Originalinstructions
Usermanual
IceDry800/1400
Desiccantdehumidier
190TGB-1037-G1307©MuntersEuropeAB2013

Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthe
faulthasoccurredwithinthewarrantyperiodand
thattheunithasbeenusedinaccordancewiththe
specications.Allclaimsmustspecifytheunittypeand
fabricationnumber.Thisinformationisstampedonthe
identicationplate,seesectionMarking.
Itisaconditionofthewarrantythattheunitforthefull
warrantyperiodisservicedandmaintainedbyaqualied
MuntersengineerorMuntersapprovedengineer.
Accesstospecicandcalibratedtestequipmentis
necessary.Theserviceandmaintenancemustbe
documentedforthewarrantytobevalid.
AlwayscontactMuntersforserviceorrepair.Operating
faultscanoccuriftheunitismaintainedinsufcientlyor
incorrectly.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W
ARNING!
W W
ARNING! ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury .
CA
UTION!
CA CA
UTION! UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty ,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,theLowVoltageDirective2006/95/EC
andtheEMCDirective2004/108/EC.The
dehumidierismanufacturedbyanISO9001:2008
accreditedmanufacturingorganisation.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Pleasesendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
iiImportantuserinformation190TGB-1037-G1307


Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
Warranty...............................
Safety..................................
ConformitywithDirectives............
Copyright..............................
Tableofcontents...........................iv
1Introduction.................................1
1.1General................................
1.2Aboutthismanual.....................
1.3Safetyandcautions...................
1.4Marking................................
1.5Supervisionofoperation..............
1.6Faultindications.......................
2Productdesign..............................4
2.1Productdescription...................
2.2Principleofoperation..................
3Transport,inspectionandstorage.......5
3.1Movingtheequipment................
3.2Packaginganddeliveryinspection...
3.3Storingtheequipment................
4Installation...................................6
4.1General................................
4.2Safety..................................
4.3Siterequirements.....................
4.4Mirrorhandedductconnections......
4.5Wheretoinstallthedehumidier.....
4.6Ducting.................................
4.6.1Generalrecommendations...
4.6.2Processairinlet................
4.6.3Dryairoutletduct..............
4.6.4Reactivationairintake........
4.6.5Ductworkforwetairoutlet.....
4.7Installationexamples—coldstorage
ii
ii
ii
ii
ii
5Operation....................................16
1
1
1
3
3
3
4
4
5
5
5
6
6
6
7
8
8
8
9
9
9
10
6Serviceandmaintenance.................21
7Faulttracing.................................24
8Technicalspecication....................26
9Scrapping....................................29
10ContactMunters............................31
room(freezer).........................
4.8Electricalconnections................
4.9Pre-startsettings......................
4.10Pre-startchecks.......................
4.11Airowcheckandadjustment........
5.1General................................
5.2Safety..................................
5.3Quickstop..............................
5.4Operatorpanel........................
5.5Operatingtheunit.....................
5.5.1General.........................
5.5.2Start.............................
5.5.3Restartafterpowerfailure.....
5.5.4Stop.............................
6.1Safety..................................
6.2General................................
6.3Serviceoptions........................
6.4Extendedwarranty....................
6.5Serviceandmaintenanceschedule..
7.1General................................
7.2Safety..................................
7.3Faulttracinglist........................
8.1Dimensionsandservicespace.......
8.2Technicaldata.........................
8.3Sounddata.............................
11
13
14
14
15
16
16
16
17
19
19
19
19
20
21
21
21
21
22
24
24
24
26
27
28
ivTableofcontents190TGB-1037-G1307

IceDry800/1400
1Introduction
1.1General
Muntersmanufacturesawiderangeofefcientdehumidiersdesignedfordifferentusesandapplications.
PleasecontactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationofyour
dehumidier,orvisitthewebsiteatwww .munters.com.
Theunitisinspectedandcheckedpriortoleavingthefactorytoguaranteeconsistentqualityandmaximum
reliability.Forproductdata,seesectionTechnicalspecication.
1.2Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforetheunitisinstalledand
used.
1.3Safetyandcautions
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualincludessuggestionsforbestworkingpracticeandshallinnowaytake
precedenceoverindividualresponsibilitiesorlocalregulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
■Thesafetyofallpersonsconcerned.
■Thesafetyoftheunitandotherproperty.
■Theprotectionoftheenvironment.
Forinformationaboutthesafetysymbolsusedinthismanual,seesectionImportantuserinformation.
190TGB-1037-G1307Introduction1

IceDry800/1400
W
ARNING!
W W
ARNING! ARNING!
-Theunitisnotintendedforuseinhazardous(classied)areaswhereexplosionsafetycompliantequipment
isrequired.
-Theunitmustnotbesplashedwithorimmersedinwater.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheunit’sidenticationplate,seesectionMarking.
-Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.
-Donotoperatetheunitnearanyheat-generatingdevicesorammableanddangerousmaterials.
-Donotinsertngersoranyotherobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventaccidents.
-AlwayscontactMuntersforserviceorrepair.
2Introduction190TGB-1037-G1307

IceDry800/1400
0919 190XX X XXX XX
0,72 kW
Max
5,4 kW
M unters Europe AB
Isafjordsgatan 1
164 26 Kista, Sw eden
M
4,38 kW
M ade in Sw eden
Fabr. N o.
Fabr. year 2009
3 ~ 400V 50 H z
Type
IP44
IceD ry800
1.4Marking
Figure1.1Locationoflabels
Explanationof"Fabr.No"ontheidenticationplate:
09=yearofmanufacture,19=weekofmanufacture,190XXX=articlenumber,XXXXX=serialnumber
1.5Supervisionofoperation
Thedehumidieriscontrolledandmonitoredfromtheoperatorpanellocatedonthefrontoftheunit.
1.6Faultindications
Faultsareclearlyindicatedontheoperatorpanel.TheashingLEDsindicatewhichcomponentthat
requiresattentionformaintenanceorreplacement.
1.Identicationplate2.Dryairoutlet
3.Wetairoutlet4.Processairinlet
5.Reactivationairinlet
190TGB-1037-G1307Introduction3

