Munters ComDry Supplemental Operating Instructions

Originalinstructions
Supplement
ComDryControlSystem
Operationinstructions
Validforunitsfromserialno.
20001
MEN-CDCS-A1808©MuntersEuropeAB2018
Tableofcontents
Tableofcontents...........................ii
1Operation....................................1
1.1Safety..................................
1.2Introduction............................
1.2.1Humiditycontrol................
1.2.2Fanmodes.....................
1.3Controlpaneloverview...............
1.4Initiationandstart.....................
1.4.1Bootthecontrolsystem........
1.4.2Startthedehumidier..........
1.5Stopthedehumidier.................
1.6Quickstop..............................
1.7Automaticstartafterpowerfailure....
1.8Navigatethemenus...................
1.9Accesslevels..........................
1.10Accessthecontrolsystem............
1.11Changethesystemsettings..........
1.12Resetanalarm........................
1.13Resetthecounters....................
1.14Restorethedefaultsettings...........
1.15Serviceintervalalarm.................
1
1
1
1
2
3
3
3
4
4
4
5
5
6
7
7
8
2Menusandparameters....................10
2.1Humidity...............................
2.1.1Internalcontrollingsensor.....
2.1.2Externalcontrollingsensor....
2.2Runtime...............................
2.3Power..................................
2.4Temperature...........................
2.5Functions..............................
2.5.1Processfanmode..............
2.5.2Humiditycontrolandunits.....
2.5.3Displayinformation............
2.6Alarm...................................
2.7Min,maxanddefaultvalues..........
2.7.1Humidity........................
2.7.2Servicetime....................
2.7.3Functions.......................
8
9
10
11
11
11
12
13
14
14
14
15
16
17
17
17
17
iiTableofcontentsMEN-CDCS-A1808
ComDryControlSystem
1Operation
1.1Safety
W
ARNING!
W W
ARNING! ARNING!
Theunitmustnotbesplashedwithorimmersedinwater.
Theunitcanrestartautomaticallywithoutwarningfollowingapowerfailure.
Donotoperatetheunitifthepowercableorplugisdamaged,riskofelectricalshock.
Donotpulltheplugwithwethands,riskofelectricalshock.
Donotinsertngersoranyobjectsintotheairvents,rotatingfansareinside.
Donotcovertheunitasthatcanblockairintakeoroutletandcauseare.
Iftheunithasoverturned,cutthepowerimmediately.
1.2Introduction
1.2.1Humiditycontrol
TheComDrydehumidierisequippedwithasophisticatedmicroprocessorbasedcontrolsystem.This,in combinationwiththebuilt-inhumidity/temperaturesensorintheprocessairinlet,makesitpossibletoset boththecontrolandpresentationofthehumiditytoeitherrelativehumidity(RH%),dewpoint(Dp°C)or absolutehumidity(Xgr/kg).Thecontrolsystemadditionallychecksthetemperaturesbeforeandafterthe heater,aswellasinthewetairaftertherotor.Ahighsafetylevelisobtainedbyvarioustemperaturesensors. Toohightemperaturesgivesareductionoftheheaterpower,whileexcessivetemperatureswillmakethe systemissueanalarmandshutthedehumidierdowninacontrolledway .Forfurtherexplanation,see
2.1,Humidityand2.5,Functions.
NOTE!Thedehumidieralwaysoperatesinautomaticmode(moisturebasedoperation).Asdefaultitwilluse
thebuilt-inhumidity/temperaturesensor,asoptionanexternalsensor.
1.2.2Fanmodes
Dependingontheapplication,thedehumidiercanberunindifferentprocessfanmodes:Fan“ON” (continuous),“INT”(INTermittent)or“DEM”(onDEMand).
Forfurtherexplanation,see2.5,Functions.
