape) should be attached to the vent connection at the bottom of the valve housing. Remove the plug and install the line. (Refer to Figure 1.)
Connecting Pneumatic Models
M2582-P and M5180-P
1. Repeat the steps above (1 thru 5), and observe the necessary cautions.
2. A lever/arm (handle) and a cocking latch are provided to allow manual
opening of the valve. The thumb-operated latch can be locked in place to hold the lever/arm latched. The cocking latch will be released when pilot pressure reaches 2.5 psi (17 kPa) [0.17 bar]). M2582-P and M5180-P automatically open at 2 psi (14 kPa) [0.14 bar], and fully open at 3 psi (21 kPa) [0.21 bar]. See Specifications, page 12 for maximum control pressure.
3. If vacuum control is desired, swap the Control Pressure connection fitting and the Breather Vent fitting on your M5180-P model (see Fig. 2).
WARNING: STOP THE ENGINE AND DISCONNECT ALL ELECTRICAL POWER BEFORE BEGINNING INSTALLATION. BEGIN THE
INSTALLATION BY SECURING AREA OF ANY HAZARDOUS CONDITIONS. SHUTOFF THE FUEL GAS SUPPLY. FOR HAZARDOUS APPLICATIONS REFER TO NATIONAL ELECTRICAL CODE SPECIFICATIONS.
Figure 1
Physical Location and Plumbing (typical)
Figure 2
Pull the lever up, and press the latch
down into ridge with thumb.
CAUTION: DO NOT TWIST THE VALVE BODY HOUSING.
CAUTION:
BE SURE PNEUMATIC SOURCE
RELEASES THE MECHANICAL LATCH WHEN RUNNING.
Installation M-7980N page 5 of 12
Master Regulator
(High pressure)
Control Pressure
Fuel Shut-off Valve
Wrench Flats
FUEL FLOW
Bypass
Regulator
Remove plug and attach vent line.
Route to non-hazardous area.
Fuel Filter
Carburetor
Level Arm (Handle)
Connection
Thumb-operated
Cocking Latch
Breather
Vent
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
Internal Wiring for M2582
M5081 Internal Wiring
M2582 Internal Wiring
Wiring shown in normal mode of operation (seat open). The 20 AWG (0.75 mm2) wire is color coded to the coil:
For CD ignitions: White and Orange For Magneto ignitions: White and Green For Battery: White and Blue
Conduit Installation
Install a 1/2 NPT conduit from the M2582 conduit connection to the power source. See M2582 Dimensions (page 3) for location.
For wiring the M2582 fuel valve to Solid-State TATTLETALE
®
annunciators, refer to pages 9, 10, and 11.
M5081 Internal Wiring
Wiring shown in normal mode of operation (seat open). The 18 AWG (1.0 mm2) wire is color coded to the coil:
For CD Ignitions: White and Orange For Magneto Ignitions: White and Green For Battery: White and Blue
Conduit Installation
Install a 1/2 NPT conduit from the M5081 conduit connection to the power source. Refer to Dimensions (on page 4) for location.
For typical wiring of the M5081 models refer to pages 7 and 8.
For wiring the M5081 fuel valves to Solid-State TATTLETALE
®
annunciators, refer to pages 9, 10, and 11.
M5081FS Internal Wiring
For typical Wiring refer to page 8.
For wiring the M5081FS to MARK IV 12/24 refer to page 10.
Magnetic Switch Adapters for Use with Capacitor Discharge Ignitions
Connect the Magnetic Switch Adapter between the fuel Valve terminal 1 and the CD Ignition. See wiring diagrams (pages 7
and 11).
WARNING: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” AND THE AREA MADE NON-HAZARDOUS.
MAKE SURE THE VOLTAGE AND CURRENT REQUIREMENTS ARE WITHIN THE FUEL SHUT-OFF VALVE RATINGS. HARD CONDUIT WITH APPROVED SEALS IS REQUIRED BY THE NEC FOR HAZARDOUS AREA INSTALLATIONS.
NOTE: For grounding the ignition (CD models only)
through the fuel valve snap-switch, use a Magnetic Switch Adapter (see Magnetic Switch Adapter, below) and install a 100 ohm; 2 watt resistor (included on page 11).
NOTE: For grounding the ignition (CD models only) through the fuel valve snap-switches, use a Magnetic Switch Adapter, see Magnetic
Switch Adapter, below and the “TO CLOSE THE FUEL VALVE and GROUND THE IGNITION” attachment, and install a 100 ohm; 2
watt resistor (included with your attachment).
