Murphy Engine and Generator Controls Keystart 9620, Keystart 9620 Installation Instructions Manual

Page 1
W
6
2
00-02-0657
Keystart 9
0 series
rev ision A, 22
nd
September 2008
catalogue section 40 & 75
Engine & Generator Controls
Installation Instructions
Please read th e f ollow ing informatio n before i nstalling. A visual inspection of this product for damage dur ing shipping is recommended before installation. It is your responsibility to ensure that qualified mechanical and el ec trical technicians install this product. If i n doubt, please contac t your local Murphy representat ive.
GENERAL INFORMATION
Product specifications
power supply:
ARNING
BEFORE BEGINNING INSTALLATION OF TH IS PRODUCT
Disconnect all electrical power to the machine Make sure the m a chi n e cann ot operate during installatio n Follow all safety warnings of the mach ine manufacturer Read and follow all installation instruction s
The Keystart 9620 series provides manual start/stop and automatic fault shutdown protection for generators, pumps and other engine­driven applicat ions.
Keyst art features a 3 way keyswitch for operator control of th e engine, with 6 LEDs for indication of status and faults - see ‘front view’ diagram for details. Electrical connection an d configurat ion option s are at the rear
- see ‘Rear view, connection and settings’ diagram. For each Keystart ordered, the following is supplied:
1 x Keystart module, fitted with 2 x panel mounting clips
2 x keys
these instructions
Panel installation
Keystart is designed for front-of-panel mounting in a DIN standard 92 x 92 mm (3.6 x 3.6 in.) c ut-out. Allow 75mm (3.0 in. ) behind the panel for the case depth, keyswitch and cable connection.
Secure the case to the panel with the two ratcheted mounting clips:
1. 2. 3.
Remove the plastic mounting clips from the Keystart case: release each clip ’s ratchet mechanism by pulling outwards (A), then slide the clip back and off the case (B).
At the front of the panel, insert the Keystart (without clips ) into th e panel cut-out (C).
At the rear of the panel, refit the two mounting clips into the slots on the Keystart case (D). Slide each clip forward until the arms ( E) are secured behind the panel face. Ratchet mechani sm (F ) prevents the clip from moving backwards.
operating voltage: steady state brown out / cranking
current consumption < 100mA
inputs:
fault switch inputs: close to negative DC during fault
–ve input defined as: –1V to +1V w.r.t. – ve DC supply
speed sensing input: generator AC (J2+J3 on)
mag. pickup (J2+J3 off)
outputs:
run, preheat positive D C, switched NO relay contact,
start (crank) positive DC via keyswitch contacts,
alarm negative DC (open collector
calibration/tacho to suit 0 – 1 mA, 75 Ohm meter
output = 0.75mA at rated engine speed
adjustable settings:
preheat timer 0 or 10 secs (link J1),
fault ov erride timer 2 to 20 secs (VR1),
overspeed trip level 100 to 130 % (VR3) of
general:
overall dimensions (w x h x d) 96 x 96 x 95 mm / 3.8 x 3.8 x 3.7 in. panel cut-out size DIN 92 x 92 mm / 3.6 x 3.6 in. weight approx . 300 g / 0.7 lb operating temperature –35°C to +55°C / –31°F to 131°F
70 – 270 VAC rms,
<50 to >60 Hz. nominal
10 – 60 VAC peak,
<2000 to >6500 Hz. nominal
(all ratings non-reactive)
10 A max. @ 24VDC
10 A max. @ 24V DC
NPN transistor), 250mA max.
nominal speed calibration (VR2),
default = 110% (of 50 or 60 Hz)
Model options
7 – 30 VDC
5 VDC
(model 9621 only)
default = 0 secs
default = 10 secs
Page 2
GENERAL INFORMATION (cont.)
Front view and operation
Rear view, connections and settings
ELECTRICAL CONNECTION
WARNING: DANG ER OF INJURY OR DEATH. Ke ystart 9621 cont r ol lers allow connection of high voltage AC cir cui t s . Bef or e connect i on, disconnection or handl ing of these units,
DANGER !
