Munchkin 399M User Manual

HEAT TRANSFER PRODUCTS, INC.
120 BRALEY RD., E. FREETOWN, MA 02717
Installing, Operating & Maintaining
MUNCHKIN™ HIGH EFFICIENCY
399M COMMERCIAL BOILER
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch: do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
This manual must only be used by a qualified heating installer / service technician. Failure to comply could result in severe personal injury, death or substantial property damage. It is also important to keep these Instructions with the appliance.
MH27745
CONTROLS
USING THIS MANUAL
2
SPECIAL ATTENTION BOXES
Throughout this manual you will see these special attention boxes similar to this one, which are intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgement of Heat Transfer Products, Inc.:
WARNINGS
THIS UNIT IS FOR CATEGORY IV VENTING - 2 PIPE ONLY. THIS IS A SEALED COMBUSTION APPLIANCE.
THIS HEATER INSTALLATION MUST CONFORM TO THE LATEST EDITION OF THE “NATIONAL FUEL GAS CODE” ANSI Z223.1 NFPA 54 AND OR CAN/CGA B149 INSTALLATION CODES. STATE AND LOCAL CODES MIGHT ALSO APPLY TO INSTALLATION.
WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, THE INSTALLATION MUST CONFORM TO THE STANDARDS FOR CONTROLS AND SAFETY DEVICES FOR AUTOMATICALLY FIRED HEATERS, ANSI/ASME HEATER AND PRESSURE VESSEL CODE, Section IV, ALONG WITH CSD1.
THE HEATER, GAS PIPING, WATER PIPING, VENTING AND ELECTRICAL MUST BE INSTALLED BY TRAINED & QUALIFIED PERSONNEL FAMILIAR WITH INSTALLATION PRACTICES, LOCAL CODE, LICENSING REQUIREMENTS.
IF THE INFORMATION IN THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT; CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE;
THE USE OF A LOW WATER CUT-OFF DEVICE MAY BE REQUIRED BY STATE OR LOCAL CODES IF THE MUNCHKIN IS INSTALLED ABOVE RADIATION LEVELS.
USING THIS MANUAL
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION Indicates a potentially hazardous situtation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
TABLE OF CONTENTS
3
TABLE OF CONTENTS
PART 1 . . . . . . . . . . . . . . . . . . . . . .4 thru 6
GENERAL INFORMATION
A How It Operates . . . . . . . . . . . . . . . . . .4
B Munchkin Ratings and Dimensions .4–5
C Pre-installation Requirements . . . . . . .5
D Pressure Relief Valve . . . . . . . . . . . . . .6
PART 2 . . . . . . . . . . . . . . . . . . . . . .6 thru 8
ELECTRICAL
A Electrical Connection . . . . . . . . . . . . . .6
PART 3 . . . . . . . . . . . . . . . . . . . . .8 thru 10
GAS CONNECTION
A Gas Connection . . . . . . . . . . . . . . . . . . .9
B Gas Piping . . . . . . . . . . . . . . . . . . . . . . .9
C Gas Table . . . . . . . . . . . . . . . . . . . . . . . .9
PART 4 . . . . . . . . . . . . . . . . . . . .11 thru 17
VENTING
A Approved Venting Materials . . . . . . . .11
B Venting the Munchkin in
4” or 6” Plastic Pipe . . . . . . . . . . . . . .11
C Longer Vent Runs Using a
Combination of 4” to 6” Pipe . . . . . . .14
D Heater Removal from a
Common Vent System . . . . . . . . . . . .15
E Condensate Requirements . . . . . . . . .17
PART 5 . . . . . . . . . . . . . . . . . . . .17 thru 28
PIPING
A Hydronic piping with
Circulators or Zone Valves . . . . . . . . .17
B Circulator Sizing . . . . . . . . . . . . . . . . .18
C Fill and Purge Heating System . . . . . .19
D Piping Illustrations . . . . . . . . . . . . .20–28
PART 6 . . . . . . . . . . . . . . . . . . . .29 thru 32
START UP PROCEDURES
A Items to be checked before
lighting the Munchkin . . . . . . . . . . . . .29
B Lighting Instructions . . . . . . . . . . . . . .29
C Operating Instructions . . . . . . . . . . . .30
D Adjusting the Temperature
on the Munchkin Display . . . . . . . . . .30
E Status Menu . . . . . . . . . . . . . . . . . . . .31
