Revision: N1.7 of 07/2017
Product Software: Version 5.17
This manual for use and maintenance is an integral part of the apparatus together with the attached
technical documentation.
This document is destined for the user of the apparatus; it may not be reproduced in whole or in part,
committed to computer memory as a file or delivered to third parties without the prior authorization of the
assembler of the system.
Munters reserves the right to effect modifications to the apparatus in accordance with technical and legal
developments.
DEVICE MENU ------------------------------------------------------------------------------------------------------------------------------------------- 37
5.10.1 Farm Thermo-5 / Temperature Curve | Set Definitions
67
68
68
68
69
70
72
73
73
74
74
75
76
6
SCALE MENU --------------------------------------------------------------------------------------------------------------------------------------------- 77
HISTORY MENU ---------------------------------------------------------------------------------------------------------------------------------------- 85
TEST MENU ------------------------------------------------------------------------------------------------------------------------------------------------- 89
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
9
SERVICE MENU ----------------------------------------------------------------------------------------------------------------------------------------- 94
10 INSTALL MENU ---------------------------------------------------------------------------------------------------------------------------------------- 106
Munters reserves the right to make alterations to specifications, quantities, dimensions etc. for production
or other reasons, subsequent to publication. The information contained herein has been prepared by
qualified experts within Munters. While we believe the information is accurate and complete, we make no
warranty or representation for any particular purposes. The information is offered in good faith and with
the understanding that any use of the units or accessories in breach of the directions and warnings in this
document is at the sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing a Farm Premium Controller!
In order to realize the full benefit from this product it is important that it is installed, commissioned and
operated correctly. Before installation or using the fan, this manual should be studied carefully. It is also
recommended that it is kept safely for future reference. The manual is intended as a reference for
installation, commissioning and day-to-day operation of the Munters Controllers.
1.3 Notes
Date of release: May 2013
Munters cannot guarantee to inform users about the changes or to distribute new manuals to them.
All rights reserved. No part of this manual may be reproduced in any manner whatsoever without the
expressed written permission of Munters. The contents of this manual are subject to change without notice.
This document describes the Farm Premium Precision Mode Broilers, Layers, and Pigs operation.
Computerized Electronic Controllers such as the Farm Premium advance the producer’s ability to grow
high quality poultry or eggs by accurately controlling the environment. Instead of struggling with
individual thermostats for heat zones and ventilation, Farm Premium brings them all together into one
convenient place with great accuracy. In Precision Mode, the Farm Premium optimizes and precisely
applies your equipment and energy sources to most benefit from the accuracy of your computer and
sensors.
Precision Mode is characterized by its large number of features that enable system setups that meet your
exact requirements. The Farm Premium precisely coordinates ventilation levels, providing the optimal
amount of fresh air balanced with heating costs. The light and feed clocks enable efficient feed
distribution. Besides advanced cooling pad methods, you benefit from superior stir fan programs to
recover ceiling heat and other features. Taken together, Precision Mode’s numerous features enable
significant profitability improvement.
Farm Premium provides a variety of management and history utilities. You can choose from simple
overviews, or fully detailed by the minute records of minimum, maximum and average temperatures for
each individual sensor. The unique Table of Events records the moment of every significant action taken
by the Farm Premium and, optionally, its operator.
• Front Panel, page 9
• Selecting the Mode, page 14
2.1 Front Panel
Figure 1 shows the Farm Premium-P XL front panel and its elements. All controllers have similar elements.
Air status (refer page 31 for details on this screen) (Broilers/Layers mode only)
Zone Inlet Position: View the inlet(s) target position, actual position, and number of
steps (refer to page 120 for details) (Layers)
Stir fans status
Increase/ decrease offset from temperature setting from the standard display only
(hold both keys) – defined in the TEMPERATURE CURVE HELP |SET
2.1.4 M
AIN SCREEN DISPLAY
The main screen display depends on the operating mode.
NOTE: When in Layer Mode, refer to Layers Main Screen, page 120.
1. Sensors: Displays individual sensor readings. Temperature sensors marked with dark squares
form the current average temperature.
o Filled square: Indicates the sensor participates in the average calculation.
o Empty square: Indicates the sensor does not participate in the average calculation.
NOTE: Go to Table 1: Sensor Readings page 117, to view all the possible sensors.
2. Av. Temp: Reports the current average temperature. This example is in Celsius.
3. Active: Displays the output relay list. The filled black boxes indicate active outputs. Controller
also informs the position of inlets and curtains, as well as the number of operating heaters or fans.
NOTE: Go to Table 2: Output List (Active), page 117 to view all the available readings (ACTIVE).
NOTE: The
ACTIVE
screen shows rectangular markers by the outputs. Filled rectangles indicate
operating outputs; empty rectangles indicate outputs that are off.
4. Status: Provides important general information such as the time and ventilation mode.
EXAMPLE
NOTE: Go to Table 1: Sensor Readings, page 117 to view all the available readings.
5. Messages: Displays important messages/alarms. The title bar displays the number of important
messages, and if there are several messages, they each appear in turn.
Farm Premium runs in four modes: Broiler, Layer, Breeders, and Pigs.
To select the mode:
1. Disconnect the power cable from the power source.
2. Reapply power while pressing Delete. The Cold Start screen appears.
3. Select Yes. The Choose Controller Type appears.
4. Select the required mode.
5. Press Enter.
NOTE: The manual is based on the Broiler Mode. Functions that are unique to Layers and Breeders
and described in separate appendixes. Except for a few functions dealing with scales, Pig
Mode supports the vast majority of functions seen in Broiler Mode. Pig Mode has some
different terminology (for example herd instead of flocks).
This screen sets the temperature targets according to the bird/pig age.
2
3
7
15
21
28
35
42
89.0
87.0
84.0
82.0
79.0
76.0
72.0
70.0
89.0
87.0
83.0
81.0
78.0
74.0
70.0
68.0
99.0
97.0
91.0
89.0
86.0
81.0
77.0
75.0
84.0
82.0
80.0
78.0
75.0
71.0
67.0
63.0
102.0
95.0
95.0
93.0
90.0
87.0
84.0
83.0
1. TEMPERATURE CURVE
2. HUMIDITY TREATMENT
3. CO2 TREATMENT
4. MIN/MAX LEVEL
5. STATIC PRESSURE
6. CONTROL MODE
7. SYSTEM PARAMETERS
8. AMMONIA TREATMENT
103
103
103
103
103
103
103
103
1. In Install > Analog Sensors (refer to Analog Sensors, page 109), designate the required number
of sensors as temperature sensors. When using more than one sensor, Farm Premiumbegins
treatments based on the average.
2. If required, go to Service > Temperature Calibration, calibrate the sensors (refer to Temperature
Calibration, page 94).
3. In Install > Temperature Definition (refer to Temperature Definition, page 114), assign specific
sensors brood setups, heater zones, and devices. If a zone does not have an assigned sensors,
calculations are based on the current average temperature.
4. In Control > Temperature Curve, define the required target temperature curve
o Set up to 20 lines, 999 growth days. When a curve is not required (for example when
growing layers), enter temperatures in the first line only.
o Define:
Day: Set the growth day. You can program negative growth days up to -2 for pre-
warming. To enter a negative growth day, type the day number followed by the ±
key.
Heat: Set the temperature to stop heat.
Tunnel: Set the temperature for tunnel ventilation to begin.
Alarm Low & High: Set average temperature alarm limits.
Floor heat: Set the temperature upon which the floor heat curve is based. Refer to
Variable Floor Heater | Set Definitions, page 22.
T.Hi: Set a high temperature alarm for Tunnel mode.
5. In Manage > Alarm Setting, set the Sensor Alarm (page 69).
NOTE: Only Pig Mode supports variable floor heaters. To enable this function define an analog
output as a floor heater (refer to Analog Output, page 110).
6. If required set the:
o Temperature Curve Help | Set Definitions, page 16
o Radiant Heaters Help | Set Definitions, page 17
o Variable Heater Help | Set Definitions, page 19
o Variable Floor Heater | Set Definitions, page 22
o Heat Cycle | Set Definitions, page Error! Bookmark not defined.
3.1.1 T
EMPERATURE CURVE HELP | SET DEFINITIONS
While viewing the Temperature Curve menu: Press
Temperature Curve Offset
Set Temp. Change Reminder (Diff)
Target Temp. Band
Heater Temp. Band
Cool Down Factor (%)
Cool Down Fast Response (Deg.)
Min Vent Below Heat Temp By:
HELP
, select SET, and press
0.0
3.0
1.5
1.0
15
3.0
ZONE
ENTER
• Temperature Curve Offset: Adjusts all temperature curves by this amount. You can use this to
temporarily adjust all temperatures up or down for special circumstances. The curve appears in
the Status Window, and you can use the ENTER and Up or ENTER and Down hot key
combinations to change the offset.
• Set Temp. Change Reminder (Diff): Sets the change in set temperature that triggers a
reminder for you to set backup thermostats. Often producers forget to set backup thermostats as
their birds grow from baby chicks to market age, so the Farm Premiumreminds you. When you
press Enter to acknowledge the reminder, the Farm Premium logs it in the Table of Events.
• Target Temp. Band: The size of the target temperature zone. This "Happy Zone” is between
Target Temperature and (Target Temperature + Band).
.
• Heater Temp. Band: Heaters turn on at ‘Band’ degrees below Heat, and turn off at the Heat
Temperature.
NOTE: Heaters operate at minimum level only; however, Radiant Heaters can operate at any
temperature or level below Tunnel.
• Cool Down Factor (%): Minimum percentage correction towards target during each increase
ventilation level delay. If average temperature does not improve by this amount, the Farm
o Radiant High – Differential (Below Low Set): Set number of degrees below Radiant Low
Heaters for HIGH Radiant Heaters to begin working (default: 1.0). To ensure proper
heater ignition, Radiant High Heaters remain on for the Radiant Ignition Time along with
the Radiant Low Heaters.
o Radiant Ignition Time (sec): Set number of seconds to power radiant ignition (default:
30).
Page 18
NOTE: The Heater Temperature Band applies to radiant heaters as well. For example, if the Heat
Temperature is 80º F and the Heater Temperature Band is 1º F, then heaters turn on at 79º F
and off at 80º F. If the Radiant Low Differential is at 2.0º F, than radiant heaters turn off at
82º F, and on 1º F below that at 81º F. However, a Radiant High Heater turns on regardless
of its temperature setting for the Radiant Ignition Time whenever the corresponding Radiant
Low Heater turns on. This feature ensures proper flame ignition.
Figure 5: Radiant Heater Differentials
3.1.3 C
YCLE HEATERS | SET DEFINITIONS
Heat Cycle means providing heat in conjunction with the ventilation system during minimum ventilation
cycles, using heaters and fans connected to relays. When enabled, heaters operate during the fans’
cycle off time (as defined in the Levels of Ventilation Cycle Timer On and Off parameters). How does it
work?
Between the Heat Temperature and the differential temperature, heaters do not operate. When the
temperature goes below the Heat Off temperature minus the Low Heat Differential:
•
Heaters begin to operate when the exhaust or tunnel fans are off. Heaters operate for the
Minimum On Time.
•
If the temperature continues to drop, heaters operate for longer periods of time, up to the
Maximum On Time (defined in Levels of Ventilation).
1. Define the required number of heater and exhaust and/or tunnel relays (Relay Layout, page
107).
2. In Control > Control Mode, set the Heater Cycle to Yes.
3. In Control > Temperature Curve > Help, scroll to Cycle Heater.
4. Define:
o
Low Heat Differential: The differential below the Heat Off temperature, at which heating
begins and runs for the minimum amount of time.
o
High Heat Differential: The differential below the Heat Off temperature, at which heating
runs for the maximum amount of time
Minumum ON Time: Minumum heating time when the exhaust or tunnel fans are off.
3.1.4 V
ARIABLE HEATER HELP | SET DEFINITIONS
The Farm Premium Controller enables configuring up to eight variable heaters. The heater output changes
according to the output of a 0 – 10 VDC device.
Install at least one analog output card.
To configure the variable heaters:
1. In Installation > Analog Output configure:
a. up to eight analog outputs as variable heaters
b. the minimum and maximum voltage output for each heater
Out No.
2. In Control > Control Mode > Analog Heat Mode, define the mode.
3. In Control > Temperature Curve > Help, define the parameters for each mode.
Page 20
3.1.4.1 Linear Heat
SYSTEM PARAMETERS
RADI ANT HEATERS
8.0
When Linear Mode is enabled:
•
Between the Heat Temperature and the Target temperature, heaters do not operate (meaning,
the output voltage is 0).
•
Between the Heat Temperature and the Low Difference Below Heat, heaters operate at the
minimum voltage output.
•
If the temperature continues to drop, the voltage output increases until it reaches the maximum
voltage output at the High Difference below Heat.
In this example:
•
Target Temperature is 80°
•
Temperature Curve Heat Off is 78°.
•
Low Heat Differential is 1°.
•
High Heat Differential is 8°.
o
If the temperature is between 77° to 78°, the output voltage is the minimum voltage
defined in Installation > Analog Output (1 volt in this example).
o
If the temperature continues to drop, the output voltate increases until it reaches the
maximum voltage defined in Installation > Analog Output. Output increases or
decreases to keep the temperature within the Target Temperature and Heat Off band.
Low Difference Below Heat: Temperature difference between the Heat Off parameter
at which the variable heater begins to function.
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABLE HEATER
Low Diff Below Heat
High Diff Below Heat
0.0
1.0
30
1.0
Page 21
o
SYSTEM PARAMETERS
RADI ANT HE ATE RS
Response Time (seconds)
15
SYSTEM PARAMETERS
RADI ANT HE ATE RS
8.0
High Difference Below Heat: Temperature at which the heater begins to operate at
maximum output.
3.1.4.2 Proportional Heat
Proportional Heat works in manner similar to Linear Mode. The difference is that Proportional Heat
features a delay time.
•
When the temperature falls below the user-defined point, the heaters begin operating at their
minimum output.
•
After the response time passes, Farm Premium checks the temperature. If it is still below the
defined point, Farm Premium increases the voltage by a certain amount (this amount of the
increase cannot be changed).
•
After the response time passes, the process is repeated until heaters operate at their maximum
output.