HIGH VOL TS
Electrical connection to 0.5 to 1.5 mm² / 16 – 20 AWG panel wiring is by spring-clamp terminal s at the rear.
pre-strip 8 to 10 mm / 0.3 to 0.4 in. of ins ulation from each wire.
Ab ove each terminal i s a square push-button with a diagonal slot.
Insert a flat-head screwdriver into the slot (A), then push down to (towards the front of the Keystart ) to open the ter minal cl amp.
insert the wire into the terminal (B), checking that the insulation is
clear of the cl amp. Release the screwdri ver/spring clamp pressure and check that the wire is secure.
General connecti on r ecommendat i ons
Murphy make several recommendations for the electrical connection of engine and generator controllers.
minimise controller output load current (i.e. wear/tear and potential
damage) by using slave relays between the controller outputs and high power end-devices such as fuel and starter solenoids.
Suppress (at source) electrical interference from panel relay and
engine solenoid coils, using flywheel diode or proprietary snubber networ ks as appropriate.
Murphy - Keystart 9620 series installation instructions 00-02-0657 revision A 22nd September 2008 p2/4
ensure that all AC and DC power suppli es ar e i sol ated. Connection to or disconnection from live wiring may also cause damage to t he Keystart’s internal components.
use separate routing for AC and DC wiring harnesses.
use separate wiring for a) connection of battery charger to battery,
and b) connection of battery to panel DC supply. Separate wiring will reduce high frequency battery charger output noise on the panel DC power supply.
Terminal f unct ions
Pin Function
Run (fuel) output
1
Preheat output
2
These r elay outputs provide control for a the engine’s preheater and (energised to run) fuel / ignition circuits.
When configuration link J3 is on (the default setting), the Preheat output (terminal 2) does not oper ate. If link J3 is removed, terminal 2 gives a positive DC output for 10 seconds, and the preheat LED lights, beginning from when the key is switched to the I (RUN) position.
After any preheat time has expired, the Run output (pin 1) gives a positive DC output (operating engine fuel) and the green ‘run’ LED lights. The Run output and LED remain active until the operator swi tches the key to O (STOP) or until the Keystart initiates an automatic fault shutdown.
Both Run and Preheat outputs are rated 10 Amp max. @ 24VDC. Murphy recommend the connection of slave relays with suppress ed coils between these outputs and fuel solenoid coil and engine preheaters - see ‘typical connection’ diagram below.
Page 3
ELECTRICAL CONNECTION (cont.)
Terminal f unct ions (cont.)
Pin Function
3 Start (crank) output
Pin 3 gives a positive DC, 16 Amp rated output when the key is switched to position II (start/crank). To prolong keyswitch contact life, connect a slave relay (with suppressed coil) between pin 3 and the engine starter solenoid coil - see ‘typical connection’ diagram below.
4
Power Supply, Positive DC
12
Power Supply, Negative DC
The Keystart operates with an y smoot h DC / battery voltage in the range 7 – 30V. Supply brown-out protection is fitted as standard. Connect a 5 Amp anti-surge fus e in the positive DC line (pin 4) .
5 Charge fail
The charge fail LED lights, but there is no shutdown or alarm, when pin 5 is connected to battery negative. When using a ch arge alternator, connect pin 5 to the al ternat or w arning l amp (WL) terminal. (Note: pin 5 supp lies the alternator excitation current).
6
Low Oil Pressure (LOP) fault input
7
Auxiliary 1 fault input
8
High Engine Temperature (HET) fault input
9
Auxiliary 2 fault input
Use remote switch/relay contacts that connect these inputs to battery negative during fault conditions. The Keystart shuts down the engine, lights the appropriate fault LED, and activates the alarm output. Note: activation of pin 9 (Aux 2 input) causes engine shutdown and illumination of the overspeed LE D.