F Test Mode . . . . . . . . . . . . . . . . . . . . . .31
G To Turn Off Gas to Appliance . . . . . . .31
PART 7 . . . . . . . . . . . . . . . . . . . .32 thru 36
SERVICING
A Sequence of operation . . . . . . . . . . . .32
B Munchkin Temporary
Fault Condition . . . . . . . . . . . . . . . . . .32
C Munchkin Fault Requiring
Manual Reset . . . . . . . . . . . . . . . . . . .34
PART 8 . . . . . . . . . . . . . . . . . . . .37 thru 41
MAINTENANCE
A Maintenance Procedures . . . . . . . . . .37
B Before Each Heating Season . . . . . . .37
C Condensate Cleaning Instructions . . .37 D Combustion Chamber
Coil Cleaning Instructions . . . . . . . . . .38
E Munchkin Controller . . . . . . . . . . . . . .39
GENERAL INFORMATION
4
B. MUNCHKIN RATINGS AND DIMENSIONS
PERFORMANCE RATING
CONNECTION SIZES
RECOMMENDED SERVICE CLEARANCES
PART 1. GENERAL INFORMATION
A. HOW IT OPERATES
When the room thermostat calls for heat, the Munchkin control board will start the circulator and start to monitor the return temperature of the system before the heater will begin to heat the water. Once the controller has sensed a drop in the return water temperature below the temperature set point minus the differential set point, the heater will start to heat the water. This eliminates the Munchkin starting every time the thermostat calls for heat. This feature keeps the system from short cycling.
Once the system has sensed the temperature difference, the Munchkin will activate the blower motor for 5 seconds to pre-purge the system before starting the Munchkin
. The Munchkin controller will now start to modulate the pre-mix burner based on analyzing the return temperature, supply water temperature and the set point temperature. By compiling this information, the controller utilizes an algorithm to fully adjust the firing rate while maintaining the desired output temperature. The pre-mix burner fan has a direct drive current low-voltage motor with a pulse relay counting. This system allows precise control over the fan speed and combustion air volumes. Coupled with the Honeywell gas valve and the Venturi system which are set to provide a one-to-one ratio of precisely measured volumes of fuel to air, an accurate and instant burner output is achieved. This keeps the Munchkin running at the
highest efficiency.
When the thermostat is satisfied, the Munchkin will then go through a 4 second post-purge cycle before shutting off. Every Munchkin heater is equipped with a display which will read the outlet temperature of the heater and then will illuminate a green light showing flame on. If a problem occurs, the front indicator light will turn red and the display will read a fault code; see Part 7, Section B/C, pages 33 and 34.
Figure 1-1
(NOTE: The Munchkin is rated at zero clearance to combustibles.)
24"
12"
24"
FRONT
12"
15"
ledoMnoitaludoMtupnIgnitaeHEODycneiciffEnoitsubmoCycneiciffElamrehT*EUFAthgieWgnippihS
M993000,993ot000,001000,972ot000,39%59%53.39%39.sbl252
ledoM
M993TPN"2"4/1-1"4
nruteR/ylppuS
noitcennoC
noitcennoCsaG
eziS.aiDtneV
5
GENERAL INFORMATION
DIMENSIONS
C. PRE-INSTALLATION REQUIREMENTS
The Munchkin is designed for installation on non-rated flooring, in alcoves, basements, utility rooms, and closet but never a bedroom closet. Choose a location for your Munchkin, centralized to the piping system, along with consideration for Electrical (Part 2, Page 6), Gas Connection (Part 3, Page 8) and Venting (Part 4, Page 11).
Figure 1-2
6
GENERAL INFORMATION / ELECTRICAL
NOTE: Service clearance of the Munchkin
1. The front of the appliance needs 24" of clearance for service minimum. It may have a non-rated or combustible door or access panel and must have a minimum of 24" clearance.
