1 Installation

Munters RJB-4 (RJB-4) enables connecting up to 16 load cells to a single RSW-2 Controller or a Platinum Controller. This document details the wiring procedures between the scales and the RJB-4, and between the RJB-4 and the RSW-2.
The RJB-4 comes with:
AWG 14 (thick) cable used to ground the silo (Figure 5)
AWG 22 (thin) cable for wiring the RJB-4 to a grounding rod (Figure 6)

1.1 Connecting Silo Load Cells to the RJB-4

Described below are the wiring connections between the load cells to the RJB-4 Junction Box, and from the junction box to the Silo Weighing Controller (RSW-2).
Load cell part numbers:
RSLC-04: 911-03-XXXXX
RSLC-10: 911-04-XXXXX
RSLC-25: 911-05-XXXXX
NOTE: The RSLC supports RSW-2 boards, version 7.0 and above.
1. Each load cell has a 4-wire shielded cable.
o
Connect each load cell to the RJB-4 double connector with exactly the colors that written
on the RJB-4 PCB board.
o
Figure 1 illustrates the connections made to a load cell.
o
Connect the shield wire to the shield input.
© Munters AB, 2018
Key:
1: Shield wire
Figure 1: RJB-4 to Load Cell Wiring Diagram
2. Repeat for each load cell.
NOTE: The RJB-4 can support more than one load cell on each terminal. To connect more than four
load cells to the RJB-4, place a second set of load cell wires into each terminal load cell block.
Figure 2 illustrates four load cells connected to the RJB-4.
Figure 2: RJB-4 Connected to Four Silos
3. The RSW-2 cell has a 4-wire shielded cable. Run these wires from the RSW-2 Silo A terminal block to the RJB-4 controller terminal block; attach each wire to the input slot with same color. For example, connect the red wire to the red input slot. Figure 3 illustrates the wiring.
© Munters AB, 2018