IceDry800/1400
2Productdesign
2.1Productdescription
ThedesiccantdehumidiersintheIceDryserieshavebeendevelopedtoeffectivelydehumidifytheairin
coldstoresinordertominimisefrostandicebuild-up
Thedehumidierisequippedwithanencapsulatedrotorunit.Therotorcasingisconstructedofdurable
thermosetplasticandcontainsisolatedsectionsthatprovideaprecisebalanceforthedehumidication,
reactivationandheatrecoveryairows.
TheelectricalcontrolsystemcomplieswiththeEN60204(IEC60204)standards.Foroperating
temperature,seesection8.2,Technicaldata.
ThedehumidierismanufacturedinaccordancewithuniformEuropeanstandardsandestablished
requirementsforCE-marking.
2.2Principleofoperation
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
Figure2.1Principleofoperation
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthrough
therotor'slargestzoneandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively ,evenatfreezingtemperatures.
4Productdesign190TGB-1037-G1307

IceDry800/1400
3Transport,inspectionandstorage
3.1Movingtheequipment
Thedehumidierisdeliveredonapalletandmustbehandledcarefully .Allpaneldoorsontheunitmustbe
closedduringtransport.Providedthatthedehumidierisstillsecuredtoitsdeliverypallet,itcanbemoved
usingafork-lifttruck.
Weightofthedehumidiercanbefoundinsection8,Technicalspecication.
3.2Packaginganddeliveryinspection
1.Checkthedeliveryagainstthedeliverynote,orderconrmationorotherdeliverydocumentationand
checkthateverythingisincludedandnothingisdamaged.
2.ContactMuntersimmediatelyifthedeliveryisnotcompleteinordertoavoidinstallationdelays.
3.Iftheunitistobeputintostoragepriortoinstallation,seesectionStoringtheequipment.
NOTE!Ifinstallationisnottobecarriedoutimmediatelyafterarrivaloftheequipment,itisadvisabletoleave
thepackagingmaterialinplaceonthedehumidier,ortore-usethepackagingmaterialtoprovidetemporary
protectionfortheunitduringlatertransportationtothesiteandduringinstallation.
4.Removeallpackagingmaterialfromtheunit,checkcarefullytomakesurethatnodamagehasoccurred
duringtransportation.
5.AnyvisibledamagemustbereportedinwritingtoMunterswithin5daysandpriortoinstallationof
theunit.
6.Disposeofthepackagingmaterialaccordingtolocalregulations.
NOTE!G3ltercartridgesforprocessandreactivationairareincludedinthedelivery.Onecartridgeismounted
onthedehumidierprocessairinletandoneontheoutsideofthecold-storageroom,inthereactivationairinlet.
3.3Storingtheequipment
Thefollowingisimportantifthedehumidieristobestoredpriortoinstallation:
■Placethedehumidierinanuprightpositiononahorizontalsurface.
■Protectthedehumidierfromphysicaldamage.
■Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
190TGB-1037-G1307Transport,inspectionandstorage5

IceDry800/1400
4Installation
4.1General
IceDrydehumidiersareintendedforinstallationincoldstoreswithambientairdowntominus25°C.
Theseconditionsrequirethatinstallationinstructionsarefollowedcarefullyasfaultyinstallationcanresult
inseriousoperationaldisturbances.
Iftheunitistobeputintostoragepriortoinstallation,seesection3.3,Storingtheequipment.
4.2Safety
W
ARNING!
W W
ARNING! ARNING!
Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,
maintenanceandrepairsmustonlybecarriedoutbyauthorisedpersonnel.
W
ARNING!
W W
ARNING! ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
CA
UTION!
CA CA
UTION! UTION!
Thebuilt-inheaterrequiresacontinuouspowersupplytopreventfunctionaldisorder.Onlyswitchofftheunit's
powerincaseofemergency.
CA
UTION!
CA CA
UTION! UTION!
Condensationiseasilyformedontheinsideoftheductduetothehighhumidityofthereactivationair.T oavoid
condensation,theductworkmustbeinsulated
CA
UTION!
CA CA
UTION! UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA
UTION!
CA CA
UTION! UTION!
Failuretocorrectlyadjusttheprocessandreactivationairowscouldcausetheunittomalfunction.
4.3Siterequirements
Thedehumidierisadaptedtooperationinsidecoldstores.Thepermittedoperationaltemperatures
arefromminus25to0°C.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
6Installation190TGB-1037-G1307

IceDry800/1400
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandfacilitateservicing.
Therefore,complywiththerecommendedservicespaces,seesection8.1,Dimensionsandservicespace.
NOTE!Theunitmustberemovedfromthecoldstoreatcertainserviceintervals.Haveextracablesforunit
connectionavailable.
4.4Mirrorhandedductconnections
Thefrontandbackpanelsareinterchangeable,sothattheconnectionsforprocessanddryairmaybe
situatedeitherontheleftorrightsideoftheunit.
Thedehumidiersaredeliveredwiththeprocessanddryairconnectionsontheleftsideoftheunit.Ifitis
requiredtothechangetheorientation,sothattheconnectionsareontherightsideoftheunit,proceed
asfollows.
W
ARNING!
W W
ARNING! ARNING!
Ensurethatmainpowerisisolatedfromthedehumidierpriortochangingtheorientatinoftheprocessanddryair
connections.
1.Removethetwobolts(B)securingthefrontpanelandcarefullyremovethepanel.
2.Removethetwoboltssecuringtherearpanelandcarefullyremovethepanel.
3.Removethetwobolts(A)andwasherssecuringthecontrolandtoppanels,thencarefullyremovethe
toppanel.
4.Removethecableductcovers(C),re-routethecablesandtthecontrolpanel(D)ontotheoppositeside
oftheunit.Retthecableductcovers.
5.Loosentherotorstop(E)andthetwoltermonitors(F).Removethecableties.
6.Fittherotorstopandltermonitorsontheoppositesideoftheunit.Tiethecables.
7.Fitthefront,rearandtoppanelsintheirnewpositions.
190TGB-1037-G1307Installation7