•
Define the parameters.
o
Difference Above Heat to Stop Heater: Differential from target temperature at which
the heater runs at minimal input
o
High Difference Below Heat: High Difference Below Heat: Temperature at which the
heater begins to operate at maximum output
o
Response Time (seconds): Amount of time before the controller begins to change the
ventilation.
3.1.4.3 Linear Valve
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABLE HEATER
Diff Above Heat to Stop Heater
High Diff Below Heat
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABLE HEATER
Low Diff Below Heat
High Diff Below Heat
0.0
1.0
30
1.0
8.0
0.0
1.0
30
1.0
Linear Valve enables defining that variable heater input voltage is always equal to or above the minimum
input defined in Installation > Analog Sensors..
When the Analog Heat Mode is defined as having Linear Valve control, there is always a minimal
voltage input. Therefore, if the minimum voltage is 1 volts:
• There is 0% voltage when the target temperature is reached.
•
Define.
o
Difference Above Heat to Stop Heater: Differential from target temperature at which
the heater runs at minimal input
o
High Difference Below Heat: High Difference Below Heat: Temperature at which the
heater begins to operate at maximum output.
3.1.5 V
ARIABLE FLOOR HEATER | SET DEFINITIONS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABLE HEATER
Low Diff Below Heat Tmp.
High Diff Below Heat Tmp.
VARIABLE FLOOR HEATER
Low Diff Below Heat Tmp.
0.0
1.0
30
0.5
4.5
0.5
4.5
Farm Premium Controllers enable configuring up to two variable floor heaters. The output of the heaters
changes as the temperature increases or decreases.
Install at least one analog output card.
To configure the variable floor heaters:
1. In Installation > Analog Output configure:
a. up to two analog outputs as variable heaters
b. the minimum and maximum voltage output for each heater
2. In Control > Temperature Curve > Help, scroll down to Variable Floor Heater.
3. Set the response time (amount of time before the controller begins to change the ventilation).
4. Variable heat parameters are dependent on the mode employed:
o Linear Heat
o Proportional Heat
Refer to the above sections for further information on these modes.
3.2 Introduction to Humidity, Ammonia, and CO2 Treatment
Farm Premium provides various options to controlling the humidity, CO2, and ammonia levels.
•
None: No treatment is provided.
•
Level: Ventilation levels increase for a designated amount of time.
•
Tunnel or exhaust fan: A designated fan turns on for a designated amount of time. The amount
of air blown into the house is greater than that provided by an increase in ventilation level.
•
Increase in air / weight: The total amount of air that fans need to provide increases by a user
defined amount. Fan stay on until CO2, humidity, or ammonia levels fall to their defined levels.
This option is only available when using Minimum Ventilation by Weight.
•
Humidity treatment by heat: In cold air situations, heaters can be turned on to lower the
relative humidity.
If there is a contradiction between CO2, humidity, and ammonia treatments:
•
Ammonia treatment has priority over CO2 treatment.
•
C02 treatment has priority over humidity treatment.
•
Increase in air / weight has priority over other treatments.
•
Humidity treatment by heat takes priority over increasing the ventilation.
Humidity treatment forces an increase in ventilation level when the humidity is too high. It holds the
increase for ‘Duration Seconds’, and checks back after ‘Interval Minutes’ for another increase. After the
duration, the ventilation level comes back down automatically.
Day Humidity
1. In Install > Analog Sensors (refer to Analog Sensors, page 109), designate up one or two
sensors as indoor humidity sensors (outdoor sensor is for information only). When using more than
one sensor, Farm Premium begins treatments based on the average.
2. If required, go to Service > Humidity Calibration, and calibrate the sensors (refer to Humidity
Calibration, page 95).
3. In Control > Humidity Treatment set the parameters as required.
o Day: Growth day. Can set multiple programs for same day (Maximum number of
programs: 20)
o Humidity: Humidity at which to begin treatment
o Delay Minute: Amount of time the controller pauses before ventilating
o Duration Seconds: Number of seconds the controller maintains the increased level of
ventilation
4. Set the Humidity Sensor Alarm (page 72).
3.3.1 H
UMIDITY TREATMENT HELP | SET DEFINITIONS
While viewing the Humidity Treatment menu: Press
Humidity Treatment below Heat
Humidity Treatment By
Outside Temp Treat by Heaters
HELP
, select SET, and press
YES
Exh 6
-18.0
ENTER
• Humidity Band (%): Hysteresis band for Humidity Treatment.
• Humidity Treatment below Heat: Select YES or NO for allowing Humidity Treatment when
heaters are operating (set in Control | Temperature Curve).
.
• Humidity Treatment By: This parameter designates the method used when humidity or CO2
treatment begins. Normally, this parameter is relevant only when minimum ventilation is
running. When a treatment is required, select one the method to be employed:
o Level: Increases the ventilation level when a treatment is required.
NOTE: When employing Ventilation by Weight (refer to page 28), the controller increases the cycle
CO2 TREATMENT
Day
Start
Stop
Delay
Duration
Value
Value
(Sec)
Sec.
1
0
3000
0
2500
0
120
0
130
0
time or the level, depending on the particular settings.
o Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
o Tunnel: Designate a specific tunnel (press a number key to select the fan).
o None: Disables the treatment.
To enable the exhaust/tunnel options, in
Analog Output
o
Humidity Treatment by Heaters: This parameter enables using the heaters to lower the
, designate a relay/variable device as a tunnel or exhaust fan.
Installation > Relay Outlet
or
Installation >
relative humidity. If enabled, define:
Outside Temp Treat by Heaters: Heaters handle humidity treatment when the
outside temperature is lower than the target temperature by this amount.
Diff to Stop Treatment by Heaters: Heaters cease the humidity treatment if the
inside temperture is lower (or higher) than the target temperature by this amount.
This number can be positive or negative.
Humidity Treatment by Heater requires designating at least one temperature sensor as an
outside temperature sensor (refer to Temperature Definition, page Error! Bookmark not
defined.).
NOTE: If the heaters are operating because of the interior temperature, Humidity Treatment by Heater
is disabled.
NOTE: Broiler and Breeder Modes support Humidity Treatment by Heaters.
3.4 CO2 Treatment
CO2 treatment forces an increase in ventilation level when the CO2 level is too high. It holds the increase
for ‘Delay Seconds’, and checks back after ‘Interval Minutes’ for another increase. After the duration, the
ventilation level may come back down automatically. If during treatment, the CO2 level drops below the
Stop Value parameter, the ventilation level automatically returns to that level used before CO2 treatment
was initiated.
1. In Install > Analog Sensors (refer to Analog Sensors, page 109), designate one sensor as a
CO2 sensor.
2. If required, go to Service > CO2 Calibration and calibrate the sensors (refer to CO2 Sensor,
page 96).
3. In Control > CO2 Treatment set the parameters as required.
o Day: Growth day. You can set multiple programs for same day (maximum number of
programs: 20)
Page 26
o Start Value: CO2 value at which to begin treatment
SYSTEM PARAMETERS
CO2 TREATMENT
CO2 Treatment Below Heat
NO
CO2 Treatment By
Exh 6
o Stop Value: CO2 value at which to end treatment
o Delay (Sec): Number of seconds the controller pauses before ventilating
o Duration (Sec): Number of seconds the controller maintains the increased level of
ventilation
4. Set the CO2 Sensor Alarm (page 72).
3.4.1
CO2 T
While viewing the CO2 Treatment menu: Press
REATMENT HELP | SET DEFINITIONS
HELP
, select SET, and press
ENTER
.
• CO2 Treatment below Heat: Select YES or NO to enable CO2 treatment when heaters are
operating (set in Control | Temperature Curve).
• CO2 Treatment By: This parameter designates the method used when humidity or CO2
treatment begins. Normally, this parameter is relevant only when minimum ventilation is
running. When a treatment is required, select one the method to be employed:
o Level: Increases the ventilation level when a treatment is required.
NOTE: When employing Ventilation by Weight (refer to page 28), the controller increases the cycle
time or the level, depending on the particular settings.
o Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
o Tunnel: Designate a specific tunnel (press a number key to select the fan).
o None: Disables the treatment.
To enable the exhaust/tunnel options, in
Analog Output
, designate a relay/variable device as a tunnel or exhaust fan.
Installation > Relay Outlet
or
Installation >
• CO2 Treatment by Heaters: This parameter enables running the heaters in situations
where the CO2 level is high. Typically this can happen in cold temperatures when CO2
is produced by the heaters. By increasing the heat in the house, ventilation can then be
increased. If enabled, define:
Outside Temp Treat by Heaters: Heaters handle CO2 treatment when the outside
temperature is lower than the target temperature by this amount.
Diff to Stop Treatment by Heaters: Heaters cease the CO2 treatment if the inside
temperture is lower (or higher) than the target temperature by this amount. This
number can be positive or negative.
CO2 Treatment by Heater requires designating at least one temperature sensor as an
outside temperature sensor (refer to Temperature Definition, page Error! Bookmark not
defined.).
NOTE: If the heaters are operating because of the interior temperature only, CO2 Treatment by
IMPORTANT: Before setting Min/Max level, go through and set up the Device Settings,
especially the ventilation levels.
Once you have entered the ventilation levels, use the Min/Max to select the range of levels to apply to
your situation. Typically, Farm Premium increases the minimum ventilation level as litter conditions
deteriorate and the birds require greater amounts of fresh air. You can also restrict the maximum level to
prevent excess airflow on young birds.
Go to
Control > Control Mode
to select the minimum ventilation method:
o By Day and By Soft Days Curve
o By Time
o Day Soft Min.
o By Weight
3.5.1 BY D
AY AND BY SOFT DAYS CURVE
3
6
10
14
21
35
0
0
• Day: Set growth day
• Min: Set minimum ventilation level for controller
2
3
4
5
6
7
0
0
16
16
16
21
21
21
0
0
• Max: Set maximum ventilation level for controller
NOTE: BY DAYS CURVE generates an incremental increase/decrease between the defined days. BY
DAYS operates according to the min/max values of the day's min/max values until the
following day defined is reached.
3.5.2 BY T
IME
10:00
13:00
18:00
21:00
00:00
00:00
00:00
00:00
4
8
6
12
8
15
1
3
0
0
0
0
0
0
0
0
• From: Set time of day (hh:mm) in 24 hour format
• Min: Set minimum ventilation level for controller
• Max: Set maximum ventilation level for controller
• Min Soft: Set minimum ventilation level for when temperature drops below heat temperature
• Min: Set minimum ventilation level for when temperature is above heat temperature
• Max: Set maximum ventilation level for controller
3.5.3.1Soft Min/Max Level Help | Set Definitions
While viewing the
•Differential Below Heat for Soft Min: Set the degree of difference from heat temperature (set
in Control | Temperature Curve) to switch minimum level from Min. to Soft Min.
Soft Min/Max Level
Diff. Below Heat for Soft Min.
menu: Press
HELP
, select SET, and press
10.0
ENTER
.
• Temp Choice for Soft Min: Select inside/outside/attic temperature to control Minimum Level
changes. The minimum level adjusts towards the Soft Min as this temperature falls. Above the
heat temperature, the minimum level is at the Min setting.
As temperature rises, INSIDE and ATTIC stay at lowest ventilation level reached until average
temperature gets to the heat setting, and then changes instantly. With the OUTSIDE selection, the
minimum ventilation level increases gradually as temperature rises to the heat setting. This means inside
and attic soft min vent choices to latch to the lowest level reached as long as the temperature remains
below the heat setting.
3.5.4 BY W
EIGHT
NOTE: Only Broilers and Layers mode supports Minimum Ventilation By Weight.
The By Weight option enables controlling the minimum air flow depending on the number of birds, their
weight and the current outside temperature. When using the Weight option, Farm Premium takes several
parameters and calculates the air speed, level of ventilation and cycle time needed to supply the required
volume. As opposed to the other ventilation methods, the Weight option is dynamic, with the ventilation
changing according to the current parameters (quantity of air required, weight of birds and number of
birds, outside air temperature). In addition, Ventilation By Weight sends out an alarm if the current
ventilation is below the minimum required level.
Warm Temp. – Diff Below Heat
Cold Temperature
Air Change
Fan Cycle Time (sec, 0 – Manual)
Minimum ON Time in Vent Cycle
Minimum OFF Time Vent Cycle
Air Change by Humidity/CO2 %
HELP
, select SET, and press
2.0
68.0
0.24
600
60
60
20
ENTER
Page 30
• Warm Temperature – Difference Below Heat: Differential below the heat temperature (refer
SOFT MIN/MAX LEVEL BY WEIGHT (OUT TEMP)
Day
Min
Level
Air Per Kg/Lb
Max
Level
Cold Warm
1
35
1
7
0.5
0
0.9
1.4
1.5
1.7
16
22
to Temperature Curve, page 15) that defines outside temperature as Warm in the Soft
Min/Max table. For example, if the Heat Temperature is 78° F, Warm Temp. – Diff Below
Heat is 2.0, than the outside temperature is defined as warm at 76° F.
• Cold Temperature: Outside temperature (or below) at which Air per Kg/Lb. (Cold) capacity is
reached.
When the outside temperature is between the Warm and Cold Temperature, the flow rate is
calculated at a proportional rate.
• Air Change: As the temperature rises from the Cold Temperature parameter to the Heat
Temperature (or drops from the Heat Temperature to the Cold Temperature parameter), the
minimal air volume rises/falls proportionally. Air Change defines the minimal change in air
temperature that must takes place to cause a change in the air supply.
• Fan Cycle Time: The total amount of time that the fans operate while operating under Minimum
Ventilation. During this time, the fans supply the required volume of air at the minimum
ventilation level required. Farm Premium adjusts the minimum ON time and OFF time as
needed. If the fans cannot supply the required volume at a particular level of ventilation, Farm
Premium automatically adjusts the minimum ventilation level.
o Minimum ON Time in Vent Cycle: The minimum amount of time that the fans operate
during a cycle. Farm Premium adjusts the actual fan time as needed.
o Minimum OFF Time in Vent Cycle: The minimum amount of time that the fans do not
operate during a cycle. Farm Premium adjusts the actual fan time as needed.
As the temperature rises, the actual Minimum OFF Time decreases until it reaches the minimum time;
only then does the Minimum On Time begin to rise.
NOTE: If the temperature goes above the Band Temperature, Power Ventilation begins and times are
adjusted accordingly.
• Air Change By Humidity/CO2%: As the humidity/CO2 levels rise above the levels specified
in Humidity Treatment and CO2 Treatment, the minimal air volume rises proportionally. Air
Change By Humidity/CO2% defines the minimal change in in these levels that must take place
to cause an increase in the air supply.
