AUTOSTART 730 (AS730 series)
The Generator Controls Division of
gen. frequency measurement range
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 730 provides for the fully automatic or manual
control of a standby generator. The unit has similar control
and instrumentation features to the Autostart 710, but with
the addition of 3 phase generator voltage and current
measurement, display and fault tripping.
Key features
• Automatic, Manual and Program modes, selected by
front facia push button keys
• 32 character, back-lit liquid crystal display (LCD)
• Fully programmable generator control options, timers,
inputs, outputs and fault protections
• Monitoring, display and programmable fault trips for
generator speed/frequency, 3 phase voltage and 3
phase current with IDMT response.
• Comprehensive automatic fault protection system:–
up to 5 programmable fault inputs, overspeed, charge
fail, emergency stop, and high and low battery volts
• 6 programmable outputs, each with over 40 different
function (or ‘action’) types.
Operation
Control of the Autostart is via 4 front facia keys:ON/MODE Turns on the Autostart and allows selection
of Auto or Manual modes.
PAGE Used to scroll through measured generator
parameters, such as 3 phase voltage
and current, engine oil pressure and
temperature, hours run and battery voltage.
SELECT Used in the programming of Autostart
OFF Turns the Autostart off, disabling the
generator and resetting any fault condition.
These keys are also labelled with
used in the programming of each Autostart (see overleaf).
Two front facia LEDs indicate the selected operating mode:
green for Auto, amber for Manual.
Control Outputs
Dedicated relay outputs are used for engine fuel and starter
motor control. The AS730 has 6 programmable outputs,
each of which may be set up for use as one of over 40
function types, e.g. preheat (4 types), engine running,
individual faults (e.g. overspeed, overcurrent, start fail,
oil pressure, etc.), energised to stop fuel, etc.
Fault Protection and Alarm System
The Autostart 730 has a comprehensive fault detection,
warning and automatic response system:-
• Dedicated inputs for low oil pressure and high engine
temperature sensors, either switch or analogue type.
The use of analogue sensors allows for pre-warning as
well as shutdown alarms, and real-time display of oil
pressure and engine temperature.
• Three programmable inputs for use with remote fault
switches. The inputs can be set to give a warning only,
generator load release or shutdown response.
• User set trip levels and response for generator speed/
frequency, 3 phase voltage and 3 phase current.
symbols,
Issue 4, revised 06/99
M011001
Catalogue section 75
Product Specification
Power supply:
Operating voltage: steady state range
crank brown-out
Current consumption typically 200 mA
Inputs:
DC inputs:-
positive input defined as: 80% to 100% of battery +ve
negative input defined as: –1V to +2V w.r.t. battery –ve
Input 1 (oil pressure) and
Input 2 (engine temperature)
Inputs 3 - 5 switch (open or closed),
Generator AC inputs:-
operating voltage range 90 – 300 V AC rms L–N
gen. frequency display accuracy <= 2% of full scale
gen. frequency display resolution 1 Hz.
Magnetic pickup:
operating voltage range 7 – 80 V AC rms
frequency measurement range 0 – 10 kHz.
generator RPM display accuracy <= 2% of full scale
generator RPM display resolution 10 RPM
AC current sensing inputs:
operating range designed for use with 5 Amp CT's
Outputs: (all ratings for resistive load)
Start and fuel relays SPNO contacts (switched +ve)
Programmable outputs 1 – 3 – ve DC (open collector transistor)
Programmable output 4 – ve DC (switched relay)
Programmable output 5
(default setting: Common Alarm)
Programmable output 6
(default setting: Gen. Contactor)
Physical:
Overall dimensions (W x H x D) 144 x 96 x 162 mm
Panel cut-out size (W x H) DIN standard 140 x 92 mm
Weight approx. 720 g
Operating ambient temperature –10 to +55 oC
In order to consistently bring you the highest quality,
full featured products, we reserve the right to change our
specifications and designs at any time.
5 – 40 V DC continuous
to 0 V for >=100mS
switch (open or closed) or analogue
(Murphy, Datcon, VDO 5 or 7 bar),
wired to –ve DC
wired to +ve or –ve DC
0 – 99 Hz.
primary ratings 10 to 5000 Amps
rated 16 A max. @ 24 V DC
250 mA max. @ 33 V DC
5 A max. @ 24 V DC
+ ve DC (switched relay)
5 A max. @ 24 V DC
volt free SPNO relay
5 A max. @ 240 V AC
• Additional fault alarms:-
+ ve DC (relays)/Emerg. stop
Frank W. Murphy Manufacturer
Frank W. Murphy Southern Division
email: murphy@macquarrie.com.au
Murphy Switch of California
Murphy de Mexico S.A. de C.V.
