Murphy A900 User Manual

SERIES A900
MURPHYMATIC
®
GENERATOR
ENGINE CONTROL SYSTEM
DESIGN, INSTALLATION
AND OPERATING MANUAL
A900-9025N
Section 40
(00-02-0197)
BEFORE BEGINNING
INSTALLATION OF THIS
MURPHY PRODUCT
Disconnect all electrical
power to the machine.
Make sure the machine
cannot operate during installation.
Follow all safety warnings of
the machine manufacturer.
Read and follow all
installation instructions.
Certain danger to human safety and to equipment may occur if some equipment is stopped without pre­warning. It is recommended that monitored functions be limited to alarm-only or to alarm before shutdown.
WARNING
Table of Contents
Section 1: Introduction page 1
1-1 System 1 1-2 Models 1 1-3 Purpose 1 1-4 Definitions 1 1-5 How To Use This Manual 1
Section 2: Specifications 1
2-1 Enclosure Type 1 2-2 Power Requirements 1 2-3 Input Ratings 1 2-4 Output Ratings 1 2-5 Field Wiring Connections 1 2-6 Operating Temperature 1
Section 3: Model Identification 1
3-1 Model Numbers 1 3-2 A901 2 3-3 A901-2 5 3-4 A902 7 3-5 A902-2 8
3-6 A903 10 3-7 A903-2 12
Section 4: Installation 14
4-1 Location 14 4-2 Wiring 14 4-3 Crank Disconnect 19 4-4 Pre-Operational Check-Out 19
Section 5: Operation 21
5-1 Operator Controls 21 5-2 Operating Modes 21
Section 6: Routine Maintenance and Operational Tests 21
6-1 Routine Maintenance 21 6-2 Operational Tests 21
Section 7: Troubleshooting and Repair 21
7-1 Tools Required 21 7-2 A900 SELECTRONIC®Control Operation and Shutdown 21 7-3 A900 SELECTRONIC®Control Alarm Circuit Operation 23
Section 8: Service Parts 24
8-1 Table 8-1: Replacement Components of the A900 Series Generator Controls 24 8-2 Table 8-2: Replacement Components of the A900 Controls for Detroit Diesel 24
Section 1: Introduction
1-1 System. 1-1.1 The MURPHYMATIC®Generator Engine Control System,
Series A900 is designed to meet the requirements of the engine control, shutdown and alarm section of NFPA-110 “Emergency And Standby Power Systems” specification. The controller also meets the minimum requirements of NFPA99 “Health Care Facilities” and the Canadian standard CAN/CSA-C282-M89 “Emergency Electrical Power Supply for Buildings” for engine control, shutdown and alarm systems. By combining one of the A900 series controls with generator instruments, a complete engine generator control panel meeting the above specifications can be provided.
1-2 Models. 1-2.1 The Series A900 is available in three basic configurations: 1-2.1.1 Model A901 for automatic start and stop generator sets
which includes the minimum shutdowns and alarms per NFPA­110 Level 1. 1-2.1.2 Model A902 for automatic start and stop generator sets which includes the minimum shutdowns and alarms per NFPA­110 Level 2. 1-2.1.3 Model A903 for automatic start and stop generator sets which includes the minimum shutdowns and alarms per NFPA­110 Level 2 and seven unlabeled alarm lights for additional customer specified alarms.
1-2.2 All models are available for 12 or 24 V DC operation. 1-2.3 All models are available for use on either two cycle or four
cycle engines. Models for two cycle engines include an alarm light for “Air Damper Closed” and an “Overspeed Relay” to operate the air shutoff solenoid for overspeed shutdown. 1-2.4 Each model is made up of two parts, a Control/Display module and a Relay module.
1-3 Purpose. 1-3.1 This manual is directed to the installation, maintenance and
operating personnel who will be in day to day contact with the A900 system. However the basic knowledge gained with this material will allow those personnel to easily adjust to special circumstances.
1-4 Definitions. 1-4.1 Throughout this manual, reference is made to organi-
zations, trade names and trademarks which may not be familiar to the reader. Some of these are:
1-4.1.1 CSA: Canadian Standards Association. 1-4.1.2 CAN/CSA-C282-M89: The standard for Emergency
Electrical Power Supply for Buildings, 1989 Edition.