• Air Per Weight Curve Mode: By default, Air per Kilo/Lb. has two data points: cold
temperature and warm. If desired, the user can add an additional intermediate data point
which is between the two default points. This point determines the quantity of air to be
distributed when the temperature reaches the midpoint between the cold and warm
temperatures.
NOTE: In a three point curve, the intermediate value must be between the cold and warm value in
AIR STATUS
Inside Temp
Weight KG
24.1
0.468
Current
Min
Max
Level
2 1 2 Cycle On
30
30
30
Cycle Off
98
134
66
Total Air M3/h
M3/h
8347
6552
11232
Air/WGT
M3h/kg
0.9
0.7
1.20
each line.
3.5.4.2 Weight Hot Screen
Selecting the Ventilation by Weight option enables an additional Hot Screen, the Air Status Screen. This
screen displays the critical parameters involved in the Ventilation by Weight option.
Outside Temp
Humidity
21.3
46.7%
• Inside Temperature: Current temperature inside the house
• Outside Temperature: Current temperature outside the house
• Humidity: Current relative humidity inside the house (requires a humidity sensor)
• Weight KG: Current average weight of the Bird Curve (page 80)
• Level: Displays the current, minimum and maximum level of ventilation.
NOTE: If the current level is below the minimum required level, Farm Premium displays an alarm
“Below Min Air”.
• Cycle On/Off: Displays the current, minimum and maximum fan on and off times.
• Total Air M3/h: Displays the current, minimum and maximum quantity of ventilation, per hour.
• Air/WGT: Displays the current amount of ventilation, per kilo/pound of bird weight.
3.6 Static Pressure
Set target parameters for Static Pressure at High and Low Outside Temperatures, as well as alarms for
high and low static pressure.
In Installation > Setup, enable a static pressure unit.
Refer to Static Pressure Calibration, page 96 and Static Pressure, page 92.
o displaying High Pressure and Pressure Sensor Failure alarms
display the alarms. Reset the alarms one time to cease the display.
Page 33
3.6.2 S
SYSTEM PARAMETERS
STATIC PRESSURE
Attic Advance Opening Time (sec)
0
TATIC PRESSURE HELP | SET DEFINITIONS
While viewing the Static Pressure menu: Press
HELP
, select SET, and press
ENTER
.
Wind Gust Delay Time (sec)
S. Pressure During Tunnel
Transitional Tunnel
Minimum Ventilation Using
Low Incoming Air (diff to Trg)
High Incoming Air (diff to Trg)
Emergency S. Press. Delay (sec)
Curt. Pos. In Emerg. S. Press.%
Low S.P. Alarm Min. Level (MinV)
Low S.P. Alarm Min. Level (Tun.)
Time To Produce S. Pressure (sec)
10
YES
NO
VENT
-25.0
-10.0
60
100
0
0
10
• Wind Gust Delay Time (seconds): Set length of time in seconds before starting Static Pressure
control after an unexpected change in air pressure.
• Static Pressure During Tunnel: Select YES or NO for using Static Pressure control when in
Tunnel mode.
• Transitional Tunnel: Select YES or NO for using tunnel curtains when static pressure is high
and vents are already at 100%.
• Minimum Ventilation Using (vent/curtain): Select VENT or CURTAIN for controlling static
pressure when in minimum ventilation.
• Low Incoming Air (Difference to Target): Define low temperature for static pressure control.
• High Incoming Air (Difference to Target): Define high temperature for static pressure control.
3.6.3 M
When in static pressure mode and employing multiple tunnel curtains, Farm Premium can open the
curtains in sequence. Opening the tunnel curtains commences when the target static pressure is reached
and the controller signals to the tunnel machine to operate the curtains. Farm Premium opens the first
tunnel curtain (as defined in the relays) to the user defined level. If additional ventilation is required, the
second tunnel curtain opens. This process continues for each defined curtain.
As pressure falls, the process is reversed; curtains close in progression starting with the last curtain.
• Emergency Static Pressure Delay (seconds): Set length of time in seconds before initiating an
emergency opening when pressure exceeds high alarm setting.
• Curtain Position in Emergency Static Pressure (%): Set the desired curtain position (in
percentage) when an emergency pressure event occurs.
• Low Static Pressure Alarm Minimum Level (MinV): Below this level, the controller ignores low
static pressure alarms.
• Low Static Pressure Alarm Min. Level (Tunnel): Below this level, the controller ignores low
static pressure alarms while in tunnel mode.
• Time to Produce Static Pressure (seconds): Enter the length of time to reach target pressure
when minimum ventilation fan cycle is on.
• Attic Advance Opening Time (seconds): Define the amount of time for the attic inlets to open
before minimum vent cycling fans turn on.
ULTI STAGE TUNNEL CURTAINS
To set up Multi Stage Tunnel Curtains:
1. In Installation > Relays define more than one relay as tunnel curtain (open and close).
Ammonia treatment forces an increase in ventilation level when the ammonia level is too high. To prevent
fans changing their ventilation too often, treatment begins after a user-defined delay. The user also defines
the treatment duration.
After the duration, the ventilation level may come back down automatically. If during treatment, the ammonia
level drops below the Stop Value parameter, the ventilation level automatically returns to that level used
before ammonia treatment began.
7
14
0
0
0
0
0
0
2
2
2
2
2
2
2
2
30
30
0
0
0
0
0
0
120
90
0
0
0
0
0
0
150
180
0
0
0
0
0
0
This function requires an ammonia sensor.
1. In Install > Analog Sensors (refer to Analog Sensors), designate one sensor as an ammonia
sensor.
2. If required, go to Service > Ammonia and calibrate the sensors (refer to Ammonia Calibration).
3. In Control > Ammonia Treatment set the parameters.
NOTE: Ammonia levels should not be higher than 30 ppm.
Day: Growth day. You can set multiple programs for same day (maximum number of
programs: 20)
o
Start Value: Ammonia value at which to begin treatment. Range: 0 to 100. Default: 2
Page 36
o
SYSTEM PARAMETERS
AMMONIA TREATMENT
Ammonia Treatment By
Level
Stop Value: Ammonia value at which to end treatment. Range: 0 to 100. Default: 2
o
Delay (Sec): When the ammonia level reaches the start value, the controller delays
treatment for this amount of time. Default: 0
o
Duration (Sec): Number of seconds the controller maintains the increased level of
ventilation. Default: 0
4. Set the Ammonia Alarm (page 72).
3.9.1 A
MMONIA TREATMENT HELP | SET DEFINITIONS
While viewing the Ammonia Treatment menu: Press HELP, select SET, and press ENTER.
Ammonia Treatment Below Heat
No
o
Ammonia Treatment below Heat: Select: Select YES or NO to enable Ammonia
Treatment when heaters are operating (set in Temperature Curve).
o
Ammonia Treatment By: This parameter designates the method used when ammonia
treatment begins. Normally, this parameter is relevant only when minimum ventilation is
running. When a treatment is required, select the method to be employed:
Level: Increases the ventilation level when a treatment is required.
NOTE: When employing Ventilation by Weight, the controller increases the cycle time or the level,
depending on the particular settings.
Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
Tunnel: Designate a specific tunnel fan (press a number key to select the fan).
None: Disables the treatment.
The Farm Premium can have many closely spaced levels of ventilation enabling it to find the optimum
average airflow for the poultry facility. Many of the levels are at exactly the same temperature setting, so
there may be a question as to how the Farm Premium chooses the correct level.
The menus in this section apply levels to ventilation, variable speed fans, curtains, and other related
matters. The levels in the various menus are consistent with each other so that a level in one menu
corresponds with that level in any other menu.
The rules that apply here are:
• Rule 1: If the temperature is at target (in the Happy Zone) stay at the current level.
• Rule 2: If the temperature moves outside the Happy Zone; have some patience.
• Rule 3: After the designated delay, increase or decrease levels appropriately.
You can find the ‘patience’ factors under HELP | SET in this menu. They are the increase level delay and
decrease level delay parameters. The factory default values are 180 seconds for an increase and 60
seconds for a decrease.
The factory default values bias the Farm Premium slightly toward warmer temperatures, as would be
appropriate for young birds. The level increase delay is longer than the level decrease delay. You may
wish to reverse these values by the time you have market age broilers, since they are more sensitive to
heat stress than to cold.
Although many of the levels have 0.0 differential temperatures, certain levels should have differentials to
account for wind chill on the birds. The first tunnel level accounts for wind chill by switching to the tunnel
temperature instead of target temperature. Higher tunnel levels require an additional wind chill because
of the increased airflow.
In addition, the last few levels before entering tunnel can form a transitional region. You may want to
build differentials from target temperature just before the first tunnel level.
The controller obeys both the time delay rules and the differential temperature rules when changing levels.
Tunnel exit has several additional rules, such as outside temperature restriction and the tunnel exit delay
described under HELP | SET. In addition, there are Cool Down and change to Min Vent on reaching the
Heat temperature features described in Control | Temperature Curve | HELP | Set parameters.
The Precision Ventilation table provides up to 30 ventilation levels controlling both variable fans and
relay-controlled fans. To program this table, start with the minimum ventilation used in the first level and
increase ventilation gradually. A reasonable rule of thumb is to increase the airflow about 25% at each
level. Increases in airflow up to 50% work satisfactorily with factory default settings.
1. Do one or both:
2. In Device Setting > Levels of Ventilation configure the parameters as required.
o In Install > Relay Outlet (refer to page 107) define at least one relay as a Tunnel Fan or
Exhaust Fan.
o In Install > Analog Output (refer to page 110) define one function as Tunnel Fan or
Exhaust Fan.
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0.0.
Air Capacity: 300 -Continuous
Chill Range: --- -Cycl e
-Rotate
Tunnel Level: T
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
45
60
80
120
160
200
250
100
120
150
180
0
150
0
Page 39
NOTE: The number appearing under Exhaust and Tunnel is refers to the numbers defined in
Continuous:
Cycle:
Rotate:
SYSTEM PARAMETERS
LEVELS OF VENTILATION
Installation.
• Number: Read-only showing the ventilation level.
NOTE: At the First Tunnel Level (defined in the Help | Set Definitions) the screen displays the tunnel
temperature (defined in Temperature Curve). T means the level is in tunnel mode.
• Differential Temperature: Triggers next level according to difference from target temperature
(time delays remain in effect).
o The first several levels normally have differential temperatures set to 0.
o If the ventilation level is below tunnel, the differential temperature is relative to the Target
temperature given in Control | Temperature Curve.
o If the ventilation level is a tunnel level, the differential temperature is relative to the Tunnel
temperature given in
• Cycle timer ON: Set ON time for fans for that ventilation level.
• Cycle timer OFF: Set OFF time for fans of that ventilation level. This parameter disappears if
Control | Temperature Curve.
cycle time is set in the HELP | SET Parameters to something other than 0 and the controller
calculates the “Cycle timer OFF” automatically.
• Exhaust: Control exhaust fans according to Continuous, Cycle, and Rotate.
• Tunnel: Control tunnel fans according to Continuous, Cycle, and Rotate.
• Air Capacity: Displays the current exhaust fan or tunnel air flow for each ventilation level. If
4.1.1 L
EVELS OF VENTILATION HELP | SET DEFINITIONS
When viewing the Levels of Ventilation menu: Press
•Define
Variable Speed Fan Levels have been set (refer to page 41), the speed percentage is taken
into account.
Works constantly without a break
Operates according to ON/OFF timer
Operates according to ON/OFF timer; in each cycle a different fan
operates
Help
, select
Maximum Levels of Ventilation
First Tunnel Level
Max Fans, Switch to Tunnel
Tunnel Exit – Diff Below Tunnel
Tun Exit-Out T. Diff from Tun.
Increase Level Delay Time (sec)
Decrease Level Delay Time (sec)
Fan Cycle Time (sec, 0-Manual)
Tunnel Exit Delay (minutes)
Wind Chill Enable
Wind Chill Limit
RH Effect
o Maximum Levels of Ventilation: Set the maximum number of levels.
o First Tunnel Level: Set the entry point to tunnel mode. Zero disables this parameter.
Page 40
o Max Fans, Switch to Tunnel: Set the maximum number of fans allowed to operate when
entering tunnel mode.
o Tunnel Exit – Differential Below Tunnel: Set degree of difference below Tunnel
temperature (set in Control | Temperature Curve) to Exit Tunnel mode.
o Tunnel Exit – Outside Differential from Tunnel: The outside temperature must read
below this (Tunnel + Differential) to allow exiting from tunnel mode.
o Increase Level Delay Time (sec): Set length of time in seconds before transitioning to
next level.
o Decrease Level Delay Time (sec): Set length of time in seconds before transitioning to
lower level.
o Fan Cycle Time (sec): If set to 0, set on and off times for each level manually. If you are
using a fixed cycle time, such as 300 seconds, enter it here and enter only the On time at
each level. Default: 0
o Tunnel Exit Delay (minutes): Set length of time in minutes before exiting Tunnel mode.
This time begins once all other parameters are satisfied.
o Wind Chill: Refer to the following section.
4.1.2 W
IND CHILL
Farm Premium can take into consideration the wind chill factor when making certain calculations related
to the temperature. In effect, the wind chill factor acts as the temperature differential. When enabled,
Farm Premium determines the “calculated temperature (actual temperature – wind chill temperature) and
uses this temperature:
• When calculating the Tunnel Mode level up/down algorithms
• When operating the Cool Pad (if enabled in System Variables; refer to Operate Cool Pad,
page 40.
NOTE: The Wind Chill factor influences controller operation from the 1st tunnel level.
The actual temperature: 1) determines the entry and exit into Tunnel Mode 2) controls the fogger.
Parameters:
• Wind Chill: Enable this parameter to include the wind chill factor in ventilation calculations.
Default = No.
• Wind Chill Limit: Maximum wind chill factor value. Default = 8° C.
• RH Effect: The decrease in temperature caused by an increase in relative humidity. Default is
0.26° C.
The Relative Humidity Effect parameter enables including the relative humidity (RH) in the wind chill
factor calculations. A rise in relative humidity reduces the wind chill factor. How does it work?
o There is no effect below 40% relative humidity.
o The user determines the increase in temperature for every 5% increase in relative
humidity.