MEN-CDCS-A1808Operation1
1.3Controlpaneloverview
Menuindicators1-6
1.Humiditymenu4.TemperaturemenuA.Alarmindicator
ComDryControlSystem
2.Timemenu5.FunctionsmenuB.Operationindicator
3.Powermenu6.AlarmmenuC.On/Offbutton
MenubuttonFunction
Table1.1Menubuttonfunctions
Up/Rightbutton
Enter/Conrmationbutton
Down/Leftbutton
2OperationMEN-CDCS-A1808
ComDryControlSystem
1.4Initiationandstart
1.4.1Bootthecontrolsystem
Connectthedehumidiertomains.Result:ThecontrolsystemwillinitiatebyashingallLEDsforafew seconds,andthedisplayrstshowstheComDrymachinetype,thenthesetfrequency,e.g.[50Hz]and nallythesoftwareversionnumber,e.g.[VER:1.00]andthecurrenthumiditylevel,e.g.[*RH146%].
NOTE!Thebootsequencetakesabout10seconds.Letthecontrolsystemnishthebootingbeforeattempting
tostartthedehumidier.
1.4.2Startthedehumidier
Followthesestepstostartthedehumidier:
StepActionIllustration
1PresstheOn/Offbutton(C)oncetostartthedehumidier.
Result:IfthemeasuredhumidityislowerthantheSetV alue,the greenoperatingindicator(B)willstarttoashinalongon/shortoff sequence.Dependingonfanmodesetting,theprocessfanwillrunor not.Theunitisnowinstand-bymode.
2Thedehumidierstartstodehumidifywhenthemeasuredhumidityis
equaltoorgreaterthantheSetValue,andtheoperatingindicator(B) willshifttocontinuouslylit.
MEN-CDCS-A1808Operation3
1.5Stopthedehumidier
CA
UTION!
CA CA
UTION! UTION!
Donotunplugthedehumidierwhileitiscoolingdown.
Thefanstopsandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandothercomponents
closetoit.
Followthesestepstostopthedehumidier:
ComDryControlSystem
Step
Action
1
PressOn/Offoncetostopthedehumidier.
2
Theunitcontinuestorunforawhileinordertocooldownandthen stops.
Result/Illustration
Thegreenoperatingindicatorstarts ashingwithequallylongandshorton andoffperiods.
1.6Quickstop
CA
UTION!
CA CA
UTION! UTION!
Onlyquickstopthedehumidierincaseofanemergency.
Thefanstopsandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandothercomponents
closetoit.
Incaseofemergency,stopthedehumidierbypullingthemainsplugor,ifitispermanentlyconnectedto mains,byusingtheexternalcircuitbreaker.
1.7Automaticstartafterpowerfailure
Ifthedehumidierisswitchedonitwillreverttooperationafterapowerfailure,regardlessofifitwas runningorinstand-by.
4OperationMEN-CDCS-A1808
ComDryControlSystem
1.8Navigatethemenus
Thethreebuttons,andonthecontrolpanelmakeitpossibletonavigatethemenus.
Followthesestepstonavigatethemenus:
Step
Action
1
Toselectamenu,pressor.untiltheselectedmenu appears.
2
3
4
Toenterthemenu,press
Use
Leavethemenubyusing
Press
ortoscrollthroughthemenu.
.
.
andgoto[EXIT].
NOTE!Allmenulistsarecircular.Attheendofeachmenuyouwillnd
thereistopress
onetimeafterhavingenteredamenu.
1.9Accesslevels
Thefollowingaccesslevelsandactionsareavailableinthecontrolsystem:
AccesslevelAvailableactions
ACCESS
ACCESS*
ACCESS**
Viewallprocessingdata
Viewallprocessingdata
Adjustrelevantparameters(setvalueRH,reset
horkWhetc.)
Result/Illustration
Theselectedmenuindicatorislit.
Themenuindicatorstartsashing.
Themenuindicatorstopsashing.
[
EXIT
]
.Thequickestwayofnavigating
Comment
Level2isfordedicatedpersonnelonly
(qualiedpersonnelorMuntersService)
Ifyouhaveaccidentallyreachedthislevelthe
codeis0000forreturningtolevel1.
