Munters ICEDRY 800, ICEDRY 1400 User Manual

Originalinstructions
Usermanual
IceDry800/1400
Desiccantdehumidier
190TGB-1037-G1307©MuntersEuropeAB2013
Importantuserinformation
Muntersdehumidiersareintendedtobeusedforthe dehumidicationofair.Anyotheruseoftheunit,or usewhichiscontrarytotheinstructionsgiveninthis manual,cancausepersonalinjuryanddamagetotheunit andotherproperty.
Nomodicationoftheunitisallowedwithoutprior approvalbyMunters.Attachmentorinstallation ofadditionaldevicesisonlyallowedafterwritten agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit leftourfactory,unlessotherwisestatedinwriting. Thewarrantyislimitedtoafreeexchangeofpartsor componentswhichhavefailedasaresultofdefectsin materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthe faulthasoccurredwithinthewarrantyperiodand thattheunithasbeenusedinaccordancewiththe specications.Allclaimsmustspecifytheunittypeand fabricationnumber.Thisinformationisstampedonthe identicationplate,seesectionMarking.
Itisaconditionofthewarrantythattheunitforthefull warrantyperiodisservicedandmaintainedbyaqualied MuntersengineerorMuntersapprovedengineer. Accesstospecicandcalibratedtestequipmentis necessary.Theserviceandmaintenancemustbe documentedforthewarrantytobevalid.
AlwayscontactMuntersforserviceorrepair.Operating faultscanoccuriftheunitismaintainedinsufcientlyor incorrectly.
Safety
Informationaboutdangersareinthismanualindicated bythecommonhazardsymbol:
W
ARNING!
W W
ARNING! ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury .
CA
UTION!
CA CA
UTION! UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty ,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential safetyrequirementsoftheMachineryDirective 2006/42/EC,theLowVoltageDirective2006/95/EC andtheEMCDirective2004/108/EC.The dehumidierismanufacturedbyanISO9001:2008 accreditedmanufacturingorganisation.
Copyright
Thecontentsofthismanualcanbechangedwithout priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Pleasesendanycommentsregardingthismanualto:
MuntersEuropeAB TechnicalDocumentation P.O.Box1150 SE-16426KISTASweden e-mail:t-doc@munters.se
iiImportantuserinformation190TGB-1037-G1307
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
Warranty...............................
Safety..................................
ConformitywithDirectives............
Copyright..............................
Tableofcontents...........................iv
1Introduction.................................1
1.1General................................
1.2Aboutthismanual.....................
1.3Safetyandcautions...................
1.4Marking................................
1.5Supervisionofoperation..............
1.6Faultindications.......................
2Productdesign..............................4
2.1Productdescription...................
2.2Principleofoperation..................
3Transport,inspectionandstorage.......5
3.1Movingtheequipment................
3.2Packaginganddeliveryinspection...
3.3Storingtheequipment................
4Installation...................................6
4.1General................................
4.2Safety..................................
4.3Siterequirements.....................
4.4Mirrorhandedductconnections......
4.5Wheretoinstallthedehumidier.....
4.6Ducting.................................
4.6.1Generalrecommendations...
4.6.2Processairinlet................
4.6.3Dryairoutletduct..............
4.6.4Reactivationairintake........
4.6.5Ductworkforwetairoutlet.....
4.7Installationexamples—coldstorage
ii
ii
ii
ii
ii
5Operation....................................16
1
1
1
3
3
3
4
4
5
5
5
6
6
6
7
8
8
8
9
9
9
10
6Serviceandmaintenance.................21
7Faulttracing.................................24
8Technicalspecication....................26
9Scrapping....................................29
10ContactMunters............................31
room(freezer).........................
4.8Electricalconnections................
4.9Pre-startsettings......................
4.10Pre-startchecks.......................
4.11Airowcheckandadjustment........
5.1General................................
5.2Safety..................................
5.3Quickstop..............................
5.4Operatorpanel........................
5.5Operatingtheunit.....................
5.5.1General.........................
5.5.2Start.............................
5.5.3Restartafterpowerfailure.....
5.5.4Stop.............................
6.1Safety..................................
6.2General................................
6.3Serviceoptions........................
6.4Extendedwarranty....................
6.5Serviceandmaintenanceschedule..
7.1General................................
7.2Safety..................................
7.3Faulttracinglist........................
8.1Dimensionsandservicespace.......
8.2Technicaldata.........................
8.3Sounddata.............................
11
13
14
14
15
16
16
16
17
19
19
19
19
20
21
21
21
21
22
24
24
24
26
27
28
ivTableofcontents190TGB-1037-G1307
IceDry800/1400
1Introduction
1.1General
Muntersmanufacturesawiderangeofefcientdehumidiersdesignedfordifferentusesandapplications. PleasecontactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationofyour dehumidier,orvisitthewebsiteatwww .munters.com. Theunitisinspectedandcheckedpriortoleavingthefactorytoguaranteeconsistentqualityandmaximum reliability.Forproductdata,seesectionTechnicalspecication.
1.2Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforetheunitisinstalledand used.
1.3Safetyandcautions
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualincludessuggestionsforbestworkingpracticeandshallinnowaytake precedenceoverindividualresponsibilitiesorlocalregulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
Forinformationaboutthesafetysymbolsusedinthismanual,seesectionImportantuserinformation.
190TGB-1037-G1307Introduction1
IceDry800/1400
W
ARNING!
W W
ARNING! ARNING!
-Theunitisnotintendedforuseinhazardous(classied)areaswhereexplosionsafetycompliantequipment
isrequired.
-Theunitmustnotbesplashedwithorimmersedinwater.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheunit’sidenticationplate,seesectionMarking.
-Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.
-Donotoperatetheunitnearanyheat-generatingdevicesorammableanddangerousmaterials.
-Donotinsertngersoranyotherobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventaccidents.
-AlwayscontactMuntersforserviceorrepair.
