mundoclima CL23190, CL23194 Installation Manual

MVD
Duct 100% fresh air
Installation manual
English
www.mundoclima.com
T
o install properly, please read this manual at first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
When all the installation work is finished, please turn on the power only after a thorough check.
No further announcement if there is any change of this manual caused by product improvement.
Indoor Unit
Enough room for installation and maintenance.
The ceiling is horizontal and it can af
ford the weight of the indoor
unit.
The air inlet and outlet are not impeded and does not affected by outdoor air too much.
The air flow can reach every part of the room.
The connecting pipe and drainpipe can be easily extracted out.
1. INST
ALLATION PRECAUTION
2. INSTALLATION PLACE
NOTE
The
installor should illustrate to users how to correctly use and maintain the air-conditioner, as well as remind users to carefully read and keep both Installation Manual and Owner's Manual well.
There is no direct radiation from heat source.
Outdoor Unit
Enough room for installation and maintenance.
The air inlet and outlet are not impeded and does not af
fected by
outdoor air too much.
Dry and well ventilated place.
The supporter is flat and horizontal and can afford the weigh of outdoor unit, without noise and vibration.
The noise and the outlet air will not influence your neighbor.
No combustible gas.
Place convenient for piping and wiring.
Please keep away from the following places, or malfunction may be caused.(if unavoidable, please consult the professionals):
There is mineral oil like the oil of cutting machine.
There is much salty air. (Near the coast)
There is caustic gas such as sulfuric gas. (Near the hotspring.)
Factory where the voltage fluctuate greatly.
In the car or in the cabin.
In the kitchen or a place full of oil steam.
There is strong electromagnetic wave.
CONTENTS
PAGE
INSTALLATION PRECAUTION..................................................................1
INSTALLATION PLACE............................................................................1
ACCESSORIES....................................................................................2
INDOOR UNIT INSTALLATION ..............................................................2
INSTALLATION SPACE..........................................................................10
HIGH STATIC PRESSURE TYPE...........................................................11
DUCT DESIGN.....................................................................................12
THROTTING COMPONENTS MAAINTENANCE......................................12
CONNECTION CONDITION..................................................................12
REFRIGERANT PIPE............................................................................13
INSTALL THE CONNECTING PIPE........................................................13
REFRIGERANT PIPE CONNECTION......................................................14
CONNECT THE DRAIN PIPE.................................................................15
WIRING...............................................................................................15
CONTROL............................................................................................16
TROUBLE SHOOTING..........................................................................18
INSTALL ELECTRIC THROTTLE PART..................................................18
INSTALL BRANCH PIPE.......................................................................19
TEST OPERATION................................................................................19
DISPOSAL˖Do
not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of esperience and knowledge ,unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Disconnect the power supply before cleaning and maintenance.
The appliance must be installed 2,3m above floor.
The appliance shall not be installed in the laundry.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
The appliance shall be installed in accordance with national wiring regulations.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
The power cord type designation is H05RN-R/H07RN-F or above.
CAUTION
Installation manual Duct 100% fresh air
1
NOTE
Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the compressor (technical process), following installation condi­tions apply.
The power connection for the air conditioner has to be done at the main power distribution.The distribution has to be of a low impedance, normally the required impedance reaches at a 32A fusing point.
No other equipment has to be connected with this power line.
For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply for products like washing machines, air conditioners or electrical ovens.
There is combustible gas or materials.
There is much evaporating acid or alkaline gas.
Other special areas.
Notes Before Installation
Select the correct carry-in path.
Move this unit as originally packaged as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
Avoid installing it in a narrow sapce which has a high requirement to noise.
Please refer to the following figure for the distance measurement between the screw bolts.
Please install with screw bolts.
The handling to the ceiling varies from the constructions, consult the construction personnels for the specific procedures.
The size of the ceiling to be handled.Do keep the ceiling flat. Consolidate the roof beam for possible vibration.
Cut of
f the roof beam.
Strengthen the place cut off, and consolidate the roof beam.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in case there is a ceiling, position the refrigerant pipes, drain pipes, indoor & outdoor lines to the connection places before hanging up the machine.
The installation of hanging screw bolts.
Installing Φ10 Hanging Screw Bolts (4 Bolts)
4. INDOOR UNIT INST
ALLATION
Cautions on remote controller installation
Never throw or beat the controller
.
Before installation, operate the remote controller to determine its location in a reception range.
Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment. (It is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a heatingsource, such as a stove. Note that the positive and negative poles are in right positions when loading batteries.
1
. Remote controller....................................1
2. Remote controller holder.........................1
3. Mounting screw
(ST2.9x10- C-H)........................................2
4. Alkaline dry battery(AM4)
..................................................................2
Remote controller & Its Frame
2
3
R
emote controller
ho lder
Mounting screw
Fig.3-1
For
power details of the air conditioner, refer to the rating
plate of the product.
For any question contact your local dealer.