MEN-CDCS-A1808Operation5
ComDryControlSystem
1.10Accessthecontrolsystem
Thecontrolsystemsettingsandcountersareprotectedagainstunauthorizedchangeusingtwoaccesslevels. Seealsosection1.9,Accesslevels.
Followthesestepstoaccessthesystem:
Step
Action
1
Tochangethesettingsyoumusthave“one-star”access.Gotomenu Functions,seesection1.8,Navigatethemenus.
2
Scrollupto[ACCESS]using
3
Pressandhold
4
Ahigher,PIN-codeprotected,“two-star”accesslevelexists.Ifan attempttogethigheraccessismadewiththemachineswitchedoff, thedisplaywillchangeto[0000].
Press
fourtimesuntil[ACCESS*]isvisibleagain.
until[ACCESS]changesto[ACCESS*].
.
Result/Illustration
Themenuindicatorisashing.
Thesystemisnowunlocked,and itispossibletomakenewsettings alternativelyresetthecounters.
NOTE!Thesystemwillreturntolockedmodeautomaticallyafterveminuteswithoutanyactivity .
NOTE!Thesystemalwaysstartsinlockedmodeafterpower-up,regardlessofaccesslevelpriortopowerloss.
Followthesestepstoforcethesystemintolockedmode:
Step
Action
1
Makesuretheunitisswitchedoff.
2
Gotomenu"Functions"
3
Navigateto[ACCESS*].Seegeneralinstructioninsection
1.8,Navigatethemenus.
4
StarttheunitbypressingOn/Off.
5
Pressandhold
until[ACCESS*]changesto[ACCESS].
Result/Illustration
Thegreenlightilluminates
Thesystemisnowlocked,anditisnot possibletomakenewsettingsortoreset thecounters.
6OperationMEN-CDCS-A1808
ComDryControlSystem
1.11Changethesystemsettings
Tochangesettingsyoumusthave“one-star”access,see1.10,Accessthecontrolsystem.
Followthesestepstochangethesystemsettings:
Step
Action
1
Navigatetotheparameteryouwanttochangebyusingor.
2
Press
3
Changethevaluewith
4
Conrmthenewsettingwith
.
and.
.
Result/Illustration
Thesettingstartstoash.
Thesettingstopstoash.
NOTE!Ifthenewsettingisnotconrmedwithin30seconds,thedisplaychangesbacktotheoldsetting.
NOTE!Read-onlyvaluesarenotchangeable.Theywillnotstarttoashif
level.T ondoutifaparameterischangeableorread-only ,seesection2,Menusandparameters.
ispressed,regardlessofaccess
1.12Resetanalarm
Followthesestepstoresetanalarm:
Step
Action
1
Writedownthealarmmessagebeforeresettingthealarm.The informationcanbehelpfulwhentroubleshooting.
2
Waituntilthedehumidierhasstopped.
Press
.
Result/Illustration
Thedisplaychangesto [RstNO]and[NO]isashing.
3
Toggle[NO]to[YES]bypressingeither
Conrmbypressing
or.
.
Whenthealarmhasbeenreset,the menusystemreturnstoitsstartposition.
NOTE!Ifthecauseofanalarmisstillpresent,thealarmcanreappearafterresetting,evenifthedehumidier
isstopped.
MEN-CDCS-A1808Operation7
1.13Resetthecounters
Toresetcountersyoumusthave“one-star”access,see1.10,Accessthecontrolsystem.
Followthesestepstoresetthecounters:
ComDryControlSystem
Step
Action
1
Navigatetothecounteryouwanttoreset.Seesection
1.8,Navigatethemenus.
2
Press
3
Toggle[NO]to[YES]bypressingeither
[
NOTE!If
RstNO
]/[
RstYES
seconds,thedisplayautomaticallychangesbacktothestored
countervalue.
4
Conrmtheresettingwith
NOTE!PressingENTERwhenthedisplayshows
again.
or.
]
isleftwithoutactionfor30
.
[
RstNO
Result/Illustration
Thedisplaychangesto [RstNO]and[NO]isashing.
Thecounterisreset.