2. The left side of the heater is 12" clearance
3. The right side of the heater is 12" clearance
4. The top of the heater is 15" clearance.
If the Munchkin is set up for liquefied petroleum (LP) gas, some geographic areas follow the Uniform Mechanical Code, section 304.6, “Liquefied petroleum gas burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air gas might collect. Appliances so fueled, shall not be installed in a below grade under-floor space or basement unless such location is provided with an approved means for removal of unburned gas.”
PART 2. ELECTRICAL
A. ELECTRICAL CONNECTION
The electrical connection for the Munchkin is on the left hand side of the unit. There is a ½” knockout location for an electrical connection for both the incoming power and the central heating circulator connection. All electrical wiring must be performed by a qualified licensed electrician in accordance with National Electrical Code ANSI Z223.1/NFPA 54 to and/or the Canadian Electrical Code, Part 1 CSA C22.1, or to the applicable codes and standards. For your convenience, we have labeled all the wires that need to be connected to operate the Munchkin.
CAUTION
Condensation removal: This is a condensing, high efficiency appliance, therefore
condensation removal must be addressed to avoid damage to surrounding area or appliance. See Part (4) Section E for Condensate Requirements.
WARNING
D. PRESSURE RELIEF VALVE
A pressure relief valve is installed into the front right side manifold. We recommend a WATTS ¾" M 335 MI valve or equivalent and meets the requirements of ANSI/ASME Heater and Pressure Vessel Code, Section IV or CSA B51; Heater, Pressure Vessel and Piping Code as applicable for heating heaters. A ¾" pipe must be directed to a floor drain or suitable location within 6" of a drain or floor. Protect from freezing, do not plug or cap pressure relief valve. Serious explosion causing property damage and or loss of life could result. Under no circumstances should the relief valve be eliminated, capped or plugged.
CAUTION
The Munchkin is certified as an indoor appliance. Do not install the Munchkin outdoors or locate where it will be exposed to freezing temperature. This includes all related piping and components. If the Munchkin is subjected to flood water or submersed in water, the Munchkin must be replaced.
7
ELECTRICAL
The electrical requirements are for standard 120 volts, 60 Hz 15 Amp service. This unit is wired with #18 awg and fused for no more than 15 Amps.
There are two ground points in the electrical compartment that must be connected to the building ground system. Connect the building ground to the green ground screw and the green ground wire inside electrical box provided.
The Incoming Power Supply is connected to the Black (Hot) and the White (Neutral).The Munchkin Control board is polarity sensitive. If the polarity is reversed, the Munchkin control will not sense a flame and lock out the system. The Orange and Brown wire are provided to the supply of 120 volts to the Central Heating Circulator. Connect the Orange (Hot) and the Brown (Neutral) directly to the Central Heating Circulator.
Connect the gray wires to your heating thermostat (TT) connection. Your thermostat heat anticipator setting is .056 amp.
It is important that the electrical power is not turned on at this time. Double check all connections and then turn the power on. The display that is provided with the Munchkin should now be reading the outlet temperature. Note: see Part 6/Startup Procedure section in the manual to change the temperature setting or run the heater.
DANGER
IT IS VERY IMPORTANT THAT THE BUILDING GROUND IS INSPECTED BY A QUALIFIED ELECTRICIAN PRIOR TO MAKING THIS CONNECTION!
DANGER
The Orange wire for the Central Heating Circulator is Switched Hot and must have a wire nut if not connected to the Central Heating Circulator. Failure to follow this instruction will result in a short, and the Control Board will have to be replaced.
CAUTION
Electrical wiring on the Incoming Power and Central Heating Circulator shall be connected directly to the intended connection source and not be connected together inside the electric box provided. An Electrical Short will result and the Control board will have to be replaced! If Electrical Requirements of the Central Heating Circulator exceeds 4 amps (or 3 amps on HA models only) please follow the wiring diagrams on Page 8, Figures 2-1, 2-2 and 2-3.
DANGER
IT IS EXTREMELY IMPORTANT THAT THIS UNIT BE PROPERLY GROUNDED!
CAUTION
Do not power zone valves directly from the heater transformer. Doing so will greatly reduce the life of the transformer. Use a separate transformer sized to handle the total electric load of all zone valves.