The default increase is 0.26° C; meaning that between 40.1% - 45% relative
humidity, the wind chill factor decreases by 0.26° C. Between 45.1% - 50%, the
wind chill factor decreases by 0.52° C, twice the default level. Between 50.1% 55%, the decrease is 0.78° C, three times the default level, and so on.
The user can set the temperature increase as required.
To disable this feature, enter '0'
In the Variable Speed Fan Level table set the speed in percentages by level.
This function requires an Analog Output card.
This card sends a low voltage control signal to a variable speed controller to run the variable speed fan.
Several kinds of speed controllers are available, such as TRIAC Control, and Variable Frequency Three
Phase drives.
Level
2
3
4
5 T
6 T
7 T
8 T
9 T
----
---45
45
60
60
75
90
30
30
45
60
60
75
75
90
30
45
45
45
60
60
75
90
1. In Install > Analog Output (refer to Analog Output, page 110), define at least one output as a
variable speed fan.
2. In Device Setting > Levels of Ventilation, define the mode (required!).
NOTE: "----" appears when this variable fan is not defined as operating at this ventilation level.
3. In Device Setting > V. Speed Fan Levels, define the fans' working percentages.
4.3 Vent & Curtain Levels
Set the curtain levels to correspond with the ventilation levels. The operating mode determines the curtain
control procedure.
NOTE: Users employing Layers Mode, refer to Layers Vent and Curtain Levels, page 121.
NOTE: Before setting the levels, define the opening mechanism (refer to Vent / Curtain Setup, page
111).
1. In Install > Relay Outlet (refer to page 107), define at least one relay as Curtain Open, Tunnel
Open, Vent Open, or Attic Open.
2. If your installation includes curtains, in Install > Setup, define Natural Ventilation as Level or
Power.
NOTE: When Natural Ventilation is Off, the Curtains don't appear in the screen.
3. In Control > Temperature curve, define the Target Temperature.
4. In Device Setting > Vent & Curtain Levels, define the minimum opening percentages.
5. Press Enter.
6. If required, configure each opening to work with a particular temperature sensor. Refer to
• Tunnel/Curtain/Vent/Attic: Set position for the tunnel curtain by level. If you have Static
Pressure in Tunnel turned on (Control | Static Pressure | Help | Set), this becomes the minimum
position for the tunnel inlet.
4.3.1 V
ENT & CURTAIN LEVELS HELP | SET DEFINITIONS
While viewing the Vent & Curtain Levels menu: Press
Stop Fans, Curt. Move (total %)
1st Day for 2nd Vent to Oper.
1st Level for 2nd Vent to Oper
ATTIC
Minimum Attic Temp. To Operate
Operate Until Day
Operate Until Level
Operate From Time
Operate To Time
HELP
, select SET, and press
30
-2
1
75
10
10
0:00
0:00
Curtains
• Stop Fans, Curtain Move (total %): Commands controller to stop fans during curtain
movements when total of all curtains is less than the total percent set in this parameter. For
example, 3 curtains at 40% each total 120% for this parameter. Default: 30%
st
• 1
Day for 2nd Vent to Operate: Set the day the second vent begins operating. Default: 1.
ENTER
.
NOTE: You can set negative days.
st
• 1
Level for 2nd Vent to Operate: Set the level the second vent begins operating. Default: 1
• Minimum Attic Temperature To Operate: Set the minimum temperature to activate the Attic
operation.
• Operate Until Day: Set the last day for attic operation (broilers only).
• Operate From/To Time: Set the time frame for attic operation.
NOTE: If one of the above options is relevant, the Attic is enabled.
• Maximum Temperature to Disable Attic: Set the maximum attic temperature to stop using attic
STIR FAN LEVELS
Level
Stir Fan No
Variable Fan
123456789012345
3 4
1
. . .
ventilation. This setting can prevent the heating effect in the growing space being too high
resulting in overheating.
4.4 Stir Fan Levels
1. Do one or both:
o In Install > Relay Outlet (refer to page 107), define at least one relay as a Stir Fan or
o InInstall > Analog Output (refer to page 110) define one function as Variable Stir Fan.
2. In Device > Stir Fan Levels, define the parameters as required.
3. Map each stir fan to a temperature sensor (refer to Temperature Definition, page 114) (option).
2
3 T
4 T
5 T
6 T
7 T
-Continuous
. . .
. . .
. . . .
. . . .
. . . .
. . . .
-Cycle On
-Cycle Off
In the Stir Fan Level table set the speed in percentage that you want the variable speed fan to work at (by
levels). For each level, program the stir fans' cycle. Configure the actual speed in Analog Output, page
110.
NOTE: The numbers shown in the screen under Variable Fan depend on how you defined the fans in
Installation > Relay Layout and Analog Output.
NOTE: T means the level is in tunnel mode.
• Ventilation Level: Read only.
• Variable Fan: Set variable speed fan operation in percentages.
• Stir Fan Number: Control stir fans according to Continuous, Cycle On, Cycle Off (ventilation
cycles are the same as previously set in Levels of Ventilation. Press +/- to set the operation
cycle.
NOTE: The Stir Fans operate according to the levels you program in this menu, and according to the
Rotate: Operates according to ON/OFF timer; in each cycle a different fan operates
programs you select in the Stir Fan Program. The fan turns on if any program or level requests
ON; all programs and levels must be OFF for the Stir Fan to be off.
Page 44
4.5 Stir Fan Program
STIR FAN PROGRAM
Fan
P R O G R A M
No.
-A-
-B-
-C-
-D-
-E-
1
8
SYSTEM PARAMETERS
PROGRAM A (for min vent)
To Time
This section contains five different programs that you can assign to each stir fan. Check the programs
applying to each fan by using the '+/-' key (further explained in STIR FAN PROGRAM HELP |SET).
NOTE: If the same variable stir fan is selected for different programs, the program having the highest
fan speed operates.
NOTE: The ~ symbol designates an analog output device.
2 ~
3 ~
4
5
6
7
• A (heaters): This program corrects temperature variations lengthwise in the building. Insert diff
and sensor numbers.
• B (for min vent): This program helps mixing minimum ventilation air for buildings having stir fans
to mix the air coming in with warm inside air.
• C, D & E (sensors diff temperature): These options create three stir fan groups which operate
according to sensor differentials.
4.5.1 S
TIR FAN PROGRAM HELP | SET DEFINITIONS
While viewing the
Stir Fan Program
Diff below Target to Operate:
Cycle On time (sec):
Cycle Off time (sec):
From Level
To Level
From Time (hh:mm)
To Time (hh:mm)
Stop During Fan Operation
menu: Press
PROGRAM B (sensors diff temp)
Operate after End of Cycle
Delay for Operation
Time for Operation
From Level
To Level
From Time
• Difference Between Cool Pads Stage: Farm Premium supports four cooling pad stages. The
Cool Pad #
Assigned Sensor
Diff Between Cool Pads Stage
Actual ON temperature
controller activates the first stage when the temperature reaches the Tunnel Temperature
(Control > Temperature Curve) plus the Tunnel Differentiation (set in the Cool Pad screen).
Each additional stage begins when the temperature reaches the Tunnel Temperature plus the
Tunnel Differentiation plus this differentiation.
For example, if:
o Tunnel Temperature = 80°
o Tunnel Diff = 2
o Diff between Cool Pads Stage = 3
Stage 1 starts at 82°, Stage 2 at 85°, Stage 3 at 88°, and Stage 4 at 91°.
Example: Cool Pad ON temperature = 80°, Diff set to 2º F:
1 Average 0.0 80°
2 Average 2.0 82°
3 Temp Sensor 2 0.0 80°
4 Temp Sensor 2 2.0 82°
• Cool Pad Minimum Level: In systems having more than one pump, this parameter enables
keeping a cool pad inoperative until the associated tunnel curtain turns on. Define the minimum
level for each cool pad.
NOTE: When the Difference Between Cool Pads Stage is enabled, the cool pads operate according to
both conditions.
Cool Pad Flush
• Flush Cool Pad At: Set time of day (hh:mm) to start continuous water application to remove
deposits from the cool cells.
• Cool Pad Flush Duration (minutes): Set the length of time in minutes for flushing. If this
parameter is set, flush is applied without regard to ventilation level or operating mode.
4.7 Foggers
This menu sets the operating conditions for the Foggers.
• Foggers and Cool Pad have a different temperature reference point. The Fogger Temperature
Differentials are relative to the target temperature; the Cool Pad is relative to the tunnel entry
temperature.
• Foggers operate even when the controller is not in tunnel mode.
• Start Time & End Time: Time of day you want foggers to start and stop.
o It is possible to set multiple start and stop times for single day.
o In the screen above, the first programmed line is at day 47. The foggers do not operate
before growth day 47 in this case. Since there are no entries other than day 47, the day
47 program lines apply from then on.
• Target Differential: Set difference from target temperature to trigger foggers.
• To Humidity: Set maximum humidity allowed before stopping foggers.
• On Sec: Set the maximum on time for each cycle of fogger operation.
• Off Sec: Set the minimum off time for each cycle of fogger operation.
4.7.1 F
OGGERS HELP | SET DEFINITIONS
While viewing the Foggers menu: Press
Temperature Band
Humidity Band (%)
Min Level to Enable Operation
Max Level to Enable Operation
Enable Rotation
HELP
, select SET, and press
2.0
2.0
1
30
NO
ENTER
.
• Temperature Band: Define the on/off hysteresis relative to temperature.
• Humidity Band (%): Define the on/off hysteresis relative to humidity.
• Min Level to Enable Operation: Select the minimum ventilation level to operate the foggers.
• Max Level to Enable Operation: Set the maximum ventilation level for fogger operation.
• Enable Rotation: Enable this function to use a different fogger relay each cycle. This function
enables dispersing the droplets at a higher pressure, to wet the animal.
NOTE: Munters recommends keeping this function set at the default setting (No).
• Difference between Foggers Stage: Farm Premium supports four fogging stages. The
controller activates the first stage when the temperature reaches the Target Temperature
(Control > Temperature Curve) plus the foggers differential. Each additional stage begins when
the temperature reaches the Target Temperature plus the fogger differentiation.
Stage 1 starts at 83°, Stage 2 at 86°, Stage 3 at 89°, and Stage 4 at 92°.
4.8 Light
This menu sets the lights operating conditions. The controller has a capacity for up to four channels of
On/Off Lights and up to 10 channels of Dimmer Lights. In addition, this menu enables using a light
sensor.
1. In Install > Analog Output (refer to Analog Output, page 110) define up to four outputs as light
dimmers.
2. In Device Setting > Light, define the parameters as required.
12
12
12
12
25
25
25
25
00:00
01:00
03:00
21:00
00:00
03:00
20:00
23:00
45
0
45
0
0
35
0
35
45
0
45
0
0
35
0
35
Water & Feed (page 51) configuration defines the Light Menu configuration:
• If you select Daily, the above screen appears when you select Light; configure the Light menu
once.
• If you select 2 – 6 Days or Week, the screen below appears.
Please Select
Light Table for Feed/No Feed
Days.
Select Table
FEED NO FEED
1. Select Feed and press Enter. The Light parameters screen appears. These parameters configure
the Light functions on feed days.
2. Configure the parameters.
3. Select No Feed and press Enter. The Light parameters screen appears. These parameters
configure the Light functions on non-feed days.
4. Configure the parameters.
• Day: Set Growth Day
In the example, the brood lights (channel 1) and bright center lights (channel 2) turn on from day
1, while the grow end lights (channel 3) are off. The example shows two channels of light dimmer,
Channel 1 at 100% and Channel 2 at 0% (for baby chicks in the brood zone).
o On day 12, the center lights turn off, and the dimmer lights go to 45%. There are two
periods of darkness: from 01:00 to 03:00 in the morning, and 09:00 PM to midnight.
This program repeats until day 25.
o From day 25 the on/off lights stay off, and the dimmer lights provide dim light during the
on periods, and go out fully for two periods of darkness. The dark periods total 6 hours,
being from midnight to 03:00 AM and from 08:00 PM (20:00) to 11:00 PM (23:00).
• Light: Check mark the desired light(s) to turn on. Apply dots for lights you would like to turn off.
Switch between check marks and dots by pressing the +/- key.
• Intensity (%): Set intensity in percentage for light dimmer(s). Dimmer lights start to brighten if
the intensity increases, and complete dimming if the intensity decreases at the set time. That is,
they start dimming the ‘sunset time’ in advance of the set time (see Help | Set below).
4.8.1 L
IGHT HELP | SET DEFINITIONS
NOTE: Pig Mode does not support Light Help parameters.
While viewing the Light menu: Press
Sunrise Time (minutes)
Sunset Time (minutes)
Allow Spiking from Day
Spike Cycle (minutes)
Spike Duration (minutes)
Spike Increase Amount (%)
Signal Light Is:
Signal Before Feed (seconds)
Signal During Feed (seconds)
HELP
, select SET, and press
10
10
1
0
0
0
LIGHT2
60
60
ENTER
.
• Sunrise Time (minutes): The amount of time required for the light intensity to rise from 0% to the
designated level.
• Sunset Time (minutes): The amount of time required for the light intensity to decline from the
designated level to 0%.
• Allow Spiking from Day: The day spiking begins.
• Spike Cycle (minutes): The time length that the spike is at its maximum level. Reaching the
maximum level and returning to the preset level both take one minute. For example if the spike
duration is 10 minutes, the spike cycle is 8 minutes.
NOTE: After the feeding period ends, all lights selected in the Light Parameters screen relight.
• Spike Durations (minutes): The total amount of time of the spike cycle, including the rise and
fall times.
• Spike Increase Amount: Set the increase in intensity for the spike in relation to the current light
intensity.
• Signal Light Is: Only one light operates during feeding times. Select which light is lit or choose
“None”.
• Signal Before Feed (seconds): Amount of time, before the feeding starts, that all other lights
go off.
• Signal During Feed (seconds): Amount of time that the selected light remains on after feeding
ends.
Page 51
NOTE: The above two parameters are disabled on no feed days.
• Light Sensor Active: The light sensor turns off all lights when sufficient outside lights exists. If a
light sensor is installed, enable this option to turn off the light during feeding time when there is
sufficient outside light. Refer to Light Sensor Calibration, page 97 for details.
Figure 6: Lighting without Spiking
Figure 7: Lighting with Spiking
NOTE: The initial reference time for the Spike Cycle is the end of Sunrise. The spike begins Spike
Duration minutes before the end of the Spike Cycle, and has one minute up and down ramps in
intensity. If Sunrise Duration is set to zero, no spiking occurs.