Frank W. Murphy Pte, Ltd.
Frank W. Murphy Ltd. en France
Warnings: low and high battery voltage, charge fail
and magnetic pickup fault
Shutdowns: emergency stop, start fail and system fail.
Programmable functions
The AS730 has all the programmable functions found on the
Autostart 710 – timers, alarm configurations, trip levels and
programmable inputs/outputs – plus the following:-
• Generator under voltage trip, under voltage reset,
over voltage trip levels.
• Generator full load current, IDMT response constant
and instant trip level.
The Autostart may be programmed by use of the front facia
keys: to prevent end-user tampering, entry to program mode
is restricted by use of a code number.
The addition of a small RS232 interface allows the AS730 to
be connected to a remote (IBM compatible) computer, either
directly or over a modem link; Murphy Modex communication
software allows a PC operator to program, monitor and
control the Autostart from a remote location.
When ordering, please specify:-
a) Unit type (Autostart 730S)
Accessories:-
AS7CA 9 way (interface) to 9 way (PC) comms lead
AS7CB 9 way (interface) to 25 way (PC) comms lead
AS7CC Local communications interface
AS7CD Modem communications interface
AS7CK AS7xx communication and programming software
Rear Facia & Electrical Connection
Generator
L1
70
L2
L3
0 - 300 VAC
N
Line - Neutral
L1
L1 return
L2
L2 return
L3
L3 return
voltage
Generator
current
0 - 5 Amp
CT's
5 – 40 VDC
– ve DC
< 250 mA
70
71
72
73
74
75
76
77
78
79
16
Input 1: low oil pressure
17
Input 2: high engine temp.
18
Input 3: programmable
19
Input 4: programmable
20
Input 5: programmable
Index Pin21
22
Fuel output
23
Starter output
24
Output 5 (alarm): + ve, < 5A
25
NO
26
CO
27
Man. Start
28
29
Live
30
Neutral
71
72
73
74
75
76
77
78
79
1
–ve DC supply
2
Charge fail input
3
4
5
Magnetic pickup input
6
Output 1
7
Output 2
8
A800 enable output
9
Output 3: – ve, < 250mA
10
Output 4: – ve DC, < 5 A
11
Remote start/mains fail input
12
- No connection -
13
- No connection -
14
- No connection -
15
- No connection -
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
+ ve DC
< 16 A
Output 6 (gen. contctr)
volt free, < 5 A
Man. Stop
– ve
Generator AC
300 VAC max.
Typical Connection
M
L1
A
L2
I
L3
N
N
S
L1
UVR500
1 2 3 4 5 6
+ve DC
fuse
+
WL
A
–
magnetic
pickup
Autostart
5A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L1
LOAD
L2
730
generator
L3
N
contactor
70
71
72
73
74
75
76
77
78
79
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
GCR1
1A
1A
MCCB
GCR
1A
HET
inputs
RFL
start
manual
stop
manual
RST
RAL
fuel
starter
alarm
IP3
IP4
IP5
LOP
G
L1
E
L2
N
L3
E
N
R
A
T
O
R
mains
contactor
L2
L3
N
MCR
RPO1
RPO2
RPO3
RPO4
MCR1
Emergency
Stop
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Since 1939
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146
email: sales@fwmurphy.com
web: http://www.fwmurphy.com
Tel: + 44 1722 410055 Fax + 44 1722 410088
Pour service en Français, tél: + 44 1722 410697
email: sales@fwmurphy.co.uk
web: http://www.fwmurphy.co.uk
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89
Direct usine Tel: + 44 1722 410697
email: sales@fwmurphy.co.uk
No. 2 Tuas South Street 2, Sprintecs Building
02-01/02, Singapore 637895
Tel: + 65 863 1398 Fax: + 65 863 0208
email: fwmsales@fwmurphy.com.sg
PO Box 1819, Rosenberg, Texas 77471, USA
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006
email: sales@fwmurphy.com
41343 12th Street West, Palmdale, CA 93551, USA
Tel: + 1 661 272 4700 Fax: + 1 661 947 7570
email: sales@murphyswitch.com
web: http://www.murphyswitch.com
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P. México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336
email: murmexsl@sanluis.podernet.com.mx