2Introduction190TGB-1037-G1307
IceDry800/1400
0919 190XX X XXX XX
0,72 kW
Max
5,4 kW
M unters Europe AB Isafjordsgatan 1 164 26 Kista, Sw eden
M
4,38 kW
M ade in Sw eden
Fabr. N o.
Fabr. year 2009
3 ~ 400V 50 H z
Type
IP44
IceD ry800
1.4Marking
Figure1.1Locationoflabels
Explanationof"Fabr.No"ontheidenticationplate:
09=yearofmanufacture,19=weekofmanufacture,190XXX=articlenumber,XXXXX=serialnumber
1.5Supervisionofoperation
Thedehumidieriscontrolledandmonitoredfromtheoperatorpanellocatedonthefrontoftheunit.
1.6Faultindications
Faultsareclearlyindicatedontheoperatorpanel.TheashingLEDsindicatewhichcomponentthat requiresattentionformaintenanceorreplacement.
1.Identicationplate2.Dryairoutlet
3.Wetairoutlet4.Processairinlet
5.Reactivationairinlet
190TGB-1037-G1307Introduction3
IceDry800/1400
2
1
4
3
2Productdesign
2.1Productdescription
ThedesiccantdehumidiersintheIceDryserieshavebeendevelopedtoeffectivelydehumidifytheairin coldstoresinordertominimisefrostandicebuild-up
Thedehumidierisequippedwithanencapsulatedrotorunit.Therotorcasingisconstructedofdurable thermosetplasticandcontainsisolatedsectionsthatprovideaprecisebalanceforthedehumidication, reactivationandheatrecoveryairows.
TheelectricalcontrolsystemcomplieswiththeEN60204(IEC60204)standards.Foroperating temperature,seesection8.2,Technicaldata. ThedehumidierismanufacturedinaccordancewithuniformEuropeanstandardsandestablished requirementsforCE-marking.
2.2Principleofoperation
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
Figure2.1Principleofoperation
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthrough therotor'slargestzoneandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This principleenablesthedehumidiertoworkeffectively ,evenatfreezingtemperatures.
4Productdesign190TGB-1037-G1307
IceDry800/1400
3Transport,inspectionandstorage
3.1Movingtheequipment
Thedehumidierisdeliveredonapalletandmustbehandledcarefully .Allpaneldoorsontheunitmustbe closedduringtransport.Providedthatthedehumidierisstillsecuredtoitsdeliverypallet,itcanbemoved usingafork-lifttruck.
Weightofthedehumidiercanbefoundinsection8,Technicalspecication.
3.2Packaginganddeliveryinspection
1.Checkthedeliveryagainstthedeliverynote,orderconrmationorotherdeliverydocumentationand checkthateverythingisincludedandnothingisdamaged.
2.ContactMuntersimmediatelyifthedeliveryisnotcompleteinordertoavoidinstallationdelays.
3.Iftheunitistobeputintostoragepriortoinstallation,seesectionStoringtheequipment.
NOTE!Ifinstallationisnottobecarriedoutimmediatelyafterarrivaloftheequipment,itisadvisabletoleave
thepackagingmaterialinplaceonthedehumidier,ortore-usethepackagingmaterialtoprovidetemporary
protectionfortheunitduringlatertransportationtothesiteandduringinstallation.
4.Removeallpackagingmaterialfromtheunit,checkcarefullytomakesurethatnodamagehasoccurred duringtransportation.
5.AnyvisibledamagemustbereportedinwritingtoMunterswithin5daysandpriortoinstallationof theunit.
6.Disposeofthepackagingmaterialaccordingtolocalregulations.
NOTE!G3ltercartridgesforprocessandreactivationairareincludedinthedelivery.Onecartridgeismounted
onthedehumidierprocessairinletandoneontheoutsideofthecold-storageroom,inthereactivationairinlet.
3.3Storingtheequipment
Thefollowingisimportantifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
190TGB-1037-G1307Transport,inspectionandstorage5
IceDry800/1400
4Installation
4.1General
IceDrydehumidiersareintendedforinstallationincoldstoreswithambientairdowntominus25°C. Theseconditionsrequirethatinstallationinstructionsarefollowedcarefullyasfaultyinstallationcanresult inseriousoperationaldisturbances. Iftheunitistobeputintostoragepriortoinstallation,seesection3.3,Storingtheequipment.
4.2Safety
W
ARNING!
W W
ARNING! ARNING!
Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,
maintenanceandrepairsmustonlybecarriedoutbyauthorisedpersonnel.
W
ARNING!
W W
ARNING! ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
CA
UTION!
CA CA
UTION! UTION!
Thebuilt-inheaterrequiresacontinuouspowersupplytopreventfunctionaldisorder.Onlyswitchofftheunit's
powerincaseofemergency.
CA
UTION!
CA CA
UTION! UTION!
Condensationiseasilyformedontheinsideoftheductduetothehighhumidityofthereactivationair.T oavoid
condensation,theductworkmustbeinsulated
CA
UTION!
CA CA
UTION! UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA
UTION!
CA CA
UTION! UTION!
Failuretocorrectlyadjusttheprocessandreactivationairowscouldcausetheunittomalfunction.
4.3Siterequirements
Thedehumidierisadaptedtooperationinsidecoldstores.Thepermittedoperationaltemperatures arefromminus25to0°C.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
6Installation190TGB-1037-G1307
IceDry800/1400
B
A
C
D
E
F
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandfacilitateservicing. Therefore,complywiththerecommendedservicespaces,seesection8.1,Dimensionsandservicespace.
NOTE!Theunitmustberemovedfromthecoldstoreatcertainserviceintervals.Haveextracablesforunit
connectionavailable.
4.4Mirrorhandedductconnections
Thefrontandbackpanelsareinterchangeable,sothattheconnectionsforprocessanddryairmaybe situatedeitherontheleftorrightsideoftheunit.
Thedehumidiersaredeliveredwiththeprocessanddryairconnectionsontheleftsideoftheunit.Ifitis requiredtothechangetheorientation,sothattheconnectionsareontherightsideoftheunit,proceed asfollows.