For all the above inputs, shutdown is inhibited during engine cranking and until the end of the fault ‘override’ time (adjustable 2 – 20 secs us ing potentiometer VR1, clockwise to increase). To reset a shutdown fault condition, turn the key to O (Off) or remove the DC power supply.
10 Alarm output
Pin 10 is a semiconductor-based (open collector NPN t ransistor) output that gives a negative DC output immediately after a fault shutdown. Output rating is 250mA max.: the output typically dr ives an audible/visi ble alarm circuit, usi ng a slave relay with suppressed coil - s ee ‘typical connection’ opposite.
11
Tachometer (speed calibration) output
This output is designed to work with a 0 - 1 mA DC ammeter, either a) during set-up to aid speed calibration, or b) in normal operation to indicate engine speed or generator Hz.
For calibration, connect meter positive to pin 11 and meter negative to battery negative, e.g. at terminal 12. See ‘speed sensing and calibration’ below for setup procedure.
For indication of engine RPM or generator Hz, the 0 – 1mA meter requires a custom scale: when correctly calibrated using VR2, Keystart gives 0 mA at 0 RPM /Hz. and 0.75mA (3/4 scale) at normal running RPM/Hz.
Pin Function
With links J2 & J3 ON:
Generator AC Live
13
Generator AC Neutral
14
When configuration links J2 and J3 are fitted (the default factory
setting), terminals 13 and 14 are configured for overspeed sensing using a high voltage, generator AC 50/60Hz. signal.
The input accepts generator AC voltages between 70 and 270 VAC rms. A 1 Am p anti-surge fuse should be connected in series with AC live (pin 13). See ‘speed sensing’ below for correct calibration of this input using potentiometers VR2 and VR3.
To configure these terminals to magnetic pickup engine speed sensing, see section below.
With links J2 & J3 OFF:
Magnetic pickup signal input
13
Magnetic pickup return
14
When configuration links J2 and J3 are removed, terminals 13 and 14 are configured for speed sensing by a magnetic pickup and flywheel/gearwheel c ombination.
Connect the magnetic pickup to the input using two-core and scr een cable. To mi nimise electrical interference on t he speed signal, connect the cable screen t o earth at one end only.
Magnetic pickup signal requirements are 10 – 60 VAC peak, with frequency between 2000 and 6500 Hz. when the engine is running at nominal speed. See ‘speed sensing’ below for correct calibration of this input using potentiometers VR2 and VR3.
To configure these terminals for generator AC frequency sen sing, see section above.
Typical connection
DANGER ! HIGH VOLTS
Murphy - Keystart 9620 series installation instructions 00-02-0657 revision A 22nd September 2008 p3/4
Page 4
SPEED SENSING AND CALIBRATION
Keystart model 9621 includes a speed sensing input and automatic shutdown protection for engine overspeed faults. Before use, model 9621’s speed input must be correctly configured (us ing circuit-board links J2 and J3) and calibrated (using potentiometers VR2 and VR3).
Selection of speed signal source: links J2 and J3
Links J2 and J3 allow configuration of the speed sensing input (terminals 13 and 14) for either generator AC (the factory default setting) or magnetic pickup signals. Use small pliers to add or remove the links as required:
J2 and J3
Terminal 13 and 14 configuration
links
ON Generator AC, 70 - 270 VAC rms, 50 or 60 Hz nominal.
OFF Magnetic pickup, 10 – 60 VAC peak, 2000 to 6500 Hz
nominal.
Speed calibration
Speed cal ibration is a two stage proces s:
1) Nominal speed calibration: potentiometer VR2
The factory default setting is for generator AC speed sensing, with standard models for 50 or 60Hz nominal calibration. To recalibrate for other systems:
Select the speed sensing method (generator AC or magnet ic
pickup) using links J2 and J3 as detailed above.
Turn VR2 fully clock wise (sets calibration for m aximum n omin al
frequency).