1-4.1.3 NFPA: National Fire Protection Association. 1-4.1.4 NFPA-70: The National Electrical Code. 1-4.1.5 NFPA-99-1990: The standard for Health Care Facilities,
1990 Edition. 1-4.1.6 NFPA-110-1988: The standard for Emergency And Standby Power Systems, 1988 Edition. 1-4.1.7 Several terms used in this manual are registered trademarks of Frank W. Murphy Mfr .
(a) MURPHYMATIC®: Refers to all Murphy automatic controls. (b) SELECTRONIC®: A name that is applied to all electronic
controls manufactured by Murphy. (c) SWICHGAGE®: A combination indicating gauge and switch. (d) T ATTLET ALE®: A term that refers to a shutdown indicating
device or circuit in the control panel.
1-5 How to use this manual. 1-5.1 Section 1, 2, 4, 5, 6 and 7 contain general information that
applies to all A900 models. 1-5.2 Section 3, Model Identification, is broken into seven sub sections. Section 3-1 allows you to chose the model that best fits your requirements and Section 3-2 through 3-7 explain each models features in detail.
Section 2: Specifications
2-1 Enclosure Type. 2-1.1 The A900 Series enclosure is designed to be mounted in a
standard electrical enclosure for indoor use.
2-2 Power Requirements. 2-2.1 The engine controls, shutdown circuits, alarm and shut-
down indicators are powered from the engine starting battery. The A900 series is available in either 12 or 24 V, negative ground.
2-2.2 The A900 is fused for 3 A maximum current. 2-3 Input Ratings.
2-3.1 All input switches should be dry contact type, maximum
current is 2 mA, 8 V DC or less. 2-3.2 Frequency signal for the speed sensing circuit requires a minimum input of 2 V rms from a magnetic pickup (preferred) or from the tachometer terminal of the battery charging alternator . 2-3.2.1 Frequency range of the speed sensing circuits is 25 Hz to 10,000 Hz.
2-4 Output Ratings. 2-4.1 The A900 Control / Display Module has outputs for remote
indication of alarm and shutdowns. These outputs are transistors that close to the negative supply (sink) and are rated at 1 amp, 30 V DC maximum. 2-4.2 The Control / Display Module also has an output for an auxiliary starter contactor which is rated 1 A, 30 V DC maximum. This is a transistor that closes to the positive supply (source). 2-4.3 The Relay Module includes 3 engine control relays with contact ratings of 7 A, 30 V DC inductive. These powered contacts must be supplied from an 8 A fuse or circuit breaker (customer supplied). The 3 alarm relays have dry contacts, also rated at 7 A, 30 V DC maximum.
2-5 Field Wiring Connections. 2-5.1 All field wiring connections are barrier terminal blocks, UL
rated for 15 A, 300 V.
2-6 Operating Temperature. 2-6.1 The operating temperature range of the A900 is -4°F to
158°F (-20°C to 70°C.)
Section 3: Model Identification
3-1 Model Numbers. 3-1.1 A901-12 and A901-24: These models are designed for an
automatic start four cycle engine driven generator, and include the shutdown and alarm points recommended in NFPA­110-1988 “Emergency and Standby Generator Systems” for Level 1 installations. These controllers also meet or exceed the minimum requirements of NFPA99-1990 “Health Care Facilities” and with the addition of a Low Water Level alarm, the Canadian standard CAN/CSA-C282-M89 “Emergency Electrical Power Supply for Buildings”. The suffix numbers -12 and -24 indicate the engine starting battery voltage. 3-1.2 A901-2-12 and A901-2-24: These models are designed for
1
an automatic-start, two-cycle, engine-driven generator, and include the shutdown and alarm points recommended in NFPA­110-1988 “Emergency and Standby Generator Systems” for Level 1 installations. These controllers also meet or exceed the minimum requirements of NFPA-99-1990 “Health Care Facilities” and with the addition of a Low Water Level alarm, the Canadian standard CAN/CSA-C282-M89 “Emergency Electrical Power Supply for Buildings”. The suffix numbers -12 and -24 indicate the engine starting battery voltage. 3-1.2.1 The A901-2 series control includes an “Air Damper Closed” light and “Overspeed Relay” to trip the air shut-off solenoid on overspeed of a two-cycle engine. 3-1.3 A902-12 and A902-24: These models are designed for an automatic-start, four-cycle, engine-driven generator, and include the shutdown and alarm points recommended in NFPA-110­1988 “Emergency and Standby Generator Systems” for Level 2 installations. The suffix numbers -12 and -24 indicate the engine starting battery voltage. 