W
ARNING!
W W
ARNING! ARNING!
Ensurethatmainpowerisisolatedfromthedehumidierpriortochangingtheorientatinoftheprocessanddryair
connections.
1.Removethetwobolts(B)securingthefrontpanelandcarefullyremovethepanel.
2.Removethetwoboltssecuringtherearpanelandcarefullyremovethepanel.
3.Removethetwobolts(A)andwasherssecuringthecontrolandtoppanels,thencarefullyremovethe toppanel.
4.Removethecableductcovers(C),re-routethecablesandtthecontrolpanel(D)ontotheoppositeside oftheunit.Retthecableductcovers.
5.Loosentherotorstop(E)andthetwoltermonitors(F).Removethecableties.
6.Fittherotorstopandltermonitorsontheoppositesideoftheunit.Tiethecables.
7.Fitthefront,rearandtoppanelsintheirnewpositions.
190TGB-1037-G1307Installation7
IceDry800/1400
4.5Wheretoinstallthedehumidier
Selectaplacewherethedehumidiercausestheleastdisturbancetothecold-storageroomactivities,while allowingformaintenanceworksuchasprocesslterreplacement.
Whentheunitisinstalledonabaseframe,thebaseframemustbedesignedinsuchawaythatitcaneasilybe removedfromthecoldstore/freezer.Makesureopeningsforforkliftareincluded.
Thedehumidiermustbeplacedsothatthereisnoriskoftheprocessintakeandltericingup.Icenormally formsnearthedoorsandair-locksofthecoldstorewherewarm,humidairowsin.
Installthedehumidierinsuchawaythatthereactivationairandwetairductsareasshortaspossible,max
1.5m.Seesection4.7,Installationexamples—coldstorageroom(freezer).
4.6Ducting
4.6.1Generalrecommendations
NOTE!Vibrationreduction.Ifthereisaneedtoforreductionofvibrationsfromthedehumidier,contactMunters
forinstructions.RefertostandardEN1299+A1:2008.
Duetothecoldsurroundingsandriskoffreezing,itisvitalthatallductingareinstalledaccordingto instructions.Seealso4.7,Installationexamples—coldstorageroom(freezer).
Tofacilitateeasytransferofthedehumidieroutofthecold-storageroomforservice,allductconnections shouldbeeasilydisassembled.Shouldthedehumidier,despitethisrecommendation,beinstalledinsucha waythatitcannotbeeasilyremovedforservice,itisimportantthattheminimumservicespacerequirements aremet,see8.1,Dimensionsandservicespace.Avapour-tightconnectionbetweenthewallandtheductisvital. Preferably,polyurethanefoamshouldbeusedifthetemperatureissufcientlyhighduringapplication.
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing recommendationsshouldbeobserved:
Thelengthofductworkshouldbekeptasshortaspossibletominimisestaticairpressurelosses.
Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
Thedesignoftheductconnectionsshouldfacilitateeasydisconnectionoftheunitforserviceoutside
thecold-storageroom.
Condensationeasilybuildsupontheinsideoftheductduetothehighhumidityofthereactivationair.
Toavoidcondensation,theductworkmustbeinsulated.
Theprocessairductworkshouldbeinsulatedtopreventcondensationfromdevelopingontheoutside
oftheductwheneverthetemperatureoftheairwithintheductfallsbelowthedewpointoftheambient airthroughwhichtheductworkisrouted.
Thewetairleavingthedehumidierwilleasilycausecondensationontheinsideoftheductwallsdueto
thehighmoisturecontent.Thismustbeavoidedbyinsulatingtheducts.
Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,seesection8.1,Dimensionsandservicespace.
Toreducenoiseand/orvibrationbeingtransmittedalongrigidductwork,goodquality,airtightexible
connectionsshouldbetted.
Ductsmounteddirectlyontothedehumidiershouldbeadequatelysupportedtominimisetheloadand
stressduetotheweightandmovementoftheducting.
8Installation190TGB-1037-G1307
IceDry800/1400
~ 0,5 m
1
3
A
B
2
Min. 2,0 m
2
Dampersforbalancingtheairowmustbeinstalledinthereactivationairinletduct.Correctairows
areessentialformaintainingtheoperatingefciencyoftheunit.Forairowadjustmentdetails,see section4.11,Airowcheckandadjustment.
Processairpressureandowareadjustedusingtheprocessairfan'sfrequencyconverter.Ifthisisthe
case,itisnotnecessarytohaveadamperinthedryairduct.
Thetotalresistanceintheprocessandreactivationductworkmustnotexceedtheperformancerating
ofthefansttedinthedehumidier.Fordetailsofminimumavailablestaticpressure,seechapter
8.2,Technicaldata.
4.6.2Processairinlet
Thedehumidierhasanexternallterboxfortheprocessairinlet.Ifthereisariskoftheprocessairlter icingup,aductshouldbeconnectedtoretrieveprocessairfromadrylocation5-10metresfromthedoor opening.Thelterboxcanthenbemovedtotheinletsideoftheduct.
4.6.3Dryairoutletduct
Channeloutthedryairfromthedehumidieranddistributeitsothatitmixeswiththewarm,humidairthat normallyentersthecoldstoreabovethedoorsandair-locksthatareopenedregularly .Installanadjustable damperintheduct.
4.6.4Reactivationairintake
Placethereactivationairintakeandlterboxoutsidethecoldstore.Mountthelterboxdirectlyonthewall.
Theducttothedehumidierreactivationairintakeshouldbeatmost1.5metreslong,andmustbeinsulated topreventicebuild-up.Thisalsoappliestothesectionofductpassingthroughthewall.Anadjustable damperisinstalledintheduct.
Topreventtheoutgoingwetairhumidifyingtheincomingreactivationair,thereactivationairintakemustbe positionedatleast2metresfromthewetairoutlet
A.Reactivationair
B.Wetair
1.Filterbox
2.Condensatedrains
3.Vapour-tightgrommet
Figure4.1Inletforreactivationairandoutletforwetair.
