Murphy AS3000 User Manual

AS3000-02127B page 1 of 2
AS3000-02127B
Revised 05-03
Catalog Section 75
(00-02-0525)
Automatic Engine Controller
FWMurphy
AS3000 Model
Auto crank disconnect
Multi-attempt starting
Fault warning and shutdown
Reduced panel wiring
Simple set set-up
Description
The AS3000 provides automatic start up, fault mon­itoring and shutdown control for engine driven applications. The unique two-module design, with a single interconnecting lead, gives reduced panel wiring and installation. This simple, compact unit is ideally suited to small engine and generator panels.
Key features
Multi-attempt cranking with auto crank disconnect
Automatic or manual modes, selected by front
facia pushbuttons. Control inputs for optional security keyswitch.
User inteface module: front of panel mounted,
92mm square DIN cut-out. Environmental sealing to IP65
Panel interface module: DIN rail mounted
PCB tray.
Fault shutdown and indication system. Low oil pressure, high coolant temperature and auxil­iary inputs are fitted to both modules, allowing use with engine mounted fault switches or panel mounted SWICHGAGE
®
units.
Speed sensing (auto crank disconnect and over­speed shutdown) is via magnetic pickup, gen­erator AC or remote contact. Speed calibration is automatic and adjustment free.
Mains charger/charge alternator fail warning LED.
Easy setup of operating options using circuit board links.
Generator AC Hz meter output, 0 – 5V.
Product Specification
Power supply
Continuous voltage range: 8 – 35 VDC Brown out voltage: < 5 VDC for 2 secs
(recovery to 8V)
Blackout voltage: 0V for 50mS (from 10V,
recovery to 5V)
Overvoltage withstand: 50 VDC for 5 sec-
onds (to SAEJ1810 load dump immunity)
Reverse voltage withstand:
100 VDC continuous.
Current consumption (standby): 50mA. Current consumption (max): 500mA (plus
output loads).
DC Inputs
Oil pressure, coolant temp, auxiliary and
charger faults: Closed to negative DC
(±3V) on fault.
Remote start positive: Open from positive
DC to start.
Remote start negative: Close to negative DC
(±3V) to start.
Lamp test: Close to negative DC (±3V)
to activate.
DC input protection: ±50 VDC maximum.
AC Inputs
Magnetic pickup: 3 – 60 VAC, 50Hz – 10 kHz. Generator AC: 600 VAC maximum (L-L or
L-N), 50/60 Hz.
Outputs
Fuel: positive DC (transistor), 5A max. Crank, preheat: positive DC (transistor),
2A max.
Common alarm, fault lockout: negative DC
(
transistor), 300mA max.
Generator Hz. Meter: 0-1mA (@ 45-65 Hz).
Physical
Dimensions: see “System Overview” on page 2. Operating temperature: 14 to 149°F (-10 to
+65°C). Relative humidity: 95% @ 140°F (60 °C). Environmental protection: AS3000 front:
IP65, NEMA4. Back of User Interface and Panel interface require weather-proof enclosures for outdoor use.
Vibration: ISO 88528 pt.9, & 3 axis 3g. Weight:
AS3000 User Interface: approx. 9 oz. (250g). AS300 Panel Interface: approx. 6 oz. (160g).
Shipping Weight: 1 lb. 4 oz. (554 g.). Shipping Dimensions: 7-3/8 x 5 x 3-1/8 inch.
(187 x 127 x 79 mm.).
AS3000-02127B page 2 of 2
How to order
Stock no. Unit type
Complete systems:
41.70.0093 AS3000 system, white faceplate
41.70.0100 AS3000 system, black faceplate
Components:
41.05.0001 AS3000 User Interface, black faceplate
41.05.0002 AS3000 Panel Interface
41.05.0003 AS3000 User Interface, white faceplate
System OverviewSystem Overview
9 8 7 6 5 4 3 2 1
AS3000 User Interface
AS3000 User Interface back view
Te rm i n als 31 - 39
(1/4" blades)
:
OFF-STOP (reset)
MANUAL mo de (+ amber LED)
AUTO mod e (+ green LED)
S
8
l
- Engine running
- Charge fault
- Auxiliary / plant fault
- Start fail/overcrank fault
- Low oil pressure fault
- High engine temp fault
- Overspeed fault
Mounting
clamp
Communication
Lead
Te rm i n als 1 - 21
(1/4" blades)
Operating option links, for setting:
- crank/rest time (5, 10 or 15 seconds)
- preheat time (0, 5, 10 or 15 seconds)
- crank disconnect speed (40% or 10%)
- engine cool time (0 or 5 minutes)
- number of crank attempts (1, 3 or 6)
- loss of speed (warning or shutdown)
31 32 33 34 35 36 37 38 39
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
3.8 in.
8 in.
(96mm)
(96mm)
(96mm)
3.8 in.
8 8
(96m)
m
3.67 in.
(93 mm)
d
1.1 in.
(28mm)
d1.9 in.
(48mm)
6.1 in. (154 mm)
AUTO
Elec
tri
cal ConnectionElec
tri
cal Connection
lamp
test
panel DC positiv
e
12 - 24 VDC
panel DC negative
low
oi
l
pressure
openwhenhealth
y
aux.
fault
hig
h
engin
e
te
mp
enabl
e
keyswitch
(link if not used
)
AC Hz.
m
eter output
01mA
(=4565 Hz
)
into50Ohm
m
ovingcoi
l m
ete
r
common
alarm
300 mA
comm
s
fue
l
rela
y
5 A
crank
rela
y
2 A
DC
power
suppl
y
1 2 3 4 5 6 7 8 9
31 32 33 34 35 36 37 3
8
10 11 12 13 14 15 16 17 18 19 20
21
common
alarm
300 mA
charg
e
alternato
r
D
+ /WL
preheat
rela
y
2 A
fault
lockout
300 mA
remote
star
t
negative
remote
star
t
positive
low
oi
l
pressure
aux.
fault
overspeed
fault
speed inpu
t
magnetic pickup
3-60V
0-10k
Hz
speed inpu
t
generator A
C
80 - 600 V
50/60 Hz
charger
fai
l
hig
h
engin
e
temp.
crank
disconnect
AS3000
User Interface/
Display Module
AS3000
Panel Interface Module
RL
RLRLRL RL
RL
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA (281) 633-4500 fax (281) 633-4588
e-mail sales@fwmurphy.com MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384 +52-444-8206264 fax +52-444-8206336 Villahermosa Office +52-993-3162117 e-mail ventas@murphymex.com.mx www.murphymex.com.mx
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. +44 1722 410055 fax +44 1722 410088 e-mail sales@fwmurphy.co.uk www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West Palmdale, California 93551-1442; USA (661) 272-4700 fax (661) 947-7570 e-mail sales@murphyswitch.com www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
MACQUARRIE CORPORATION
1620 Hume Highway Campbellfield, Vic 3061; Australia +61 3 9358-5555 fax +61 3 9358-5558 e-mail murphy@macquarrie.com.au
FWMurphy
P.O. Box 470248 Tulsa, Oklahoma 74147 USA (918) 317-4100
fax (918) 317-4266 e-mail sales@fwmurphy.com
www.fwmurphy.com
R
E
G
I
S
T
E
R
E
D
Printed in U.S.A.
Warranty
A two-year warranty on materials and workmanship is given with this FWMurphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/warranty.asp.
CAUTION: Do not bundle AC and DC wiring together. They must be separated by 2 inches ideally, and require separate conduit runs.
AS3000 Panel Interface
Operator control keys
tatus/fault LED indicators x
- Remote start/Mains fai
closedonfaul
t
Loading...