Murphy 1400 User Manual

MFR.
DISCONTINUED
®
S14-8908B
Revised 08-93
Catalog Section 50
FRANK W.
SELECTRONIC®Annunciator
Series 1400
Alphanumeric Display
Start/Run Timer
Pre/Post Lube Timer
Four Control Relay Outputs
Field Adjustable
EPROM Memory
Description
The Series 1400 is a microprocessor based fault annunciator. It tells in alphanumeric characters which protective device has signaled an alarm or caused equipment shutdown. Basic programming for each application is completed at Murphy and can be changed in the field by simply plugging in a new preprogrammed microchip. Information is called up and adjustments are made on a six-but­ton keypad on the face of the unit.
Four SPDT relays are available for alarm and/or shutdown functions. A digital output version (S1400-SP) port interfaces with micro-controllers (7 bit straight binary code).
The S1400 and S1400-SP are powered from a 120 VAC or 12/24 VDC Class I, Division 1 explosion-proof power supply. The monitor is rated intrinsically safe.
Features
*
Applications
Although designed primarily as an intrinsically safe annunciator for gas compressors, the Series 1400 can be programmed to monitor most engine or motor driven process applications, such as:
Air compressors
Gas compressors■Water treatment
Fire pumps
Sewage pumps
Generators
Process control
Burner systems
Natural gas refueling
Specifications
Power Consumption: 120 VAC (8 watts),
Sensor Inputs: For up to 32 N.O. and/or N.C.
Approved for Class I,
®
Division 1, Group D
Outputs: 4-SPDT relays, 4 A,
32 sensor inputs (N.O. and/or N.C.) for
alarm or shutdown
Six-button keypad for easy operation and
adjustments
Digital output for interface with micro-con-
trollers (optional)
Adapter for CD ignition interface with opto-
isolator input (optional)
Relay board expansion, provides 7 additional
control relay outputs or binary representa­tion of alarm/shutdown terminal number
(specify) Start-run timer Four control relay outputs Pre/Post lube time delay Typical standard program or customized*
These options are NOT approved by CSA.
Murphy provides various standard preprogrammed configurations. If a customer sensor input configu­ration is needed, Murphy will custom program your unit at the time you order. Call for quote.
24 VDC (7.2 watts) or 12 VDC (2.5 watts).
inputs such as Murphy SWICHGAGE ments. Each input is factory programmed as a class A, B or C shutdown, alarm, or control function (specify).
®
instru-
NOTE: An isolation barrier (such as the Murphy LCDT-ISB) must be used between the sensor switch and input terminals if the sensor output comes from any energy storing device such as a relay or transistor.
Timers: 4 adjustable for: lockout at start-up, test,
Time Delay: Up to 0.9 minutes before ignition
Memory: Memory held in EPROM, 4k,
Backup Battery: Rechargeable during normal
Run Sensing: Either ignition or switch input. Operating Temperatures: 32 to 122°F (0 to 50°C). Storage Temperatures: -4 to 158°F
Case: ABS plastic, Interface Output: Digital, 7 bit straight bina Display: Alphanumeric dot matrix, 2 line
Power Supply
1
/20 HP,
125/250 VAC/3A, 30 VDC.
prelube and postlube.
grounds or electric motor stops.
192 bytes of RAM.
operation. Provides up to 5 hours backup time.
(-20 to 70°C).
1
/4 DIN (90 x 90 mm).
ry
code.
32-character display.
Enclosure: Explosion-proof, Class I, Division 1. Barrier: Intrinsically safe barrier built into
power supply, 120 VAC and 12 or 24 VDC power supply barrier with dry contacts relay functions such as:
Fuel valve
Shutdown
Alarm
Control (Pre/Post Lube).
Dimensions
6 in.
(152 mm)
10-3/4 in. (273 mm)
8-3/4 in.
(222 mm)
15 in. (381 mm)
clearance for conduit
4-1/2 in.
(114 mm)
3 in.
(76 mm)
9 in.
(229 mm)
SIDE VIEW
TOP VIEW
3-1/2 in. (89 mm)
3-3/4 in. (95 mm)
3-1/2 in. (89 mm)
4-3/8 in.
(111 mm)
4-5/8 in.
(117 mm)
3-3/4 in. (95 mm)
BACK VIEW
SIDE VIEW
3-9/16 in.
(90 mm)
3-9/16 in.
(90 mm)
MOUNTING HOLE
6-3/4 in.
(171 mm)
clearance for plug
Mounting
Clamp
Model S1400SP
only
®
FRANK W.
MFR.