190TGB-1037-G1307Installation9
IceDry800/1400
4.6.5Ductworkforwetairoutlet
Thewetairductmustbemadeofplasticoranothercorrosionresistantmaterial.Itmustbeabletohandle temperaturesbetween-30°Cand75°C,benomorethan1.5metreslongandbeinsulatedtopreventice formation.Thisalsoappliestothepartoftheductpassingthroughthewall.
Becauseofitshighmoisturecontentthewetairleavingthedehumidierwillcondenseontheinsideof theductwalls.Duetothelowambienttemperaturethereisariskoficeformation.Thewetairductmust thereforebeinsulated.
Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainaway
possiblecondensation.Thedeclinemustbeatleast2cm/mofduct.
5mmdrainholesshouldbemadeatlowpointsoftheducttopreventwateraccumulationintheduct.
Topreventtheoutgoingwetairfromhumidifyingtheincomingreactivationair,thewetairoutletmust
beplacedatleast2metresfromthereactivationinlet.SeeFigure4.1.
NOTE!Alwaysdrillthedrainholesontheoutsideofthecoldstorage/freezerroomwall.
W
ARNING!
W W
ARNING! ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
10Installation190TGB-1037-G1307
IceDry800/1400
A
B
2 - 3 m
4.7Installationexamples—coldstorageroom(freezer)
Muntersrecommendsthefollowinginstallations.Ifindoubt,contactMuntersforadvice.
Notetheservicespacerequirementsinsection8.1,Dimensionsandservicespace.
Figure4.2Positionabovedoor/airlock
A.ProcessairinletB.Dryairoutlet
Figure4.3Positionbehindscreen.
190TGB-1037-G1307Installation11
5 - 10 m
Figure4.4Positionfarawayfromdoor/airlock.
5 - 10 m
IceDry800/1400
Figure4.5Processairductfarawayfromdoor/airlock.
CA
UTION!
CA CA
UTION! UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
Theopeningsofinletandoutletductsmustbewellsealedduringinstallationandoperationstops,whenthe dehumidierisnormallyswitchedoff.Thispreventsiceformationinductsanddehumidiercausedby unintendedventilationandlowtemperatureinthecold-storageroom.
12Installation190TGB-1037-G1307
IceDry800/1400
4.8Electricalconnections
W
ARNING!
W W
ARNING! ARNING!
Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
Allunitsaredeliveredcompletewithallinternalcablinginstalledandconguredtothevoltageand frequencygivenontheIDplate.
NOTE!Supplyvoltagemustnotvarymorethan10%ofthespeciedoperatingvoltage.
Theunitmustbeadequatelyconnectedtoearth.
Forconnectiondetails,refertotheIDplate,Electricalcircuitdiagramsorsection8.2,Technicaldata.The connectioncableandmainfusesmustbesuitabletotheunitbeinginstalled.
Connecttheunitwithaexiblecabletoawallmountedsocket.Thiswaytheunitcaneasilybedisconnected fromthepowersupplybyremovingtheplugfromthesocket.
190TGB-1037-G1307Installation13
IceDry800/1400
4.9Pre-startsettings
Ondeliverytheoperationalparametersaresetforuseinacoldstore.
Theapplicationdoesnotrequiretheconnectionofexternalsensorsorexternalinput/outputsignals.
4.10Pre-startchecks
W
ARNING!
W W
ARNING! ARNING!
Themainpowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,maintenance
andrepairsmustonlybecarriedoutbyauthorisedpersonnel.
Beforestartingthedehumidierforthersttime,ensurethatthemainpowersupplyisisolatedfromthe dehumidierandcarryoutthefollowingchecks:
1.MakesurethatthemodeselectorswitchonthedehumidierisintheOFFposition..
2.Makesurethattheairintakeltersareundamagedandproperlytted,andthatallareasinsidetheunit arecleanandfreefromice.
3.Visuallyinspectallductingandductconnectionstomakesurethatallconnectionshavebeencorrectly installedandthattherearenosignsofdamagetothesystem.Alsocheckthatallductsarefreefrom obstaclesblockingtheairpassage.
4.Checkthattheincomingpowersupplyvoltageiscorrectandthatthecablesarecorrectlyconnected.
5.Afterconnectingtheprocessfantopower,checkthefanturningdirection.
6.Openthedehumidier'sfrontpanel.
7.Startthedehumidierandcheckthatthefanisturning.
8.Switchoffthedehumidierandcheckthefanjustbeforeitstops.Makesureithasaclockwiserotation
9.Makesurethattheunit'spowersupplyandmainswitchareonassoonastheunithasbeeninstalledinthe cold-storageroom.Ifnot,checkifthereisiceintheunit.
10.Setthedamperforthereactivationairowfullyopen.
11.Setthedamperfortheprocessairow50%open.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
14Installation190TGB-1037-G1307
IceDry800/1400
4.11Airowcheckandadjustment
ContactMuntersServicefordehumidierinstallationandadjustment.TheaddressestoMunterscanbe foundonthebackpageofthismanual.
CA
UTION!
CA CA
UTION! UTION!
Iftheprocessandreactivationairowsarenotproperlyadjusted,theunitcanmalfunction.Theairowmustbeset
tomaximum10%abovethespeciednominalvaluelistedinsection8.2,Technicaldata.
1.Byadjustingthedampersinstalledinthedryairoutletandreactivationairinletducts,theprocessand reactivationairowscanbechangedtotherequiredsetting.
2.Startthedehumidierforapproximately10minutestoallowthereactivationheatertoreachitsnormal operatingtemperature.Seesection5.5,Operatingtheunit.
3.Checkthatthetemperaturedifferencebetweenreactivationairdownstreamoftheheater,andthe regenerationtemperatureisapprox.95°C(tolerancelimitis±5°C).