]
willreturnthestoredcountervalueinthedisplay
1.14Restorethedefaultsettings
Torestorethefactorydefaultsettingsyoumusthave“one-star”access,see1.10,Accessthecontrolsystem.
Followthesestepstorestoreallthedefaultfactorysettings:
Step
Action
1
GototheFunctionsmenuandnavigatetoDefault.
2
Press
3
Toggle[NO]to[YES]bypressing
either
4
Conrmbypressing
or
Result/Illustration
Thedisplaychangesto[RstNO]and [NO]isashing.
.
Allvaluesrevertstofactorysettings.
8OperationMEN-CDCS-A1808
ComDryControlSystem
1.15Serviceintervalalarm
TheServiceinterval[T-xxxxh]canbesetbetween500and8.000hours.
Toresetcountersyoumusthave“one-star”access.Followthesestepstochangetheserviceinterval(seealso
1.11,Changethesystemsettings):
Step
1
2
2
3
Action
GototheTimemenu.
Navigateto"Serviceinterval"[T-xxxxh]
Adjustthe"Serviceinterval"[T-xxxxh]instepsof100hours
Resetthe"Timetoservice"counter[Sxxxxh].
Result/Illustration
NOTE!The"Timetoservice"countercanberesetatanytime.Whenthecounterisreset,itstartscountingupor
downagainfromthepre-setvalue[T-xxxxh]dependingonhowthe"Serviceinterval"hasbeenadjusted.
TheTimetoservicecounter[Sxxxxh]countsdowntozero.Whenitreacheszero,thesystemissuesa"soft alarm"thenexttimetheunitisswitchedon.Thealarmonlymakesthealarmmenusymbolash,notthe redalarmindicator,and[TIMEFORSERVICE]isshowninthedisplay.Thealarmwillnotmaketheunit stop.Theunitcanstillbeoperatedasnormalwiththealarmpresent.
Followthesestepstochecktheserviceparametersandstoptheservicealarm:
Step
1T oseeorcheckparameters,eitherresetthealarmbypressing
2T ostopthealarmcompletely ,navigatetothe"Timetoservice"
Action
andresetit,orleavetheAlarmmenuwith[EXIT].
counter[S0000]inthismenuandresetit.
Result/Illustration
NOTE!EvenifthealarmhasbeenresetintheAlarmmenu,itwillbere-issuedthenexttimetheunitisswitched
on.
SeetheUsermanualforpropermaintenanceaction.
MEN-CDCS-A1808Operation9
ComDryControlSystem
2Menusandparameters
Tosetthesystemparameters,see1.11,Changethesystemsettingsand1.13,Resetthecounters.Forlimitswhen settingparameters,see2.7,Min,maxanddefaultvalues.
2.1Humidity
Thedehumidierisalwaysoperatinginautomaticmode.Itwilldehumidifyuntilthedesiredhumiditylevel (SetValueminusHysteresisvalue)isreached.Thenthegreenoperatingindicatorwillstarttoashinalong onandshortoffsequence,indicatingthatthedehumidierisinstand-by.Itwillstarttodehumidifyagain whenthehumidityisequalto,orgreaterthantheSetValue.
Typeofhumiditycontrol(relativehumidity,dewpointorabsolutehumidity)andunitsystem(metricor imperial)governsthereadingsandsettingsinthismenu.See2.5,Functionsforreferenceandexplanation.
Displayview
DescriptionType
Internalsensorreading
(Externalsensorreading)
SetValueHumidityADJUSTABLEHIGHER/LOWER
Hysteresis
1
READONLYD1.../X1...
READONLYD2.../X2...
ADJUSTABLEHIGHER/LOWER
Settingoption
1)
Onlywhenexternalhumiditysensorsareconnected
Controllingsensor(ADJUSTABLE)
1
1
(*RH2)
,(*RH3)
10MenusandparametersMEN-CDCS-A1808
1
ComDryControlSystem
2.1.1Internalcontrollingsensor
Theinternalhumiditysensoristhecontrollingsensorasdefault.Thisisindicatedbya(*)beforethereading inthedisplay(*RH1…/*D1…/*X1…).
