Murphy AS705S User Manual

AUTOSTART 705 (AS705S series)
The Generator Controls Division of
R
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 705 provides the control features for the automatic or manual starting, load transfer and shutdown of a standby diesel generator or pump. The AS705 is a micro­processor based controller, giving full programmability of timers, trip levels and control options, with front facia LEDs for the indication of generator status and faults.
Automatic or manual operation, selected by rotary switch
(key-switch available as an option).
17 LED status and fault indicators, including 5 LEDs
for custom programming and labelling
RS232 communications link for engine monitoring,
control and Autostart programming from local PC
Comprehensive fault protection and alarm system:–
low oil pressure, high engine temperature, overspeed, underspeed, charge fail, emergency stop, start fail, high and low battery voltage, 3 programmable fault inputs.
6 programmable outputs, allowing remote signalling
and control of over 30 different functions.
Pin compatibility with Autostart 710 and Keystart 9700
ranges, allowing standardisation of panel wiring.
96 x 96mm DIN standard, front panel mounted case
Operation
Autostart’s operating mode is selected by use of its 3 position front facia switch:–
Off/reset. Disables the engine and resets a latched fault condition.
Automatic start-up, load transfer and return to standby in response to a mains fail or remote start condition, with full fault protection.
Manual start and stop of the generator, either immediately on selecting manual mode or by use of remote push button switches.
Green and amber LEDs around the switch indicate the selection of Auto and Manual modes. On keyswitch versions, the key is common to all units and may be removed in the Off and Auto positions only.
Control Outputs
The following are provided:-
Single pole, switched +ve relay outputs for the control
of engine fuel and starter motor circuits.
Switched +ve outputs for signalling auto and manual
modes, plus a –ve DC output for Off/reset.
6 function programmable outputs (see overleaf).
Fault Protection and Alarm System
In Auto or Manual modes, Autostart will shut down and latch out the generator on detection of low oil pressure, high engine temperature, overspeed, start fail or emergency stop faults. The Autostart may also be set up to shut down the generator on low generator frequency or speed.
3 additional inputs may be used with remote fault switches (giving a ‘shutdown’ or ‘warning’ response), or as control inputs with remote contacts or panel switches (see overleaf).
Non-latching, 'warning only' alarms are fitted for high and low battery volts, charge fail and mag. pickup fail conditions.
Issue 6, revised 06/99
M011101
Catalogue section 75
(MS5258)
Product Specification
Power supply:
Operating voltage: steady state range crank brown-out Current consumption typically 150 mA
Inputs:
DC inputs (inputs 1 - 5, remote start)
positive input voltage range 80% to 100% of battery +ve negative input voltage range –1V to +2V w.r.t. battery –ve
Generator AC input:-
operating voltage range 90 – 300 V AC rms frequency measurement range 0 – 99 Hz.
Magnetic pickup:-
operating voltage range 7 – 80 V AC rms frequency measurement range 0 to 10 kHz
Outputs: (all ratings for resistive load)
Start and fuel relays + ve DC (switched SPNO contact) Programmable outputs 1 – 3 – ve DC (open collector transistor) Programmable output 4 – ve DC (switched SPNO contact) Programmable output 5
(default setting: Common Alarm) Programmable output 6 (default setting: Gen. contactor) Auto & Manual outputs + ve DC, 250mA max. Off/reset output – ve DC, 250mA max.
Physical:
Overall dimensions (W x H x D) 96 x 96 x 162 mm Panel cut-out size DIN standard 92 x 92 mm Weight approx. 650 g Operating ambient temperature –10 to +55 oC Case sealing IP22
In order to consistently bring you the highest quality,
full featured products, we reserve the right to change our
specifications and designs at any time.
5 – 40 V DC continuous
to 0V for <= 100 mSec
rated 16A max. @ 24V DC
rated 250mA max. @ 33 VDC
rated 5A max. @ 24V DC
+ ve DC (switched SPNO contact)
rated 5A max. @ 24V DC
volt free SPNO contacts
rated 5A max. @ 240V AC
Programmable functions
16
17
18
19
20
22
23
24
25
26
27
28
29
30
21 Index Pin
– ve DC supply
Charge fail input
+ ve DC power supply
+ ve DC (relays)/Emerg. stop
A800 enable (engine running)
Output 3: –ve, < 250mA
Output 5 (alarm): +ve, 5A max.
250mA max.
MODEX
Frank W. Murphy Manufacturer Frank W. Murphy Southern Division
Frank W. Murphy Ltd.
Macquarrie Corporation
email: murphy@macquarrie.com.au
Murphy Switch of California
Murphy de Mexico S.A. de C.V.
Frank W. Murphy Pte, Ltd. Frank W. Murphy Ltd. en France
The Autostart 705 has over 40 programmable functions:-
Timers:-
Start delay; preheat, crank and crank cool (dwell) times; fault override time; warm-up delay, mains restore delay; engine cool (run on, off load) time, speed signal delay.