IceDry800/1400
4.5Wheretoinstallthedehumidier
Selectaplacewherethedehumidiercausestheleastdisturbancetothecold-storageroomactivities,while
allowingformaintenanceworksuchasprocesslterreplacement.
Whentheunitisinstalledonabaseframe,thebaseframemustbedesignedinsuchawaythatitcaneasilybe
removedfromthecoldstore/freezer.Makesureopeningsforforkliftareincluded.
Thedehumidiermustbeplacedsothatthereisnoriskoftheprocessintakeandltericingup.Icenormally
formsnearthedoorsandair-locksofthecoldstorewherewarm,humidairowsin.
Installthedehumidierinsuchawaythatthereactivationairandwetairductsareasshortaspossible,max
1.5m.Seesection4.7,Installationexamples—coldstorageroom(freezer).
4.6Ducting
4.6.1Generalrecommendations
NOTE!Vibrationreduction.Ifthereisaneedtoforreductionofvibrationsfromthedehumidier,contactMunters
forinstructions.RefertostandardEN1299+A1:2008.
Duetothecoldsurroundingsandriskoffreezing,itisvitalthatallductingareinstalledaccordingto
instructions.Seealso4.7,Installationexamples—coldstorageroom(freezer).
Tofacilitateeasytransferofthedehumidieroutofthecold-storageroomforservice,allductconnections
shouldbeeasilydisassembled.Shouldthedehumidier,despitethisrecommendation,beinstalledinsucha
waythatitcannotbeeasilyremovedforservice,itisimportantthattheminimumservicespacerequirements
aremet,see8.1,Dimensionsandservicespace.Avapour-tightconnectionbetweenthewallandtheductisvital.
Preferably,polyurethanefoamshouldbeusedifthetemperatureissufcientlyhighduringapplication.
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
■Thelengthofductworkshouldbekeptasshortaspossibletominimisestaticairpressurelosses.
■Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
■Thedesignoftheductconnectionsshouldfacilitateeasydisconnectionoftheunitforserviceoutside
thecold-storageroom.
■Condensationeasilybuildsupontheinsideoftheductduetothehighhumidityofthereactivationair.
Toavoidcondensation,theductworkmustbeinsulated.
■Theprocessairductworkshouldbeinsulatedtopreventcondensationfromdevelopingontheoutside
oftheductwheneverthetemperatureoftheairwithintheductfallsbelowthedewpointoftheambient
airthroughwhichtheductworkisrouted.
■Thewetairleavingthedehumidierwilleasilycausecondensationontheinsideoftheductwallsdueto
thehighmoisturecontent.Thismustbeavoidedbyinsulatingtheducts.
■Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,seesection8.1,Dimensionsandservicespace.
■Toreducenoiseand/orvibrationbeingtransmittedalongrigidductwork,goodquality,airtightexible
connectionsshouldbetted.
■Ductsmounteddirectlyontothedehumidiershouldbeadequatelysupportedtominimisetheloadand
stressduetotheweightandmovementoftheducting.
8Installation190TGB-1037-G1307

IceDry800/1400
~ 0,5 m
1
3
A
B
2
Min.
2,0 m
2
■Dampersforbalancingtheairowmustbeinstalledinthereactivationairinletduct.Correctairows
areessentialformaintainingtheoperatingefciencyoftheunit.Forairowadjustmentdetails,see
section4.11,Airowcheckandadjustment.
■Processairpressureandowareadjustedusingtheprocessairfan'sfrequencyconverter.Ifthisisthe
case,itisnotnecessarytohaveadamperinthedryairduct.
■Thetotalresistanceintheprocessandreactivationductworkmustnotexceedtheperformancerating
ofthefansttedinthedehumidier.Fordetailsofminimumavailablestaticpressure,seechapter
8.2,Technicaldata.
4.6.2Processairinlet
Thedehumidierhasanexternallterboxfortheprocessairinlet.Ifthereisariskoftheprocessairlter
icingup,aductshouldbeconnectedtoretrieveprocessairfromadrylocation5-10metresfromthedoor
opening.Thelterboxcanthenbemovedtotheinletsideoftheduct.
4.6.3Dryairoutletduct
Channeloutthedryairfromthedehumidieranddistributeitsothatitmixeswiththewarm,humidairthat
normallyentersthecoldstoreabovethedoorsandair-locksthatareopenedregularly .Installanadjustable
damperintheduct.
4.6.4Reactivationairintake
Placethereactivationairintakeandlterboxoutsidethecoldstore.Mountthelterboxdirectlyonthewall.
Theducttothedehumidierreactivationairintakeshouldbeatmost1.5metreslong,andmustbeinsulated
topreventicebuild-up.Thisalsoappliestothesectionofductpassingthroughthewall.Anadjustable
damperisinstalledintheduct.
Topreventtheoutgoingwetairhumidifyingtheincomingreactivationair,thereactivationairintakemustbe
positionedatleast2metresfromthewetairoutlet
A.Reactivationair
B.Wetair
1.Filterbox
2.Condensatedrains
3.Vapour-tightgrommet
Figure4.1Inletforreactivationairandoutletforwetair.
190TGB-1037-G1307Installation9