3-1.4 A902-2-12 and A902-2-24: These models are designed for an automatic-start, two-cycle, engine-driven generator, and include the shutdown and alarm points recommended in NFPA­110-1988 “Emergency and Standby Generator Systems” for Level 2 installations. The suffix numbers -12 and -24 indicate the engine starting battery voltage. 3-1.4.1 The A902-2 series control includes an “Air Damper Closed” light and “Overspeed Relay” to trip the air shut-off solenoid on overspeed of a two-cycle engine. 3-1.5 A903-12 and A903-24: These models are designed for an automatic-start, four-cycle, engine-driven generator, and include the shutdown and alarm points recommended in NFPA-110­1988 “Emergency and Standby Generator Systems” for Level 2 installations plus seven unlabeled alarms that the user may specify and an “Alarm Silence Switch”. The suffix numbers -12 and -24 indicate the engine starting battery voltage. 3-1.6 A903-2-12 and A903-2-24: These models are designed for an automatic-start, two-cycle, engine driven generator, and include the shutdown and alarm points recommended in NFPA­110-1988 “Emergency and Standby Generator Systems” for Level 2 installations plus seven unlabeled alarms that the user may specify and an “Alarm Silence Switch”. The suffix numbers
-12 and -24 indicate the engine starting battery voltage. 3-1.6.1 The A903-2 series control includes an “Air Damper Closed” light and “Overspeed Relay” to trip the air shut-off solenoid on overspeed of a two-cycle engine. 3-1.7 Table 3-1.7 illustrates the alarm and shutdown require­ments of NFPA-110, NFPA99 and CAN/CSA-C282-M89 and compares the features of the A900 series controls to those requirements.
3-2 A901. 3-2.1 Control / Display Module. The Control / Display Module,
figure 3-2.1, includes the control and test switches, the solid state logic elements, shutdown and alarm TATTLETALE®lights that make up the generator engine control for a four-cycle engine. 3-2.1.1 Mode Selector Switch, OFF-AUTO-TEST :
(a) OFF; turns off the control system and resets any shutdown
circuits.
(b) AUTO; turns on the engine controls and shutdown circuits.
System is on standby waiting for a contact closure to start engine.
(c) TEST; turns on the engine controls and shutdown circuits.
A start signal is applied to the automatic control and the engine start sequence begins.
3-2.1.2 Lamp Test Pushbutton: Tests the lights on the A901 module. 3-2.1.3 Alarm Silence Pushbutton: Turns off any audible alarm that is connected to the Local or Remote Audible Alarm Relays. The indicating light will remain on as long as the condition exists. If the Alarm Silence pushbutton is not operated, the audible alarm will turn off when the alarm contact clears. 3-2.1.4 The A901 SELECTRONIC®Control Module includes the following engine control features:
(a) Cycle crank circuit; will crank the engine for 15 seconds
then rest for 15 seconds until the engine starts. The crank/rest time can be selected for either 10, 15, 20, 25 or 30 seconds. If the engine false starts, goes above crank disconnect speed then drops below that speed, the control will rest for a fixed 10 second period before cranking again.
(b) Crank Disconnect Speed Switch; this circuit detects
engine speed and terminates cranking when engine speed rises above the speed switch setting. The speed switch is adjustable, 25 Hz to 2000 Hz, and is factory set at 1180 Hz. This would be 600 RPM on an engine with 118 teeth on the flywheel ring gear.
(c) Auxiliary Crank Disconnect Circuit; this circuit, required by
NFPA-110, is provided as a back up for the Crank Disconnect Speed Switch. It is operated by an external switch sensing either speed, generator voltage or some other variable that could be used to terminate cranking. Either circuit will disconnect the starter when the engine starts.
Low Water
Temperature
AUTO
OFF
TEST
Loss of Speed
Signal
Lamp Test
Water
Temperature
Low Battery
Voltage
Alarm Silence
High Battery
Voltage
Low Fuel
Level
High Water Temp.
PreAlarm
Battery Charger
AC Failure
Switch
Not In AUTO
Low Oil Pressure
PreAlarm
Oil Pressure
Overspeed
Overcrank
6-1/2 in.
(165 mm)
9-3/4 in.
(248 mm)
Figure 3-2.1
2
Table 3-1.7
3
Level 1
C.V.