4.9 Water & Feed
This menu sets the operating conditions for water and feed devices. There are control two methods:
1. Set the parameters as required
o Day: Set growth day. You can define days as negative days. Enter the number and then
press the +/-key.
o Time: Set event times for water, feeder, or auger. Check marks indicate ON at the event
time, and dots indicate OFF. Toggle between check marks and dots with the +/- keys.
o Water: Select a check mark to mark water lines to turn on, dot the ones to turn off.
o Feeder: Check mark feed lines to turn on, dot the ones to turn off.
o Auger: Check mark auger lines to turn on, dot the ones to turn off.
2. Set the Water Overflow Alarms and Water Shortage Alarms (page 71).
NOTE: You can implement mealtime, clean up meals and other options similarly as shown earlier in the
• Day: Set growth day. You can define days as negative days. Enter the number and then press
the +/-key. Growth days stay at the defined parameters until the next defined day.
• From Time/To Time: Set the time period during which water and feeding lines can operate.
• Water: Select a check mark to mark water lines to turn on, dot the ones to turn off.
Page 53
• Feeder: Check mark feed lines to turn on, dot the ones to turn off.
SYSTEM PARAMETERS
WATER & FEEDS
YES
Feed Day Cycle
Quantity
DAYS CYCLE
Day: 1 2
Feed: √
WATER ON NO FEED DAYS
Start
Stop
Start
Stop
10;00
10:30
11:30
12:30
SYSTEM PARAMETERS
WATER & FEEDS
YES
Feed Day Cycle
Quantity
DAYS CYCLE
Day:
SUN
MON
TUE
WED
THU
FRI
SAT
Feed:
√ √√ √
WATER ON NO FEED DAYS
Start
Stop
Start
Stop
10:00
10:30
11:30
12:30
• Feed: Enter the quantity of feed provided from the silos during the From/To time.
o You can provide feed from multiple silos, enabling specific feed mixes.
o Distribution continues until the To Time or until the defined quantity is reached, whichever
comes first.
o If a relay is not defined as an auger the Feed numbers still appear. However any quantity
entered is meaningless.
Water runs continually between the From/To times. Only feed is distributed in cycles.
NOTE: This function only works when relays are defined as augers and each silo is mapped to an
auger. Defining a digital sensor as a feed count does not enable Control by Quantity.
NOTE: If both Control via Quantity and a digital feed counter are enabled, Control via Quantity takes
priority.
4.9.3 W
ATER AND FEED HELP | SET DEFINITIONS
These parameters define the feed and water delivery schedule through the week.
NOTE: The Water and Feed parameters work in conjunction with the Lighting parameters.
• Feed Day Cycle:
o Daily: Same schedule for every day of the week.
o 2 – 6 Days: Select a cycle that lasts the number of days chosen and then repeats itself.
For example, 2 Days means that the cycle lasts two days and then repeats itself.
2 DAYS
o Week: Select which days in the week that feed and water are delivered.
• Quantity: Enable this feature to enable Control by Quantity.
NOTE: If you choose Daily, the Scale function is always enabled. If you choose 2- 6 Days or Week,
CAUTION If you want to provide feed every day, select Daily. Selecting Week and marking each
EXTRA SYSTEMS
System
1 2 3
4
Start Time
Off (sec)
10:30
300
06:15
300
14:20
2000
00:00
0
day causes problems with this function.
If you select the 2 – 6 Day schedule or the Week schedule, configure:
• Days Cycle (2 – 6 Days): Select which days in the cycle that feed and water is delivered.
• Week Cycle: Select the days that feed and water is delivered.
• Water on No Feed Days: Select up to two time periods when water is delivered on non-feed
days.
NOTE: On feed days, water is delivered when feed is delivered.
4.10 Extra Systems
This menu sets the parameters of other devices that are not listed in the controller.
End Time
From Temp
To Temp
From Hum.
To Hum.
On (sec)
18:45
75.5
93.0
55
85
45
20:30
85.5
95.5
60
85
45
03:15
60
98.0
60
85
300
00:00
0.0
0.0
0
0
0
• Start Time: Time at which this Extra System starts.
• End Time: Time at which this Extra System stops.
• From Temp: Temperature above which Extra System operates.
• To Temp: Temperature below which Extra System operates.
• From Humidity: Humidity above which Extra System operates
• To Humidity: Humidity below which Extra System operates.
• On (sec): On time for the Extra System. If set to 0, the extra system does not operate.
• Off (sec): Off time for Extra System after completion of on time. If you have values in both ON
and Off, the extra system cycles. If you have zero OFF time, and any ON time, the system
simply stays on as long as the other parameters are satisfied.
NOTE: All parameters must be satisfied for an Extra System to operate. For example if the
temperature is below the From Temperature or the Humidity below the From Humidity, the
system is OFF. You can assign specific temperature sensors to an Extra System in Install | Temp
Definition. The Extra System uses the Inside Humidity, not the Outside Humidity. If there is no
humidity sensor, the Extra Systems ignore the humidity parameters.
4.11 Emergency Setting
This selection applies to optional emergency cards. These cards are battery backed, and operate as
standard switch and relay cards during normal operation. If an emergency occurs, the cards continue to
operate according to their emergency settings.
This function requires installing an Emergency card.
Page 55
EMERGENCY SETTING
Relay
Function
Diff
Day
Operate
31
35
Heat 4
Tun. Fan 8
-5.0
0.0
6.0
Min
Temp.
SYSTEM PARAMETERS
EMERGENCY SETTING
Delay Time to Start Fans (sec)
30
2.0
4.0
10
20
30
0
Vent
Temp.
Temp.
32
33
34
Exh. Fan 1
Tun. Fan 6
Tun. Fan 7
• Relay: The Farm Premium determines the relay numbers automatically from the position in the
controller in which the Emergency Switch card is installed.
• Function: Assign the relay function in Install | Relay Layout. Your selections will likely be
different from the example above. The Farm Premium does not allow certain selections for the
emergency functions.
• Differential: The difference from target temperature at which the device operates during
emergency operation.
• Day: After this day, the device operates continuously without regard to temperature setting
during emergency operation. In this example:
o Exhaust Fan 1 operates up to the target temperature using the Min Vent timer calculated
in Help | Set on the next page, and continuously above the target temperature.
However, from Growth Day 10 forward, the fan operates continuously without regard to
temperature.
o Tunnel Fan 6 is off below 2.0º + Target, and operates continuously if the temperature is
more than 2.0º above Target Temperature. However, if the Growth Day is 20 or
greater, Tunnel Fan 6 operates continuously without regard to temperature during
• Operate: Choose whether the Minimum Vent timer applies to this device or only the
temperature differential.
4.11.1 E
MERGENCY SETTING HELP | SET DEFINITIONS
While viewing the Emergency Setting menu: Press
Diff Above Target For Emergency
Diff Below Target For Emergency
Min. Vent On Time Da y1 (sec)
Min. Vent Off Time Day 1 (sec)
Min. Vent On Time Day 21 (sec)
Min. Vent Off Time Day 21 (sec)
HELP
, select SET, and press
15.0
-10.0
30
270
300
0
ENTER
• Diff above target for emergency: Set a value above temperature target at which the
emergency card enters emergency operation.
• Diff below target for emergency: Set a value below temperature target at which the
emergency card enters emergency operation.
• Min. vent on time day 1 (sec): Set the minimum ventilation on time for 1-day-old birds in this
parameter. The card calculates on times between days 1 to 21.
.
• Min. vent off time day 1 (sec): Set the off time for minimum ventilation cycle timer during
emergency for growth day 1.
• Min. vent on time day 21 (sec): Set the on time for minimum ventilation for three-week old
• Min. vent off time day 21 (sec): Set the off time for minimum ventilation cycle timer during
WATER ON DEMAND
Time
hh:mm
WOD-RLY
1 2 3 4
1
12:00
2
6:00
3
8:00
5
10:00
7
12:00
9
14:00
emergency for growth day 21.
• Delay time to start fans (sec): Set a delay time for the card to wait upon entering emergency
before starting fans. This delay gives air inlet devices time to pre-position before they turn on
and build static pressure. Otherwise, the static pressure could cause air inlet curtains to stick to
wire mesh barriers.
4.12 Water on Demand
The Water on Demand (WOD) function enables regulating the pressure of all nipple lines in the house
from one central point, ensuring uniform pressure in all lines. The function also enables immediate
transitioning between different preset pressures of all nipple lines in the house by closing and opening of
valves at the central point (manual or solenoid according to the mode installed).
Farm Premium enables controlling the water cycle times using relays and controlling the water pressure
using analog input and output sensors. The two methods are complimentary. A user can use either one
alone or both.
• Relay Control
• Sensor Control
NOTE: The two methods are complimentary.
4.12.1 R
ELAY CONTROL
You can specify up to 50 time periods.
Day
1. In Installation > RelayLayout designate up to four relays as WOD valves (relays 179 to 182).
Refer to page 107 for details.
2. In Device > Water on Demand, configure the following parameters:
o Day: Specifies the day to activate the selected WOD valve. You can define days as
negative days. Enter the number and then press the +/-key.
o Time: Specifies the time to activate the enabled valves. The valves continue running until
the next scheduled day and time.
o WOD Relay: Enable the required relays.
3. Set the WOD alarms in Alarm Setting Help | Set Definitions, page 70.
NOTE: When using sensor control, WOD status appears on the Main Screen, Hot Screen 7, and Hot
Screen 0.
Day
To add precision measurements:
1. To control the water valve opening, In Installation > Analog Output:
a. designate one output device as Water on Demand Precision.
b. set the minimum input and output voltages.
2. In Installation > Analog Sensor, designate one sensor as Water of Demand Pre. This setting
enables a sensor to measure the water flow.
3. In Device > Water on Demand, configure the following parameters:
o Day: Specifies the day to activate the selected WOD valve. You can define days as
negative days. Enter the number and then press the +/-key
o Time: Specifies the time to activate the enabled valves. The valves continue running until
the next scheduled day and time.
o WOD Relay: Enable the required relays.
o Pressure: Specifies the required water pressure. The unit that appears is the unit defined
in Installation > Setup (pressure unit) (page 106).
4. In Device > Water on Demand > Help set the parameters (optional).5. In Service > WOD
Calibration:
a. Enter the first pressure and voltage data points.
b. Repeat for second data point.
c. Set the Help definitions (optional, refer to WOD Calibration Help | Set Definitions, page
104).
6. Set the WOD alarms in Alarm Setting Help | Set Definitions, page 70
4.12.3 W
ATER ON DEMAND HELP | SET DEFINITIONS
• Water Pressure During Flush: Designate the system water pressure when nipple flush is
operative.
• Relay Active During Flush: Designate which WOD relays remain active during flushing.
The Natural Program enables supplying the house's air requirements using the wind. Using the Natural
Program depends on a variety of environmental and scheduling factors. While in this mode, curtains open
and close based on the target temperature.
Setting up the Natural Ventilation is a multistep process.
• Preliminary Steps
• Defining Natural Conditions
• Defining Natural Operation
• Natural Programming Help | Set Definitions
4.13.1 H
OW DOES NATURAL VENTILATION WORK
For Farm Premium to switch to Natural Ventilation:
• Natural Ventilation works only during the defined growth days and daily schedule.
• The temperature inside the chicken house must be within the inside temperature band.
• The temperature outside the chicken house must be within the outside temperature band.
o If the temperature is below either of the above two parameters, ventilation switches to
Minimum.
o If the temperature is above either of the above two parameters, ventilation switches to
Tunnel (there is an option to remain in natural ventilation; refer to Minimum Wind Speed
for Tunnel Temp).
• The wind speed must be within the wind speed band.
• The wind direction must be within the user-defined area.
NOTE: Including the wind speed and direction in Natural Ventilation calculations is optional and
requires in the installation and configuration of additional equipment.
• If the weather conditions meet the above requirements, curtains open to a calculated position
based on the difference temperature and minimum and maximum percentage. If more air is
required, the curtains adjust themselves automatically using a calculation based on the minimum
and maximum curtain position. The larger the difference between the minimum and maximum
openings, the larger the step.
• Any change in the curtain position takes place after the Delay Time.
Install a wind speed and rain detector (optional).
Install a wind direction sensor (optional).
1. In Installation > Setup > Natural Ventilation, select:
o Program: This option uses the parameters listed below to determine curtain opening.
o Level: This option instructs the controller to run Natural Ventilation using the levels shown
in Device Settings > Vent and Curtain Levels. If you choose this option, no further setup is
required.
2. If you installed a wind speed and rain detector, in Installation > Digital Sensors, define the
sensors accordingly.
3. If you installed a wind direction sensor:
a. In Installation > Analog Sensor, define the sensor accordingly.
b. If required, calibrate the wind direction sensor (refer to Wind Direction Calibration, page
104).
c. In Installation> Vent/Curtain Setup, define the each curtain's direction. When making
Natural Program calculations, the controller only takes into consideration winds coming from
a certain direction. Any wind whose source is outside of this area is disregarded.
The number entered here defines the area (the number entered ±90°) (Figure 10).
If you enter 90, the range is from 0 - 180°
If you enter 45, the range is from 315 - 135°
Figure 8: Wind Direction Sensor Definition
CAUTION In both cases, winds A or B would be factored into the calculations whereas winds C or
D would not. Only calibrate the sensors if you have reason to believe that they are producing
inaccurate results.
The number entered here defines the area on both sides of the sensor! Figure 10 illustrates a
chicken house with four wind sensors. Sensor 1's Wind Direction parameter is defined as 45°
or 90° total. Winds that come within this area (A) are used for Natural Programing. The
controller disregards winds outside of this area (B & C).
4. If required, in Installation > Temperature Definition designate a temperature sensor as an outside
o Disable Stir Fan above Wind Speed: Above this speed, Stir Fans cease to operate when
NOT IN NATURAL MODE
Wind Speed
Targ Temp
Wind Dir
Rain
Out Temp
Humidity In
Avg. Temp
Humidity Out
NATURAL MODE ENABLE CONDITIONS
Between Growth Days
1 - 50
Time Frame
24 hrs
Between Inside Temp
79.0 – 91.0
Between Outside Temp
62.0 – 89.0
Between Wind Speed
11.2 – 22.4
in Natural Programming.
o Minimum Time in Any Vent Mode: Minimal amount of time that the controller waits
before changing into Natural Programming (from Minimum Ventilation or Tunnel Mode).