PART 3. GAS CONNECTION
8
WARNING
Failure to follow all precautions could result in fire, explosion or death!
ELECTRICAL / GAS CONNECTION
Figure 2-3: For circulator amp loads greater than 4 amps (3 amps for “HA” models) use the wiring diagram shown at left. The brown and orange wires will not be used in this application.
Figure 2-1: Connection Wiring Directly to Central Heating Circulator
Figure 2-2: Connection Wiring without Wiring Central Heating Circulator
Note to Electrical Contractor: The orange wire is 120 Volt/4 Amp maximum for central
heating circulator only. Loads greater than 4 amps or 3 amps for HA models only will blow the fuse on the board. The brown wire is the neu­tral wire for the central heating pump only.
DIAGRAM "A"
WIRING DIAGRAM CONNECTING TO CIRCULATOR
GREEN (GROUND)
WHITE (NEUTRAL)
BLACK
NORMALLY OPEN
THERMOSTAT
CONNECTION
GRAY
T
GRAY
T
BROWN (NEUTRAL)
ORANGE (HOT)
GREEN (GROUND)
(NEUTRAL)
ELECTRICAL
SWITCH JUNCTION BOX
120V 60 HZ
WHITE
(GROUND)
GREEN
BLACK (HOT)
ZONE
THERMOSTAT
R845A
SWITCHING
RELAY ZONE
1K1
T
5
3
BOILER
"TT"
GRAY
DIAGRAM "B"
WIRING DIAGRAM WITHOUT CONNECTION TO CIRCULATOR
IMPORTANT NOTE: BE CERTAIN THAT THE ORANGE WIRE IS SECURELY CAPED.
GREEN
ORANGE
NORMALLY OPEN
THERMOSTAT
CONNECTION
GRAY
T
GRAY
T
BROWN
ORANGE (HOT)
BROWN (NEUTRAL)
SWITCH JUNCTION BOX
120V 60 HZ
FAILURE TO DO SO COULD RESULT IN INJURY OR FIRE AND COULD DAMAGE THE CONTROL.
WHITE
(NEUTRAL)
GREEN (GROUND)
GREEN
(GROUND)
ELECTRICAL
BLACK (HOT)
GROUND
BUS
T
1
2
1K1 1K2
4
6
BOILER
"TT"
GRAY
L1 HOT (BLACK) 120 VOLT
L2 NEUTRAL
(WHITE)
ZONE
CIRCULATOR
9
GAS CONNECTION
A. GAS CONNECTION
The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pressure (3.5 kPa), and a minimum of 7" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop greater than 0.5" as stated in the National Fuel Gas Code. This information is listed on the rating plate. It is very important that you are
connected to the type of gas as noted on the rating plate. "LP" for liquefied petroleum,
propane gas or, "Nat" natural or city gas. All gas connections must be approved by the local gas supplier, or utility in addition to the governing authority, prior to turning the gas supply on. The nipple provided is 1¼" and it is mandatory that a 1 x 1¼" reducing coupling (provided) is used, threaded into the branch of a 1¼" tee, and a drip leg fabricated, as per the National Fuel Gas code. You must ensure that the entire gas line to the connection at the Munchkin is no smaller than 1¼". Once all the inspections have been performed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the maximum inlet pressure, you must isolate the Munchkin from the gas line. In order to do this, you must shut the gas off using factory and field-installed gas cocks (following the lighting instructions in Part 6 Section B.) This will prevent high pressure. Failure to do so may damage the gas valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced.
Never use an open flame (match, lighter, etc.) to check gas connections.
B. GAS PIPING
1. Run the gas supply line in accordance with all applicable codes.
2. Locate and install manual shutoff valves in accordance with state and local requirements.
C. GAS TABLE
Refer to Table (1) to size the supply piping to minimize pressure drop between meter or regulator and unit.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch water Column
(TABLE 1) (Based on a 0.60 Specific Gravity Gas)
It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas piping must be sized for the proper flow and length of pipe, to avoid pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is undersized or in need of service. You can attach a manometer to the incoming gas drip leg, by
Nominal Iron Pipe Internal Length of Pipe (Feet) Size Diameter (inches) (inches) 10 20 30 40 50 60 70 80 90 100 125 150 175 200. 3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55} BTU'S
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100} PER 1 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210} HOUR 1 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320} X 1,000
10
WARNING
Failure to follow all precautions could result in fire, explosion or death!
