Murphy M50, M25 User Manual

M25 and M50 Series
Instant Response to Shut Off Signal
Positive Valve Closure
Vents Gases Trapped After Shutdown
Explosion-proof Models Available
Models Available for Magneto, CD Ignition or 12/24 VDC
Description
These fuel shutoff valves are semi-automatic devices for shutdown of natural gas fueled engines. The valve is opened manually and closes when the electromagnet is energized and trips the latch. The valve can be closed manually by turning the valve’s disconnect knob. A normally energized model is available that holds the valve open elec­trically and closes when the coil is de-energized. A vent in the valve body relieves trapped gas when the valve closes. A pop-out indicator button informs you when the valve is open or closed.
The valve’s tripping power is provided by an engine ignition system or battery. Models are avail­able for magneto, CD ignition or 12/24 V battery.
The M2582 is a 1 inch (25 mm) valve with 1 NPT connections. It has one SPDT snap-switch. The valve body is made of sandcast aluminum. It does not include the open/close indicator button.
M5081 is a 2 inch (51 mm) valve with 2 NPT connections. It has two SPDT snap-switches. The valve body is available in sandcast alu­minum or cast steel (optional).
M5081FS is the same as the M5081 but has a normally energized circuit. This circuit allows the valve to be held open electrically and close by interruption of the coil’s power circuit. A
manual trip knob is not available on this model.
An optional 2 in. (51 mm) steel flange pipe con­nection is available for M5081 and M5081FS steel body models (see Dimensions page 3).
Specifications
Valve Body: Sandcast aluminum, painted
red (corrosion resistance). Optional cast steel available for M5081 and M5081FS models only.
Valve Seat: Buna-N
Maximum Pressure Rating:
• M2582: 80 psig (552 kPa) [5.52 bar]
• M5081: 100 psig (689 kPa) [6.89 bar]
• M5081FS: 100 psig (689 kPa) [6.89 bar] Coil Rating: Intermittent duty; coil
type must match power source;
• CD ignition coil resistance: 72 Ω CD primary voltage: 1.38 to 3.8 A
• M5081FS model: Energized to run
(continuous-duty coil) coil resistance:
12 Volt model: 33 Ω (0.36 A) 24 Volt model: 136 Ω (0.17 A)
• Magneto ignition coil resistance: 0.5 Ω
• Magneto primary voltage: 1 to 5 A
• Battery coil resistance : 7 Ω 12 or 24 VDC: 1.2 to 2.4 A
Wiring (See Internal Wiring page 2):
• M2582: Wire leads
• M5081 and M5081FS: Terminal blocks
Snap-switch Rating: 5 A @ 480 VAC
Laboratory Approval: CSA listed for Class I,
Groups C and D Hazardous Locations. 5 amps maximum; intermittent duty; models M5081 and M5081-CD engine ignition powered, and model M5081-B, 12 or 24 VAC or VDC; switch con­tacts rated 5 A @ 480 VAC maximum.
Options and Accessories
Diode Package (65010065)
The Murphy 202 V diode package is designed to allow the fuel shutoff valve to be used with dual Magneto Ignition systems. Sold separately (see How to Order).
Magnetic Switch Adapter
As ignition systems wear from usage their power output becomes less and less. Ignition may not have the capacity to reliably trip the fuel valve. Therefore, the use of a Magnetic Switch Adapter for CD ignition systems is recommended. The adapter stores energy from the CD ignition to trip the fuel valve. Three models are available:
65020126: For Negative Ground CD Ignitions
up to 240 VDC
65020127: For Positive Ground CD Ignitions up
to 450 VDC
65020155: For Negative Ground CD Ignitions
240 VDC to 450 VDC
Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
Model M5081
MV-94134B
Revised 07-99
Catalog Section 55
(00-02-0124)
Electromechanical Fuel Shutoff Valves
250
[7.08]
500
[14.16]
1000
[28.32]
1250
[35.40]
1500
[42.48]
1750
[4956]
2000
[56.64]
2250
[63.72]
2500
[70.80]
3000
[84.96]
2750
[77.88]
750
[21.24]
0
1.0
[25.4]
2.0
[50.8]
3.0
[76.2]
4.0
[101.6]
5.0
[127.0]
6.0
[152.4]
7.0
[177.8]
8.0
[203.2]
9.0
[228.6]
10.0
[254.0]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (0.11 kg.)
10 oz. (0.28 kg.)
5 psig (34 kPa) [0.34 bar]
10 psig (69 kPa) [0.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
4 oz. (.11 kg.)
10 oz. (.28 kg.)
10 psig (69 kPa) [.69 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
M2582
M5081 and M5081FS
M2582
M5081 and M5081FS
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Inches water column (p) drop across valve.
Millimeters water column in brackets [ ].
Standard cubic feet per hour. Cubic meters per hour in brackets [ ].
Internal WiringFlow Rates
NOTE: For grounding the ignition (CD models only) through the fuel valve’s internal snap-switch, a Murphy Magnetic Switch adapter (see page 4) must be used in addition to a 100 ohm, 2 watt resistor (supplied with valve).
NOTE: For grounding the ignition (CD models only) through the fuel valve’s internal snap-switch, a Murphy Magnetic Switch adapter (see page 4) must be used in addition to a 100 ohm, 2 watt resistor (supplied with valve).
MV-94134B page 2 of 4
Optional Resistor (See Note)
White
Black
Red
Ground
3.0
[76.2]
2.0
[50.8]
1.0
[25.4]
500
0
[14.16]
[28.32]
1000
2000
1500
[42.48]
2500
[56.64]
[70.80]
4 oz. (.11 kg.)
4 oz. (.11 kg.)
10 oz. (.28 kg.)
10 oz. (.28 kg.)
a) [.69 b
a
9 kP
(6
(69 kP
sig
sig
10 p
10 p
20 psig (138 kPa) [1.38 bar]
20 psig (138 kPa) [1.38 bar]
30 psig (207 kPa) [2.07 bar]
30 psig (207 kPa) [2.07 bar]
3000
3500
4000
[84.96]
[99.12]
[113.28]
[127.44]
4500
ar]
ar]
) [.69 b
5000
[141.60]
M5081
Valve
Ground
10
Jumper
Disconnect Switches
Ignition 1 Ignition 2
Coil
7265 19384
Optional
Jumper
Resistor (See Note)
Ground
10
M5081FS
Switch 2
Valve Coil
Switch 1
(see Note)
7265 19384