Similarly, the controller remains in Natural Ventilation for at least this time.
o Use Tunnel in Natural Curtain: Use tunnel curtains when in Natural Programming. When
disabled, curtains remain closed.
• Wind & Rain Effect
o Wind Low speed: Below this speed, curtains open completely. This number must be
higher than the Minimum Wind Speed to Enter.
o Wind High speed: Above this wind speed, the controller lowers the curtain maximum
opening percentage to this point.
o Between these levels, the controller opens the curtain based on a curve.
o Wind & Rain Low speed:
o Wind & Rain High speed
4.13.6 N
ATURAL PROGRAM HOT SCREEN
When the Main Screen is displayed, press 5 to view the Natural Program Hot Screen. The Hot Screen
display depends on the Natural Program Status.
4.13.6.1 Ventilation is Not in Natural Mode
When Farm Premium is employing Minimum or Tunnel Ventilation, the Hot Screen displays the conditions
needed to enter Natural Mode.
NOTE: The Between Temp parameters can change based on the wind speed. Refer to Minimum Wind
When ventilation is in the Natural Mode, this screen displays the Natural Operation parameters.
NOTE: If the Tunnel Curtains are used as Natural Curtains, display the tunnel's state by pressing 5
while the Natural Hot Screen is displayed.
NOTE: Step Temp and Step Pos are calculations, not parameters. They display when the conditions
under which Natural Mode changes its settings.
4.13.7 W
HAT HAPPENS WHEN THE CONTROLLER TRANSITIONS?
When the controller transitions to or from Natural Ventilation the following changes take place
• Side/Power > Natural: Fans stop, curtains open to the calculated position and finally the side
inlets close.
• Tunnel > Natural: Fans stop, curtains open to the calculated position. When the curtains reach
their maximum opening position, the tunnel closes (unless the tunnel mode operates to open in
natural Mode.
• Natural > Side/Power: The controller automatically calculate most suitable Power Ventilation
Level, depending on the Target Temperature and current Inside Temperature
• Natural > Tunnel: The controllers automatically calculates the most suitable ventilation level
depending on the Target Temperature and current Inside Temperature (minimum or tunnel).
4.14 Feed Scale Program
NOTE: Broiler Mode supports this function
Feed Scale enables mixing different types of feeds from (up to) four different silos. The user fills each bin
with the required feed type and sets the mixture rations and quantities in Farm Premium. The augers then
distribute the feed as defined.
This screen defines:
• the total quantity of feed to be delivered to the birds
• the auger feed mixture.
1. In Install > Relay Layout (page 107), define relays as augers as required.
2. In Management > Bird Inventory (page 66), enter the number of birds.
Day: Define the days at which the feed per bird changes. Farm Premium calculates a
o
Feed per Bird: Define the amount of feed per bird/pigs (kilograms) to be distributed.
o
Silo (%): If there is more than one silo supplying feed, enter the percentage of the feed
o
Total Feed: Displays the amount of feed required for that day. This amount is calculated
o
Today: These numbers display the actual amount of feed required for the current growth
feed curve based on these days. You can define the days as negative days. Enter the
day number and press +/-.
Farm Premium calculates the total amount of feed to be distributed based on this
parameter and the Bird Inventory parameters.
package that each silo supplies. Note that by default, Silo 1 supplies 100% of the feed.
Any number entered in Silo 2, 3, or 4 is subtracted from Silo 1.
by multiplying the feed per bird by the number of birds in the bird inventory (taking into
account any birds culled, died, or moved).
day. In the example shown above, the growth day is Day 2. Farm Premium calculates the
curve from Day 1 to Day 5 and adjusts the numbers accordingly.
4.14.1 F
•
EED SCALE HELP | SET DEFINITIONS
Define:
o
Time: What time the hopper begins distributing feed to the birds or animals.
o
Maximum Portion Weight: Enter the feed scale container size.
o
Maximum Auger Time [minutes]: This parameter sets an alarm for the auger running
time. Enter the number of minutes that the auger can run, after which an alarm appears
on the Main Screen.
Not Empty Time [minutes]: This parameter sets an alarm for the feed scale container.
The container should distribute all of its feed to the feed lines. If feed remains in the
container, it could mean that there is a problem (for example, the valve doesn't open).
Set the amount of time that feed can remain in the container, after which an alarm
appears on the Main Screen.
o
Stop Differential 1/2/3/4 Weight: After each silo stops supplying feed to its auger
line, a certain amount of feed continues to flow. This differential compensates for this
excess and ensures that only the required amount gets to the feed container. Enter the
approximate amount of feed that can be found in the augers. The number does not need
to be exact. In the following feed runs, Farm Premium will correct the amount entered.
o
Optimizer: This parameter sets the unit's sensitivity to signal noise (caused by a variety of
factors). The sensitivity plays a role as the controller stabilizes itself. Greater amounts of
noise require faster optimization. To view an indication of the controller's stability, go to
Scale Menu > Test (refer to page 61) and perform a test. If the number remains stable,
slower optimization is indicated. There are three settings; Default, Slower, Faster.
NOTE: Munters recommends leaving this parameter at the default level.
o
Valve Close Time [seconds]: Set the delay in time, if any, that the valve emptying the
feed scale closes.
o
Feed Tare [A/D count]: This specification is used for certain tests performed by a
certified technician.
NOTE: Munters recommends leaving this parameter unedited.
4.14.2 F
EED SCALE HOT SCREEN
Press "Right and Up Arrows" to view the Feed Scale Hot Screen.
This screen shows the status of different areas of the feeding apparatus. illustrates the system components.
•
Status: Shows the feed scale status: Idle, Emptying, or Filling.
•
Weight: Shows the feed scale container weight.
•
Auger 1/2/3/4: Shows if the auger is running (√) or closed (●)
•
Valve: Shows if the valve emptying the feed scale is open.
•
Feed S. Active: This field shows which controller is managing the feed scale.
•
Feed S. Interlock: The Feed Scale Interlock is a digital sensor which detects which damper is
active.
•
Hopper: The hopper is a digital sensor which detects if the feed has reached the maximum
level in the feed bin. Define this sensor in Install > Digital Sensor. This screen shows the sensor's
current status. If the feed reaches the maximum amount, an alarm is triggered.
Intermediate: The intermediate sensor is a digital sensor which detects if the feed has reached
the maximum level in the feed bin. Define this sensor in Install > Digital Sensor. This screen
shows the sensor's current status. If the feed reaches this sensor, an alarm is generated.
•
Alarm: This parameter shows if there are active alarms. View the alarms on the Main Screen.
• Maintain inventory by entering quantities in the upper half of the screen. There are separate
FEED INVENTORY
No.
Date
Silo
1 2 3
4
1
8
2-Jan-08
- -
7800
0
0
0
0
0
0
0
Total Feed:
ACTI VE
15800
√
9000
√
150000
√
10000
√
columns for male and female. If you do not wish to keep separate data, simply enter the data
into one or the other.
• Initially, enter the number of birds/animals placed. Thereafter, enter the quantity found dead,
culled (Add Culled) or moved as needed. The Farm Premium shows totals and subtotals in the
lower portion of the screen.
• You can correct an error, so long as you correct it on the same day before midnight, by
entering a negative quantity (press the +/- key after the number) to subtract the error. After
midnight, the information transfers to the History Menu.
5.2 Feed Inventory
Maintain your feed inventory by entering data into the controller. The software version determines the
function's parameters.
2
3
4
5
6
7
5-Jan-08
13-Jan-08
- -
- -
- -
- -
0
8000
0
0
0
0
9000
0
0
0
0
0
15000
0
0
0
0
0
10000
0
0
0
0
0
To enter feed inventory manually:
1. Type the day of the month and press ENTER.
2. Select the month and press ENTER.
3. Type the two-digit year and press ENTER.
4. Enter the feed quantity under the silo and press ENTER. The cumulative total appears in the Total
Feed row.
6. To delete an entry, change the quantity to zero for all silos and press ENTER. Exit the menu and
the entry disappears when you enter the menu again.
7. Set the Feed Alarms (page 71).
If you have installed load cells and connected silo scales to your Farm Premium, it automatically maintains
feed inventory, including delivery dates and feed consumption data. You can monitor your fill system and
maintain approximate feed inventory using the Digital Inputs. In this case, you need to enter your own
delivery dates.
This information transfers to theHistory > Water and Feed menus daily, or optionally as often as selected
(by the minute) in History View.
Total Feed In Silo-1
Total Feed In Silo-2
Total Feed In Silo-3
Total Feed In Silo-4
0
0
0
0
• Total Feed in Silo-1/ -2/ -3/ -4: Manually change or correct the amount of feed in the silos.
• Active Silo: Select the required silo for use. It is possible to select all of them.
5.3 Time & Date
This menu sets the current time and date for the controller.
Date
• Current Time: Enter the current time in 24 hour format.
• Date: Enter the date in day-month-year format.
10-Mar-08
• Day of the Week: Select the day of the week from the drop down menu.
5.4 Growth Day & Flock/Group
This menu defines the number of growth days and flock number.
Group No.
Figure 13: Pigs Growth Day and Group
Number
• Current Growth Day: Enter current growth day, if necessary. It is possible to enter negative
growth days up to -2. If you reset the growth day for a new flock using this tool, your old history
data does not clear. Use New Flock function to clear out old history in preparation for new
birds.
• Group/Flock No.: The controller automatically increments the flock number each time you
choose New Flock. You can edit the flock number. Since this field accepts six digits, some
producers enter a flock number that is made of the day, month and year the birds arrived.
• New Group/Flock: Use the new flock function on arrival of a new set of birds to set the
ALARM SETTING
Global Alarm Delay (sec)
Auger Overtime Delay (minute)
1
15
growth day back to 1, 0, -1, or -2, and to clear out old history data.
5.5 Alarm Setting
This menu defines the various alarm settings.
Alarm Reminder (min., 0-Disable)
SENSOR ALARM
Sensor Low Temp. Range
Sensor High Temp. Range
Sensor Alarm-Diff From Lo. Alarm
Sensor Alarm-Diff From Hi. Alarm
ALARM
Alarm Test At Time: (hh:mm)
Day Of Alarm Test:
Alarm Test Duration (sec)
AUGER OVERTIME ALARM
30
32.0
122.0
1.0
1.0
12:00
DAILY
0
NOTE: See Fail Safe Setting.
• Global Alarm Delay (sec): Alarms without a separate alarm delay, use this global delay
before signaling the alarm.
• Alarm Reminder (min., 0-Disable): Amount of time before a reminder is sent if the situation
has not yet been corrected.
Sensor Alarm
• Sensor Low Temperature Range: Sets the minimum reading a sensor can have to be
considered a valid sensor reading. Sensor readings below this are rejected. This generates a
sensor out of range alarm. This does not apply to the special Circuit Breaker Sensor or Outside
Temperature Sensor.
• Sensor High Temperature Range: Sets the maximum reading a sensor may have to be
• Sensor Alarm-Differential from Low Alarm: Individual sensor (or zone) alarm if any active
• Sensor Alarm-Differential from High Alarm: Individual active growth area sensors alarm if
• Alarm Test at Time: Schedule the alarm test time.
• Day of Alarm Test: Choose Daily or a particular day of the week for the scheduled alarm.
• Alarm Test Duration (sec): Choose the alarm test duration.
considered a valid sensor reading. Sensor readings above this reading are rejected. This
generates a sensor out of range alarm. This does not apply to the special Circuit Breaker
Sensor or Outside Temperature Sensor.
sensor reads this much or more below the Control > Temperature Curve >Low Alarm Temperature (page 15).
they read this much or more above the Control > Temperature Curve >Low Alarm Temperature
(page 15).
• Auger Overtime Delay: Set the maximum auger run time for your cross fill system. If you have
a monitor connected to the digital inputs programmed as Feeder-1 Overtime or Feeder-2
Overtime the Farm Premium sends an alarm after this delay.
• Feeder Off During Overtime: Choose whether to shut the feed systems off after a feeder
overtime alarm. Options:
o No: All augers and feeders remain on.
o All: Al augers and feeders shut down.
o Related: Only the specific auger from which the alarm originated and it feeders shut
down.
NOTE: If you choose
All
or
Related
, the feed system turns off and does not resume until you select
Reset Alarm in the Management Menu.
Feeder Overtime Alarm
• Feeder Overtime Delay: Set the maximum feeder run time for your cross fill system. If you have a
monitor connected to the digital inputs programmed as Feeder-1 Overtime or Feeder-2 Overtime the
sends an alarm after this delay.
• Feeder Off During Overtime: Choose whether to shut the feed systems off after a feeder overtime
alarm. Options:
• No: All augers and feeders remain on
• All: Al augers and feeders shut down.
• Related: Only the specific auger from which the alarm originated and it feeders shut down.
NOTE: This alarm functions in the Broiler mode only.
NOTE: Setting the Feeder Off During Overtime to All in either the Auger Overtime Alarm or the Feeder
Overtime Alarm shuts down the augers and feeders, regardless of the other alarm's setting.
Auger Empty Alarm
• Condition Detection Delay (sec.): Farm Premium sends an alarm when the current goes to the
level set in the following parameter after this delay.
• Below Nominal Current: Send an alarm when the nominal current drops to this level.
This alarm is operative only if 1) Current Sense Relays are installed and calibrated 2)
augers have been calibrated.
5.5.1 A
While viewing the Alarm Setting menu: Press
•Advanced Alarms: When selecting YES, the following additional alarms appear on the
ALARM SETTINGS screen (press MENU and then ENTER to reenter the screen):
.
Page 71
Water on Demand Alarms
• High/Low Pressure Diff (PSI): Sends an alarm when the difference between the current WOD
pressure and the defined pressure reaches these levels. 0 means that the alarm is disabled.
• Shutdown Pressure Diff (PSI): Shuts down the Water on Demand system when the pressure
reaches this level.
o Shutdown pressure must be equal to or higher than the High/Low Pressure Difference.
o However, to disable this alarm set it to 0 (zero), even if the High/Low Pressure is
above 0.
Feed Alarms
• Allow Feed Alarm From/To: Set a starting time from which the controller can send feed
shortage alarms.
• Low Feed Alarm Limit: Alarm if feed in Silo 1/2/3/4 is below this limit and time is between
From and To limits.
