Murphy 518E, 520APH, 521PH Specification Sheet

78793B page 1 of 4
Description
TATTLETALE®annunciators and Magnetic Switches are the nerve centers that translate SWICHGAGE®contact operations into decisions and operate the alarm or shutdown device. They are the electrical load carrying devices for the alarm or shutdown device. TATTLETALE
®
annunciators indicate which monitored function failed leading to the alarm or shutdown whereas magnetic switches do not. Magnetic switches operate basically as a latching relay.
Application
Magnetic Switches and TATTLETALE®annunciators are available for use with engines or electric motors. Various circuits, time delays, and contact configurations are available to match the power source and mode of operation required for alarm only, alarm before shutdown or shutdown only.
For distributor ignition engines, the magnetic switch opens the distributor coil circuit to cause shutdown. For magneto or CD ignitions the magnetic switch grounds the ignition output. Some models can also trip fuel valves instead of or in addition to grounding the ignition. Diesel engines are shut down by either closing off the fuel or air supply. Magnetic switches and TATTLETALE®annunciators can make or break circuits for these engines.
For electric motor applications, various magnetic switches are available to operate the motor starter, holding coil directly or in conjunction with appropriate Murphy Transformer-Relay assembly.
Features
Magnetic switches and TATTLETALE®annunciators described in this bulletin are electrically tripped relay type devices. Models are available to operate from battery power, 120 VAC, conventional magnetos and capacitor discharge type ignitions. Energized to run models allow CLOSED LOOP circuitry. Others draw momentary power to trip. Configurations are available for contact make or contact break to cause shutdown. Some models have both make and break contacts.
All models have a weather resistant case with screw terminals for ease of customer hookup. Manually reset models have a face mounted reset push button which also serves as a fault indicator in the TATTLETALE®version. In this application, one or more TATTLETALE®/magnetic switches are used to advise operating personnel which monitored function caused shutdown. Only the TATTLETALE®connected to that function sensor trips causing the reset push button to pop out.
Electrically reset models perform the same functions as the manually reset models and are reset by cycling the power supply off and then on.
Time delay models use reliable solid state timing circuits to lockout operated switch contacts for start-up and/or to allow operation of alarms before shutdown occurs. Specific models allow application of power to a shutdown circuit and automatic disconnect of power after a given time delay.
See the chart on page 2 for features by part number.
Nerve Centers for Murphy SWICHGAGE
®
Instruments and Automation Systems
* Applies to selected models.
*
78793B
Revised 4-08
Catalog Section 25
TATTLETALE®Annunciators and Magnetic Switches
78793B page 2 of 4
MS2100
Multi purpose TATTLETALE
®
with dry contacts that can be used to make two circuits and break another when tripped. Operates from 120 VAC or Capacitor Discharge Ignition. The operating coil is inter­mittent duty and must be disconnected by an external circuit when tripped. The MS2100 is a replacement for 100PH, 307CD, 307PHCD and 224CD.
MS2110
Multi purpose TATTLETALE
®
with dry contacts that can be used to make two circuits and break another when tripped. Operates from 12 or 24 VDC or 24 VAC. The operating coil is intermittent duty and must
be disconnected by an external circuit when tripped. The MS2110 is a replacement for 221PH, 169PH, 274 and 274PH.
NOTES
The chart above indicates features/configurations available for each model.
1. Coil Voltage-Coils are specific voltage rated or multiple voltage rated.
2. Contacts-This is the control circuit output. In the latched position the NCH con-
tact has a “hot” output; in the tripped position the NOH contact has a “hot” out­put. In the latched position, the NCG has a “grounded” output; in the tripped position, the NOG has a “grounded” output.
3. Latch Type-Refers to whether the magnetic coil is momentarily energized to trip
or requires continuous power in the operating mode and de-energizes to trip.
4. Reset Type-Refers to manual or electric reset; manual indicating type is a TAT-
TLETALE®.
5. Time Delay-Indicates operation of the time delay.
6. Coil Resistances in OHMS, or coil and resistor
1.) 0.5 2.)18 3.)30 4.)72 5.)90/190 for 12/24 6.)288 7.)339/678 for 12/24
8.)339/618 for 12/24
117/117PH Use to shutdown 12V thru
32V distributor ignition or diesel engines. Breaks circuit when tripped. Opens distributor coil cir­cuit or power circuit to diesel run device. Automatically disconnects from battery after trip. Contacts 10 amps 32 VDC. 14 amp fuse.