4.Ifthetemperaturedifferenceliesoutsideofthetolerancelimit,thereactivationairdampercanbe adjustedinsmallsteps(whichcausesthetemperatureindicatortostabiliseaftereachadjustment)until reactivationtemperatureiswithinthespeciedtolerances.
Example:
Inletairtemperature=15°C
Reactivationairtemperature=110°C
Temperatureincrease=95°C
190TGB-1037-G1307Installation15
IceDry800/1400
5Operation
5.1General
ThedehumidierisequippedwithanoperatorpanelthatcontainsmodeswitchandLEDindicators.The modeswitchoftheoperatorpanelhastwooperatingmodes: MAN(Manualmode): Thedehumidiersfans,rotorandreactivationheateroperatecontinuouslywithfullcapacity. AUT(Automaticmode)-notapplicable.
5.2Safety
W
ARNING!
W W
ARNING! ARNING!
Inthecaseofapowercut,thedehumidierwillrestartautomaticallywhenthepowersupplyisrestored.
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA
UTION!
CA CA
UTION! UTION!
Topreventdamagetothefans,theunitmustnotberunforlongerthanafewminutespriortosetting-uptheprocess
andreactivationairows.
CA
UTION!
CA CA
UTION! UTION!
Donotturnoffthemainpowerswitch.Thiscanleadtoiceformationandmalfunctionofthedehumidier.
5.3Quickstop
Themodeswitchisusedtostartandstoptheunitinnormaloperation.Incaseofanemergency,usethemain powerswitchonthedehumidier,seesection5.4,Operatorpanel.
CA
UTION!
CA CA
UTION! UTION!
Onlyusethemainpowerswitchtostoptheunitinthecaseofanemergency.Thenormalshutdownsequencewill
notbefollowed.Thefansstopandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandother
componentsclosetoit.
16Operation190TGB-1037-G1307
IceDry800/1400
1
150 C
100 C
50 C
o
o
o
AU T
MAN
4
56 7810 9
11
12
13
14
0
2 3
5.4Operatorpanel
ItemDescriptionFunction
1MainPowerSwitchWiththemainpowerswitchselectedtothe“0”position,poweris
removedfromthecontrolcircuitandtheunitcannotbestarted.
Withthemainpowerswitchselectedtothe“1”position,poweris
appliedtothecontrolcircuitandthedehumidiercanbestarted
usingtheModeswitch.
Themainpowerswitchmustalwaysbeontoavoidbuildupof
iceinsidetheunit.
2ReactivationairfanindicatorThereactivationairindicatorisonwhenthefanisrunning.The
indicatorwillashtoindicateafanfault.
3ReactivationairtemperaturedisplayIndicatesreactivationairtemperature.
4ModeswitchWiththemodeswitchinthe“MAN”position,thedehumidier
willoperateinthemanualmode.Inthismodetheunitwillrun
continuously(fullcapacity).
Withthemodeswitchinthe“O”position,thedehumidieris
switchedoff.
5Notapplicable
NOTE!AUT(Automaticmode)-notapplicable
6Reactivationheater(Stage1)Indicator .Theindicatorisonwhentherelevantheaterstageisswitched
190TGB-1037-G1307Operation17
on.Theindicatorwillashtoindicateaheater(stage1)fault.
IceDry800/1400
ItemDescriptionFunction
7ReactivationHeater(Stage2)IndicatorTheindicatorisonwhentherelevantheaterstageisswitched
on.Theindicatorwillashtoindicateaheater(stage2)fault.
8ProcessAirFanIndicatorTheprocessairfanindicatorisonwhenthefanisrunning.The
indicatorwillashtoindicateafault.
9DrivemotorindicatorThedrivemotorindicatorisonwhentherotordrivemotoris
operating.Theindicatorwillashtoindicateadrivemotorfault.
10Notapplicable
11Notapplicable
12FaultwarningindicatorWhenthefaultwarningindicatorisashing,itindicatesthat
theunithasshut-downduetooneofthefollowingfaultsbeing
detected:
-Processairfanfault
-Reactivationairfanfault
-Drivemotorfault
-Electricreactivationheater(stage1)fault
-Electricreactivationheater(stage2)fault
Toassistwithfaultdiagnosis,thecorrespondingindicatorwill
beashing.
Inadditiontheremotefaultoutputrelaywillbeactivated-
generalindication. Forfurtherdetailsrefertosection7,Faulttracing.
13UnitrunningindicatorIndicatesthattheunitisrunning.
14PowerConnectedindicatorIndicatesthatmainpowerhasbeenconnectedtothe
dehumidierandthemainpowerswitchisinthe“1”position.
Table5.1Functionsforoperatorpanel.
18Operation190TGB-1037-G1307
IceDry800/1400
5.5Operatingtheunit
5.5.1General
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
Whentheunitisinstalledintothefreezerandthereactivationcircuitisconnected,theconnectionshave tobeblockeduntiltheunitcanbestarted.Ifthisisnotdonethereisriskthattherewillbeicebuildupin thereactivationpiping.
Beforestartingtheunit,makesurethatthereactivationductingisfreeofice.
Powermustbeconnectedtotheunitassoonaspossibletokeepthereactivationfanfreeofice(heater inside).
Unlessthepowerisconnectedimmediatelyuponinstallation,waitaminimumof12hourspriortothestart oftheunit.
5.5.2Start
1.Ensurethepowerconnectedindicatorisilluminated
2.OperatethemodeswitchontheOperator´spaneltotheMANposition.
NOTE!Thereactivationairfanandreactivationheaterwillstartimmediatelyandwillberunningforapprox.5
minutesbeforetheprocessairfanandthedrivemotorfortherotorstartoperating.
3.Checkthatthefollowingindicatorsareon:
Powerconnectedindicator
Unitrunningindicator
Bothreactivationheaterindicators
Processandreactivationairfanindicators
Drivemotorindicator
4.Allowtheunittorunforapproximately10minutestoensurethattheoperatingconditionshave stabilizedandcheckthatthereactivationheaterisoperating(temperatureindicatordisplaysreactivation airtemperature).