NOTE: Wiring shown in normal mode of operation (seat open). The 18 AWG (1.0 mm2)
wire is red color for both options: 12 VDC and 24 VDC.
WIRING INFORMATION
GND
ALT
1
SW
+
ALT
2
IN4007
Negative ground
Magnetic Switch Adapter shown
65700053 (was 65020126): For use with
negative ground ignitions up to 240 VDC.
65700054 (was 65020127): For use with
positive ground ignitions up to 450 VDC.
65700055 (was 65020155): For use with
negative ground ignitions up to 450 VDC.
Installation M-7980N page 6 of 12
FV–
FV+
(IGN)
White
Orange
FV–
FV+
(IGN)
White
Orange
White
Black
Red
Ground
Ground
10
Jumper
Valve
Coil
7265 19384
Disconnect
Switches
Ignition 1 Ignition 2
Jumper
(See Note)
Optional Resistor (Note)
Optional
Resistor
Valve
Coil
Switch 2
Ground
10
7265 19384
Switch 1
(Note)
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
g
TYPICAL WIRING for M5081-C (CD IGNITION MODELS)
Start-run
timer
To additional TATTLETALE
®
7265 1938 4
Ground
10
+
--
DC Power
source
M5081-B
Battery Models
Terminal Block
Jumpers
MS2110
IN4005 Diode
for flyback protection
*
*
6 2 3
5
1 4
MS2110
6 2 3
5
1 4
TYPICAL WIRING for M5081-B (BATTERY IGNITION MODELS)
Installation M-7980N page 7 of 12
10
Ground
Start-run
timer
MS2100
6 2 3
1
M5081-C
CD Ignition Models
Terminal Block
7265 1938 4
Jumpers
4
5
MS2100
6 2 3
1
GND ALT1 ALT2 SW
CD ignition
100 ohm, 2 watt Resistor
4
5
(Notes 3 and 4)
To additional TATTLETALE
Magnetic
Switch
Adapter
Additional
CD ignition
®
NOTE 1: To CLOSE FUEL VALVE–NOT GROUNDING THE IGNITION (Single CD Ignition Systems) Remove the factory-installed jumper on terminals 6-5.
Do NOT ground terminal 6. NOTE 2: To CLOSE FUEL VALVE–NOT GROUNDING THE IGNITIONS (Dual CD Ignition Systems) Remove the jumper on terminals 6-5.
Connect second ignition to Magnetic Switch Adapter terminal ALT2. NOTE 3: To CLOSE FUEL VALVE and GROUND THE IGNITION (Single CD Ignition Systems) Remove the jumper on terminals 6-5.
Connect a 100 ohm, 2 watt resistor between valve terminals 1-2. Ground terminal 6.
NOTE 4: To CLOSE FUEL VALVE and GROUND THE IGNITION (Dual CD Ignition Systems) Remove the jumper on terminals 6-5. Connect a 100 ohm, 2 watt resistor between valve terminals 1-2. Ground terminal 6. Connect second i
nition to Magnetic Switch Adapter terminal ALT2.
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
TYPICAL WIRING for M5081-A (MAGNETO IGNITION MODELS)
g
TYPICAL WIRING for M5081FS (NORMALLY ENERGIZED MODELS)
Installation M-7980N page 8 of 12
M5081-A
Magneto Ignition Models
Terminal Block
7265 1938 4
Jumpers
MS2120
Magneto
Additional
Magneto
MS2120
65010065 Diode Package (See Notes 2/4)
Start-run
10
Ground
timer
6 2 3
1 4 6 2 3
5
1 4
5
To additional TATTLETALE
®
NOTE 1: To CLOSE FUEL VALVE–NOT GROUNDING THE IGNITION (Single Magneto Systems) Remove the factory-installed jumper on terminals 6-5.
Do NOT ground terminal 5. NOTE 2: To CLOSE FUEL VALVE–NOT GROUNDING THE IGNITIONS (Dual Magneto Systems) Remove the factory-installed jumpers on terminals 6-5 and 9-8.
Add 65010065 diode package as shown. Do NOT ground terminals.
NOTE 3: To CLOSE FUEL VALVE and GROUND THE IGNITION (Single Magneto Systems) The factory-installed jumpers (6-5 and 9-8) must be in place. Add ground wire to terminal 5.