GAS CONNECTION
removing the cap and installing the manometer. The gas pressure must remain between 7" and 14" during stand-by (static) mode and while in operating (dynamic) mode. If an in-line regulator is used,
it must be a minimum of 10 feet from the Munchkin. It is very important that the gas line is prop­erly purged by the gas supplier or utility. Failure to properly purge the lines or improper line siz­ing, will result in ignition failure. This problem is especially noticeable in NEW LP installations and
also in empty tank situations. This can also occur when a utility company shuts off service to an area to provide maintenance to their lines. This gas valve must not be replaced with a conventional gas valve under any circumstances. As an additional safety feature, this gas valve has a flanged con­nection to the Venturi and blower.
MUNCHKIN BURNERTECH GAS VALVE
Fig. 3-1
Fig. 3-2
110 VOLT AC ELECTRICAL CONNECTION
VENTURI
INLET PRESSURE TAP
(NOTE: INLET GAS PRESSURE CAN BE MEASURED TO ASSURE PROPER GAS SUPPLY)
THROTTLE ADJUSTER
(NOTE: IF FOR ANY REASON THE THROTTLE
NEEDS TO BE ADJUSTED,
IT IS VERY IMPORTANT THAT A " COMBUSTION ANALYZER " BE USED TO ENSURE SAFE AND PROPER OPERATION TURN THE ADJUSTER TO THE (+) TO INCREASE GAS OR TO THE (-) TO DECREASE THE GAS SUPPLY.
THIS ADJUSTMENT COULD AFFECT THE CO/CO % LEVELS.
MAKE SURE THE LEVELS CORRESPOND TO THE CHART IN FIG. 3-2 COMBUSTION SETTINGS)
OUTLET PRESSURE TAP (NOTE: A NEGATIVE READING WILL BE MEASURED WHILE THE FAN IS IN OPERATION)
2
SGNITTESNOITSUBMOC
saGlarutaNPLenaporP
wolhgihwolhgih
mppOCnobraC
edixonoM
OCnobraC
%2
edixoiD
mpp02–0mpp531–mpp07mpp02–0mpp051–08
%2/1-9%2/1-8%2/1-9%2/1-8%2/1-01%2/1-9%2/1-01%2/1-9
SLEDOMLLANOSETARGNIRIFWOLdnaSETARGNIRIFHGIH
11
VENTING
PART 4. VENTING
A. APPROVED VENTING MATERIALS
Exhaust V
ent
Use Plastic 4" Pipe Schedule 40 or 80.
1. Non-Foam Core PVC Pipe
2. Non-Foam Core CPVC Pipe
3. Non-Foam Core ABS Pipe
Vent Piping must conform to following
1. PVC Non Foam Core Pipe (Polyvinyl Chloride) to ASTM D-1785 or D-1784 Class 12454-B, Formerly designated Type 1, Grade 1.
2. CPVC (Chlorinated Polyvinyl Chloride) Class 23447-B, Formerly designated Type IV, Grade 1 con­forming to ASTM D-1784.
3. ABS (Acrylonitrile-Butadiene-Styrene) Class 3-2-2-2-2 conforming to ASTM D3965.
The Munchkin is a direct vent appliance. The Munchkin is listed as a Category IV Condensing Appliance. (The Munchkin Venting is rated at Zero Clearance to combustibles.)
Note: For Concrete construction or to meet certain fire codes, exhaust and inlet piping at the wall penetration to the Munchkin must be CPVC Schedule 40 or 80 to meet local fire codes. The balance from the penetrated wall to the outside, may be PVC Schedule 40 or 80.
Inlet Air V
ent
Use the same material as used for exhaust in either 4" or 6" Plastic Pipe. Cellular Foam Core Pipe may be used for the inlet only, NEVER ON EXHAUST PIPING!
B. VENTING THE MUNCHKIN IN 4" OR 6" PLASTIC PIPE
DANGER
It is extremely important to follow these venting instructions carefully. Failure to do so can cause severe personal injury, death or substantial property damage.