DISCONTINUED
Series 1400 monitor (head)
Power Supply Box
Series 1400 System
The basic S1400 system consists of (1) the monitor, (2) a sensor input termi­nal strip assembly (rail mount) (3) a 36 inch (914 mm) flat ribbon cable for connecting the terminal strip to the monitor, (4) a power supply which includes the control Inputs/Outputs and an intrinsically safe barrier, with cable assembly. S1400SP; same as the S1400 system except the (1) monitor, includes an extra connector (port) for connection to S14BCM92 relay board expansion or for a digital output to interface with micro-controllers.
NOTE: Each unit is programmed to the customer specifications.
Accessories
S14RSA92 Adapter: Used to interface the S1400 opto-isolator input (also
called run input) to CD ignition systems. (Not approved by CSA.)
S14BCM92 Relay Board Expansion: Can either be used to expand the
S1400 relay capabilities an additional 7 relay control outputs, or for binary representation of the alarm/shutdown terminal number(s) to a PC board. (Not approved by CSA.)
LCDT-ISB Intrinsically safe barrier for N.O. sensors
accept non-intrinsically safe normally open inputs and convert them to intrinsically safe outputs. Each LCDT-ISB provides for two (2) channels.
Warranty
A two-year limited warranty on materials and workmanship is given with this Murphy product. Details are available on request and are packed with each unit.
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Frank W. Murphy Manufacturer
P.O. Box 470248; Tulsa, Oklahoma 74147; USA
tel. (918) 627-3550 fax (918) 664-6146 e-mail fwmurphy@ionet.net
Frank W. Murphy Southern Division
P.O. Box 1819; Rosenberg, Texas 77471; USA
tel. (281) 342-0297 fax (281) 341-6006 e-mail murphysd@intertex.net
Printed in U.S.A.
Since 1939
Frank W. Murphy, Ltd.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
tel. +44 1722 410055 fax +44 1722 410088 tlx 477088 e-mail sales@fwmurphy.co.uk
Frank W. Murphy Pte., Ltd.
26 Siglap Drive; Republic of Singapore 456153
tel. +65 241-3166 fax +65 241-8382 e-mail fwmsales@fwmurphy.com.sg
Murphek Pty., Ltd.
1620 Hume Highway; Campbellfield, Vic 3061; Australia tel. +61 3 9358-5555 fax +61 3 9358-5558
:
Is designed to
How to Order
Specify model numbers below:
S1400: Complete system (see “Series 1400 System” section on left). S1400SP: Complete system (with digital output for interface).
To order individual components and accessories specify the model number:
Specify Description
S1400H Monitor (head) only S1400HSP Monitor (with digital output for interface) only S1400TB32 Terminal block only S1400CA36 Cable assembly only S1400PS Power supply only S14RSA92 CD ignition adapter for run signal input S14BCM92 Relay board expansion w/cable and connectors LCDT-ISB Intrinsically safe barrier for normally open sensors
Shipping Weights and Dimensions
Weight Dimension
S1400 28 Lb. (12.7 kg.) 20 x 14 x 12­S1400H 2 Lb. (0.907 kg.) 6 x 6 x 6 in. (152 x 152 x 152 mm) S1400HSP 2 Lb. (0.907 kg.) 6 x 6 x 6 in. (152 x 152 x 152 mm) S1400TB32 2 Lb. (0.907 kg.) 12 x 7 x 4 in. (305 x 178 x 102 mm) S1400CA36 2 Lb. (0.907 kg.) 6 x 6 x 6 in. ( 152 x 152 x 152 mm) S1400PS 22 Lb. (9.98 kg.) 17 x 10 x 9­S14RSA92 1 Lb. (0.453 kg.) 6 x 6 x 6 in. (152 x 152 x 152 mm) S14BCM92 2 Lb. (0.907 kg.) 9-
3
/4 x 9 x 5-1/2 in. (248 x 229 x 140 mm)
LCDT-ISB 3 Lb. (1.3 kg.) 9 x 10 x 6 in. (229 x 254 x 152 mm)
Murphy de México, S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.; México 78384
tel. +52-48-206264 fax +52-48-206336 e-mail murmexsl@infosel.net.mx
Murphy Switch of California
P.O. Box 900788; Palmdale, California 93590; USA
tel. (805) 272-4700 fax (805) 947-7570 e-mail sales@murphyswitch.com
Frank W. Murphy France
tel. +33 1 30 762626 fax +33 1 30 763989
1
/2 in. (508 x 356 x 318 mm)
3
/4 in. (431 x 254 x 248 mm)
0889797