Murphy 1501 User Manual

Alarm/Shutdown for 32 or 64 N.O. or N.C. Sensors
Operating Sequence Selection
Field Adjustable Sensor Nomenclature
Selectable Sensor Lockouts Class A, B, C or P
Built-In Tachometer/Overspeed Function
RS232 or RS485 Modbus RTU Communications
Two Start/Run Timers and Elapsed Time Meter
Description
The Series 1501 instrument is a microprocessor­based alarm, shutdown and control system with tachometer/hourmeter function. It annunciates in alphanumeric characters the protective device that has signaled an alarm or caused equipment shutdown. Information is called up and adjust­ments are made on a six-button keypad on the face of the unit. Configurations such as: Alarm or Shutdown Nomenclature, Preset Timers, and Tachometer Calibration can be made in the field.
Murphy’s Series 1501 system has seven SPDT relays. On the standard model, the relays are assigned to the following functions: Lube, Crank, Ignition/Motor, Fuel Valve, Load, Alarm, Shutdown.
The complete Series 1501 system consists of a head (monitor), sensor input terminal strip (two needed for 64 sensor models), 36 inch (914 mm) flat ribbon cable(s) for connecting the ter­minal block to the head/monitor, and a Class I, Div. 1, explosion-proof power supply.
The Series 1501 system is powered from 120 VAC or 12 or 24 VDC. The head/monitor is rated intrin­sically safe and includes a communication port: RS232 or RS485 (Modbus RTU slave). This port allows for remote control functions such as Start/Stop, Load/Unload, etc., and for access to Series 1501 registers.
Applications
The Series 1501 system can be configured to mon­itor applications such as: Air and Gas Compressors, Natural Gas Refueling, and other Industrial Operations. For a list of applications and our cataloged programs contact a Murphy sales representative. Custom programming available at additional charge.
Features
32 or 64 sensor inputs (N.O. or N.C.) for alarm or shutdown.
Easy operation/adjustments Six-button keypad.
RS232 or RS485 Modbus RTU communica­tions.
Automatic Engine Control.
Two Start-Run Timers.
Seven Control Relay Outputs.
Pre/Postlube Time Delay.
Automatic Compressor Loading.
Specifications
Power Consumption: 120 VAC (7.5 VA);
12 VDC (3.5 watts); 24 VDC (3.5 watts).
Sensor Inputs: 32 to 64 N.O. and/or N.C. inputs
such as Murphy Swichgage
®
instruments. Field selectable as a Class A, B1, B2 , C , P or ESD for shutdown, alarm, or control function.
Outputs: 7-SPDT relay outputs, 5 A, 1/16 HP,
125/250 VAC/ 1 A, 30 VDC.
NOTE: For hazardous areas an approved isola­tion barrier must be used between sensor switch and input terminals if the sensor output comes from any energy storing device such as a relay or transistor.
Adjustable Time Delays:
(standard Series 1501)
Prelube
Rest
Process Delay•Permissive
Run Delay•Idle/Cooldown
Purge
Postlube
Fuel Delay•Crank
Load Delay•Test
Class B1 Sensor Lockout
Class B2 Sensor Lockout
Before Ignition Ground or Electric Motor Stop (for up to 59 seconds)
Sensor Inputs Terminal Block: Rail mount
DIN type; 32 terminals, screw type.
Opto-Isolated Tach/Run Input: Magnetic
pickup, 4.5 to 120 Vrms, 0-10 kHz. CD igni­tion, positive or negative ground, 100 to 300 VDC, 3-666 Hz. 12 to 125 VDC or 120 Vrms, 50/60 Hz may be used for run signals.
Operating Temperatures: 32 to 122°F
(0 to 50°C).
Storage Temperatures: -4 to 158°F (-20 to 70°C). Case: ABS plastic, 1/4 DIN (90 x 90 mm). Interface Output: Factory configured for
RS232; field-selectable for RS485 (specify for factory configured RS485).
Alphanumeric Display: 2 lines, each line with
16 characters (32 characters total).