Connect a 0 – 1mA, 75 Ohm meter between pin 11 and battery
negative, as detailed in ‘electric al connection’ above.
Start and run the engine to nominal (normal running) speed.
Tu rn VR2 anti-clockwise (decreasing th e cali bration frequ ency)
until the ammeter rises to read 0.75mA.
Maintenance and Warranty
The Keystart series contains no user-servic eable parts. Maintenance is therefore limited to the following preventative checks:
Check th at all electr ical connections are secure.
Check that the Keystart is securely clamped in the front of
panel aperture, and kept free f rom ingress of water or build up of excessive dust/dirt. The front face label and casing may be wiped with a clean, damp cloth. Do not use cleaning solvents.
Each Keystart is supplied with a two year warranty on materials and workmanship. In the event of a fault or technical query, please contact your Murphy representative for technical support.
2) Overspeed setting: potentiometer VR3
VR3 allow s adjustment of t he overspeed tri p point, between approximately 100 and 130% of the nominal AC or magnetic pickup frequency (as set us ing VR2). The VR3 factory default setting is 110% (of either 50 or 60Hz). To adjust the overspeed trip level:
Turn VR3 fully clockwise (to maximum, approx. 130% of nominal)
Start and run the engine. Increase engine speed to the required
oversp eed/over-frequency tri p level.
Tu rn VR3 slowly anti -clockwis e (decreasing the ov erspeed trip
level) until the Keystart shuts down the engine and indicates ‘overspeed’.
Where the engine speed cannot be22 September 2008 adjusted, or if the speed signal cannot be simulated (e.g. with an adjustable signal generator), an approximate overspeed setting must be made (e.g. potentiometer mid-span = approximately 115% of VR2 nominal).
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
FW MURPHY
P.O.Box 470248, Tulsa, Oklahoma 74147 USA +1 918 317 4100 Fax: +1 918 317 4266 E-mail: sales@fwmurphy.com
INDUSTRIAL PANEL DIVISION
Fax: +1 918 317 4124 E-mail: ipdsales@fwmurphy.com
MURPHY POWER IGNITION
Website: www.murphy-pi.com
CONTROL SYSTEMS AND SERVICES DIVISION
P.O.Box 1819, Rosenberg, Texas 77471 USA Phone: +1 281 633 4500 Fax: +1 281 633 4588 E-mail: sales@fwmurphy.com
Murphy - Keystart 9620 series installation instructions 00-02-0657 revision A 22nd September 2008 p4/4
MURPHY, the Murphy logo, are registered and/or common law trademarks of Murphy Industries, Inc. This document, including
textual matter and illustrations, is copyright protected by Frank W Murphy Ltd., with all rights reserved. © 2008 Frank W Murphy Ltd.
FRANK W. MURPHY LTD.
Church Rd, Laverstock, Salisbury, SP1 1QZ, Unite d Kingdom Tel: +44 1722 410055 Fax: +44 1722 410088 E-mail: sales@fwmurphy.co.uk Web: www.fwmurphy.co.uk
COMPUTRONIC CONTROLS
41 – 43 Railway Terrace, Nechells, Birmingham, B7 5NG, United Kingdom Tel: +44 121 327 8500 Fax: +44 121 327 8501 E-mail: sales@computroniccontrols.com Web: www.compu troniccontrols.com
FW MURPHY INTERNATIONAL TRADING (SHANGHAI) CO. LTD.
Suite 1704, Tower B, City Center of Shanghai; 100 Zunyi Road, Shanghai, 200051 China Phone: +86 21 6237 2082 Fax: +86 21 6237 2083 E-mail: mhong@fwmurphy.com
FW MURPHY INSTRUMENTS (HANGZHOU) CO. LTD.
rd
Street, Hangzhou Economic & Technological Development Area
77 23 Hangzhou, Zhejiang 310018 China Phone: +86 571 8788 6060 Fax: +86 571 8684 8878
Loading...