2.1.2Externalcontrollingsensor
Optionally,anexternalsensorcanbeconnected.ItwillautomaticallybedesignatedRH2/D2/X2)bythe system.Whenconnected,itispossibletochooseexternalsensorascontrol.Thedisplaywillthenshow (*RH2.../*D2.../*X2…).
Withanexternalsensorsetascontrolsensor,itispossibletodisconnectandreconnecttheexternalsensor withoutlosingthecontrolsetting,e.g.[*RH2…]whiletheunitisswitchedoff(butpowered).When switchedon,thesystemmakesveattempts(during20seconds)tocontacttheexternalcontrollingsensor. Ifthisfails,thesystemrevertstotheinternalRH1-sensor.Subsequentlyanyrenewedassignmentofthe externalsensorascontrolmustbecarriedoutmanually.
2.2Runtime
Runtimeisregisteredaslongastheprocessairfanisoperating.Itstopscountingwhentheunitisinstand bymodeorisswitchedoff.Thesystemhastworuntimecounters,oneresettabletripmeterandone non-resettabletotalruntimecounter.
Displayview
DescriptionType
Runtimetripmeter
Totalruntime(Displayjumps from“TOT AL”todisplayview andback).
Timetoservice
ServiceintervalADJUSTABLE
RESETTABLEY es/No
READONLY
RESETTABLEY es/No
Settingoption
Every100hours
MEN-CDCS-A1808Menusandparameters11
ComDryControlSystem
2.3Power
TheComDrydehumidierisequippedwithanintegrated,resettablekWhcounter.Theenergy consumptionisregisteredwhenthedehumidierisconnectedtomains,regardlessofbeingswitchedon,off orinstand-bymode.ThecountershowstheconsumptionaswholekW-hours. ItisalsopossibletomonitorrealtimePower(W),current(A)andvoltage(V)measurementsinthismenu.
NOTE!Resettingisalwaysperformedmanually .Unpluggingtheunit(orapowerfailure)willnotresetthekWh
counter.
DisplayviewDescriptionType
kWhcounter
RealtimePower
RealtimeCurrent/V oltageREADONL Y
RESETTABLEYes/No
READONLY
Settingoption
12MenusandparametersMEN-CDCS-A1808
ComDryControlSystem
2.4Temperature
Theairtemperatureismeasuredindifferentpositionsinthedehumidier.Allvaluesareread-only.
Ifexternalhumidity/temperaturesensorsareconnected,thesewillalsobefoundinthelist.Thereactivation inlettemperature(Ri)beforetheheaterandreactivationtemperature(Rt)aftertheheater,aswellasthewet airtemperature(Wt)andtheprocessairinlettemperature(T1)ismeasured.
ThetemperatureisshownindegreesCelsiusorFahrenheit,dependingonthesettingintheFunctionsmenu.
DisplayviewDescriptionT ype
Processairinlettemperature(internal sensor)
(Externalsensor)
Reactivationtemperature
Wetairtemperature
1
READONLY
READONLY
READONLY
READONLY
Settingoption
Reactivationinlettemperature
1
)Onlyifexternalsensorisconnected
MEN-CDCS-A1808Menusandparameters13
READONLY
ComDryControlSystem
2.5Functions
2.5.1Processfanmode
Therearethreeprocessfanmodes:
FanmodeDescription
[FanON]In[FanON]mode,thedehumidierwillruntheprocessfancontinuously,regardlessofthereisa
dehumidicationneedornot.Thisisthedefaultmode.
[FanINT]
(INTermittent)
[FanDEM](on
DEMand)
In[FanINT](INT ermittent)mode,thefanwillstopwhenthedesiredhumidity(SetValueminusHysteresis)
isreached.IfthehumidityreadingstaysbelowtheSetV alue,theprocessfanwillanyhowstartafter30
minutestoletthebuilt-insensormoreaccuratelysensetheconditionoftheincomingprocessair.The
fanwillrunforaminutetoproduceapropermeasurement.IfthehumidityisstillbelowtheSetV alue,
thefanwillstopagain.ThisisrepeateduntilthehumidityreachestheSetV alue,whichwillmakethe
dehumidicationstartagain.
