mundoclima CL23220, CL23223, CL23420, CL23423 Installation Manual

MVD
Installation manual
English
CL23220 to CL23223
www.mundoclima.com
Be sure to be in conformity with the local, national and international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safty items. Observe them and never forget.
Keep this manual with the owner's manual in a handy place for future reference.
1. PRECAUTIONS
The safty precautions listed here are divided into two categories. In either case, important safty information is listed which must be read carefully.
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on
how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the owner's manual for future reference.
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Disconnect the power supply before cleaning and maintenance.
Failure to observe a warning may result in death.
Failure to observe a caution may result in injury or damage to the equipment.
Install according to this installation instructions strictly.
If installation is defective, it will cause water leakage, electrical shock fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts for installation.
otherwise, it will cause the set to fall, water leakage, electrical shock fire.
Install at a strong and firm location which is able to withstand the set' s weight.
If the strength is not enough or installation is not properly done, the set will drop to cause injury.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cord is damaged, it must be replaced by the manufacture or its service agent or similarly qualifued person in order to avoid a hazard.
An all-pole disconnection swith having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents.
CAUTION
WARNING
W
ARNING
CONTENTS P
AGE
PRECAUTIONS........................................................................................1
INSTALLATION INFORMATION............................................................... 2
ACCESSORIES ......................................................................................3
INSPECTING AND HANDLING THE UNIT.................................................4
INDOOR UNIT INSTALLATION.................................................................4
CONNECT THE DRAIN PIPE....................................................................6
INSTALL THE CONNECTING PIPE...........................................................6
WIRING...................................................................................................9
CONTROL..............................................................................................12
Installation manual Console
1
TEST OPERATION.................................................................................14
TROUBLESHOOTING..................................................................13
To install properly
, please read this "installation manual" at
first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the power only after a thorough check.
Regret for no further announcement if there is any change of this manual caused by product improvement.
2. INSTALLA
TION INFORMATION
Ground the air conditioner.
Do
not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires , then connect the indoor unit wires.
You are not allow to connect the air conditioner with the power source until wiring and piping the air conditioner is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Don't install the air conditioner in the following locations:
There is petrolatum existing.
There is salty air surrounding (near the coast).There is petrolatum existing.
There is salty air surrounding (near the coast). If this can't be avoided, choose a anticorrosive model.
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
If the refrigerant leaks during installation, ventilate the area immediately.
T
oxic gas may be produced if the refrigerant comes into the
place contacting with fire.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
After completing the installation work, check that the refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
INSTALLA
TION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
Installation manual Cassette 4 way compact
2
3. ACCESSORIES
Table 3-1
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully
.
Fig.3-1
Never throw or beat the controller.
Before installation, operate the remote controller to determine its location in a reception range.
Keep the remote controller at least 1m apart from the nearest
TV set or stereo
equipment. (it is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
Note that the positive and negative poles are right positions when loading batteries.
This manual is subject to changes due to technological improvement without further notices.
Cautions on remote controller installation:
Remote controller
holder
Mounting screw B
ST2.9x10-C-H
QUANTITYSHAPENAME
1.Hook
8. Installation manual
3. Remote controller
4. Frame
6. Alkaline
dry batteries (AM4)
2
1
1
2
2
1
Installation fittings
Remote controller & Its Frame
Others
5. Mounting screw(ST2.9×
10-C-H)
2. Mounting screw(ST3.9×
25-C-H)
10
7. Remote controller manual
1
9. Remote alarm signal wires
1
10. Remote control signal wires
1
11. Flexible hose tube
1
Remote
controller
RESET
TIME ON
TIME
OFF
CLOCK
SWING
AIR DIRECTION
OK
ECO
SWING
MODE
FAN SPEED
0
LOCK
C/H
AUTO
COOL
DRY
HEAT
FAN
TEMP
SET
CLOCK
SET
HOUR
FAN SPEED
RESET
TIME ON
TIME
OFF
CLOCK
SWING
AIR DIRECTION
OK
ECO
SWING
MODE
FAN SPEED
0
LOCK
C/H
AUTO
COOL
DRY
HEAT
FAN
TEMP
SET
CLOCK
SET
HOUR
FAN SPEED
1
12.Copper:
Use for pipe connection
of engineering installation
Installation manual Cassette 4 way compact
3
5. INDOOR UNIT INSTALLA
TION
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should be reported immediately to the service agent.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
Choose on before hand the path along which the unit is to be brought in.
Move this unit as originally package as possible.
When lifting the unit , always use protectors to prevent belt damage
and pay attention to the position of the
unit’s centre of gravity.
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.)
When run some of the units among the indoor units in heating mode, voice of refrigeration flowing comes from some other non-operating indoor units, however, this is a normal phenomena.
When you are going to install the unit at a quiet requirement place, please consult the local distributor firstly.
There is enough room for installation and maintenance.
(Refer to Fig.5-1 and Fig.5-2)
The outlet and the inlet are not impeded, and the influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out easily.
There is no direct radiation from heaters.
5.1 Installation place
The indoor unit should be installed in a location that meets the following requirements:
CAUTION
Fig.5-1
Fig.5-2
Fig.5-3
≥100mm
195mm
≥100mm
≥100mm
Hook
≥1000mm
700mm
210mm
600mm
(unit˖mm)
64
)007(
431
591
591
62
05
475
)006(
061
35
53
446
105
052
210
1 04
032
Installation manual Cassette 4 way compact
4
Loading...
+ 11 hidden pages