Power Supply Enclosure: Explosion-proof,
Class I, Division 1. Intrinsically safe barrier built into the power supply, 120 VAC with 7 form “C” relay outputs for the following functions (with standard S1501):
Lube•Load •Crank•Alarm
Ignition/Motor•Shutdown •Fuel Valve
NRTL/C
S15-96122B
Revised 07-06
Catalog Section 50
Series 1501 Selectronic
®
Micro-Controller/Annunciator
S15-96122B page 1 of 2
S15-96122B page 2 of 2
Terminal Block
Power Supply
Module Side View
Back View
DimensionsHow to Order
To order the Series 1501 system specify the model number for each individual component and accessory:
Specify: To Order:
S1501H-32-2
Head with RS232 port for 32 sensors.
S1501H-64-2
Head with RS232 port for 64 sensors.
S1501H-32-4
Head with RS485 port for 32 sensors.
S1501H-64-4
Head with RS485 port for 64 sensors.
S1501CH-32-2
Head w/custom* program, RS232 port, 32 sensors.
S1501CH-64-2
Head w/custom* program, RS232 port, 64 sensors.
S1501CH-32-4
Head w/custom* program, RS485 port, 32 sensors.
S1501CH-64-4
Head w/custom* program, RS485 port, 64 sensors.
S1501CC48
Communications Cable Assembly, 48 in. (1.2 m) long.
S1500TB32
Terminal Block only**
S1500CA36
Ribbon Cable Assembly**
S1501PS-120
120 VAC, 12 or 24 VDC Power Supply.
Accessories:
S1501PCA72
Power and Control Cable Assembly, 72 in. (1.8 m) long.
S1501PS-120-E
Power Supply with 90° Conduit Elbow fitting.
S1501PS-120-LC
Power Supply Less Case.
* Specify program number or contact Murphy for available programs listings.
** Two required for 64 sensor models.
Approximate Shipping Weights
Complete Series 1501 System: 28 lb. (12.7 kg). S1501H-32-2; S1501H-64-2; S1501H-32-4; S1501H-64-4; S1501CH-32-2;
S1501CH-64-2; S1501CH-32-4; S1501CH-64-4: 2 lb. (0.907 kg). S1500TB32: 2 lb. (0.907 kg). S1500CA36; S1501CC48; S1501PCA72: 2 lb. (0.907 kg).
S1501PS-120-LC: 3 lb. (1.36 kg). S1501PS-120 and S1501PS-120-E: 22 lb. (9.98 kg).
Approximate Shipping Dimensions
Complete Series 1501 System: 20 x 14 x 12-1/2 in. (508 x 356 x 318 mm). S1501H-32-2; S1501H-64-2; S1501H-32-4; S1501H-64-4; S1501CH-32-2;
S1501CH-64-2; S1501CH-32-4; S1501CH-64-4: 6 x 6 x 6 in. (152 x 152 x 152 mm). S1500TB32: 12 x 7 x 4 in. (305 x 178 x 102 mm). S1500CA36; S1501CC48; S1501PCA72: 6 x 6 x 6 in. (152 x 152 x 152 mm). S1501PS-120-LC: 12 x 7 x 4 in. (305 x 178 x 102 mm).
S1501PS-120 and S1501PS-120-E: 17 x 10 x 9-3/4 in. (431 x 254 x 248 mm).
Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time. MURPHY, the Murphy logo, and Selectronic®are registered and/or com­mon law trademarks of Murphy Industries, Inc. This document, including textual matter and illustrations, is copy­right protected by Murphy Industries, Inc., with all rights reserved. (c) 2006 Murphy Industries, Inc.
www.fwmurphy.com
918.317.4100 Email: sales@fwmurphy.com
3-3/4 in. (95 mm)
3-1/16 in.
(78 mm)
4-1/2 in.
(114 mm)
4-5/8 in.
(117 mm)
Mounting
Clamp
4-3/8 in.
(111 mm)
6-3/4 in. (171 mm)
(178 mm)
9 in.
(229 mm)
(219 mm)
3-1/2 in. (89 mm)
clearance for plug
7 in.
8-5/8 in.
64-sensor
models only
3-1/2 in. (89 mm)
3-1/32 in.
(77 mm)
15 in. (381 mm) clearance for conduit
10-5/8 in. (270 mm)
(2) places
3/4 NPT
conduit
fittings
1/2 NPT conduit fitting
5-15/16 in. (151 mm)
Loading...