IceDry800/1400
4.6.5Ductworkforwetairoutlet
Thewetairductmustbemadeofplasticoranothercorrosionresistantmaterial.Itmustbeabletohandle
temperaturesbetween-30°Cand75°C,benomorethan1.5metreslongandbeinsulatedtopreventice
formation.Thisalsoappliestothepartoftheductpassingthroughthewall.
Becauseofitshighmoisturecontentthewetairleavingthedehumidierwillcondenseontheinsideof
theductwalls.Duetothelowambienttemperaturethereisariskoficeformation.Thewetairductmust
thereforebeinsulated.
■Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainaway
possiblecondensation.Thedeclinemustbeatleast2cm/mofduct.
■5mmdrainholesshouldbemadeatlowpointsoftheducttopreventwateraccumulationintheduct.
■Topreventtheoutgoingwetairfromhumidifyingtheincomingreactivationair,thewetairoutletmust
beplacedatleast2metresfromthereactivationinlet.SeeFigure4.1.
NOTE!Alwaysdrillthedrainholesontheoutsideofthecoldstorage/freezerroomwall.
W
ARNING!
W W
ARNING! ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
10Installation190TGB-1037-G1307

IceDry800/1400
4.7Installationexamples—coldstorageroom(freezer)
Muntersrecommendsthefollowinginstallations.Ifindoubt,contactMuntersforadvice.
Notetheservicespacerequirementsinsection8.1,Dimensionsandservicespace.
Figure4.2Positionabovedoor/airlock
A.ProcessairinletB.Dryairoutlet
Figure4.3Positionbehindscreen.
190TGB-1037-G1307Installation11

Figure4.4Positionfarawayfromdoor/airlock.
IceDry800/1400
Figure4.5Processairductfarawayfromdoor/airlock.
CA
UTION!
CA CA
UTION! UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
Theopeningsofinletandoutletductsmustbewellsealedduringinstallationandoperationstops,whenthe
dehumidierisnormallyswitchedoff.Thispreventsiceformationinductsanddehumidiercausedby
unintendedventilationandlowtemperatureinthecold-storageroom.
12Installation190TGB-1037-G1307

IceDry800/1400
4.8Electricalconnections
W
ARNING!
W W
ARNING! ARNING!
Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
Allunitsaredeliveredcompletewithallinternalcablinginstalledandconguredtothevoltageand
frequencygivenontheIDplate.
NOTE!Supplyvoltagemustnotvarymorethan10%ofthespeciedoperatingvoltage.
Theunitmustbeadequatelyconnectedtoearth.
Forconnectiondetails,refertotheIDplate,Electricalcircuitdiagramsorsection8.2,Technicaldata.The
connectioncableandmainfusesmustbesuitabletotheunitbeinginstalled.
Connecttheunitwithaexiblecabletoawallmountedsocket.Thiswaytheunitcaneasilybedisconnected
fromthepowersupplybyremovingtheplugfromthesocket.
190TGB-1037-G1307Installation13

IceDry800/1400
4.9Pre-startsettings
Ondeliverytheoperationalparametersaresetforuseinacoldstore.
Theapplicationdoesnotrequiretheconnectionofexternalsensorsorexternalinput/outputsignals.
4.10Pre-startchecks
W
ARNING!
W W
ARNING! ARNING!
Themainpowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,maintenance
andrepairsmustonlybecarriedoutbyauthorisedpersonnel.
Beforestartingthedehumidierforthersttime,ensurethatthemainpowersupplyisisolatedfromthe
dehumidierandcarryoutthefollowingchecks:
1.MakesurethatthemodeselectorswitchonthedehumidierisintheOFFposition..
2.Makesurethattheairintakeltersareundamagedandproperlytted,andthatallareasinsidetheunit
arecleanandfreefromice.
3.Visuallyinspectallductingandductconnectionstomakesurethatallconnectionshavebeencorrectly
installedandthattherearenosignsofdamagetothesystem.Alsocheckthatallductsarefreefrom
obstaclesblockingtheairpassage.
4.Checkthattheincomingpowersupplyvoltageiscorrectandthatthecablesarecorrectlyconnected.
5.Afterconnectingtheprocessfantopower,checkthefanturningdirection.
6.Openthedehumidier'sfrontpanel.
7.Startthedehumidierandcheckthatthefanisturning.
8.Switchoffthedehumidierandcheckthefanjustbeforeitstops.Makesureithasaclockwiserotation
9.Makesurethattheunit'spowersupplyandmainswitchareonassoonastheunithasbeeninstalledinthe
cold-storageroom.Ifnot,checkifthereisiceintheunit.
10.Setthedamperforthereactivationairowfullyopen.
11.Setthedamperfortheprocessairow50%open.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
14Installation190TGB-1037-G1307

IceDry800/1400
4.11Airowcheckandadjustment
ContactMuntersServicefordehumidierinstallationandadjustment.TheaddressestoMunterscanbe
foundonthebackpageofthismanual.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessandreactivationairowsarenotproperlyadjusted,theunitcanmalfunction.Theairowmustbeset
tomaximum10%abovethespeciednominalvaluelistedinsection8.2,Technicaldata.
1.Byadjustingthedampersinstalledinthedryairoutletandreactivationairinletducts,theprocessand
reactivationairowscanbechangedtotherequiredsetting.
2.Startthedehumidierforapproximately10minutestoallowthereactivationheatertoreachitsnormal
operatingtemperature.Seesection5.5,Operatingtheunit.
3.Checkthatthetemperaturedifferencebetweenreactivationairdownstreamoftheheater,andthe
regenerationtemperatureisapprox.95°C(tolerancelimitis±5°C).
4.Ifthetemperaturedifferenceliesoutsideofthetolerancelimit,thereactivationairdampercanbe
adjustedinsmallsteps(whichcausesthetemperatureindicatortostabiliseaftereachadjustment)until
reactivationtemperatureiswithinthespeciedtolerances.
Example:
Inletairtemperature=15°C
Reactivationairtemperature=110°C
Temperatureincrease=95°C
190TGB-1037-G1307Installation15