S
L.A.
R.A.
R.V.
Level 2
C.V.
S
L.A.
R.A.
R.V.
NFPA-110
NFPA99
C.V.
S
L.A.
R.A.
R.V.
CAN/CSA
C282-M89
C.V. S L.A. R.A. R.V.
A901
C.V.
S L.A. R.A. R.V.
A902
C.V. S L.A.
R.A.
R.V.
A903
C.V.
S
L.A.
R.A. R.V.
a. Overcrank X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
b. Low Water Temperature X — X X X X — X O O X — X X X X — X X X X — X X X X — X O O X — X O O
c. High Engine Temp. Prealarm X — X X X O — O — O X — X X X O — O O O X — X X X — — — — — — X O O
d. High Engine Temperature X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
e. Low Lube Oil Pressure Prealarm X — X X X X X O — O X — X X X O — O O O X — X X X — — — — — — X O O
f. Low Lube Oil Pressure X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
g. Overpeed X X X X X X X X O O X X X X X X X X X X X X X X X X X X O O X X X O O
h. Low Fuel Main Tank X — X X X O — O O O X — X X X X — X X X X — X X X — — — — — — X O O
i. Control Switch not set in Auto X — X X X O — O — O — — — — — X — X X X X — X X X — — O — O — — — —
j. High Battery Voltage X — X — X O — O — O — — — — — — — — — — X — X — X — — O — O — — — —
k. Low VoltageBattery X — X — X O — O — O — — — — — X — X X X X — X — X — — O — O — — — —
l. Lamp Test X — — — X X — — — — — — — — — X — — — — X — — — — X — — — — X — — — —
m. Audible Alarm Silencing switch — — X X — — — — O — — — — — — — — X X — — — — X — — — — O — — — X O —
n. Low Starting Air Pressure X — X — X O — O — O — — — — — X — X X X — — — — — — — — — — — — — — —
o. Low Starting Hydraulic Pressure X — X — X O — O — O — — — — — X — X X X — — — — — — — — — — — — — — —
q. Remote Emergency Stop — X — — — — X — — — — — — — — — O — — — — X — — — — X — — — — X — — —
r. Low Coolant Level — — — — — — — — — — — — — — — X — X X X — — — — — — — — — — — — — — —
s. Battery Charger AC Failure X — X — X O — O — O — — — — — — — — — — X — X — X — — O — O — — — —
③③ ③③
KEY
C.V.: Control panel-mounted Visual indication.
S: Shutdown of EPS
L.A.: Local Audible contacts.
R.A.: Remote Audible contacts.
R.V.: Remote Visual contacts.
X: Required
O: Optional
: Items “N” or “O” apply only when applicable as
a starting method.
: NFPA99 requires an audible alarm for all alarm and
shutdown functions. May be connected to L.A. contacts.
③: Air Damper Closed and is available on -2 models only.
④: R.A. and R.V. relays not supplied in model A902 or
A903, optional.
: Circuits and indicators supplied without labels.
p. Air shutdown dampner when used X X X X X X X X O O — — — — — X X X — X X X X X O O X O O
(d) Overcrank circuit; will stop automatic cranking and
indicate overcrank if engine fails to start after 3 attempts.
The number of cranks are selectable for 1, 2, 3, 4 or 5
cycles before shutdown. The overcrank circuit may also
be turned off so no overcrank shutdown occurs.
(e) Shutdown Time Delay Bypass; this delay prevents the oil
pressure, water temperature and loss of speed signal
shutdown circuits from operating for 15 seconds after the
engine starts as detected by the crank disconnect circuit.
This same delay also locks out the Low Oil Pressure Pre-
alarm and High Water Temperature Pre-alarm circuits
when the engine is not running.
(f) Overspeed Speed Switch;
1. Provides a signal to the overspeed shutdown circuit if the engine exceeds the preset speed. The factory setting is approximately 3894 Hz, or 1980 RPM on an engine with 118 teeth on the flywheel ring gear. The adjustment range is 300 Hz to 10,000 Hz.
2. A push-to-test switch is provided to allow testing of the overspeed circuit without overspeeding the engine. When switch is depressed, the set point of the speed switch is lowered approximately 10%.
3. The push-to-test switch can also be used to set the overspeed switch at approximately 110% of running speed. Hold the switch depressed while adjusting the setting until the overspeed trips. When switch is released, the set point will be 10% above normal running speed. This is the method used to make the factory setting. With engine speed at 1800 RPM or 3540 Hz.