Specifications
MS2120
Multi purpose TATTLETALE
®
with dry contacts that can be used to make two circuits and break another when tripped. Operates from Magneto Ignition. The operating coil is intermittent duty and must be disconnected by an external circuit when tripped. The MS2120 is a replacement for 307, 307PH and 224.
117
117PH
MS2100
MS2110
MS2111
MS2120
Coil Voltage
12 volt 24 volt 12/24 volt
*
120 VAC Magneto ignition CD ignition
Coil
(see Note 6 below)
Contacts
NCH NOH NCG NOG
(see Note 2 below)
22 62 41 7 7
A AAAAA
B B
Latch Type
Energize to trip Energize to latch
Reset Type
Manual indicating Manual non-indicating Electric non-indicating
Time Delay
Before shutdown Start only After shutdown
*
Multi-voltage AC or DC systems. See circuit descriptions below and on next page.
Dry contacts normally wired in hot circuit.
A:
Dry contacts normally wired in ground circuit.
B:
518APH
518PH
518E
521PH
520APH
760A ‡
761APH
22PH
8
M4264-1
R129A
ETS30S
787 52 3 5
BBB
B
‡ Does not latch after shutdown signal clears, automatically resets.
C S B
6 2 3
1
4
5
6 2 3
1
4
5
6 2 3
1
4
5
78793B page 3 of 4
518APH
Allows for SWICHGAGE®and/or N.C. contacts to be wired “Closed Loop” (in series). Any contact open or SWICHGAGE
®
contact close in the circuit shunt trips the 518APH. Specify 12 or 24 VDC. Contacts 10 amps 24V. 14 amp fuse.
518E
Same as 518APH but recommended for high vibration application where nuisance shutdowns typically occur due to higher than normal vibrations (ie. wood chippers) 12 Volt
only.
520APH
Same as 518APH except with 30 second time delay before trip on one SWICH­GAGE®contact input but immediate trip on the second SWICHGAGE®contact input. Typical use is for immediate stop of engine from oil pressure or coolant temperature, but delayed shutdown from alignment switches on center pivot irrigation system. Specify 12 or 24 VDC and length of time delay. Time delays are available from 5 to 120 seconds. Contacts 10 amps 24 V. 14 amp fuse.
521PH
Use with N.C. SWICHGAGE®or switches to ground magneto or CD ignition when tripped. Trip coil energized to run, de­energized to shutdown when N.C. contacts open. Specify 12 or 24 VDC. Contacts 10 amps 24 V.
822PH
Used in Murphy TR-assemblies as master disconnect. 24 VAC coil energizes when SWICHGAGE®contact closes to ground; breaks and makes circuit when tripped. Manual reset.
M4264 Series
Detects loss of magneto/CD ignition output and transfers con­tacts for customer use. Contacts 10 amps; 48 VAC/VDC. M42641CD transfers SPDT dry contacts when tripped.
760A/760AF/761APH
Use for distribu­tor ignition or diesel. Time delay lockout of SWICHGAGE®contacts on start-up only; cus­tomer wired for delayed or immediate trip on shutdown. Breaks and makes circuits when tripped. 760A resets automatically when the shutdown signal is removed or power is removed. 761APH has manual reset. 760AF is 760A with inline fuse. Must specify 12 or 24 VDC, and length of time delay. Optional time delays: 15, 30 (standard) or 60 seconds. Contacts 10 amps 24 V. 14 amp fuse. Models 760A and 761APH carry the CE mark.
NOTE : The 760A cannot be adequately protected by a circuit breaker in a dead short condition with a battery as the power source. The circuit breaker will take a finite amount of time to react, during which time the circuit board of the 760A will be dam­aged beyond repair. Fuses are the optimal method for protecting the 760A.
R129A
A SPDT relay with 10 amp dry contacts. Specify 12 or 24 VDC. Contacts 10 amps 24 VDC. 14 amp fuse.