IceDry800/1400
5Operation
5.1General
ThedehumidierisequippedwithanoperatorpanelthatcontainsmodeswitchandLEDindicators.The
modeswitchoftheoperatorpanelhastwooperatingmodes:
MAN(Manualmode):
Thedehumidiersfans,rotorandreactivationheateroperatecontinuouslywithfullcapacity.
AUT(Automaticmode)-notapplicable.
5.2Safety
W
ARNING!
W W
ARNING! ARNING!
Inthecaseofapowercut,thedehumidierwillrestartautomaticallywhenthepowersupplyisrestored.
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA
UTION!
CA CA
UTION! UTION!
Topreventdamagetothefans,theunitmustnotberunforlongerthanafewminutespriortosetting-uptheprocess
andreactivationairows.
CA
UTION!
CA CA
UTION! UTION!
Donotturnoffthemainpowerswitch.Thiscanleadtoiceformationandmalfunctionofthedehumidier.
5.3Quickstop
Themodeswitchisusedtostartandstoptheunitinnormaloperation.Incaseofanemergency,usethemain
powerswitchonthedehumidier,seesection5.4,Operatorpanel.
CA
UTION!
CA CA
UTION! UTION!
Onlyusethemainpowerswitchtostoptheunitinthecaseofanemergency.Thenormalshutdownsequencewill
notbefollowed.Thefansstopandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandother
componentsclosetoit.
16Operation190TGB-1037-G1307

IceDry800/1400
150 C
100 C
50 C
o
o
o
AU T
MAN
4
56 7810 9
11
12
13
14
0
2 3
5.4Operatorpanel
ItemDescriptionFunction
1MainPowerSwitchWiththemainpowerswitchselectedtothe“0”position,poweris
removedfromthecontrolcircuitandtheunitcannotbestarted.
Withthemainpowerswitchselectedtothe“1”position,poweris
appliedtothecontrolcircuitandthedehumidiercanbestarted
usingtheModeswitch.
Themainpowerswitchmustalwaysbeontoavoidbuildupof
iceinsidetheunit.
2ReactivationairfanindicatorThereactivationairindicatorisonwhenthefanisrunning.The
indicatorwillashtoindicateafanfault.
3ReactivationairtemperaturedisplayIndicatesreactivationairtemperature.
4ModeswitchWiththemodeswitchinthe“MAN”position,thedehumidier
willoperateinthemanualmode.Inthismodetheunitwillrun
continuously(fullcapacity).
Withthemodeswitchinthe“O”position,thedehumidieris
switchedoff.
5Notapplicable
NOTE!AUT(Automaticmode)-notapplicable
6Reactivationheater(Stage1)Indicator .Theindicatorisonwhentherelevantheaterstageisswitched
190TGB-1037-G1307Operation17
on.Theindicatorwillashtoindicateaheater(stage1)fault.

IceDry800/1400
ItemDescriptionFunction
7ReactivationHeater(Stage2)IndicatorTheindicatorisonwhentherelevantheaterstageisswitched
on.Theindicatorwillashtoindicateaheater(stage2)fault.
8ProcessAirFanIndicatorTheprocessairfanindicatorisonwhenthefanisrunning.The
indicatorwillashtoindicateafault.
9DrivemotorindicatorThedrivemotorindicatorisonwhentherotordrivemotoris
operating.Theindicatorwillashtoindicateadrivemotorfault.
10Notapplicable
11Notapplicable
12FaultwarningindicatorWhenthefaultwarningindicatorisashing,itindicatesthat
theunithasshut-downduetooneofthefollowingfaultsbeing
detected:
-Processairfanfault
-Reactivationairfanfault
-Drivemotorfault
-Electricreactivationheater(stage1)fault
-Electricreactivationheater(stage2)fault
Toassistwithfaultdiagnosis,thecorrespondingindicatorwill
beashing.
Inadditiontheremotefaultoutputrelaywillbeactivated-
generalindication.
Forfurtherdetailsrefertosection7,Faulttracing.
13UnitrunningindicatorIndicatesthattheunitisrunning.
14PowerConnectedindicatorIndicatesthatmainpowerhasbeenconnectedtothe
dehumidierandthemainpowerswitchisinthe“1”position.
Table5.1Functionsforoperatorpanel.
18Operation190TGB-1037-G1307

IceDry800/1400
5.5Operatingtheunit
5.5.1General
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
Whentheunitisinstalledintothefreezerandthereactivationcircuitisconnected,theconnectionshave
tobeblockeduntiltheunitcanbestarted.Ifthisisnotdonethereisriskthattherewillbeicebuildupin
thereactivationpiping.
Beforestartingtheunit,makesurethatthereactivationductingisfreeofice.
Powermustbeconnectedtotheunitassoonaspossibletokeepthereactivationfanfreeofice(heater
inside).
Unlessthepowerisconnectedimmediatelyuponinstallation,waitaminimumof12hourspriortothestart
oftheunit.
5.5.2Start
1.Ensurethepowerconnectedindicatorisilluminated
2.OperatethemodeswitchontheOperator´spaneltotheMANposition.
NOTE!Thereactivationairfanandreactivationheaterwillstartimmediatelyandwillberunningforapprox.5
minutesbeforetheprocessairfanandthedrivemotorfortherotorstartoperating.
3.Checkthatthefollowingindicatorsareon:
■Powerconnectedindicator
■Unitrunningindicator
■Bothreactivationheaterindicators
■Processandreactivationairfanindicators
■Drivemotorindicator
4.Allowtheunittorunforapproximately10minutestoensurethattheoperatingconditionshave
stabilizedandcheckthatthereactivationheaterisoperating(temperatureindicatordisplaysreactivation
airtemperature).
NOTE!IfthereactivationairtemperatureisnotindicatedatallordoesnotreachabovetherstquarteroftheLED
bargraphthereasonmightbethattheairowistoohigh.SeeAirowCheckandAdjustment.
5.5.3Restartafterpowerfailure
Whenthepowerisremovedfromtheunit,orthereisaunitstopduetoaunitmalfunction,thereactivation
owandheaterisalsostopped.
190TGB-1037-G1307Operation19