(g) Cooldown circuit; this circuit keeps the engine running
for five minutes after the transfer switch has removed the load from the generator and signaled the A901 to stop the engine. This feature may be selected (turned On, standard setting is Off) with a switch on the back of the Control / Display Module.
3-2.1.5 Seven (7) First-out Shutdown Circuits; provide first-out indication of cause of shutdown. These circuits deactivate the fuel relay and lockout the A901 until reset. Shutdown circuits are activated by the crank disconnect circuit and are not active when the engine is stopped. Six (6) Red Shutdown Indicating Lights are provided. The Remote Shutdown circuit does not have an indicator light.
(a) Overcrank; tripped by the overcrank sensing circuit which
counts the number of cranking attempts.
(b) Overspeed; tripped by overspeed switch when engine
exceeds a preset speed.
(c) Oil Pressure; tripped by the oil pressure SWICHGAGE
®
if pressure drops below preset point while the engine is running.
(d) Water Temperature; tripped by the water temperature
SWICHGAGE®if engine coolant temperature exceeds the switch setting.
(e) Spare Shutdown; tripped by an external switch. This
circuit is provided for an additional shutdown that may be recommended by the engine supplier.
(f) Loss of Speed Signal; tripped by an internal sensing
circuit that detects the loss of the Magnetic Pickup frequency signal for the speed switches while the engine is still running. Since the Overspeed shutdown circuit is
activated by the frequency input, it prevents the engine from running without overspeed protection.
(g) Remote Shutdown; this circuit is provided to shutdown
the engine generator from a remote location. No indicating light is provided.
3-2.1.6 Nine (9) Alarm Indicating Circuits; provide indication of cause of alarm. These circuits activate the alarm relays. Alarm circuits are active as long as power is applied to the A901. All are active when the engine is running, shutdown or on standby except Low Oil Pressure Pre- alarm and High Water Temperature Pre­alarm. Nine (9) Amber Alarm Indicating Lights are provided.
(a) Low Water Temperature; operated by low water temp-
erature SWICHGAGE®.
(b) Spare Alarm; operated by an external switch. This circuit
is provided for an additional alarm that may be required by the user.
(c) Switch Not In Automatic; operated by the OFF-AUTO-
TEST mode selector switch. (d) Low Fuel Level; operated by level switch on fuel tank. (e) High Battery Voltage; operated by relay contact in
battery charger. (f) Low Battery Voltage; operated by low voltage sensing
device in battery charger . (g) Low Oil Pressure Pre-alarm; operated by pre-alarm
switch in oil pressure SWICHGAGE®.
(h) High Water Temperature Pre-alarm; operated by pre
alarm switch in water temperature SWICHGAGE®.
(i) Battery Charger AC Failure: operated by a relay contact in
the Battery Charger .
3-2.2 Relay Module. The Relay Module, figure 3-2.2, includes all of the control, alarm and shutdown relays that are required to make up the generator engine control. Relays are available for operation on either 12 or 24 volt battery systems. Five (5) relays are included for: 3-2.2.1 Fuel Relay; this relay provides two outputs, one to energize the engine fuel solenoid and a separate circuit to
4
DC12V
3A Fuse
1A
4 5 6 7 8 9
16 17 18 19 20 21 22 23 24 25
RH2V2
-U
DC12V
RH2V2
-U
DC12V
RH2V2
-U
DC12V
RH2V2
-U
DC12V
RH2V2
-U
6-1/4 in.
(159 mm)
4-1/2 in.
(114 mm)
Figure 3-2.2
energize the battery charging alternator field. 3-2.2.2 Shutdown Relay; this relay is operated by the shutdown circuits of the Control / Display Module and provides an output that can be used to trip the generator circuit breaker on an emergency shutdown. 3-2.2.3 Local Audible Alarm Relay; provides a contact closure to operate a local audible alarm as required by NFPA-110, Level 1 and Level 2. 3-2.2.4 Remote Audible Alarm Relay; provides a contact closure to operate a remote audible alarm as required by NFPA­110, Level 1. 3-2.2.5 Remote Visual Alarm Relay; provides a contact closure to operate a remote visual alarm as required by NFPA- 110, Level 1. 3-2.3 Status Signals. The relay module also includes three outputs that can be used with external circuits for signaling or control functions. 3-2.3.1 The Control On function at terminal 12 is on (closed to negative) as long as the Mode Selector Switch is in either Auto or Test. When the Mode Selector is turned Off, the Control On signal is open. This can be used to signal switch position or to reset an external circuit when the Mode Selector is turned Off. 3-2.3.2 The System Ready signal at terminal 13 is on (closed to negative) as long as the Mode Selector Switch is in either Auto or Test and no shutdown Tattletale circuit is latched on. This can be used to signal that the generator engine is ready to automatically start or is running in Test. 3-2.3.3 The Control On function at terminal 14 is on (closed to positive) as long as the Mode Selector Switch is in either Auto or Test. When the Mode Selector is turned Off, the Control On signal is open. This can be used to signal switch position or to reset an external circuit when the Mode Selector is turned Off.
