This manual for use and maintenance is an integral part of the apparatus together with the attached
technical documentation.
This document is destined for the user of the apparatus: it may not be reproduced in whole or in part,
committed to computer memory as a file or delivered to third parties without the prior authorization of
the assembler of the system.
Munters reserves the right to effect modifications to the apparatus in accordance with technical and
legal developments.
MANAGE MENU ---------------------------------------------------------------------------------------------------------------------------------- 50
5.1 Inventory
5.2 Feed Inventory
5.2.1 Feed Inventory Help | Set Definitions
5.3 Time & Date
5.4 Growth Day & Flock
5.5 Alarm Setting
5.5.1 Alarm Setting Help | Set Definitions
5.6 Alarm Reset
5.7 Password
6
SCALE MENU ----------------------------------------------------------------------------------------------------------------------------------------- 57
TEST MENU --------------------------------------------------------------------------------------------------------------------------------------------- 68
10 INSTALL MENU -------------------------------------------------------------------------------------------------------------------------------------- 79
Munters reserves the right to make alterations to specifications, quantities, dimensions etc. for production
or other reasons, subsequent to publication. The information contained herein has been prepared by
qualified experts within Munters. While we believe the information is accurate and complete, we make no
warranty or representation for any particular purposes. The information is offered in good faith and with
the understanding that any use of the units or accessories in breach of the directions and warnings in this
document is at the sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing an AC-2000 3G!
In order to realize the full benefit from this product it is important that it is installed, commissioned and
operated correctly. Before installation or using the controller, this manual should be studied carefully. It is
also recommended that it is kept safely for future reference. The manual is intended as a reference for
installation, commissioning and day-to-day operation of the Munters Controllers.
1.3 Notes
Date of release: July 2010
Munters cannot guarantee to inform users about the changes or to distribute new manuals to them.
All rights reserved. No part of this manual may be reproduced in any manner whatsoever without the
expressed written permission of Munters. The contents of this manual are subject to change without notice.
This document describes the AC-2000 3G Precision Mode operation.
Computerized Electronic Controllers such as the AC-2000 3G advance the producer’s ability to grow
high quality eggs by accurately controlling the environment. Instead of struggling with individual
thermostats for heat zones and ventilation, AC-2000 3G brings them all together into one convenient
place with great accuracy. The AC-2000 3G optimizes and precisely applies your equipment and energy
sources to most benefit from the accuracy of your computer and sensors.
The AC-2000 3G coordinates your ventilation equipment in precise levels of ventilation to provide the
optimal fresh air balanced with heating costs. The light and feed clocks provide additional channels for
greater capability. Besides advanced Cooling Pad methods, you benefit from superior stir fan programs
to recover ceiling heat and other features. Precision Mode’s additional features enable you to improve
your profitability significantly.
AC-2000 3G provides a variety of management and history utilities. You can choose from simple
overviews, or fully detailed
by the minute
records of minimum, maximum and average temperatures for
each individual sensor. The unique Table of Events records the moment of every significant action taken
by the AC-2000 3G and, optionally, its operator.
3. Active: Displays the output relay list. The filled black boxes indicate active outputs. Controller
also informs the position of inlets and curtains, as well as the number of operating heaters or fans.
Go to Table 2: Output List (Active), page 104 to view all the available readings (ACTIVE).
The ACTIVE screen shows rectangular markers by the outputs. Filled rectangles indicate operating
outputs; empty rectangles indicate outputs that are off.
4. Status: Provides important general information such as the time and ventilation mode.
mp set to
cycle ends operation
Go to Table 1: Sensor Readings, page 104 to view all the available readings.
5. Messages: Displays important messages/alarms. The title bar displays the number of important
messages, and if there are several messages, they each appear in turn.
Define: Day: Sets growth day. You can program negative growth days up to -7 for
pre-warming. To enter a negative growth day, type the day number followed by
the +/- key.
TEMPERATURE CURVE
Non Brood Area Diff. From Heat
-3.0
6. In
Manage > Alarm Setting
7. If required set the:
o
o
o
o
o
Target: Set the desired temperature.
Heat: Set the temperature to stop heat.
Tunnel: Set the temperature for tunnel ventilation to begin.
Alarm Low & High: Set average temperature alarm limits. See Manage | Alarm
Settings for zone alarm settings.
, set the Sensor Alarms (page 52).