IceDry800/1400
CA
UTION!
CA CA
UTION! UTION!
Donotrestarttheunitwithoutrstleavingthereactivationheateronfor12hours.Seriousdamagetotheunitcan
betheresult.Withoutimmediateactionthereisariskthattherewillbeicebuild-upinthereactivationcircuit.
Toavoidtheriskforicetobuildup,theinandoutletopeningshavetobeblockedsonomoisturecanenter
thecircuitandcondensateandfreezeup.Withhighhumidityvaluesoutsidethiswillcreateaproblemwithin
afewhours.
ContactMuntersServicetodiscussthebestsolutionhowtominimisetheeffectsofapowersupplyfailure.
5.5.4Stop
1.Operatethemodeswitchtothe“0”positionandcheckthatbothreactivationheaterindicatorsgoout.
NOTE!Inorderfortheunittocooldown,thereactivationairfan,processairfanandthedrivemotorwillcontinue
torun(aftertheunithasbeenswitchedoff)untilthetemperaturehasfallenbelow50°C.
2.Checkthatwhenthereactivationairtemperaturefallsbelow50°C,theprocessairfan,reactivationfan
anddrivemotorindicatorsgooutandthatthepowerindicatorremainson.
CA
UTION!
CA CA
UTION! UTION!
Duringstand-by(themodeswitchinposition0)themainpowerswitchmustalwaysbeontoavoidbuildupof
iceinsidetheunit.
3.Inordertodissipateanyresidualheat,thereactivationairfanandtherotordrivemotorwillcontinueto
rununtilthereactivationtemperaturehasfallenbelowapproximately50°C.
4.Checkthatthereactivationairfanandthedrivemotorstoponcethereactivationtemperaturehasfallen
belowapproximately50°C.Afewminutesdelayisnormal.
20Operation190TGB-1037-G1307

IceDry800/1400
6Serviceandmaintenance
6.1Safety
W
ARNING!
W W
ARNING! ARNING!
Adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnel.
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationandwetairinletsandoutletsmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
6.2General
Thedehumidierisdesignedforcontinuoususeoveralongperiodoftimewithaminimalamountof
supervision.Undernormaloperatingconditions,maintenancerequirementsareminimal.Theservice
intervaldependsmainlyontheoperationalconditionsandworkingenvironment.
Seesection6.5,Serviceandmaintenancescheduleforanexampleofastandardserviceandmaintenanceprogram.
6.3Serviceoptions
Inadditiontocommissioningoftheunittherearefourserviceoptions(A-D)asstandard.
S.Commissioning/start-up.
A.Inspectionandifnecessarychangeoflter.Generalfunctioncheck.
B.InadditiontoA,safetycheckandcapacity ,temperatureandhumidityregulationmeasurements.
C.InadditiontoB,preventivereplacementofsomecomponentsafter3yearsofoperation.
D.InadditiontoC,preventivereplacementofsomecomponentsafter6yearsofoperation.
NOTE!AlwayscontactMuntersforserviceorrepair.Operatingfaultscanoccuriftheunitismaintained
insufcientlyorincorrectly.
NOTE!Commissioning/Start-upinspection"S"byMuntersismandatorytovalidatethefullwarranty.
Muntersserviceengineershavespecialequipmentandrapidsparepartsaccesstohandleserviceonall
Muntersproducts.Alltestequipmentusedbyourpersonneltoensurepropersystembalancingiscertied
foraccuracy .
MuntersServicecanofferaserviceplanadaptedtosuittheconditionsofaspecicinstallation.Seecontact
addressesonthebackpageofthismanual.
6.4Extendedwarranty
MuntersoffersanextendedwarrantytothestandardtermswhentheCustomersignsaservicecontractwith
Munters.Detailsareavailableonrequest.
190TGB-1037-G1307Serviceandmaintenance21

6.5Serviceandmaintenanceschedule
ServicelevelSABACABAD
IceDry800/1400
Servicework
FilterreplacementandoperationalchecksXXXXXXXXX
Preventiveinspectionincl.safetycheckXXXXX
Capacitycheck,rotorinspectionXX
ReplacementofHTCOThermostatsX
Inspectdrivebeltandbackingrollers,replaceif
necessary
RotordrivemotorreplacementX
Fanrevision(impellers,motors,bearings)X
Switchboard-controlbox,operationalcheckXXXXX
ChecktemperaturecontrolsensorsXXXX
Rotorcovers-rotorseals-connectionpiece,
replacement
Operatingtimeinhours040008000120001600020000240002800032000
Calendartimeinmonths0612182430364248
XX
Table6.1Serviceandmaintenanceschedule(0-48months)
X
NOTE!TheunitmustberemovedfromthecoldstorageroomatservicelevelCandD.
22Serviceandmaintenance190TGB-1037-G1307

IceDry800/1400
ServicelevelABACABAD
Servicework
FilterreplacementandoperationalchecksXXXXXXXX
Preventiveinspectionincl.safetycheckXXXX
Capacitycheck,rotorinspectionXX
ReplacementofHTCOThermostatsX
Inspectdrivebeltandbackingrollers,replaceif
necessary
RotordrivemotorreplacementX
Fanrevision(impellers,motors,bearings)X
Switchboard-controlbox,operationalcheckXXXX
ChecktemperaturecontrolsensorsXXXX
Rotorcovers-rotorseals-connectionpiece,
replacement
Operatingtimeinhours3600040000440004800052000560006000064000
Calendartimeinmonths5460667278849096
XX
Table6.2Serviceandmaintenanceschedule(54-96months)
X
NOTE!TheunitmustberemovedfromthecoldstorageroomatservicelevelCandD.
190TGB-1037-G1307Serviceandmaintenance23