In[FanDEM](onDEMand)mode,thefanwillstopwhenthedesiredhumidity(SetValueminus
Hysteresis)isreached.Itwillstartagainwhenthesensedhumidityisequalto,orgreaterthantheSet
Value.Thisgivesinpracticeacontrolwithgreaterhysteresisthan“FanINT”,dependingonthefollowing:
Whenthedehumidierhasreachedthedesiredhumiditylevel,itwillshifttostand-byandstoptheprocess
fan.Afterawhile,internalmachineheatwillincreasethetemperatureofthehumiditysensor .Thismakes
thesensorreadingevenlower ,i.e.thesystemfunctionsasiftherewasa“negativehysteresis”.Asa
result,agreaterhumidityloadwillbenecessarytomakethedehumidierstartcomparedwiththe“Fan
INT”mode.
2.5.2Humiditycontrolandunits
Itispossibletosetthecontrol/presentationofthehumiditytoeitherRelativehumidity(RH%),Dewpoint (Dp°C)orabsolutehumidity(Xgr/kg).
Dependingonunitsystemsetting,SIformetricorIPforImperial,thereadingswillbeshowninCelsiusand g/kg,orFahrenheitandgrain/lb.AllthesesettingsaremadeintheFunctionsmenu.
14MenusandparametersMEN-CDCS-A1808
ComDryControlSystem
2.5.3Displayinformation
DisplayviewDescriptionType
ProcessfanrunningmodesADJUSTABLEFanON,INT ,DEM
Metricorimperialunits
Humidity
Unitserialno
ADJUSTABLESI,IP
ADJUSTABLE
READONLY
Settingoption
RH,Dp,Absolutehumidity
IDno
ACCESSLevelADJUSTABLEACCESS*
Restoretodefaultsettings (onlypossiblewhen dehumidierisOFF).
MainsfrequencyADJUSTABLE
RESETTABLE
YesorNo
50or60Hz
MEN-CDCS-A1808Menusandparameters15
ComDryControlSystem
2.6Alarm
Shouldanoperationfaultoccur,theredalarmindicatorandthealarmmenuindicatorwillstarttoash.The causeofthealarmwillbeshowninthedisplayandthedehumidierwillstopafterithascooleddown.
Thiscantakeacoupleofminutes.
CA
UTION!
CA CA
UTION! UTION!
Donotunplugthedehumidierwhileitiscoolingdown–thereasonforthealarmcanbeoverheating.
DisplayviewDescriptionType
SourceofalarminfulltextRESETTABLE
Alarmstatus
READONLY
16MenusandparametersMEN-CDCS-A1808
ComDryControlSystem
2.7Min,maxanddefaultvalues
2.7.1Humidity
Thistableshowstheminimum,maximumanddefaulthumidityvalues:
Parameter
Max.95404099300
SV_(set
value)
HYS_
(hysteresis)
Default
Min.
Max.10101,01010
Default
Min.000,000
RH(%)Dp(°C)X(gr/kg)Dp(°F)X(grain/lb)
5097,34951
5
220,222
-300,5-202
Table2.1Minimum,maximumanddefaulthumidityvalues
2.7.2Servicetime
Thistableshowstheminimum,maximumanddefaultservicetimevalues:
Parameter
T—h(servicetime)
Defaultsetting
40008000500
Table2.2Time,min/maxanddefaultservicetimevalues
2.7.3Functions
Max.Min.
ThistableshowsthedefaultsettingsandsettingoptionsoftheFunctionsmenu:
Parameter
Fan
Unit
Humidity
DefaultsettingOptions
FanON
SI(metricunits)IP(imperialunits)
RH(%)
Table2.3DefaultsettingsandsettingoptionsoftheFunctionsmenu
FanINT ,FanDEM
Dp(°C/°F)
X(gr/kg)/(grain/lb)
MEN-CDCS-A1808Menusandparameters17