Munters MWI, MWI 4408 B, MWI 4413 B Quick Assembly Manual

Page 1
Quick Assembly Guide
MWI
Side Wall Inlet
Parts List:
Item Part Name/Description QTY
1 Left Side Support 1
2 Right Side Support 1
3 Top header 1
4 Bottom header 1
5 Door, curved 1
6 Left side door, end cap 1
7 Right side Door, end cap 1
8 Gasket seal 2
9 Metal Guard 1
10 Rubber seal 1
11 L-screw hook 2
1
2
10
11
5
7
3
6
11
3
4
4
2
9
8
Insert top and bottom headers into the right-side lateral support.
5
Slide insert the left side lateral support.
Insert the left and right side end caps onto the curved louver. Add seal.
6
Properly secure the MWI lateral supports using a rubber mallet. Use
Slide the curved louver in the Bottom header slot
7
Insert the rubber seal in the top header slot and along door sides.
Slide the metal grid in the headers slot
!
WARNING:
Do Not use metal hammer to secure the MWI. The use of a metal hammer can result in damage to MWI.
caution!
NOTE: The following guidelines should be used and closely followed when assembling and installing MWI.
In order to assure proper performance and correct functioning of the inlets, the installer must understand the importance of quality construction-work and use quality materials. Attention to details relating the assembly work, proper sealing or prevention of air leaks is a must and must be undertaken by the installer.
WARNINGS: Do not overtighten the screws! Tighten until flush. Do not dent the housing! Overtightening the screws will result in damage to MWI.
1
Page 2
Quick Installation Guide
MWI
Side Wall Inlet
Item
Black inch cm inch cm MWI 4413 B 44 x 13 x 4 111.8 x 33 x 10 44.5 x 13.5 113 x 34.3 MWI 4408 B 44 x 8.25 x 4 111.8 x 21 x 10 44.5 x 8.75 113 x 22.2
1
Place the inlet into framed opening. NOTES: the opening size
is critical! Leave always a gap of
0.2inch or 5mm evenly distributed around the unit.
Inlet Size
W x H x D W x H (±0.06inch or ±0.2cm)
2 3
Fasten the left and right lateral side support using appropreite
screws (2-inch or 5 cm). NOTES:
Fastening points are marked on both supports. Screws and fittings are not included, Choose screws and fittings that are suited to the material in the wall and have sufficient holding power. If uncertain, contact
Munters.
Should be 0.5inch or 1.2cm
larger than the inlet size
Fasten the bottom header profile using appropriate screw.
NOTES: Fastening should be done in
the center, on the marked line. Make sure the bottom header is straight (linear) when fastening.
Framed Opening Size
4
Push slightly up on the top header center, 0.25 inch or 0.6 cm. needed difference.Fasten the top header profile using
appropriate screw. NOTES:
Make sure the slight curvature of approximately 0.25 inch or 0.6 cm is achieved before fastening. Fastening should be done in the center, on the marked line.
5
Verify the correct movement,
opening and closing of the inlet.
Caulk all sides four internal edges of the MWI after
9
10
tallation using a caulk gun. NOTE: Mounting hardware,
ins
silicone and caulk gun are not included.WARNING: Do not
use expandable foam to seal the edges of MWI! The use of expandable foam can result in damage of MWI.
After the actuator & wire-rope or rod system are installed, re-adjust all MWI properly to assure correct opening and closing.
6
Fasten the (2) L-Screw hooks evenly spaced above header. Place 0.5 inch or 1.2 cm above the top header, opposite to the direction of pull.
NOTES: Avoid interference with the
pulling cable or rod.
7
Install a small pulley at the top
of the inlet. NOTES: Pulley or fitting
are not included. Choose pulleys that are suited to the type of system or wall and have sufficient holding power. If uncertain , contact Munters.
Australia Munters Pty Limited, Phone +61 2 6025 6422, Brazil Munters Bra-
sil Industria e Comercio Ltda, Phone +55 41 3317 5050, Canada/US Munters Corporation Mason, MI Phone +1 517 676 7070, China Munters Air Treatment Equipment (Beijing) Co. Ltd, Phone +86 10 80 481 121, Denmark Munters A/S, Phone +45 9862 3311, India Munters India, Phone +91 20 3052 2520, Indone-
sia Munters, Phone +62 818 739 235, Italy Munters Italy S.p.A., Chiusavecchia,
Phone +39 0183 52 11, Japan Munters K.K., Phone +81 3 5970 0021, Korea Munters Korea Co. Ltd., Phone +82 2 761 8701, Mexico Munters Mexico, Phone +52 818 262 54 00, Russia Munters AB, Phone +7 812 448 5740, Singapore Munters Pte Ltd., Phone +65 744 6828, South Africa and Sub-Sahara Countri-
es Munters (Pty) Ltd., Phone +27 11 997 2000, Spain Munters Spain S.A., Phone