3-3 A901-2. 3-3.1 Control / Display Module. The Control / Display Module,
figure 3-3.1, includes the control and test switches, the solid state logic elements, shutdown and alarm TATTLETALE®lights that make up the generator engine control for a two-cycle engine. 3-3.1.1 Mode Selector Switch, OFF-AUTO-TEST :
(a) OFF; turns off the control system and resets any shutdown
circuits.
(b) AUTO; turns on the engine controls and shutdown
circuits. System is on standby waiting for a contact closure to start engine.
(c) TEST; turns on the engine controls and shutdown circuits.
A start signal is applied to the automatic control and the engine start sequence begins.
3-3.1.2 Lamp Test Pushbutton: Tests the lights on the A- 901-2 module. 3-3.1.3 Alarm Silence Pushbutton: Turns off any audible alarm that is connected to the Local or Remote Audible Alarm Relays. The indicating light will remain on as long as the condition exists. If the Alarm Silence pushbutton is not operated, the audible alarm will turn off when the alarm contact clears. 3-3.1.4 The A901-2 SELECTRONIC
®
Control Module includes
the following engine control features:
(a) Cycle crank circuit; will crank the engine for 15 seconds
then rest for 15 seconds until the engine starts. The
crank/rest time is selectable for either 10, 15, 20, 25 or 30 seconds. If the engine false starts, goes above crank disconnect speed then drops below that speed, the control will rest for a fixed 10 second period before cranking again.
(b) Crank Disconnect Speed Switch; this circuit detects
engine speed and terminates cranking when engine speed rises above the speed switch setting. The speed switch is adjustable, 25 Hz to 2000 Hz, and is factory set at 1180 Hz. This would be 600 RPM on an engine with 118 teeth on the flywheel ring gear.
(c) Auxiliary Crank Disconnect Circuit; this circuit, required by
NFPA-110, is provided as a back up for the Crank Discon­nect Speed Switch. It is operated by an external switch sensing either speed, generator voltage or some other variable that could be used to terminate cranking. Either circuit will disconnect the starter when the engine starts.
(d) Overcrank circuit; will stop automatic cranking and
indicate overcrank if engine fails to start after 3 attempts. The number of cranks are selectable for 1, 2, 3, 4 or 5 cycles before shutdown. The overcrank circuit may also be turned off so no overcrank shutdown occurs.
(e) Shutdown Time Delay Bypass; this delay prevents the oil
pressure, water temperature and loss of speed signal shutdown circuits from operating for 15 seconds after the engine starts as detected by the crank disconnect circuit. This same delay also locks out the Low Oil Pressure Pre­alarm and High Water Temperature Pre-alarm circuits when the engine is not running.
Low Water
Temperature
AUTO
OFF
TEST
Loss of Speed
Signal
Lamp Test
Water
Temperature
Air Damper
Closed
Low Battery
Voltage
Alarm Silence
Battery Charger
AC Failure
High Battery
Voltage
Low Fuel
Level
High Water Temp.
PreAlarm
Switch
Not In AUTO
Low Oil Pressure
PreAlarm
Oil Pressure
Overspeed
Overcrank
6-1/2 in.
(165 mm)
9-3/4 in.
(248 mm)
Figure 3-3.1
5
(f) Overspeed Speed Switch;
1. Provides a signal to the overspeed shutdown circuit if the engine exceeds the preset speed. The factory setting is approximately 3894 Hz, or 1980 RPM on an engine with 118 teeth on the flywheel ring gear. The adjustment range is 300 Hz to 10,000 Hz.