Temperature Curve Help | Set Definitions, page 10
Radiant Heaters Help | Set Definitions, page 11
Cycle Heaters | Set Definitions, page 12
Variable Heater Help | Set Definitions, page 13
Variable Floor Heater | Set Definitions, page 16
3.1.1 T
EMPERATURE CURVE HELP | SET DEFINITIONS
While viewing the Temperature Curve menu: Press HELP, select
SYSTEM PARAMETERS
Temperature Curve Offset
Set Temp. Change Reminder (Diff)
Target Temp. Band
Heater Temp. Band
Cool Down Factor (%)
Cool Down Fast Response (Deg.)
Min Vent Below Heat Temp By:
•
Temperature Curve Offset: Adjusts all temperature curves by this amount. You can use this to
temporarily adjust all temperatures up or down for special circumstances. The curve appears in
the Status Window, and you can use the ENTER and Up or ENTER and Down hot key
combinations to change the offset.
•
Set Temperature Change Reminder (Diff): Sets the change in set temperature that triggers a
reminder for you to set backup thermostats. Often producers forget to set backup thermostats as
their birds grow from baby chicks to market age, so the AC-2000 3G reminds you. When you
press Enter to acknowledge the reminder, the AC-2000 3G logs it in the Table of Events.
•
Target Temperature Band: The size of the target temperature zone. This "Happy Zone” is
between Target Temperature and (Target Temperature + Band).
•
Heater Temperature Band: Heaters turn on at ‘Band’ degrees below Heat, and turn off at the
Heat Temperature.
SET
, and press
0.0
3.0
1.5
1.0
15
3.0
ZONE
ENTER.
NOTE Heaters operate at minimum level only; however, Radiant Heaters can operate at any
temperature or level below Tunnel.
•
Cool Down Factor (%): Minimum percentage correction towards target during each increase
ventilation level delay. If average temperature does not improve by this amount, the AC-2000
3G increases ventilation by one level.
Cool Down Fast Response (Deg.): Set a limit to the maximum degrees per minute of cooling.
•
If Average Temperature drops more than this in one minute, the AC-2000 3G decreases
NOTE Avoid making this parameter too small or the normal temperature variation caused by timer fans
reduces the ventilation level.
•
Min Vent Below Heat Temp By: Tells controller to go directly to Min Level in some cases.
Select from the following choices:
o
None: Operate by the normal level decrease time delay rule.
o
Zone: Go directly to minimum level if any active temperature sensor reaches heat
temperature.
o
Avg.: Go directly to minimum level if the average temperature reaches heat temperature.
•
Non Brood Area Diff. From Heat: Set differential temperature for non-brood heaters. You
normally use this to set temperatures in unoccupied areas.
NOTE When set at -99° F the heaters are effectively disabled, since it will probably never go to 99º F
below the heater temperature. Putting this parameter at 0º sets the non-brood areas to the
heater temperature.
3.1.2 R
ADIANT HEATERS HELP | SET DEFINITIONS
To configure the radiant heaters:
1. In
Installation > Relay Layout
page 80).
2. Configure the following parameters:
o
Radiant Low – Differential from Heat Set: Set degree of difference from Heat for LOW
Radiant Heaters to begin working. This differential can be positive or negative. (default:
2.0)
o
Radiant High – Differential (Below Low Set): Set number of degrees below Radiant
Low Heaters for HIGH Radiant Heaters to begin working (default: 1.0). To ensure
proper heater ignition, Radiant High Heaters remain on for the Radiant Ignition Time
along with the Radiant Low Heaters.
o
Radiant Ignition Time (sec): Set number of seconds to power radiant ignition (default:
30).
SYSTEM PARAMETERS
0.0
3.0
1.5
1.0
15
3.0
ZONE
-3.0
0.0
1.0
30
Temperature Curve Offset
Set Temp. Change Reminder (Diff)
Target Temp. Band
Heater Temp. Band
Cool Down Factor (%)
Cool Down Fast Response (Deg.)
Min Vent Below Heat Temp By:
Non Brood Area Diff. From Heat
RADI ANT HE ATERS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
define at least one relay as a radiant heater (Relay Layout,
The Heater Temperature Band applies to radiant heaters as well. For example, if the Heat
Temperature is 80º F and the Heater Temperature Band is 1º F, heaters turn on at 79º F and off at
80º F. If the Radiant Low Differential is 2.0º F, radiant heaters turn off at 82º F, and on 1º F below
that (81º F). However, a Radiant High Heater turns on regardless of its temperature setting for the
Radiant Ignition Time whenever the corresponding Radiant Low Heater turns on. This feature
ensures proper flame ignition.