NOTE 4: To CLOSE FUEL VALVE and GROUND THE IGNITION (Dual Magneto Systems) Remove the jumper on terminals 9-8. Add 65010065 diode packa
e as shown. Add ground wire to terminal 5.
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
M5081FS
12 or 24 VDC Models
Terminal Block
10
Ground
MS2110 MS2110
6 2 3
1 4 6 2 351 4
7265 1938 4
Ground
5
*
*
*
Start-run timer
+
--
DC Power
source
IN4005 Diode
*
for flyback protection
IGN 1
NO
C
NC
Relay Contacts
FV(+)
GND
M2582 Fuel Valve
White
Black
Red
Ground
LCDT-PS-CD-N
*
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
FV(-)
*
+
IGN 1
F/V+
F/V-
GRD
MARK IV-N terminal block
M2582 Fuel Valve
White
Black
Red
Ground
+
M2582 Fuel Valve
White
Black
Red
Ground
LCDT-PS-CD (R)-P
IGN 1
FV(-)
NO
C
NC
Relay Contacts
FV(+)
GND
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
+
TYPICAL WIRING to SOLID-STATE TATTLETALE®Annunciators
M2582-C
to LCDT-PS-CD (R)-P (positive ground)
M2582-C
to LCDT-PS-CD-N (negative ground)
M2582-C
to MARK IV-N (negative ground)
WARNING: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” AND THE AREA MADE NON-
HAZARDOUS. MAKE SURE THE VOLTAGE AND CURRENT REQUIREMENTS ARE WITHIN THE FUEL SHUT-OFF VALVE RATINGS. HARD CONDUIT WITH APPROVED SEALS IS REQUIRED BY THE NEC FOR HAZARDOUS AREA INSTALLATIONS.
M5081-C
to LCDT-PS-CD (R)-P (positive ground)
M5081-C
to LCDT-PS-CD-N (negative ground)
M5081-C
to MARK IV-N (negative ground)
Installation M-7980N page 9 of 12
M5081 Terminal block
7265 1938410
jumperjumper
FV(-) FET output rated: 0.5 A @ 250 VDC max.
*
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
M5081 Terminal block
7265 1938410
jumperjumper
FV(-) FET output rated: 0.5 A @ 250 VDC max.
*
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
LCDT-PS-CD (R)-P
Terminal block
+
IGN 1
GND
FV
FV(-)
*
NO
C
NC
LCDT-PS-CD-N Terminal block
+
IGN 1
FV(+)
FV(-)
*
GND
NO
C
NC
Relay Contacts
Relay Contacts
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
M5081 Terminal block
7265 1938 410
jumperjumper
MARK IV has FET outputs rated: 0.5 A @ 250 VDC max.
*
F/V+
F/V-
GRD
MARK IV-N terminal block
IGN 1
*
TYPICAL WIRING to SOLID-STATE TATTLETALE®Annunciators
WARNING: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” AND THE AREA MADE NON-
HAZARDOUS. MAKE SURE THE VOLTAGE AND CURRENT REQUIREMENTS ARE WITHIN THE FUEL SHUT-OFF VALVE RATINGS. HARD CONDUIT WITH APPROVED SEALS IS REQUIRED BY THE NEC FOR HAZARDOUS AREA INSTALLATIONS.
M5081-B
to MARK IV-12/24
M5081FS
to MARK IV-12/24
M5081FS
to MARK III-12/24
M5081-C
to MARK III-N
M5081-C
to TTDJ-IGN-(T)
M2582-C
to TTDJ-IGN-(T)
Installation M-7980N page 10 of 12
M5081FS Terminal Block
7265 1938410
*
IN4005 Diode
*
for flyback protection
1
MARK IV has FET outputs rated: 0.5 A @ 250 VDC max.
M5081FS Terminal Block
7265 1938 410
*
IN4005 Diode
*
1
MARK III has FET outputs rated:
0.5 A @ 250 V max.
2
Auxiliary Relays must be hermetically-sealed, third party certified for use in Class I, Division 2, Gps. C & D areas.
for flyback protection
MARK IV-12/24 terminal block
+
--
DC Power
source
1
MARK III-12/24 terminal block
12/24 S/D
FV ALM GRD
*
*
K1
K2
+
+
1
12/24V SD F/V GRD
+
--
12/24 VDC
Power source
2
Auxiliary Relay
2
Auxiliary or Shutdown Relay
M5081-B
7265 1938 410
*
jumperjumper
IN4005 Diode
*
for flyback protection
1
MARK IV has FET outputs rated: 0.5 A @ 250 VDC max. Remove shunt jumper E2 for ignition ground time delay.