2. A push to test switch is provided to allow testing of the overspeed circuit without overspeeding the engine. When switch is depressed, the set point of the speed switch is lowered approximately 10%.
3. The push to test switch can also be used to set the overspeed switch at approximately 110% of running speed. Hold the switch depressed while adjusting the setting until the overspeed trips. When switch is released, the set point will be 10% above normal running speed. This is the method used to make the factory setting. With engine speed at 1800 RPM or 3540 Hz.
(g) Cooldown circuit; this circuit keeps the engine running
for five minutes after the transfer switch has removed the load from the generator and signaled the A901-2 to stop the engine. This feature may be selected (turned On, standard setting is Off) with a switch on the back of the Control / Display Module.
3-3.1.5 Seven (7) First-out Shutdown Circuits; provide first-out indication of cause of shutdown. These circuits deactivate the fuel relay and lockout the A901-2 until reset. Shutdown circuits are activated by the crank disconnect circuit and are not active when the engine is stopped. Six (6) Red Shutdown Indicating Lights are provided. The Remote Shutdown circuit does not have an indicator light.
(a) Overcrank; tripped by the overcrank sensing circuit which
counts the number of cranking attempts.
(b) Overspeed; tripped by overspeed switch when engine
exceeds a preset speed.
(c) Oil Pressure; tripped by the oil pressure SWICHGAGE®if
pressure drops below preset point while the engine is running.
(d) Water T emperature; tripped by the water temperature
SWICHGAGE®if engine coolant temperature exceeds the switch setting.
(e) Spare Shutdown; tripped by an external switch. This
circuit is provided for an additional shutdown that may be recommended by the engine supplier.
(f) Loss of Speed Signal; tripped by an internal sensing
circuit that detects the loss of the Magnetic Pickup frequency signal for the speed switches while the engine is still running. Since the Overspeed shutdown circuit is activated by the frequency input, it prevents the engine from running without overspeed protection.
(g) Remote Shutdown; this circuit is provided to shutdown
the engine generator from a remote location. No indicating light is provided.
3-3.1.6 Nine (9) Alarm Indicating Circuits; provide indication of cause of alarm. These circuits activate the alarm relays. Alarm circuits are active as long as power is applied to the A901-2. All are active when the engine is running, shutdown or on standby except Low Oil Pressure Pre- alarm and High Water Temperature Pre-alarm. Nine (9) Amber Alarm Indicating Lights are provided.
(a) Low Water Temperature; operated by low water temp-
erature SWICHGAGE®.
(b) Air Damper Closed; operated by an external switch or by
the Overspeed Relay circuit. This circuit is provided with a selector switch to allow the user to determine the source of the signal.
(c) Switch Not In Automatic; operated by the OFF-AUTO-
TEST mode selector switch. (d) Low Fuel Level; operated by level switch on fuel tank. (e) High Battery Voltage; operated by relay contact in battery
charger . (f) Low Battery Voltage; operated by low voltage sensing
device in battery charger . (g) Low Oil Pressure Pre-alarm; operated by pre-alarm
switch in oil pressure SWICHGAGE®. (h) High Water Temperature Pre-alarm; operated by pre-
alarm switch in water temperature SWICHGAGE®. (i) Battery Charger AC Failure; operated by relay contact in
Battery Charger .
3-3.2 Relay Module. The Relay Module, figure 3-3.2, includes all of the control, alarm and shutdown relays that are required to make up the generator engine control. Relays are available for operation on either 12 or 24 volt battery systems. Six (6) relays are included for:
3-3.2.1 Fuel Relay; this relay provides two outputs, one to energize the engine fuel solenoid and a separate circuit to energize the battery charging alternator field. 3-3.2.2 Shutdown Relay; this relay is operated by the shutdown circuits of the Control / Display Module and provides an output that can be used to trip the generator circuit breaker on an emergency shutdown. 3-3.2.3 Overspeed Relay; operates only on an Overspeed shutdown. This relay provides an output to trip an air shut off solenoid to close the air damper on a two-cycle engine. 3-3.2.4 Local Audible Alarm Relay; provides a contact closure
DC12V
3A Fuse
1A
4 5 6 7 8 9
16 17 18 19 20 21 22 23 24 25
DC12V
DC12V DC12V
DC12V DC12V
6-1/4 in.
(159 mm)
4-1/2 in.
(114 mm)
Figure 3-3.2
6
Loading...
+ 19 hidden pages