• Feed Alarm Limit (per hour): An alarm is generated if the feed flow is greater than this
amount. This alarm is activated when a problem arises inside the barn (as opposed to when
something happens to the feed scale).
Water Overflow Alarms
• According to Light Table: Change overflow alarm level when the lights are off.
• First Day: Overflow on the FIRST day applies to the first day operation. You can define a first
day at which to start increasing the overflow limit automatically. Days prior to the ‘First Day’ use
the First Day overflow limit; days following the first day have an incremental curve toward the
LAST DAY OVERFLOW parameter setting.
• Overflow on First Day: Number of gallons/liters per minute that generate an overflow alarm
on the first day.
• Last Day: Set the last day for the overflow curve.
• Overflow on Last Day: Set the maximum overflow limit (gallons/liters) for those days following
the last curve day.
• Overflow At Dark: Select overflow limit. When it is dark, controller checks every minute.
• Overflow Alarm Delay: Define delay time before the controller generates an overflow alarm.
• Extra Delay At Light Start: When the first light appears, define the amount of minutes before
the controller begins to operate according to the set Overflow for that day.
• Fogger Water Overflow: Define the water overflow for foggers (per minute).
Water Shortage Alarms
• Allow Water Shortage Alarm From/To: Set the period for which the controller generates
water shortage alarms.
• Shortage During Lights Off: Select whether water shortage alarm are disabled when all lights
are out.
• Quantity for Shortage: Minimum flow rate that must be maintained or a water shortage alarm
is generated.
• Shortage Alarm Delay: Minimum period of time that the shortage must extend through before
• Shortage Start Day: Define on what day shortage alarms begin. This parameter prevents false
alarms caused by young birds low water usage. Default: 0 (meaning alarms function normally
throughout the growth cycle).
Bird Scales Alarms
• Allow Bird Scale Alarms From/To: Set time frame for which the controller begins and ends
generating alarms for the bird scale.
Auxiliary Alarms
• Assign auxiliary alarms in the Install menu. Note that digital sensors, auxiliary alarm input with
related relay must always match their relay status.
• Related Relay For Aux Alarm 1/2/3/4: Relay for Auxiliary Alarm 1/2/3/4.
• AUX. Alarm Delay (sec): Separate from the Global Alarm Delay. If there is a dry contact, the
alarm is sent after the defined AUX. Alarm Delay.
Circuit Breaker Alarm
• Temperature for Circuit Breaker Alarm: Set circuit breaker alarm temperature.
CO2 Sensor Alarm
• CO2 High Level: Set the maximum allowed CO2 level above which an alarm is sent. The
alarm ceases when the CO2 drops below this level. If the user acknowledges the alarm, the
alarm messages temporarily cease (for the reminder time).
Humidity Sensor Alarm
• Humidity High Level Alarm: Set the maximum allowed humidity level above which an alarm is
sent. The alarm ceases when the humidity drops below this level. If the user acknowledges the
alarm, the alarm messages temporarily cease (for the reminder time).
Ammonia Alarm
•
Ammonia High Level: Set the ammonia level at which an alarm is sent.
Secondary Alarms
•
Enable Secondary Alarms: Refer to Prioritizing Alarms, page 72.
Potentiometer Alarm
5.5.2 P
RIORITIZING ALARMS
Farm Premium 5.16 enables prioritizing alarms. When enabled:
•
ventilation-related alarms are defined as critical. The main alarm relay will transmit these
alarms to the device wired to the relay (for example, a dialer).
•
non-ventilation alarms are defined as non-critical. A secondary relay will transmit alarms to
another device (for example, an ELS).
• SIREN ONLY: Resets only the siren, alarms remain
• YES: Resets alarms
Selecting YES:
• Clears the alarm relay for all current alarms. The alarms may remain valid, but the unit does
not register new alarms. If a new alarm occurs, or an existing alarm clears and reoccurs, the
alarm relay signals again (after any appropriate delay).
• Restores normal operation after an emergency pressure or feed overrun incident. If the
controller experiences a high-pressure alarm for too long, it enters emergency pressure
operation by opening all known air sources. Curtains open to preset amounts as set in Control
| Static Pressure. If you select SIREN ONLY, the alarm relay returns to the no alarm condition,
but the emergency pressure status continues.
• Restores normal operation after a feed overrun situation that calls for turning off the feeding
system. If the feed monitor senses the cross auger runs too long, it trips a feed overrun alarm
and optionally turns off the feed system. If you select SIREN ONLY, the alarm relay returns to
the no alarm condition, but the feed overrun status continues.
5.7 Fail Safe Setting
When there is a problem such as extremely high air temperature, the Fail-Safe function immediately
activates a backup system (for example the Farm Back Up-27) to ensure that adequate ventilation
continues.
The owner can set new passwords for himself, all users and visitor. The owner cannot see user passwords
once entered or changed by the users. The users can access the controller and make changes to all
controller settings and their own password. A user can only see and change the user's own password.
The visitor can access the controller, but cannot make changes. Each time someone accesses the
controller with a password, an event is recorded in the History| Table of Events.
NOTE: If your controller uses passwords, the controller also requires a password entry to
acknowledge switch position changes. If the switch change is not acknowledged the controller
signals an alarm.
5.9 Relay Current
NOTE: The Relay Current feature supports
This menu configures the relay current sense parameters. You can configure:
• the minimum and maximum amperage flowing to the relays
single phase electricity
only.
• the relay current alarm
• voltage type
NOTE: Configuring the amperage is not required. The Farm Premium controller automatically
NOTE: Calibrate the relay before configuring these parameters. Refer to Current Sense Relay
FARM THERMO-5 / TEMPERATURE CURVE
Day
Temp.
Stage 1
HEAT
Stage 2
HEAT
Stage 3
COOL
Stage 4
COOL
Stage 5
COOL
2
31.0
29.0
26.0
33.0
35.0
37.0 5 33.0
31.0
28.0
35.0
37.0
39.0 7 35.0
33.0
30.0
37.0
39.0
41.0
10
37.0
35.0
32.0
39.0
41.0
43.0
FARM THERMO-5 STAGE DIFF
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
-2.0
-5.0
2.0
4.0
6.0
Calibration, page 103. Relays that are not calibrated (or if the relay is not a Current Sense
relay) do not display amperage readings (see relays 37 and 38 in the above figure).
To configure the relay current:
1. Using the arrow buttons, select a minimum or maximum amperage setting.
2. Configure the parameter as required.
NOTE: The minimum amperage must be greater than the default minimum and the maximum
amperage must be less than the default maximum. For example, relay 35’s amperage must be
more than 2.3 and less than 5.0 amps.
The Nom amperage is the parameter set when calibrating the relay (refer to page 103).
3. Configure the alarm:
o No: Alarms are not sent in the event of low or high current
o Yes: Alarms are sent in the event of low or high current
o No at zero: The controller sends an alarm if the current is low or high, but not if power is
cut off entirely.
4. Configure the voltage: Select 110 or 220 volts.
NOTE: All relays’ minimum/maximum current settings per equipment type must be within 30% (±) of
the nominal value. However, the augers minimum can go down to 0.0 amperes.
5.10 Farm Thermo-5 / Temperature Curve
Munters Farm Thermo-5 is a five stage digital thermostat that works in conjunction with Farm Premium
Controllers or as a stand-alone unit. When wired to the Farm Premium, you can use the Farm Premium to
set the Farm Thermo-5's stage activation temperatures (which is easier than setting the temperatures on the
Farm Thermo-5 screen). The stage activation temperature determines when cooling and heating
operations take place. Farm Thermo-5 supports a 10 point temperature curve.
Wire the Farm Premium communication card to the Farm Thermo-5's communication card.
Refer to the Farm Thermo-5 manual for details.
1. In Install > Communication, define the expansion device as Dig. Thermostat.
2. In Management > Farm Thermo-5 / Temp. Curve, define the parameters (up to a 10 point
curve).
o
Day: The growth day
o
Temp.: The target temperature for that day.
o
Stage 1 – 5: The temperatures at which heating or cooling starts (read only)
Farm Thermo-5 Stage Difference: The differences from the target temperature at which
heating or cooling starts at each stage (read only; set these numbers in the Help).
Farm Premium automatically calculates and displays the stage activation temperatures.
CAUTION
Verify that the Farm Thermo-5's growth day and the controller's growth day are the same!
Days set differently means that the temperature curves will be asynchronous.
3. In Farm Thermo-5 / Temperature Curve> Set Definitions, define the parameters as
required.
Notes:
o
Farm Premium does not store these temperatures; Farm Thermo-5 does. If you connect the
Farm Premium to a different Farm Thermo-5 unit, you must re-enter the temperature curve.
o
If you previously defined the temperature curve in the Farm Thermo-5, Farm Premium
retrieves the data and you can edit the data in this screen.
o
When connecting the RDT-5 to a Farm Premium Controller:
If a Farm Premium Extension box is currently is currently connected to the Farm
Premium controller, a message appears in the Message box when you disconnect
the Extension box. However, no alarm is sent out.
After configuring the Farm Thermo-5, disconnect the unit from the Farm Premium
and reconnect the Extension box. If the Extension box is not reconnected, Farm
Premium sends out alarms.
5.10.1 F
ARM THERMO-5 / TEMPERATURE CURVE | SET DEFINITIONS
While viewing the Farm Thermo-5 / Temperature Curve menu: Press HELP, select SET, and press
ENTER.
•
Define the parameters as required:
o
Stage 1 – 5 Diff: Enter the difference from the target temperature that activates a heater
or cooler for each stage. These numbers appear on the Farm Thermo-5 / Temperature
Curve screen.
o
Stage 1 – 5 Type: Select Heat or Cool. Each Farm Thermo-5 relay serves as a heater or
cooler relay. This parameter enables displaying the relay definition on the screen.
CAUTION
Selecting Heat or Cool in this screen does not define the relay; it only displays the relay
type. Actual relay definition is done in the Farm Thermo-5 unit, by placing a jumper on
certain pins. Meaning: if a relay is defined in this screen as a heater, but the jumper
placement defines the relay as a cooler, the relay is a cooler. Refer to the Farm Thermo-5
manual for details.
A loading truck will come to fill the bin or silo. Define the Filling Detection Weight to stop the augers
from operating during a loading event (Default: 300 Kg). Next, a Minimum Filling Weight needs to be
defined in order to have the filling event recorded in the Feed Inventory (Default: 2000 Kg). Once the
loading of the feed is finished, the timer begins to count down for the augers to resume normal operation
(Resume Time, Default: 5 minutes) and for the filling event to be recorded as completed.
6.5 Bird Curve
This screen displays data according to growth day for broilers, turkeys, or breeders, previously set in
General Settings.
NOTE: Only Broilers/ Layers Mode support this function.
7
14
21
28
35
42
0.31
0.66
1.26
2.07
3.15
4.45
0.35
0.70
1.54
2.73
4.27
6.15
Edit the growth days and weights for the bird curves to fit individual preference.
6.5.1 B
IRD CURVE HELP | SET DEFINITIONS
While viewing the
Bird Curve
menu: Press
HELP
, select
SET
and press
ENTER.
• Bird Curve Offset: Enter the factor used to adjust the weight curve. This amount is added to the
“Now” field. Range: 0.0 – 10.0 Kg/Lb.
6.6 History
The scale history shows bird weight statistics. You can review daily data for each scale, or separately. The
unit records up to two-bird scale data; if you have more than one scale-1 or one scale-2, their data is
combined.
NOTE: Only Broiler/Layers Mode supports this function
• If you selected SEXED weighing, the history includes average data for the combined scales,
and on the next screens separate data for each scale.
• If you select MIXED weighing, the history includes average data for all birds, and separate
male and female data for Scale 1 and for Scale 2.
o Use the arrow keys to scroll to the separated scale data, or up and down for data that is
off screen.
o The average and the number of weights are the usual definition. The Standard Deviation
is the usual biased estimator (see a suitable textbook on statistical measurements). The
Uniformity is the industry standard 10% uniformity (number of birds per 100 within 10%
of the average weight), and the Coefficient of Variation or C.V. is the normalized
standard deviation (standard deviation divided by average times 100 %.)
6.7 Feed Conversion
This screen displays the amount of feed converted into the bird’s weight.
NOTE: Only Broiler/Layers Mode supports this function.
The temperature history menu stores minimum, average and maximum temperatures by growth day. The
average is weighted, so if most of the day has been warm the average is closer to the maximum than the
minimum.
7.2 Humidity
The humidity history menu stores minimum, average and maximum inside humidity by growth day. The
average is weighted, so if most of the day has been humid the average is closer to the maximum than the
minimum.
NOTE: If two humidity sensors are installed, this screen displays their average. The History View
display shows reading of both sensors only if they have been selected for logging.
7.3 CO2
The CO2 history menu stores minimum, average and maximum inside CO2 levels by growth day. The
average is weighed, therefore if most of the day has been high CO2 levels the average is closer to the
maximum than the minimum.
7.4 Water
The water menu records daily water consumption and shows the daily differential change from the
previous day in percent. You must have the water monitor digital inputs connected. You can monitor up to
two drinking water meters, total drinking water, total water, cool pad, fogger, and cool pad flush
WATER
Day
Water P.bird
Water-1
Water-2
1
0.0 (%)
0.0 (%)
0.0 (%)
WATER
Feed P.Bird
Daily
Feed-1
Daily
Feed-2
Daily 1 0.0 (%)
0.0 (%)
0.0 (%)
consumption.
As an option, you can monitor the water per bird.
1. Go to History > Water > Help.
2. Enable Display History Per Bird.
The screen displays the amount and the percentage change.
7.5 Feed
The feed menu records daily feed consumption and shows the daily differential change from the previous
day in percent for silos or fill systems.
You must install a feed silo weighing system to use the feed system or to monitor the auger
system.
The feed data can be based on one of the following inputs. If more than one input is installed, priority is
according to the order of the bulleted list.
• Silo: If silos (load cells) are installed, feed consumption data of each bin is based on the silo
weight.
• Current Sense: If Current Sense Relays for Augers are installed and calibrated (refer to Current
Sense Relay Calibration, page 103), feed consumption data of each auger is based on the
current sense, calculation method settings, and actual auger run-time. The run-time is calculated
based on the measured current, when the actual current is higher than the nominal value (refer
to Relay Current, page 74).
• Feed Count: If a feed count sensor is installed feed consumption for each feed count input is
based on the feed count method settings (refer to Digital Sensors, page 110).