M5081 Terminal block
7265 1938 410
jumperjumper
IN4005 Diode
*
MARK III has FET outputs rated:
0.5 A @ 250 V max.
††
Alarm Relay must be hermetically-sealed, third party certified for use in Class I, Division 2, Gps. C & D areas.
for flyback protection
K1K2
+
--
DC Power
source
K1 and K2: External Relay(s)
F/V
GRD
MARK IV-12/24 terminal block
*
+––
K1
MARK III-N
terminal block
S/D
††
IGN +FV
-FV ALM GRD
K1
*
+
12/24V
1
Alarm Relay
Power Supply
Ignition 90-250 Vdc
K2
*
+
M5081 Terminal block
7265 1938 410
jumperjumper
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
M2582 Fuel Valve
IGN NA
GRD
FV+
FV­ALR NA NA
Black
Red
White
+
IGN NA
GRD
FV+
FV­ALR NA NA
TYPICAL WIRING to SOLID-STATE TATTLETALE®Annunciators
continued
WARNING: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” AND THE AREA MADE NON-
HAZARDOUS. MAKE SURE THE VOLTAGE AND CURRENT REQUIREMENTS ARE WITHIN THE FUEL SHUT-OFF VALVE RATINGS. HARD CONDUIT WITH APPROVED SEALS IS REQUIRED BY THE NEC FOR HAZARDOUS AREA INSTALLATIONS.
(A) M5081-B
to TTDJ-DC-(T)
TTDJ-DC-(T)
to Relays
Connections Shown for Use with
Diagrams (A), (B), (C), and (D) on this page.
(C) M2582-C
w/Magnetic
Switch Adaptor to CD Ignition
(D) M5081-C
w/Magnetic
Switch Adaptor to CD Ignition
M5081FS
to TTDJ-DC-(T)
(B) M2582-B
to TTDJ-DC-(T)
Installation M-7980N page 11 of 12
M5081 Terminal block
7265 1938 410
jumperjumper
1
K1 and K2 are hermetically Sealed
To 12 or 24 VDC power supply
*
K2
1
auxiliary relays, third party certified for use in Class I, Div. 2, Gps. C & D areas.
* 1N4005 diode for flyback protection
.
IGNITION RELAY
12-24 VDC Power supply
1
K1 and K2 are hermetically Sealed auxiliary relays, third party certified for use in Class I, Div. 2, Gps. C & D areas.
* 1N4005 diode for flyback protection
1
–+
K1
*
1
+
K2
*
.
To 12 or 24 VDC power supply
M2582 Fuel Valve
White
SD 10-32VDC GRD
K1
NA FV ALR
MPU
GRD
1
K1 and K2 are hermetically Sealed
Red
Black
K2
K1
1
SD
10-32VDC
GRD NA FV ALR MPU GRD
auxiliary relays, third party certified for use in Class I, Div. 2, Gps. C & D areas.
To 12 or 24 VDC power supply
.
SD
10-32VDC
GRD NA FV ALR MPU GRD
SD
10-32VDC
GRD NA FV ALR MPU GRD
M5081FS Terminal Block
7265 1938 410
*
* 1N4005 diode for flyback protection
Magnetic
Switch
Adapter
M2582 Fuel Valve
White
Black
Red
1
K2 is hermetically sealed auxiliary relay, third party certified for use in Class I, Div. 2, Gps. C & D areas.
1-800-548-1191 - http://www.partdeal.com - info@partdeal.com
GND ALT1 ALT2 SW
K2
1
Magnetic
Switch
M5081 Terminal block
GND ALT1 ALT2 SW
+
7265 1938 410
jumperjumper
1
K2 is hermetically sealed auxiliary relay, third party
K2
1
+
certified for use in Class I, Div. 2, Gps. C & D areas.