Heat Cycle means providing heat in conjunction with the ventilation system during minimum ventilation
cycles, using heaters and fans connected to relays. When enabled, heaters operate during the fans’
cycle off time (as defined in the Levels of Ventilation Cycle Timer On and Off parameters). How does it
work?
Between the Heat Temperature and the differential temperature, heaters do not operate. When the
temperature goes below the Heat Off temperature minus the Low Heat Differential:
•
Heaters begin to operate when the exhaust or tunnel fans are off. Heaters operate for the
Minimum On Time.
•
If the temperature continues to drop, heaters operate for longer periods of time, up to the
Maximum On Time (defined in Levels of Ventilation).
Between the Heat Temperature and the Target temperature, heaters do not operate (meaning,
the output voltage is 0).
•
Between the Heat Temperature and the Low Difference Below Heat, heaters operate at the
minimum voltage output.
•
If the temperature continues to drop, the voltage output increases until it reaches the maximum
voltage output at the High Difference below Heat.
In this example:
•
Target Temperature is 80°
•
Temperature Curve Heat Off is 78°.
•
Low Heat Differential is 1°.
•
High Heat Differential is 8°.
o
If the temperature is between 77° to 78°, the output voltage is the minimum voltage
defined in Installation > Analog Output (1 volt in this example).
o
If the temperature continues to drop, the output voltage increases until it reaches the
maximum voltage defined in Installation > Analog Output. Output increases or
decreases to keep the temperature within the Target Temperature and Heat Off band.
•
Define the parameters:
o
Low Difference Below Heat: Temperature difference between the Heat Off parameter
at which the variable heater begins to function.
SYSTEM PARAMETERS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
High Difference Below Heat: Temperature at which the heater begins to operate at
maximum output.
3.1.4.2 Proportional Heat
Proportional Heat works in manner similar to Linear Mode. The difference is that Proportional Heat
features a delay time.
•
When the temperature falls below the user-defined point, the heaters begin operating at their
minimum output.
•
After the response time passes, AC-2000 3G checks the temperature. If it is still below the
defined point, AC-2000 3G increases the voltage by a certain amount (this amount of the
increase cannot be changed).
•
After the response time passes, the process is repeated until heaters operate at their maximum
output.
SYSTEM PARAMETERS
•
Define the parameters.
o
Difference Above Heat to Stop Heater: Differential from target temperature at which
the heater runs at minimal input
o
High Difference Below Heat: High Difference Below Heat: Temperature at which the
heater begins to operate at maximum output
o
Response Time (seconds): Amount of time before the controller begins to change the
ventilation.
3.1.4.3 Linear Valve
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABL E HEATER
Diff Above Heat to Stop Heater
High Diff Below Heat
Response Time (seconds)
SYSTEM PARAMETERS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABL E HEATER
Low Diff Below Heat
High Diff Below Heat
0.0
1.0
30
1.0
8.0
0.0
1.0
30
1.0
Linear Valve enables defining that variable heater input voltage is always equal to or above the minimum
input defined in Installation > Analog Sensors..
When the Analog Heat Mode is defined as having Linear Valve control, there is always a minimal
voltage input. Therefore, if the minimum voltage is 1 volts:
There is 0% voltage when the target temperature is reached.
•
Define.
o
Difference Above Heat to Stop Heater: Differential from target temperature at which
the heater runs at minimal input
o
High Difference Below Heat: High Difference Below Heat: Temperature at which the
heater begins to operate at maximum output.
3.1.5 V
ARIABLE FLOOR HEATER | SET DEFINITIONS
SYSTEM PARAMETERS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABL E HEATER
Low Diff Below Heat Tmp.
High Diff Below Heat Tmp.
VARIABLE FLOOR HEATER
Low Diff Below Heat Tmp.
0.0
1.0
30
0.5
4.5
0.5
4.5
AC-2000 3G Controllers enable configuring up to two variable floor heaters. The output of the heaters
changes as the temperature increases or decreases.
Install at least one analog output card.
To configure the variable floor heaters:
1. In
a. up to two analog outputs as variable heaters
b. the minimum and maximum voltage output for each heater
3. Set the response time (amount of time before the controller begins to change the ventilation).
4. Variable heat parameters are dependent on the mode employed.
o
Linear Heat
o
Proportional Heat
o
Linear Valve
3.2 Introduction to Humidity, Ammonia, and CO2 Treatment
AC-2000 3G provides various options to controlling the humidity, CO2, and ammonia levels.