1
Re
mote
controller
T
able.3-1
The following are selectable accessories
3. ACCESSORIES
1
1
1
Na
me of
Accessories
Ins
tallation manual
Pipe insula­tion material
Adhesive tape for seal
Heat insulation
To connect drain pipe
Q‘
ty
4
(
This manual)
Out
line
Us
age
Wire
control the
air-conditioner
Clasp
Network matching wire
1
1
1
Water outlet joint
For drainage
Chucking the joint which connect the drain hose and the outlet of indoor unit
The indoor unit which at the terminal of communication system shouldconnect a impedance between port P and port Q
20.0-28.0
2
Water connec­ting pipe
20.0-28.0
1
To connect drain pipe
Wire controller
12.5-14.0
12.5-14.0
12.5-14.0
20.0-28.0
2
Copper nut
1
Use for pipe connection of engineering installation
Installation manual Duct 100% fresh air
2
Fig.4-1
Hanging screw bolt s
Ceiling
Timber over the beam
Roof beam
Put the square timber traversely overthe roof beam, then install the hanging screw bolts. (Refer to
Fig.4-1
)
Wooden construction
New concrete bricks
Fig.4-2
Inlaying or embedding the screw bolts (Refer to
Fig.4-2)
Blade shape insertion Slide insertion
Overhanging the indoor unit
Overhang
the indoor unit onto the hanging screw bolts with
block.
Position the indoor unit in a flat level by using the level indicator, unless it may cause leakage.
Screw nut
Overhang part
washer
Hanging screw bolt
Fig.4-5
Fig.4-8
Fig.4-7
Fig.4-6
T
ake out the air-in grill.
Dismantle the air filter
Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy , please use soft brush and mild detergent to clean it and dry out in cool place).
The air-in side should face down when using water. (See Fig.4-7)
Install the main body
Installing the dust proof net and canvas air passage
Open the air-in grill Anti-clockWise the bolts as indicated in follow figure sketch.Then pull down the air-in grill.
ķ
ĸ
Ĺ
ĺ
Ļ
ļ
Pipe Connection
The
static pressure outside the unit is 200Pa , the length of
the air pipe attached is determined by this parameter.
The positioning of ceiling hole and indoor unit and hanging screw bolts
Routine method of installation: the size of installation for indoor unit following Fig.4-9
Please install with Φ10 hanging screw bolts.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the
operation, determine the direction of the position the refrigerant pipes, drain pipes, indoor & outdoor lines and line­controlled lines to the connection places before.
ķ
ĸ
Ĺ
For original concrete bricks
Steel roof beam structre
Fig.4-3
Fig.4-4
St
eel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Use embeding screw bold, crock and stick harmness (refer to
Fig.4-3)
H
anging screw bolt
Hanging bolts
Supporting
Install and use directly the supporting angle steel. (refer to
Fig.4-4)
angl
e steel
The air-in side should face up when using vacuum cleaner
.
(See Fig.4-8)
Installation manual Duct 100% fresh air
3
Fig.4-9
12.5~14kW
Unit: mm
The positioning of ceiling hole and indoor unit and hanging screw bolts
routine method of installation: the size of installation for indoor unit following the Fig.4--9 and Fig.4-10
1073
64
31
82
339
82
AIR OUTLET
1300
11
48
6-Φ5 HOLES FOR AIR OUTLET DUCT CONNECTION
AIR OUTLET DUCT FLANGE
400
AIR INTAKE DUCT FLANGE
4-12*25 OBLONG SUSPENTION BOLT HOLES
AIR INTAKE
4-Φ5 HOLES FOR AIR OUTLET DUCT CONNECTION
400
65
15
37
638
600
17
253
638
14
136
69
90
15
50
800
11
48
137
125
11
28
169
691
52
35
136
123
179
15
ELECTRICAL
CONTROL
BOX
PLASTIC COVER
930
135 88
24
46
68
82
82
56
270
420
249
29
75
61
43
189123
REFRIGERANT
-PIPE FLANED
CONNECTION Φ16(5/8)
REFRIGERANT-PIPE FLANED CONNECTION Φ9.52(3/8)
SAFETY DRAIN CONNECTING PIPE
CONNECTING POINT OF DRAIN PIPE
Installation manual Duct 100% fresh air
4
12
Screw
For fixing the safety drain tray
CAU
TION
Fi
g.4-10
Fi
g.4-11
Wa
ter Tray
Po
sition A
Position B
Safety Drain Tray
1. The whole unit status show as Fig.4-10.
2. Remove the all 11 screw from fixed Safety Drain Tray, and then take off the tray as figure showed in Fig.4-11.
3.Take
off the tray along the direction of the arrow show in Fig.4-11.
4. Clean the tray and evaporator
5. Re-install the unit follow the reverse above orders.
1
. Please shut down the unit and cut off power cable before maintain the motor.
2. Don’t heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
Installation manual Duct 100% fresh air
5
Fig.4-13
Fig.4-12
The method of installation:
Adopt following method if the air-conditioning’s size of installationsite is limited and the indoor unit can’t put into the
installtionsite.
W
ater Tray
Position A
Position B
1
1-Screw
Safety Drain
Tray
1. The whole unit status show as Fig.4-12
2. Remove the all 11 screw from fixed Safety Drain Tray, and then take off the tray as figure showed in Fig.4-12.
3. T
ake off the tray along the direction of the arrow show in Fig.4-13
4. Clean the tray and evaporator.
5. Re-install the unit follow the reverse above orders.
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Don’t heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
CAUTION
Installation manual Duct 100% fresh air
6