Inputs:-
Inputs 1 and 2 are dedicated for use with low oil pressure and high engine temperature switch sensors. Inputs 3, 4 and 5 may be programmed for a range of uses, including shutdown or warning faults, lamp test, manual restore (of mains), test off load, alarm mute, etc. The inputs may be set up to work with remote contacts which either open or close when active, with wiring to either +ve or –ve DC.
Outputs:-
6 programmable outputs, each of which may be set to give one of over 30 signalling or control ‘actions’, including: Preheat (4 types), Energised to Stop Fuel, Louvre Control, Generator Available, Common Alarm, Alarm (muteable), Shutdown Fault, Warning Fault, Overspeed, Start Fail, individual input faults (1 - 5), etc.
LED indicators:-
5 programmable LED indicators, each of which may be set to display extra status information (e.g. ‘generator on load’, ‘fuel on’) or specific faults which are not indicated by the dedicated LEDs (e.g. low/high/faulty battery voltage, low generator volts, magnetic pickup failure, etc.).
Next to the 5 LEDs is a windowed 'pocket' in the front label, into which a custom message label may be inserted. A sheet of typical fault and status messages is supplied with each unit.
Other System parameters:-
Crank release (by engine RPM, generator Hz. or charge alternator WL voltage), underspeed and overspeed trip levels (Hz. or RPM); maximum number of start attempts; high and low battery voltage warning levels; enable or disable loading of generator in manual mode.
Each Autostart is programmed by use of Murphy-Modex communication software running on an IBM compatible PC or lap-top. The computer is connected to the Autostart through a small interface unit and serial lead. Autostart program ‘profiles’ may be created, edited or saved on the computer’s hard disk, up-loaded from or down-loaded to any number of Autostarts, quickly and error-free.
The software also has a real-time monitoring feature, allowing the PC to display data such as operating mode, engine running status, speed/ frequency, hours run, fault conditions, battery voltage, input/output status, etc.
Front Facia
10 pre-set status and fault LEDs
5 programmable status LEDs (2 amber, 3 red)
3 position operating mode switch:-
Off/reset Auto Manual
START DEMAND ENGINE RUNNING START FAIL LOW OIL PRESSURE HIGH ENGINE TEMP OVERSPEED UNDERSPEED CHARGE FAIL PLANT FAIL EMERGENCY STOP
Rear Facia & Electrical Connection
1
5 – 40 VDC
2 3 4
Magnetic pickup input
5
Output 1
6
Output 2
7
– ve DC
8
Input 1: low oil pressure Input 2: high engine temp. Input 3: programmable Input 4: programmable Input 5: programmable
Fuel output Starter output
+ ve DC 16A max.
9
Output 4: –ve DC, 5A max.
10 11
Remote start/mains fail input
12
-
No connection -
13
Off output: – ve DC, < 250mA
14
Manual output
15
Auto output
+ ve DC 250mA max.
NO
Output 6 (gen. contactor)
CO
Live Neutral
volt free, 5A max.
Man. Start
Man. Stop
Generator AC 300 VAC max.
– ve
For a typical connection circuit, please see Autostart 710 data sheet (the Autostart 705 and 710 are pin compatible).
When ordering, please specify:-
Switch option:-
K = keyswitch R = rotary (knob) switch
Generator AC voltage:-
Accessories:-
AS7CA 9 way (interface) to 9 way (PC) comms lead AS7CB 9 way (interface) to 25 way (PC) comms lead AS7CC interface for local RS232 communications AS7CK AS7xx communication and programming software
D = 230 VAC C = 110 VAC
AS705S
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Since 1939
PO Box 470248, Tulsa, Oklahoma 74147, USA Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 email: sales@fwmurphy.com web: http://www.fwmurphy.com
Tel: + 44 1722 410055 Fax + 44 1722 410088 Pour service en Français, tél: + 44 1722 410697 email: sales@fwmurphy.co.uk web: http://www.fwmurphy.co.uk
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 Direct usine Tel: + 44 1722 410697 email: sales@fwmurphy.co.uk
No. 2 Tuas South Street 2, Sprintecs Building 02-01/02, Singapore 637895 Tel: + 65 863 1398 Fax: + 65 863 0208 email: fwmsales@fwmurphy.com.sg
PO Box 1819, Rosenberg, Texas 77471, USA Tel: + 1 281 342 0297 Fax: + 1 281 341 6006 email: sales@fwmurphy.com
41343 12th Street West, Palmdale, CA 93551, USA Tel: + 1 661 272 4700 Fax: + 1 661 947 7570 email: sales@murphyswitch.com web: http://www.murphyswitch.com
1620 Hume Highway, Campbellfield, Vic. 3061 Australia Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P. México 78384 Tel: + 52 48 206264 Fax: + 52 48 206336 email: murmexsl@sanluis.podernet.com.mx
Loading...