As an option, you can monitor the feed per bird.
1. Go to History > Water > Help.
2. Enable Display History Per Bird.
Day
7.6 Mortality
The mortality history menu maintains daily summaries of mortality, cull, and total dead. It also shows the
percentage dead and gives an updated count of bird inventory. The history is maintained separately for
male, female and total. Use the left and right arrow keys to switch to the next screen.
The Farm Premium maintains daily total run times of each heater. The table fills several screens; to view
the off screen data, use the arrow keys to scroll. The data is in hours:minutes format.
7.8 Radiant Heaters
The Farm Premium maintains daily total run times of each radiant heater, including separate data for low
level and high-level heaters. The table fills several screens; to view the off screen data, use the arrow keys
to scroll. The data is in hours:minutes format.
7.9 Alarms
The alarm history records the growth day and time of each alarm. Alarms that are currently active show
up as flashing on the screen. Alarm history is not reset when using Management, Growth Date & Flock > New Flock. The last 250 alarms are saved, and as the table is filled, new alarms push out the older
alarms.
7.10 Table of Events
The Farm Premium records significant events with growth day and time stamp. The Table of Events is
1000 events long and is not reset when using Management, Growth Date & Flock > New Flock. New
events push out the older events.
Typical events recorded are switch changes, entry into tunnel mode, natural or minimum ventilation, alarm
resets, ventilation mode changes and more. The Table of Events is an excellent tool to determine whether
your controller is going in and out of tunnel due to marginal settings as well as finding and identifying
problems.
NOTE: Go to the Table 4, page 118 to view all the available events.
7.11 History View
The History View menu has detailed history on a variety of sensors and data. Go to Help > Set under
History View to select the particular data to collect.
1. In Install > Setup> History Resolution, set the frequency of your data collection. Factory default
collects one-hour data on a selection from the choices below.
2. Under Help | Graph you can select a variety of graphs of the detailed history.
3. In the HISTORY VIEW | HELP | SET menu, set the desired choice by using the '+/-'.
The options are as follows:
• Target Temp.
• House Temperature: Minimum, Average and Maximum
• Temp – 1-9: Minimum, Average and Maximum
• Attic Sensor: Minimum, Average and Maximum
• Outside Temperature: Minimum, Average and Maximum
The Test Menu screen shows internal information in order to verify that the Farm Premium is operating
correctly. Moreover, it can help find broken wires or any other problems related to it.
• Switches & Relays, page 89
• Alarm, page 90
• Analog Sensors, page 90
• Digital Sensors, page 91
• Analog Output, page 91
• Static Pressure, page 92
• Communication, page 92
• Hardware Checklist, page 93
• Emergency Status, page 93
1. SWITCHES & RELAYS
2. ALARM
3. ANALOG SENSORS
4. DIGITAL SENSORS
5. ANALOG OUTPUT
6. STATIC PRESSURE
7. COMMUNICATION
8. HARDWARE CHECKLIST
9. EMERGENCY STATUS
8.1 Switches & Relays
This menu displays a screen of identified switches and relays installed in the controller. Use this option to
determine faulty hardware.
The Farm Premium supports a maximum of:
• 20 relays: Farm Premium-P
• 30 relays: Farm Premium-P XL
• 40 relays: Farm Premium/ Farm Premium XL
• 50 relays: Farm Premium XL 50
• Up to 40 extra relays using a Farm Premium Extension
The following screen illustrates a system having 80 switches and relays.
Note that the alarm relay is powered for the ‘NO ALARM’ condition to provide automatic Power Fail
Alarm in case of power failure to the Farm Premium. That is, the Normally Open side is closed during NO
ALARM.
Relay Alarm: ON
Press ENTER For On/Off
8.3 Analog Sensors
Observe the converter readings for analog sensors with this menu.
Define sensors in Installation > Analogue Sensors.
The readings can vary from 0 to 1023. The values displayed in the 'Value' column indicate that the
analog sensor is operating or not according to the following:
• If a very large value is shown (such as a four digit number) or a small value is shown (such as a
one digit number): sensor is not connected.
• If the unit displays a 3-digit number, usually beginning with the digit '4: sensor is operating.
8.4 Digital Sensors
This screen displays the digital sensors states.
Define sensors in Installation > Digital Sensors.
A ‘1’ implies a shorted input, a ‘0’ an open input. The digital sensors operate with dry contact inputs such
as the Arad Water Meter, or micro-switches.
You can apply a short/open input to each channel; the response is then displayed.
NOTE: The water meter quantities appear on the main screen or on Hot Screen 0.
8.5 Analog Output
This screen tests light dimmers, variable speed fans, and variable heaters.
1. Scroll to the required output.
2. Enter the test voltage and verify that the device is operating.
Define sensors in Installation > Analogue Output.
Observe the converter readings for the static pressure sensor. The nominal ‘zero’ pressure reading is
130. Remove the air hoses from the brass connectors on the left side outside of the controller to check
this reading.
8.7 Communication
This menu facilitates testing on communication networks. A multiplexer in loop back mode is used to test
the communication. The Farm Premium follows its' own communication to check for failed hardware.
Follow the instructions displayed on the screen.
must short RX with TX on
the non-priority channel of
the multiplexer
Check the installed hardware that has been identified by the Plug and Play system. The system detects all
cards except communication. The standard optional communication card provides lightning protection,
and does not have local computerized intelligence to identify itself to the system. Note that if a card is
missing, turn the power OFF and then ON for a card rescan.
Digital Input
Analog Output
Scales
Static Pressure
Alarm
N.C. Emergency Card
N.O. Switch Card
N.C. Switch Card
1
7
0
0
8.9 Emergency Status
This screen displays the emergency cards' status (if installed).
Emergency Card 2 Temp.
Set Temperature
Battery 1 Level
Battery 2 Level
Min. Vent Cycle On (sec)
The Service Menu items calibrate various Farm Premium functions.
• Temperature Calibration, page 94
• Humidity Calibration, page 95
• CO2 Sensor, page 96
• Static Pressure Calibration, page 96
• Light Sensor Calibration, page 97
• Feed Calibration, page 98
• Water Calibration, page 98
• Ventilation Potentiometer Calibration, page 98
• Nipple Flushing, page 99
• Feeders & Drinkers, page 100
• Save Settings, page 101
• Load Settings, page 102
• Current Sense Relay Calibration, page 103
• Wind Direction Calibration, page 104
• WOD Calibration, page 104
1. TEMP. CALIBRATION
2. HUMIDITY CALIBRATION
3. CO2 CALIBRATION
4. STATIC PRESSURE CAL.
5. LIGHT SENSOR CALIBRATION
6. FEED CALIRATION
7. WATER CALIBRATION
8. POTENTIOMETER CALIBRATION
9. NIPPLE FLUSING
10. FEEDERS & DRINKERS
11. SAVE SETTINGS
12. LOAD SETTINGS
13. RELAY CURRENT CALIB.
14. WIND DIRECTION CALBIRATION
15. W.O.D/ CALIBRATION
1. TEMP. CALIBRATION
2. HUMIDITY CALIBRATION
3. CO2 CALIBRATION
4. STATIC PRESSURE CAL.
5. FEED CALIRATION
6. WATER CALIBRATION
7. POTENTIOMETER CALIBRATION
8. SAVE SETTINGS
9. LOAD SETTINGS
10. RELAY CURRENT CALIB.
11. WIND DIRECTION CALBIRATION
12. W.O.D CALIBRATION
Figure 19: Poultry Service Screen Figure 20: Pigs Service Screen
9.1 Temperature Calibration
The Farm Premium temperature sensors are typically accurate to approximately 0.5º F within the range of
temperatures for poultry production. Calibrate them in this menu by adding/subtracting a constant
correction factor to each sensor. Adjust the sensor of your choice with the left/right arrow keys.
Calibrating against infrared or in air temperature sensors generally results in less accuracy than the basic
sensors have without calibration.
CAUTION Only calibrate the sensors if you have reason to believe that they are producing
inaccurate results.
To calibrate the sensor:
1. Obtain an accurate reference sensors and a pail of water at the approximate required
temperature.
2. Stir the reference sensor together with the Farm Premium sensor vigorously in the bucket of water.
Keep hands off the sensor itself, so that it responds accurately to the water temperature. Stirring is
necessary to preclude stratification within the bucket of water.
3. Call out the accurate reading to a second person standing at the Farm Premium. Walkie-talkie
radios may be a good idea.
4. The individual at the controller should double-check that you are calibrating the correct sensor.
You might warm/cool the sensor temporarily to see which sensor changes temperature
appropriately.
5. Once you determine the correct temperature and allow approximately one minute for
stabilization in the water, adjust the sensor reading at the controller.
6. Offset the factor using the left/right arrow keys.
• Refer to Temperature Curve, page 15.
9.2 Humidity Calibration
To calibrate the humidity level, obtain a suitable humidity test kit and use the procedures described there.
They are commonly available via the Internet.
CAUTION Only calibrate the sensors if you have reason to believe that they are producing
inaccurate results.
• Adjust the Farm Premium reading as needed using the left/right arrow keys.
To calibrate the CO2 level, obtain a suitable test kit and use the procedures described in the kit. Ensure
that the house is well ventilated, either naturally or using fans.
CAUTION Only calibrate the sensors if you have reason to believe that they are producing
inaccurate results.
• Ppm at 4 mA / 1 VDC: Parts per million for 4 mA or 1 VDC
• Ppm at 20 mA / 5 VDC: Parts per million for 20 mA or 5 VDC
• Factor (ppm): (-/+) ppm shift from the current reading
• CO2 (ppm): Current CO2 readings
• Adjust the Farm Premium reading as needed using the left/right arrow keys.
• Refer to CO2 Treatment, page 25.
9.4 Static Pressure Calibration
The Static Pressure should be 0 when there is no ventilation and the house is closed. When the controller
A/D counts is 100, this means that there is zero (0) static pressure.
CAUTION: The Static Pressure sensor is factory calibrated. Only calibrate the sensor if you have
reason to believe that they are producing inaccurate results.
NOTE: Run Farm Premium for a few hours so that the temperature in the box becomes stable and only
then calibrate.
CAUTION DO NOT blow the air into the hose to see of the pressure changes! The sensor is
sensitive and blowing air can cause irreparable damage.
To calibrate the Static Pressure Sensor:
1. Disconnect the air hoses.
2. Go to Service > Static Pressure Cal.
3. If the A/D count is 100 +/- 30 (70 to 130), press Enter.
4. If the A/D count is less than 70 or greater than 130:
a. Check for blocked air hoses or wind interference.
b. Adjust the zero pressure reading to approximately 100 by turning the calibration screw.
c. When the A/D count is within the permitted range, press Enter.
Page 97
STATIC PRESSURE CALIBRATION
A/D Counts:
110
Disconnect air hoses from the Farm
Premium to zero the pressure
Then Press ENTER to calibrate
STATIC PRESSURE CALIBRATION
A/D Counts:
110
GOOD CALIBRATION
Press MENU to exit
The static pressure sensor is located inside the controller in the upper left hand corner to the left of the
power supply.
• Refer to Static Pressure, page 31.
9.5 Light Sensor Calibration
NOTE: Broilers/Layers mode supports this feature.
Installing a light sensor enables turning off the lights when there is sufficient outside light.
To calibrate the light sensor:
1. Go to Install > Analog Sensors (page 109).
2. Define one sensor as a light sensor.
3. Go to Device > Light (page 49).
4. Press Help, highlight Set, and press Enter.
5. Scroll down to Light Sensor Active and set to Yes.
6. Place the sensor in the required location.
7. Go to Service > Light Sensor Calibration.
8. When the outside light is bright enough, press Enter
Farm Premium can use silo scales or less expensive digital monitoring devices to keep track of your feed.
This menu calibrates the digital monitoring devices.
1. Select the feed counting method. Your digital monitoring device may generate a dry contact
pulse for each quantity of feed, or it may simply indicate that the feed is running.
2. Enter the quantity of feed per pulse in case you use a dry contact pulse. Otherwise, enter the
amount of feed delivered per minute of auger operation.
3. Select one of the following:
o Pulse: Weight per pulse
o Time: Weight per minute
o Current Sense: Motor run time when the auger contains feed
4. Enter quantity (weight per minute or per pulse).
Method Pulse: Weight per Pulse
Method Time: Weight per Minute
Method Current: Weight per Minute
9.7 Water Calibration
Farm Premium supports up to four dry contact pulse output water meters. Enter the quantity of water per
pulse for your water meters.
9.8 Ventilation Potentiometer Calibration
Use this screen to calibrate the ventilation potentiometer control. Potentiometer calibration is required
before ventilation can be controlled via a potentiometer.
Before calibrating the potentiometers:
o Disable the static pressure unit in Install > Setup (page 106).
o Define at least one relay as vent/inlet/tunnel in Install > Relay Outlet (page 107).
o Define at least one analog sensor as a potentiometer in Install > Analog Sensor
NIPPLE FLUSHING
Start
Time
On Time
(min)
06:00
2
AUTO
15:40
1
AUTO
00:00
0
AUTO
00:00
0
AUTO
00:00
0
AUTO
FLUSH ORDER
Line: 1 2 3 4
--
--
--
Order:
1 2 3 4 --
--
--
FLUSHING DAYS
Day:
Sun
Mon
TUE
WED
THU
FRI
SAT
Flush:
▪√√▪▪▪▪
(page 109).
1. Select a potentiometer number.
2. Press Enter.
The device relay closes and then opens. As this takes place, the numbers in the Close, Current, and
Open columns change. After a few minutes, the process completes and a "Good Calibration"
message appears.
NOTE: After potentiometer calibration, the times displayed in the Vent/Curtain Setup screen change.
Refer to Vent & Curtain Levels, page 41 for details.
9.9 Nipple Flushing
NOTE: Broiler/Layer Mode supports this function.
To use this selection, program the water solenoids using the following relay codes:
• 111 Water Main: The control's supplementary for the usual water line
• 112 Water Bypass: The control's supplementary to bypass the water pressure regulator
• 113 Water line 1 through 122 Water line 10: Individual water line supplementary to select
the line to flush
During normal operation, only relay 111 water main is active. During flushing relay, code 112 is active
together with each of the individual water line relays in turn.
• Configure up to 20 flush times.
• Set start time/duration of water flushing (water lines as defined by relay layout)