NOTE!IfthereactivationairtemperatureisnotindicatedatallordoesnotreachabovetherstquarteroftheLED
bargraphthereasonmightbethattheairowistoohigh.SeeAirowCheckandAdjustment.
5.5.3Restartafterpowerfailure
Whenthepowerisremovedfromtheunit,orthereisaunitstopduetoaunitmalfunction,thereactivation owandheaterisalsostopped.
190TGB-1037-G1307Operation19
IceDry800/1400
CA
UTION!
CA CA
UTION! UTION!
Donotrestarttheunitwithoutrstleavingthereactivationheateronfor12hours.Seriousdamagetotheunitcan
betheresult.Withoutimmediateactionthereisariskthattherewillbeicebuild-upinthereactivationcircuit.
Toavoidtheriskforicetobuildup,theinandoutletopeningshavetobeblockedsonomoisturecanenter thecircuitandcondensateandfreezeup.Withhighhumidityvaluesoutsidethiswillcreateaproblemwithin afewhours.
ContactMuntersServicetodiscussthebestsolutionhowtominimisetheeffectsofapowersupplyfailure.
5.5.4Stop
1.Operatethemodeswitchtothe“0”positionandcheckthatbothreactivationheaterindicatorsgoout.
NOTE!Inorderfortheunittocooldown,thereactivationairfan,processairfanandthedrivemotorwillcontinue
torun(aftertheunithasbeenswitchedoff)untilthetemperaturehasfallenbelow50°C.
2.Checkthatwhenthereactivationairtemperaturefallsbelow50°C,theprocessairfan,reactivationfan anddrivemotorindicatorsgooutandthatthepowerindicatorremainson.
CA
UTION!
CA CA
UTION! UTION!
Duringstand-by(themodeswitchinposition0)themainpowerswitchmustalwaysbeontoavoidbuildupof
iceinsidetheunit.
3.Inordertodissipateanyresidualheat,thereactivationairfanandtherotordrivemotorwillcontinueto rununtilthereactivationtemperaturehasfallenbelowapproximately50°C.
4.Checkthatthereactivationairfanandthedrivemotorstoponcethereactivationtemperaturehasfallen belowapproximately50°C.Afewminutesdelayisnormal.
20Operation190TGB-1037-G1307
IceDry800/1400
6Serviceandmaintenance
6.1Safety
W
ARNING!
W W
ARNING! ARNING!
Adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnel.
CA
UTION!
CA CA
UTION! UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA
UTION!
CA CA
UTION! UTION!
Beforestartingtheunit,thereactivationandwetairinletsandoutletsmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
6.2General
Thedehumidierisdesignedforcontinuoususeoveralongperiodoftimewithaminimalamountof supervision.Undernormaloperatingconditions,maintenancerequirementsareminimal.Theservice intervaldependsmainlyontheoperationalconditionsandworkingenvironment.
Seesection6.5,Serviceandmaintenancescheduleforanexampleofastandardserviceandmaintenanceprogram.
6.3Serviceoptions
Inadditiontocommissioningoftheunittherearefourserviceoptions(A-D)asstandard.
S.Commissioning/start-up.
A.Inspectionandifnecessarychangeoflter.Generalfunctioncheck.
B.InadditiontoA,safetycheckandcapacity ,temperatureandhumidityregulationmeasurements.
C.InadditiontoB,preventivereplacementofsomecomponentsafter3yearsofoperation.
D.InadditiontoC,preventivereplacementofsomecomponentsafter6yearsofoperation.
NOTE!AlwayscontactMuntersforserviceorrepair.Operatingfaultscanoccuriftheunitismaintained
insufcientlyorincorrectly.
NOTE!Commissioning/Start-upinspection"S"byMuntersismandatorytovalidatethefullwarranty.
Muntersserviceengineershavespecialequipmentandrapidsparepartsaccesstohandleserviceonall
Muntersproducts.Alltestequipmentusedbyourpersonneltoensurepropersystembalancingiscertied foraccuracy .
MuntersServicecanofferaserviceplanadaptedtosuittheconditionsofaspecicinstallation.Seecontact addressesonthebackpageofthismanual.
6.4Extendedwarranty
MuntersoffersanextendedwarrantytothestandardtermswhentheCustomersignsaservicecontractwith Munters.Detailsareavailableonrequest.
190TGB-1037-G1307Serviceandmaintenance21
6.5Serviceandmaintenanceschedule
ServicelevelSABACABAD
IceDry800/1400
Servicework
FilterreplacementandoperationalchecksXXXXXXXXX
Preventiveinspectionincl.safetycheckXXXXX
Capacitycheck,rotorinspectionXX
ReplacementofHTCOThermostatsX
Inspectdrivebeltandbackingrollers,replaceif
necessary
RotordrivemotorreplacementX
Fanrevision(impellers,motors,bearings)X
Switchboard-controlbox,operationalcheckXXXXX
ChecktemperaturecontrolsensorsXXXX
Rotorcovers-rotorseals-connectionpiece,
replacement
Operatingtimeinhours040008000120001600020000240002800032000
Calendartimeinmonths0612182430364248
XX
Table6.1Serviceandmaintenanceschedule(0-48months)
X
NOTE!TheunitmustberemovedfromthecoldstorageroomatservicelevelCandD.
22Serviceandmaintenance190TGB-1037-G1307
IceDry800/1400
ServicelevelABACABAD
Servicework
FilterreplacementandoperationalchecksXXXXXXXX
Preventiveinspectionincl.safetycheckXXXX
Capacitycheck,rotorinspectionXX
ReplacementofHTCOThermostatsX
Inspectdrivebeltandbackingrollers,replaceif
necessary
RotordrivemotorreplacementX
Fanrevision(impellers,motors,bearings)X
Switchboard-controlbox,operationalcheckXXXX
ChecktemperaturecontrolsensorsXXXX
Rotorcovers-rotorseals-connectionpiece,
replacement
Operatingtimeinhours3600040000440004800052000560006000064000
Calendartimeinmonths5460667278849096
XX
Table6.2Serviceandmaintenanceschedule(54-96months)
X
NOTE!TheunitmustberemovedfromthecoldstorageroomatservicelevelCandD.