DANGER
Foam Core Pipe is not to be used in connecting the exhaust pipe.
WARNING
This vent system will operate with a positive pressure in the vent pipe. Do not connect vent connectors serving appliances by natural draft into any portion of mechanical draft systems operating under positive pressure.
DANGER
It is extremely important to follow these venting instructions exactly. Failure to do so can cause severe personal injury, death or substantial property damage.
12
VENTING
The inlet pipe on the back of the cabinet should be 4" PVC schedule 40. It is very important that you plan the location properly to eliminate long pipe runs and excessive fittings. Inlet pipe size must not be reduced. Do not combine the inlet air with any other inlet pipe including an inlet to an additional similar appliance. The joints must be properly cleaned, primed and cemented. The piping must also be properly supported as per Local and National Standard Plumbing Codes. It is important that the piping must be clean and free from burrs, debris, ragged ends and particles of PVC.
Exhaust piping should be sloped back to the connection on the Munchkin, at least ¼" per foot to remove additional condensate that forms within the pipe. The total combined length of pipe (intake piping plus exhaust piping added together) including elbow allowances intake and exhaust (each elbow = 5' of pipe) should not exceed 85'. The combined vent length should not be less than a com­bined length of 6' plus two 90 degree elbows. Choose your vent termination locations carefully. You must also make certain that exhaust gas does not re-circulate back into the intake pipe. You must place them in an open area and follow the following guidelines.
1) Never vent into a walkway, patio area, alley or otherwise public area less than 7' from the ground. (See detail below references Fig. A.10.8 in the National Fuel Gas Code 2002 “Exit Terminals of Mechanical Draft and Direct-Venting Systems”.)
2) Never vent over or under a window or over a doorway where the exhaust plume or conden­sation liquid will cause obtrusive or dangerous conditions. (Or refer to National Fuel Gas Code, CAN B149)
3) Never install a heat saver or similar product to capture waste heat from exhaust.
4) Always have a vent location at least 1' above maximum snow level.
5) Always have vent 1' above ground level, away from shrubs and bushes.
6) Follow local gas codes in your region or refer to National Fuel Gas Code, Can B149.
7) Always have at least 3' from an inside corner of outside walls.
8) Maintain at least 4' clearance to electric, gas meters, windows, exhaust fans, chimneys, inlets or mechanical vents.
9) Very Important! The inlet air connection must be connected to outside air and should be located no closer than 8" to the exhaust and no further than 36".
10) Always place screens in all openings in intake and exhaust to prevent foreign matter from entering the Munchkin.
11) The vent intake and exhaust must be properly cleaned and glued for a pressure tight joint. Several methods for venting the Munchkin can be found in Figures 4-1 thru 4-4, this section. Use these layouts as guidelines: certain site conditions such as multiple roof lines/pitches may require venting modifications (consult factory). The air inlet must be a minimum of 1' vertically above the maximum snow level. It is very important that there are no other vents, chimneys or air inlets in any direction for at least 4'.
CAUTION
The following are code restrictions for the location of the flue gas vent terminal. Compliance to these requirements doesn’t insure a satisfactory installation; good common sense must also be applied. It is important to make sure that exhaust gases are not recirculated into the inlet air of the Munchkin.
13
RECOMMENDED VENTING CLEARANCES PER THE NATIONAL FUEL GAS CODE*
All venting must be properly supported. The Munchkin is not intended to support any venting whatsoever. All piping, glue, solvents, cleaners, fittings and components, must conform to ASTM
(American Society for Testing and Materials), and ANSI (American National Standards Institute). It is recommended that you use one of the optional vent kits specifically designed for Munchkin installa­tions, available from Heat Transfer Products, Inc.
Friction Loss Equivalent Table for 4" or 6" vent
Fittings or Piping Equivalent Feet
4" or 6" 90 degree elbow = 5 4" or 6" 45 degree elbow = 3 4" or 6" Coupling = 0 4" or 6" air inlet tee = 0 4" or 6" Plastic Pipe = 1 4" or 6" V2000 vent kit = 0
Example: Installation requires the following material for both inlet and exhaust piping for the Munchkin
VENTING
EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEM
* REFERENCE: THE NATIONAL FUEL GAS CODE 2002 EDITION
CAUTION
Flue Gas will condense as it exits the vent termination. This condensate can freeze on exterior building surfaces which may cause discoloration of these surfaces. Consideration should be given to the plume of condensation that exits the exhaust which may affect the cosmetic appearance of the building.
