Float/Boost Voltages: 
Battery Type Float Volts (VDC) Boost Volts (VDC)
12V Lead Acid (6 cells) 13.6 14.1
www.fwmurphy.com
FW Murphy
P.O. Box 470248, Tulsa, OK 74147 
phone:
+1 918.317.4100
fax: 918.317.4266 e-mail: sales@fwmurphy.com
Murphy Battery Chargers
0610058 07/06  Printed in U.S.A.
Sentry Model
Features: 
●
CE and UL Approvals 
●
Float Charging 5A at 12v 
●
Auto boost operation 
●
Electronic self-resetting output fuse protection 
●
Temperature compensation 
●
Charge fail relay output 
●
Stainless steel enclosure 
Power Supply
Nominal operating voltages: 120V units 
Permissible voltage variation: ± 6% of nominal 
Nominal operating frequency: 50-60Hz 
DC Charge Output 
Maximum current ADC: 5 
Nominal voltage VDC: 12 
Charge Fail Output 
Relay type: volt free SPDT contacts; relay de-energized on fault 
Contact rating: 1A at 30V, DC (resistive load) 
General
Operating temperature: +14 to +131°F (-10 to +55°C) 
EMC emission/immunity: EN 58801-2 / EN50082-2  
Weight: 11.9 lbs. (5.6 Kg.) 
Model Info:
BCES-12-5 12 volt, 5A, lead acid cells 
Guardian Model
Features
●
CE and UL approvals 
●
Heavy duty float charging: 10A at 12/24 VDC, 20A at 24 VDC
●
Short circuit and reverse polarity protection 
●
Lead acid calibrations 
●
Auto boost operation 
●
Charge fail relay output 
●
Under volts and over volts alarms 
●
Temperature compensation 
●
NFPA110 alarms 
Power Supply 
Nominal operating voltages: 120VAC ± 6% 
Permissible voltage variation: 120VAC ± 6% 
Nominal operating frequency: 50/60Hz 
DC Charge Output
Maximum current ADC: 20/20 
Nominal voltage VDC: 24/12 
Charge Fail Output 
Relay type: volt free SPDT contacts; relay de-energized on fault 
Contact rating: 1A at 30V, DC (resistive load) 
General 
Operating temperature: +14 to +100°F (-10 to +38°C) 
EMC emission/immunity: EN 58801-2 / EN50082-2 
Weight: 17.9 lbs. (6.4 Kg.) 
Fixing hole dimensions: 
Width (between holes): 6.8” (173mm) 
Height (between holes): 10” (255mm) 
Fixing holes Ø=0.2” (6mm)
Model Info: 
BCEG-12-10 12 volt, 10A, lead acid cells 
BCEG-24-10 24 volt, 10A, lead acid cells 
BCEG-24-20 24 volt, 20A, lead acid cells