•
None: No treatment is provided.
•
Level: Ventilation levels increase for a designated amount of time.
•
Tunnel or exhaust fan: A designated fan turns on for a designated amount of time. The amount
of air blown into the house is greater than that provided by an increase in ventilation level.
•
Increase in air / weight: The total amount of air that fans need to provide increases by a user
defined amount. Fan stay on until CO2, humidity, or ammonia levels fall to their defined levels.
This option is only available when using Minimum Ventilation by Weight.
•
Humidity treatment by heat: In cold air situations, heaters can be turned on to lower the
relative humidity.
If there is a contradiction between CO2, humidity, and ammonia treatments:
•
Ammonia treatment has priority over CO2 treatment.
•
C02 treatment has priority over humidity treatment.
•
Increase in air / weight has priority over other treatments.
•
Humidity treatment by heat takes priority over increasing the ventilation.
3.3 Humidity Treatment
Humidity treatment forces an increase in ventilation level when the humidity is too high. It holds the
increase for ‘Duration Seconds’, and checks back after ‘Interval Minutes’ for another increase. After the
duration, the ventilation level comes back down automatically.
(refer to Analog Sensors, page 81), designate up one or two sensors
as indoor humidity sensors (outdoor sensor is for information only). When using more than one
sensor, AC-2000 3G begins treatments based on the average.
2. If required, go to
Service > Humidity Calibration
Calibration, page 72).
3. In
Control > Humidity Treatment
o
Day: Growth day. Can set multiple programs for same day (maximum number of
programs: 20)
o
Humidity: Humidity at which to begin treatment
o
Delay Minute: Amount of time the controller pauses before ventilating
o
Duration Sec.: Number of seconds the controller maintains the increased level of
ventilation
4. Set the Humidity Sensor Alarm (page 55).
3.3.1 H
UMIDITY TREATMENT HELP | SET DEFINITIONS
While viewing the Humidity Treatment menu: Press HELP, select SET, and press ENTER.
Humidity Treatment below Heat
Humidity Treatment By
Outside Temp Treat by Heaters
, and calibrate the sensors (refer to CO2 Sensor
set the parameters as required.
HUMIDITY TREATMENT
YES
Exh 6
-18.0
• Define:
o
Humidity Band (%): Hysteresis band (delay) for Humidity Treatment.
o
Humidity Treatment below Heat: Select YES or NO for allowing Humidity Treatment
when heaters are operating (set in Temperature Curve).
o
Humidity Treatment By: This parameter designates the method used when humidity or
CO2 treatment begins. Normally, this parameter is relevant only when minimum
ventilation is running. When a treatment is required, select one the method to be
employed:
Level: Increases the ventilation level when a treatment is required.
NOTE When employing Ventilation by Weight, the controller increases the cycle time or the level,
depending on the particular settings.
Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
Tunnel: Designate a specific tunnel (press a number key to select the fan).
None: Disables the treatment.
To enable the exhaust/tunnel options, in
Output
, designate at least one relay/variable device as a tunnel or exhaust fan.
o
Humidity Treatment by Heaters: This parameter enables using the heaters to lower the
Installation > Relay Outlet
or
Installation > Analog
relative humidity. If enabled, define:
Outside Temp Treat by Heaters: Heaters handle humidity treatment when the
outside temperature is lower than the target temperature by this amount.
Diff to Stop Treatment by Heaters: Heaters cease the humidity treatment if the
inside temperature is lower (or higher) than the target temperature by this amount.
This number can be positive or negative.
Humidity Treatment by Heaters requires designating at least one temperature sensor as an
outside sensor (refer to Temperature Definition, page 85).
NOTE If the heaters are operating because of the interior temperature, Humidity Treatment by Heaters
is disabled.
3.4 CO2 Treatment
CO2 treatment forces an increase in ventilation level when the CO2 level is too high. It holds the increase
for ‘Delay Seconds’, and checks back after ‘Interval Minutes’ for another increase. After the duration, the
ventilation level may come back down automatically. If during treatment, the CO2 level drops below the
Stop Value parameter, the ventilation level automatically returns to that level used before CO2 treatment
was initiated.
1. In
Install > Analog Sensors
sensor.
2. If required, go to
page 81).