Adapter
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA +1 281 633 4500 fax +1 281 633 4588
e-mail sales@fwmurphy.com
MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 +52 444 8206264 fax +52 444 8206336 Villahermosa Office +52 993 3162117 e-mail ventas@murphymex.com.mx www.murphymex.com.mx
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. +44 1722 410055 fax +44 1722 410088 e-mail sales@fwmurphy.co.uk www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West Palmdale, California 93551-1442; USA +1 661 272 4700 fax +1 661 947 7570 e-mail sales@murphyswitch.com www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
MACQUARRIE CORPORATION
1620 Hume Highway Campbellfield, Vic 3061; Australia +61 3 9358 5555 fax +61 3 9358 5558
e-mail murphy@macquarrie.com.au
FW Murphy
P.O. Box 470248 Tulsa, Oklahoma 74147 USA +1 918 317 4100
fax +1 918 317 4266 e-mail sales@fwmurphy.com
www.fwmurphy.com
R
E
G
I
S
T
E
R
E
D
USA–ISO 9001:2000 FM 28221
UK–ISO 9001:2000 FM 29422
Printed in U.S.A. 0966106
M2582 M5081 M5081FS
M5081FS Coil Assembly
12 VDC 24 VDC
Latch Block Assembly
Latch block assembly Latch block switch and coil assembly Latch block switch and mounting bracket assembly
Coil Assembly
Battery CD Ignition Magneto Ignition
55000128 55000129 55000094
-----------­55000096
55000097 55000137 --------------- --------------- ---------------
55000102
------------
55000102
------------
5500148
------------
55000154
------------
55000095
------------
------------
55000074
-----------­55000118
------------
-----------­55000196
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
55000158 55000159
------------
------------
------------
------------
55000126 55000127 55000080
------------
------------
------------
------------
------------
------------
------------
------------
------------
SERVICE PARTS
M2582-P
M5180-P
Handle and Latch Kit
Handle and latch kit Handle kit
Manual DIsconnect Assembly
55000098 55000072 55000160 --------------- ---------------
Snap Switch Assembly
------------ 55000138 55000138 --------------- ---------------
Close/Open Indicator Assembly
55000093 55000075
55000135 55000147 55000135
Stem and Seat Kit
55000146 55000131 55000161 55000150 55000155
Top Works Complete Valve Less Body and Vent
55000143 55000132
55000132
65700053
65700053
------------
65010065 ------------
------------ ------------
65700054
65700054
65700055
65700055
55000143
55000132
Vent Bushing Assembly
------------ ------------
------------
55000184 55000153
Diaphragm Assembly
------------
------------ ------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
00007908
55050420
Pilot Diaphragm
Single/Dual ign. – negative ground up to 240 VDC
Single/Dual ign. – positive ground up to 450 VDC
Single/Dual ign. – negative ground up to 450 VDC
Diode Package for Dual Magneto Ignitions
Magnetic Switch Adapter for CD Ignitions
SPECIFICATIONS
Valve Body: Sandcast aluminum, painted red (corrosion resistance);
Optional cast steel available for M5081 and M5081FS models only.
Valve Seat: Buna-N
Maximum Valve Inlet Pressure:
• M2582/M2582-P: 80 psi (552 kPa) [5.52 bar]
• M5081/M5081FS/ M5180-P: 100 psi (689 kPa) [6.89]
Maximum Control Pressure (Pneumatic Models):
• M2582-P: 75 psi (517 kPa) [5.17 bar]
• M5180-P: 80 psi (552 kPa) [5.52 bar]
Snap-switch: M2582: One SPDT, 5 A @ 480 VAC
M5081, and M5081FS: Two SPDT, 5 A @ 480 VAC
Wiring: M2582: Wire leads; M5081, and M5081FS: Terminal blocks
NOTE: All aluminum versions of the M5081 Series Fuel Valve carry Canadian Registartion Number OC1476.2.
Coil Rating: Intermittent duty; coil type must match power source;
• CD ignition coil resistance: 72 CD ignition primary voltage: 1.38 to 3.8 A
• M5081FS: Energized to Run (continuous-duty coil) coil resistance:
12 V model: 33 ; 24 V model: 136
• Magneto ignition coil resistance: 0.5
Magneto primary voltage: 1 to 5 A
• Battery coil resistance : 7
12 or 24 VDC: 1.2 to 2.4 A
Laboratory Approval: CSA listed for Class I, Groups C and D Hazardous Locations. 5 amps maximum; intermittent duty; models M5081 and M5081-CD engine ignition powered, and model M5081-B, 12 or 24 VAC or VDC; switch contacts rated 5 A @ 480 VAC maximum. Maximum pressure 100 psi (689 kPa) [6.89 bar].
Installation M-7980N page 12 of 12