190TGB-1037-G1307Serviceandmaintenance23
IceDry800/1400
7Faulttracing
7.1General
Thepurposeofthischapteristoprovideguidanceinbasicfaulttracingandprovideinstructionsfor correctiveactionstoremedyanyfaults.GothroughthelistbelowbeforecontactingMuntersService.
7.2Safety
W
ARNING!
W W
ARNING! ARNING!
Adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnel.
W
ARNING!
W W
ARNING! ARNING!
Alwaysswitchoffthemainpowerswitchbeforeremovingtheunit'spanels.
7.3Faulttracinglist
Seethewiringdiagramforidenticationofelectricalcomponents.
Fault symptom
Unithas stopped.
Unithas stopped.
Unithas stopped.
Unithas stopped.
Indica­tors
Alloff.
No.12 doesnot ash.
No.12, 6and 7are ashing.
No.12 and either6 or7are ashing.
Possiblecause
Powersupplyfailure.Checkthepowersupplytotheunit.
CircuitbreakerQM25trippeddue toawiringfault.
Mainpowerswitch(no.1)issetto ”0”.
TransformerTC25fuseFU26 failure.
CircuitbreakerQM25trippeddue toawiringfault.
Theunithasbeensetto AUTomaticmodebymistake.
Ifbothindicators6and7are ashing,itindicatesthat one(orboth)ofthehigh temperaturecut-outs(BT27 andBT30)havetripped,due toeitheranobstructioninthe reactivationairow,orbecause thereactivationairowhasbeen settoolow .
Safetydevicehavetrippeddueto aheaterelementorwiringfault.
Correctiveaction
IfthetimeofthepowerfailureisnotknownseesectionRestartafterpower failureorcallMuntersServicebeforestartup.
Ifobservedimmediately ,resetthecircuitbreaker .
Setthemainsupplyswitchto”1”andcheckthatthemainconnection indicator(no.14)islit.
Investigatethecauseofthefault,andrectify.Replacethefuse.Ifthefault re-occurs,contactMunters.
Investigatethecauseofthefault,andrectify.ResetQM25.
SetthemodeswitchtoMANual,andcheckthattheunitstarts.
Leavetheunittocooldown. ResetQM12andQM14circuitbreakersasrequired. Checkthattheairinletandoutletductsandltersarefreefromobstructions andarenotblockedbyiceordirt. SetthemainsupplyswitchtoONtoresetthefaultwarning.Adjustthe reactivationairow.
Switchoffthemainsupplyandallowtheunittocooldown.
Investigatethecauseofthefault,andrectify.
ResetQM12andQM14asrequired.
Switchonthemainsupplyatthemainsupplyswitchtoresetthefault warning. NOTE!Themainpowerswitchmustbeonforatleast12hoursbefore thestart.Thistimeisrequiredtolettheinternalheatequipmentremove possibleicebuiltup.
24Faulttracing190TGB-1037-G1307
IceDry800/1400
Fault symptom
Unithas stopped.
Indica­tors
No. 12,2,8 and/or 9are ashing.
Table7.1Faulttracinglist
Possiblecause
Safetydevicehastrippeddueto oneofthefollowing:Fanmotor faultDrivemotorfaultWiring fault.
Correctiveaction
Switchoffthemainsupplyandallowtheunittocooldown.
Investigatethecauseofthefault,andrectify.
ResetQM16—reactivationfan. ResetQM21—processfananddrivemotor .
Switchonthemainsupplyatthemainpowerswitch,andstarttheunitto resetthefaultwarning. NOTE!Themainpowerswitchmustbeonforatleast12hoursbefore thestart.Thistimeisrequiredtolettheinternalheatequipmentremove possibleicebuiltup. Ifthefaultre-occurscallMunters.
190TGB-1037-G1307Faulttracing25
8Technicalspecication
s
420
ML
Munter
B
J
C
P
M
L
1
2
N
A
N
4
ØE
3
F
H
G
P
ØR
ØD
Z
Y
X
40 0
25 0
12 0
20 0
12 0
14 5
14 5
8.1Dimensionsandservicespace
IceDry800/1400
Figure8.2Holepattern
Figure8.1Requiredservicespace
1.Processairinlet3.Reactivationairinlet
2.Dryairoutlet4.Wetairoutlet
Dimensions(mm)
Model
IceDry80071559013101601252502702326501102323724029570084550128
IceDry140071559014102001252502702327501102323724029570084550146
(1)Spaceforservice.
ABCØDØEØRFGHJLMNPX
(1)Y(1)Z(1)
26Technicalspecication190TGB-1037-G1307
Weight(kg)
IceDry800/1400
8.2Technicaldata
Processair
Ratedairow(m
Ratedairow(m
Minimumavailablestaticpressure(Pa)200300
Fanmotorpower(kW)at50Hz0,551,10
Fanmotorpower(kW)at60Hz1,32
Reactivationair
Ratedairow(m
Ratedairow(m
Minimumavailablestaticpressure(Pa)100100
Fanmotorpower(kW)at50Hz0,160,24
Fanmotorpower(kW)at60Hz0,29
1
3
/s)0,2220,388
3
/h)8001400
1
3
/s)0,0430,071
3
/h)155254
IceDry800IceDry1400
RatedCurrent
Current(Amps/Phase)3~50Hz380V9,415,1
Current(Amps/Phase)3~50Hz400V9,114,6
Current(Amps/Phase)3~50Hz415V8,914,3
Current(Amps/Phase)3~60Hz230V24,4
Current(Amps/Phase)3~60Hz440V13,6
Current(Amps/Phase)3~60Hz460V13,2
ReactivationHeater
Temperatureincreaseacrossheater(°C)9595
ReactivationHeaterPower(kW)4,36,3
OtherTechnicalData
Operatingrangefordehumidier,ambienttemperature(°C)–25to+40–25to+40
Drivemotorpower(W)1010
Heaterreactivationfanhousing(W)240240
Heaterinelectricalcabinet(W)250250
Airltration(standard)G3G3
Electricalprotectionstandard,dustandwaterresistant(maincasing)IP44IP44
FanMotorWindingInsulationClassClassFClassF
DriveMotorWindingInsulationClassClassFClassF
HighT emperatureCut-Out(°C)160+/-5160+/-5
Contactorcoil,voltage(VAC)2424
190TGB-1037-G1307Technicalspecication27
IceDry800/1400
External(Volt-free)OutputContacts
MaxnoiselevelUnducted(dBA)8080
1
Figuresquotedarenominal,basedonfaninlettemperatureof20°C,andanairdensityof1.2kg/m
2
ContactsonthePCBusedtogivearemotefaultoutput
2
3
.