ETS30S
All solid-state time delay for energized to stop circuits such as solenoids. When a shutdown signal is received, the ETS30S applies power to the shutdown device for 30 seconds and then disconnects the power. Input power 12 or 24 VDC.
518PH
Aallows for SWICHGAGE®and/or N.C. contacts to be wired “Closed Loop” (in series). Any contact open or SWICHGAGE
®
contact close in the circuit shunt trips the 518PH. Specify 12 or 24 VDC. Contacts 10 amps 24V. 14 amp fuse.
* Complies with EMC Council directive 89/336/EEC regarding electromagnetic compatibility.
*
*
MS2111
Replaces 221PH w/72 ohm coil. Used with NICS-78 non-incendive control system. Service part only.
*
GNC
R
SW1 SW2
B
GNO NC
R
SW1 SW2
B
GNO NC
TD
R
SW1 SW2
TD
G NO NC BS
NO NC C SW
B
Sensing
Circuit
G SWNC C
6 2 3
1 4
5
IGN
NO CBY NC
NO NC S BG
IGN
78793B page 4 of 4
How to Order
Accessories
Order accessories as a separate item. Specify part number when ordering.
25050016 Weathercap.
25050547 Clear flexible dust boot for push button.
30050323 Single unit mounting panel.
65010026 In-line fuse holder with 14 amp fuse.
Base Models
117
*
117PH
*
518PH 518APH 518E
**
520APH 521PH 760A
*
761APH
*
822PH M42641M
M42641CD
R129A ETS30S MS2100 MS2111 MS2110 MS2120
Time Delay (where applicable)
15 = 15 seconds 30 = 30 seconds 60 = 60 seconds Specify other.
Voltage/Ground (where applicable)
12 = 12 VDC 24 = 24 VDC
Options
Not all options may not be available on all models in combination with other options. See “Configurations Available” chart below.
AS = Auxiliary SPDT switch ES = Environmentally sealed EL = Explosion-proof less case
760AF – 15 – 12 –
Specify model number and options using the diagram below. List options in alphabetical order (A to Z) followed
by numeric in ascending order. Place a dash (–) between each option.
Configurations Available
*
Add the letter “F” to the base model to indicate an inline fuse instead of a base mounted fuse. Example: 760AF, 761APHF, 117F.
**
12 Volt negative ground version only.
Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product.
A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
78793B
FRANK W. MURPHY, LTD
Church Rd Laverstock Salisbury SP1 1QZ UK Phone: +44 172 241 0055 Fax: +44 172 241 0088 E-mail: sales@fwmurphy.co.uk Web site: www.fwmurphy.co.uk
COMPUTRONIC CONTROLS, LTD
41 - 43 Railway Terrace Nechells Birmingham B7 5NG UK Phone: +44 121 327 8500 Fax: +44 121 327 8501 E-mail: info@computroniccontrols.com Web site: www.computroniccontrols.com
FW MURPHY INSTRUMENTS (HANGZHOU) CO. LTD
77 23rd Street Hangzhou Economic & Technological Development Area Hangzhou, Zhejiang 310018 China Phone: +86 571 8788 6060 Fax: +86 571 8684 8878
FW MURPHY INTERNATIONAL TRADING (SHANGHAI) CO., LTD.
Suite 1784, Tower B, City Center of Shanghai; 100 Zunyi Road Shanghai, 200051 China Phone: +86 21 6237 2082 Fax: +86 21 6237 2083 E-mail: mhong@fwmurphy.com
FW MURPHY
P.O. Box 470248 Tulsa, Oklahoma 74147 USA +1 918 317 4100 Fax: +1 918 317 4266 E-mail: sales@fwmurphy.com
INDUSTRIAL PANEL DIVISION
Fax: +1 918 317 4124 E-mail: ipdsales@fwmurphy.com
MURPHY POWER IGNITION
Web site: www.murphy-pi.com
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819 Rosenberg, Texas 77471 USA Phone: +1 281 633 4500 Fax: +1 281 633 4588 E-mail: sales@fwmurphy.com
Printed in U.S.A.
www.
fwmurphy
.com
MS2120
MS2110
MS2111
518/518A/518E
Non-PH
PH
PH-ES
MS2110