IceDry800/1400
7Faulttracing
7.1General
Thepurposeofthischapteristoprovideguidanceinbasicfaulttracingandprovideinstructionsfor
correctiveactionstoremedyanyfaults.GothroughthelistbelowbeforecontactingMuntersService.
7.2Safety
W
ARNING!
W W
ARNING! ARNING!
Adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnel.
W
ARNING!
W W
ARNING! ARNING!
Alwaysswitchoffthemainpowerswitchbeforeremovingtheunit'spanels.
7.3Faulttracinglist
Seethewiringdiagramforidenticationofelectricalcomponents.
Fault
symptom
Unithas
stopped.
Unithas
stopped.
Unithas
stopped.
Unithas
stopped.
Indicators
Alloff.
No.12
doesnot
ash.
No.12,
6and
7are
ashing.
No.12
and
either6
or7are
ashing.
Possiblecause
Powersupplyfailure.Checkthepowersupplytotheunit.
CircuitbreakerQM25trippeddue
toawiringfault.
Mainpowerswitch(no.1)issetto
”0”.
TransformerTC25fuseFU26
failure.
CircuitbreakerQM25trippeddue
toawiringfault.
Theunithasbeensetto
AUTomaticmodebymistake.
Ifbothindicators6and7are
ashing,itindicatesthat
one(orboth)ofthehigh
temperaturecut-outs(BT27
andBT30)havetripped,due
toeitheranobstructioninthe
reactivationairow,orbecause
thereactivationairowhasbeen
settoolow .
Safetydevicehavetrippeddueto
aheaterelementorwiringfault.
Correctiveaction
IfthetimeofthepowerfailureisnotknownseesectionRestartafterpower
failureorcallMuntersServicebeforestartup.
Ifobservedimmediately ,resetthecircuitbreaker .
Setthemainsupplyswitchto”1”andcheckthatthemainconnection
indicator(no.14)islit.
Investigatethecauseofthefault,andrectify.Replacethefuse.Ifthefault
re-occurs,contactMunters.
Investigatethecauseofthefault,andrectify.ResetQM25.
SetthemodeswitchtoMANual,andcheckthattheunitstarts.
Leavetheunittocooldown.
ResetQM12andQM14circuitbreakersasrequired.
Checkthattheairinletandoutletductsandltersarefreefromobstructions
andarenotblockedbyiceordirt.
SetthemainsupplyswitchtoONtoresetthefaultwarning.Adjustthe
reactivationairow.
Switchoffthemainsupplyandallowtheunittocooldown.
Investigatethecauseofthefault,andrectify.
ResetQM12andQM14asrequired.
Switchonthemainsupplyatthemainsupplyswitchtoresetthefault
warning.
NOTE!Themainpowerswitchmustbeonforatleast12hoursbefore
thestart.Thistimeisrequiredtolettheinternalheatequipmentremove
possibleicebuiltup.
24Faulttracing190TGB-1037-G1307

IceDry800/1400
Fault
symptom
Unithas
stopped.
Indicators
No.
12,2,8
and/or
9are
ashing.
Table7.1Faulttracinglist
Possiblecause
Safetydevicehastrippeddueto
oneofthefollowing:Fanmotor
faultDrivemotorfaultWiring
fault.
Correctiveaction
Switchoffthemainsupplyandallowtheunittocooldown.
Investigatethecauseofthefault,andrectify.
ResetQM16—reactivationfan.
ResetQM21—processfananddrivemotor .
Switchonthemainsupplyatthemainpowerswitch,andstarttheunitto
resetthefaultwarning.
NOTE!Themainpowerswitchmustbeonforatleast12hoursbefore
thestart.Thistimeisrequiredtolettheinternalheatequipmentremove
possibleicebuiltup.
Ifthefaultre-occurscallMunters.
190TGB-1037-G1307Faulttracing25

8Technicalspecication
C
P
M
L
1
2
N
A
N
4
ØE
3
F
H
G
P
ØR
ØD
40 0
25 0
12 0
20 0
12 0
14 5
14 5
8.1Dimensionsandservicespace
IceDry800/1400
Figure8.2Holepattern
Figure8.1Requiredservicespace
1.Processairinlet3.Reactivationairinlet
2.Dryairoutlet4.Wetairoutlet
Dimensions(mm)
Model
IceDry80071559013101601252502702326501102323724029570084550128
IceDry140071559014102001252502702327501102323724029570084550146
(1)Spaceforservice.
ABCØDØEØRFGHJLMNPX
(1)Y(1)Z(1)
26Technicalspecication190TGB-1037-G1307
Weight(kg)

IceDry800/1400
8.2Technicaldata
Processair
Ratedairow(m
Ratedairow(m
Minimumavailablestaticpressure(Pa)200300
Fanmotorpower(kW)at50Hz0,551,10
Fanmotorpower(kW)at60Hz—1,32
Reactivationair
Ratedairow(m
Ratedairow(m
Minimumavailablestaticpressure(Pa)100100
Fanmotorpower(kW)at50Hz0,160,24
Fanmotorpower(kW)at60Hz—0,29
1
3
/s)0,2220,388
3
/h)8001400
1
3
/s)0,0430,071
3
/h)155254
IceDry800IceDry1400
RatedCurrent
Current(Amps/Phase)3~50Hz380V9,415,1
Current(Amps/Phase)3~50Hz400V9,114,6
Current(Amps/Phase)3~50Hz415V8,914,3
Current(Amps/Phase)3~60Hz230V—24,4
Current(Amps/Phase)3~60Hz440V—13,6
Current(Amps/Phase)3~60Hz460V—13,2
ReactivationHeater
Temperatureincreaseacrossheater(°C)9595
ReactivationHeaterPower(kW)4,36,3
OtherTechnicalData
Operatingrangefordehumidier,ambienttemperature(°C)–25to+40–25to+40
Drivemotorpower(W)1010
Heaterreactivationfanhousing(W)240240
Heaterinelectricalcabinet(W)250250
Airltration(standard)G3G3
Electricalprotectionstandard,dustandwaterresistant(maincasing)IP44IP44
FanMotorWindingInsulationClassClassFClassF
DriveMotorWindingInsulationClassClassFClassF
HighT emperatureCut-Out(°C)160+/-5160+/-5
Contactorcoil,voltage(VAC)2424
190TGB-1037-G1307Technicalspecication27