2A,50VAC2A,50VAC
Table8.1Technicalspecications
8.3Sounddata
Noisefor
dB(A)Lwt631252505001000200040008000
Duct1Na101-10-2-9-13-20-22-27-33
Duct2Na102-3-5-13-20-20-19-21-26
Duct3Na94-5-6-5-1720-21-23-27
Duct4Na88-2-6-12-25-31-31-33-35
Room6490-1-8-14-16-20-23-26-31
CorrectionKokdBatISO-bandcentrefrequency,Hz
Noisepathstosurroundings
1.Ductworkfordryair
2.Ductworkforprocessair
3.Ductworkforreactivationair
4.Ductworkforwetair
SYMBOLS
Lwt=TotalnoiseleveldB(rel.10-12W)
Lw=NoisepowerlevelinoctavebanddB(rel.10-12W)
Kok=CorrectionforcalculatingLw(Lw=Lwt+Kok)
dB(A)=Ratednoiselevelat100m
2
roomabsorption
28Technicalspecication190TGB-1037-G1307
IceDry800/1400
9Scrapping
Theunitmustbescrappedinaccordancewithapplicablelegalrequirementsandregulations.Contactyour localauthorities.
Therotormaterialisnotcombustible,andshouldbedepositedlikeglassbrematerials.
Iftherotorhasbeenexposedtochemicalsthataredangeroustotheenvironmenttheriskmustbeassessed. Thechemicalscanaccumulateintherotormaterial.Takethenecessaryprecautionstocomplywith applicablelegalrequirementsandregulations.
W
ARNING!
W W
ARNING! ARNING!
Iftherotoristobecutinpieces,wearasuitableCEmarkedfacemaskselectedandttedinaccordancewiththe
applicablesafetystandardstoprotectfromthedust.
190TGB-1037-G1307Scrapping29
IceDry800/1400
10ContactMunters
AUSTRIA
BELGIUM
DENMARK
FINLAND
FRANCE
GERMANY
ITAL Y
NETHERLANDS
POLAND
SPAIN
SWEDEN
SWITZERLAND
UNITEDKINGDOM
MuntersGmbH AirTreatment ZweigniederlassungWien
MuntersBelgiumnv AirTreatment
MuntersA/S AirTreatment
MuntersFinlandOy Kuivaajamyynti
MuntersFranceSAS AirTreatment
MuntersGmbH AirTreatment-Zentrale
MuntersItalyS.p.A AirTreatment
MuntersV ochtbeheersingEnergieweg69
MuntersSp.zo.o. OddzialwPolsce AirTreatment
MuntersSpainSA AirTreatment
MuntersEuropeAB AirTreatment
MuntersGmbH AirTreatment ZweigniederlassungRümlang
MuntersLtd AirTreatment
Eduard-Kittenberger-Gasse56, Obj.6 A-1235Wien
Blarenberglaan21c B-2800Mechelen
Ryttermarken4 DK-3520Farum
Hakamäenkuja3 FI-01510V ANTAA
106,BoulevardHéloise F-95815ArgenteuilCedex
Hans-Duncker-Str.8 D-21035Hamburg
StradaPiani2 I-18027Chiusavecchia IM
NL-2404HEAlphena/dRijn
ul.Swietojanska55/11 81-391Gdynia
EuropaEpresarial.EdicioLondres. C/PlayadeLiencres2. 28230LasMatas.Madrid
POBox1150 S-16426Kista
Glattalstr.501 CH-8153Rümlang
PathnderPlace10RamsayCourt HinchingbrookeBusinessPark HuntingdonPE296FYCambs
Tel:+4316164298–9251 luftentfeuchtung@munters.at www.munters.at
Tel:+321528561 1 service@muntersbelgium.be www.muntersbelgium.be
Tel:+4544953355 info@munters.dk www.munters.dk
Tel:+358207768230 laitemyynti@munters. www.munters.
Tel:+331341 15757 dh@munters.fr www.munters.fr
Tel:+49(0)40879690-0 mgd@munters.de www.munters.de
Tel:+390183521377 marketing@munters.it www.munters.it
Tel:+31172433231 vochtbeheersing@munters.nl www.munters.nl
Tel.:+48583053517 dh@munters.pl www.munters.com.pl
Tel:+34916400902 marketing@munters.es www.munters.es
Tel:+4686266300 avfuktning@munters.se www.munters.se
Tel:+41523438886 info.dh@munters.ch www.munters.ch
Tel:+441480432243 info@munters.co.uk www.munters.co.uk
AUSTRALIA
BRAZIL
CANADA
CHINA
INDIA
JAPAN
KOREA
Tel:+61288431588 dh.info@munters.com.au
Tel:+551150540150 www.munters.com.br
Tel:+1-800-843-5360 dhinfo@munters.com
Tel:+861080418000 marketing@munters.cn
Tel:+912066818900 info@munters.in
Tel:+81359700021 mkk@munters.jp
Tel:+8227618701 munters@munters.kr
MEXICO
SINGAPORE
SOUTHAFRICA
TURKEY