3. In
Control > CO2 Treatment
o
Day: Growth day. Can set multiple programs for same day (Max. programs 20)
o
Start Value: CO2 value at which to begin treatment
o
Stop Value: CO2 value at which to end treatment
o
Delay (Sec): Number of seconds the controller pauses before ventilating
o
Duration (Sec): Number of seconds the controller maintains the increased level of
ventilation
CO2 TREATMENT
7
14
0
0
0
0
0
0
2700
2500
0
0
0
0
0
0
2200
2000
0
0
0
0
0
0
(refer to Analog Sensors, page 81), designate one sensor as a CO2
While viewing the CO2 Treatment menu: Press HELP, select SET, and press ENTER.
REATMENT HELP | SET DEFINITIONS
SYSTEM PARAMETERS
CO2 TREATMENT
Outside Temp Treat by Heaters
Diff to Stop Treatment by Heaters
•
CO2 Treatment below Heat: Select YES or NO to enable CO2 treatment when heaters are
-18.0
3.6
operating (set in Control | Temperature Curve).
•
CO2 Treatment By: This parameter designates the method used when humidity or CO2
treatment begins. Normally, this parameter is relevant only when minimum ventilation is
running. When a treatment is required, select one the method to be employed:
o
Level: Increases the ventilation level when a treatment is required.
NOTE When employing Ventilation by Weight (refer to page 22), the controller increases the cycle
time or the level, depending on the particular settings.
o
Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
o
Tunnel: Designate a specific tunnel (press a number key to select the fan).
o
None: Disables the treatment.
To enable the exhaust/tunnel options, in
Output
, designate a relay/variable device as a tunnel or exhaust fan.
o
CO2 Treatment by Heaters: This parameter enables running the heaters in situations
Installation > Relay Outlet
or
Installation > Analog
where the CO2 level is high. Typically this can happen in cold temperatures when CO2
is produced by the heaters. By increasing the heat in the house, ventilation can then be
increased. If enabled, define:
Outside Temp Treat by Heaters: Heaters handle CO2 treatment when the outside
temperature is lower than the target temperature by this amount.
Diff to Stop Treatment by Heaters: Heaters cease the CO2 treatment if the inside
temperature is lower (or higher) than the target temperature by this amount. This
number can be positive or negative.
CO2 Treatment by Heater requires designating at least one temperature sensor as an
outside sensor (refer to Temperature Definition, page 85).
NOTE If the heaters are operating because of the interior temperature only, CO2 Treatment by Heater
is disabled.
3.5 Min/Max Level
IMPORTANT: Before setting Min/Max levels, go through and set up the Device Settings,
especially the ventilation levels.
Once you have entered the ventilation levels, use Min/Max to select the range of levels to apply to your
situation. Typically, you increase the minimum ventilation level as litter conditions deteriorate and the
Min Soft: Set minimum ventilation level for when temperature drops below heat temperature
•
Min: Set minimum ventilation level for when temperature is above heat temperature
•
Max: Set maximum ventilation level for controller
.
SOFT MIN/MAX LEVEL
1
3
6
10
14
21
35
0
0
0
1
11
2
11
3
11
4
11
5
11
6
11
7
0
0
0
0
0
0
3.5.3.1 Soft Min/Max Level Help | Set Definitions
While viewing the Soft Min/Max Level menu: Press HELP, select SET, and press ENTER.
16
16
16
16
21
21
21
0
0
0
Diff. Below Heat for Soft Min.
10.0
•
Differential Below Heat for Soft Min: Set the degree of difference from heat temperature (set
in Control | Temperature Curve) to switch minimum level from Min. to Soft Min.
Temp Choice for Soft Min: Select inside/outside/attic temperature to control Minimum Level
•
changes. The minimum level adjusts towards the Soft Min as this temperature falls. Above the
heat temperature, the minimum level is at the Min setting.
As temperature rises, INSIDE and ATTIC stay at lowest ventilation level reached until average
temperature gets to the heat setting, and then changes instantly. With the OUTSIDE selection, the
minimum ventilation level increases gradually as temperature rises to the heat setting. This means inside
and attic soft min vent choices to latch to the lowest level reached as long as the temperature remains
below the heat setting.
3.5.4 BY W
EIGHT
The By Weight option enables controlling the minimum air flow depending on the number of birds, their
weight and the current outside temperature. When using the Weight option, AC-2000 3G takes several
parameters and calculates the air speed, level of ventilation and cycle time needed to supply the required
volume. As opposed to the other ventilation methods, the Weight option is dynamic, with the ventilation
changing according to the current parameters (quantity of air required, weight of birds and number of
birds, outside air temperature). In addition, Ventilation By Weight sends out an alarm if the current
ventilation is below the minimum required level.