*IMPORTANT NOTE
HEAT TRANSFER
PRODUCTS
RECOMMENDS A
MINIMUM CLEARANCE OF 4 FEET WHERE THE
PLUME CAUSED BY
THE UNIT MAY
OBSTRUCT VIEWS
OR AFFECT THE
COSMETIC LOOK OF
THE BUILDING.
e
M
ra
d term (see 10
raft
anical d
ech
M
al
in
12 in.m
vent term
10.8.2)*
(see
inim
Less
um
than 10 ft.
3 ft.minim
um
rad
G
Forced air inlet
e
C
um
inim
12 in.minimum
Direct vent terminal clearance Minimum clearance, C
Input (Btu/hr) 10,000 or less 10,001 to 50,000
Over 50,000 (see 10.8.3)*
For SI units: 1 ft = 0.305 m; 1 in. = 25.4 mm; 1 Btu/hr = 0.293 W
Clearance (in.)
4 ft.m
4 ft.
minimum
12 in.minimum
6 9
12
ch ft ven
in
anical
al
.8.1)*
t
14
VENTING
Required: 4 Pcs. 4" 90 degree elbow (4 x 5 = 20 Equivalent Feet) = 20 Equivalent Feet
Required: 20' of 6" Plastic PVC Pipe (20 x 1 = 20 Equivalent Feet) = 20 Equivalent Feet
Total Friction Loss in Equivalent Feet (20 + 20 = 40 Equivalent Feet) = 40 Equivalent Feet
C. LONGER VENT RUNS USING A COMBINATION 4" TO 6" PIPE
The connection of air inlet and exhaust vent at the heater must remain 4" and each vent must extend from the heater a minimum of 15 equivalent feet before transitioning to a 6" vent. The overall extended maximum length of pipe on the inlet exhaust combined, must not exceed 125 equivalent feet. Listed below are the 4" and 6" size equivalent table.
Fittings or Piping Equivalent Feet
4" or 6" 90 degree elbow = 5 4" or 6" 45 degree elbow = 3 4" or 6" Coupling = 0 4" or 6" air inlet tee = 0 4" or 6" Plastic Pipe = 1 4" or 6" V2000 Vent Kit = 0
Example: Installation requires the following material for both the inlet and exhaust piping when extending the vent run for the Munchkin.
Requirements for 4" Venting
2 Pcs. – 4" 90 degree elbow (2 x 5 = 10 Equivalent Feet) = 10 Equivalent Feet 20' of 4" Plastic PVC Pipe (20 x 1 = 20 Equivalent Feet) = 20 Equivalent Feet
Total of 4" Equivalent Piping with Fittings = 30 Equivalent Feet
Requirements for 6" Venting
6 Pcs. – 6" 90 degree elbows (6 x 5 = 30 Equivalent Feet) = 30 Equivalent Feet 4 Pcs. – 6" 45 degree elbows (4 x 3 = 12 Equivalent Feet) = 12 Equivalent Feet 40' of 6" Plastic PVC Pipe (40 x 1 = 40 Equivalent Feet) = 40 Equivalent Feet
Total of 6" Equivalent Piping with Fittings = 82 Equivalent Feet
Total Friction Loss in Equivalent Feet for both 4" and 6" (30 + 82 = 112 Equivalent Feet) = 112 Equivalent Feet
CAUTION
Do not exceed the 85 foot maximum requirement for 4" PVC and the 125 foot maximum requirement for 6" PVC (intake plus exhaust piping added together) including fitting allowance shown in friction loss equivalent table on previous page.
CAUTION
Transitioning from 4" to 6" should be done in the Vertical position to avoid condensation blockage. If done in the horizontal position check to make sure condensation blockage will not occur.
DANGER
The Munchkin is not intended to be common vented with any other
existing appliance!