IceDry800/1400
External(Volt-free)OutputContacts
MaxnoiselevelUnducted(dBA)8080
1
Figuresquotedarenominal,basedonfaninlettemperatureof20°C,andanairdensityof1.2kg/m
2
ContactsonthePCBusedtogivearemotefaultoutput
2
3
.
2A,50VAC2A,50VAC
Table8.1Technicalspecications
8.3Sounddata
Noisefor
dB(A)Lwt631252505001000200040008000
Duct1Na101-10-2-9-13-20-22-27-33
Duct2Na102-3-5-13-20-20-19-21-26
Duct3Na94-5-6-5-1720-21-23-27
Duct4Na88-2-6-12-25-31-31-33-35
Room6490-1-8-14-16-20-23-26-31
CorrectionKokdBatISO-bandcentrefrequency,Hz
Noisepathstosurroundings
1.Ductworkfordryair
2.Ductworkforprocessair
3.Ductworkforreactivationair
4.Ductworkforwetair
SYMBOLS
Lwt=TotalnoiseleveldB(rel.10-12W)
Lw=NoisepowerlevelinoctavebanddB(rel.10-12W)
Kok=CorrectionforcalculatingLw(Lw=Lwt+Kok)
dB(A)=Ratednoiselevelat100m
2
roomabsorption
28Technicalspecication190TGB-1037-G1307

IceDry800/1400
9Scrapping
Theunitmustbescrappedinaccordancewithapplicablelegalrequirementsandregulations.Contactyour
localauthorities.
Therotormaterialisnotcombustible,andshouldbedepositedlikeglassbrematerials.
Iftherotorhasbeenexposedtochemicalsthataredangeroustotheenvironmenttheriskmustbeassessed.
Thechemicalscanaccumulateintherotormaterial.Takethenecessaryprecautionstocomplywith
applicablelegalrequirementsandregulations.
W
ARNING!
W W
ARNING! ARNING!
Iftherotoristobecutinpieces,wearasuitableCEmarkedfacemaskselectedandttedinaccordancewiththe
applicablesafetystandardstoprotectfromthedust.
190TGB-1037-G1307Scrapping29


IceDry800/1400
10ContactMunters
AUSTRIA
BELGIUM
DENMARK
FINLAND
FRANCE
GERMANY
ITAL Y
NETHERLANDS
POLAND
SPAIN
SWEDEN
SWITZERLAND
UNITEDKINGDOM
MuntersGmbH
AirTreatment
ZweigniederlassungWien
MuntersBelgiumnv
AirTreatment
MuntersA/S
AirTreatment
MuntersFinlandOy
Kuivaajamyynti
MuntersFranceSAS
AirTreatment
MuntersGmbH
AirTreatment-Zentrale
MuntersItalyS.p.A
AirTreatment
MuntersV ochtbeheersingEnergieweg69
MuntersSp.zo.o.
OddzialwPolsce
AirTreatment
MuntersSpainSA
AirTreatment
MuntersEuropeAB
AirTreatment
MuntersGmbH
AirTreatment
ZweigniederlassungRümlang
MuntersLtd
AirTreatment
Eduard-Kittenberger-Gasse56,
Obj.6
A-1235Wien
Blarenberglaan21c
B-2800Mechelen
Ryttermarken4
DK-3520Farum
Hakamäenkuja3
FI-01510V ANTAA
106,BoulevardHéloise
F-95815ArgenteuilCedex
Hans-Duncker-Str.8
D-21035Hamburg
StradaPiani2
I-18027Chiusavecchia
IM
NL-2404HEAlphena/dRijn
ul.Swietojanska55/11
81-391Gdynia
EuropaEpresarial.EdicioLondres.
C/PlayadeLiencres2.
28230LasMatas.Madrid
POBox1150
S-16426Kista
Glattalstr.501
CH-8153Rümlang
PathnderPlace10RamsayCourt
HinchingbrookeBusinessPark
HuntingdonPE296FYCambs
Tel:+4316164298–9251
luftentfeuchtung@munters.at
www.munters.at
Tel:+321528561 1
service@muntersbelgium.be
www.muntersbelgium.be
Tel:+4544953355
info@munters.dk
www.munters.dk
Tel:+358207768230
laitemyynti@munters.
www.munters.
Tel:+331341 15757
dh@munters.fr
www.munters.fr
Tel:+49(0)40879690-0
mgd@munters.de
www.munters.de
Tel:+390183521377
marketing@munters.it
www.munters.it
Tel:+31172433231
vochtbeheersing@munters.nl
www.munters.nl
Tel.:+48583053517
dh@munters.pl
www.munters.com.pl
Tel:+34916400902
marketing@munters.es
www.munters.es
Tel:+4686266300
avfuktning@munters.se
www.munters.se
Tel:+41523438886
info.dh@munters.ch
www.munters.ch
Tel:+441480432243
info@munters.co.uk
www.munters.co.uk
AUSTRALIA
BRAZIL
CANADA
CHINA
INDIA
JAPAN
KOREA
Tel:+61288431588
dh.info@munters.com.au
Tel:+551150540150
www.munters.com.br
Tel:+1-800-843-5360
dhinfo@munters.com
Tel:+861080418000
marketing@munters.cn
Tel:+912066818900
info@munters.in
Tel:+81359700021
mkk@munters.jp
Tel:+8227618701
munters@munters.kr
MEXICO
SINGAPORE
SOUTHAFRICA
TURKEY
UAE(Dubai)
USA
Tel:+527222704029
munters@munters.com.mx
Tel:+6567446828
singapore@muntersasia.com
Tel:+27119972000
info@munters.co.za
Tel:+902165481444
info@muntersform.com
Tel:+97148813026
middle.east@munters.com
Tel:+1-800-843-5360
dhinfo@munters.com
190TGB-1037-G1307ContactMunters31

www.munters.com