3.5.4.1 Min/Max Level By Weight Help | Set Definitions, Version 9.18 and Below
While viewing the Min/Max Level by Weight menu: Press HELP, select SET and press ENTER.
SYSTEM PARAMETERS
Warm Temp. – Diff Below Heat
Cold Temperature
Air Change
Fan Cycle Time (sec, 0 – Manual)
Minimum ON Time in Vent Cycl e
Minimum OFF Time Vent Cycle
Air Change by Humidity/CO2 %
•
Warm Temperature – Difference Below Heat: Differential below the heat temperature (refer
2.0
68.0
0.24
600
60
60
20
to Temperature Curve, page 9) that defines outside temperature as Warm in the Soft Min/Max
table. For example, if the Heat Temperature is 78° F, Warm Temp. – Diff Below Heat is 2.0,
than the outside temperature is defined as warm at 76° F.
•
Cold Temperature: Outside temperature (or below) at which Air per Kg/Lb (Cold) capacity
is reached.
When the outside temperature is between the Warm and Cold Temperature, the flow rate is
calculated at a proportional rate.
•
Air Change: As the temperature rises from the Cold Temperature parameter to the Heat
Temperature (or drops from the Heat Temperature to the Cold Temperature parameter), the
minimal air volume rises/falls proportionally. Air Change defines the minimal change in air
temperature that must takes place to cause a change in the air supply.
•
Fan Cycle Time: The total amount of time that the fans operate while operating under Minimum
Ventilation. During this time, the fans supply the required volume of air at the minimum
ventilation level required. AC-2000 3G adjusts the minimum ON time and OFF time as
needed. If the fans cannot supply the required volume at a particular level of ventilation, the
controller automatically adjusts the minimum ventilation level.
o
Minimum ON Time in Vent Cycle: The minimum amount of time that the fans operate
during a cycle. The controller adjusts the actual fan time as needed.
o
Minimum OFF Time in Vent Cycle: The minimum amount of time that the fans do not
operate during a cycle. The controller adjusts the actual fan time as needed.
As the temperature rises, the actual Minimum OFF Time decreases until it reaches the minimum time.
Only then does the Minimum On Time begin to rise.
NOTE If the temperature goes above the Band Temperature, Power Ventilation begins and times are
adjusted accordingly.
•
Air Change By Humidity/CO2/Ammon%: As the humidity, CO2, or ammonia levels rise
above the levels specified in Humidity Treatment, CO2 Treatment, or Ammonia Treatment the
minimal air volume rises proportionally. Air Change By Humidity/CO2/Ammon% defines the
minimal change in in these levels that must take place to cause an increase in the air supply.
•
Air Per Weight Curve Mode: By default, Air per Kilo/Lb has two data points: cold
temperature and warm. If desired, the user can add an additional intermediate (computer
defined) data point which is between the two default points. This point determines the quantity
of air to be distributed when the temperature reaches the midpoint between the cold and warm
NOTE In a three point curve, the intermediate value must be between the cold and warm value in each
line.
3.5.4.2 Min/Max Level By Weight Help | Set Definitions Version 9.19
Version 9.19 has an additional parameter, Medium Temp, which enables setting up a more accurate
temperature curve in Air by Weight. By default, the curve is determined by the Air per Kg/Lb Cold and
Warm Temperatures. Medium Temp adds an additional (user-defined) point to the curve.
To add the Medium Temp point:
1. Configure Air by Weight as shown in By Weight, page 22.
2. Go to Control > Min/Max > Help and configure the parameters (refer to Min/Max Level By
Weight Help | Set Definitions, Version 9.18 and Below, page 24 for details).
3. In the Help screen, define the Air per Weight Curve Mode:
•
Using the number pad keys to define the mode as 2 or 3.
o
If set to 2, the Medium Temp parameter is disabled.
o
If set to 3, define the Medium Temp parameter.
SYSTEM PARAMETERS
Warm Temp. – Diff Below Heat
Medium Temp
Cold Temperature
Air Change
Fan Cycle Time (sec, 0 – Manual)
Minimum ON Time in Vent Cycle
Minimum OFF Time Vent Cycle
Air Change by Humidity/CO2/Ammon% %
2.0
72.0
68.0
0.24
600
60
60
20
It can be no lower than the Cold Temperature.
It can be no higher than the Warm Temperature minus Warm Temp. –Diff below
Heat differential.
Go to the Control Menu screen, re-enter the Mini/Max screen, and the Medium