This manual provides information on the proper installation, operation and maintenance requirements for Multistack watercooled modular chillers. Follow these instructions to help ensure that the chiller performs properly. Failure to follow these instructions can signicantly aect the chiller’s performance and reliability and may adversely aect the equipment warranty.
Nameplate and Model Number Nomenclature..............................................................................................................................4
Chiller Arrangement and Components, Standard and Total Access™ Modules...............................................................5-7
General Data................................................................................................................................................................................................8
Clearances and Dimensions............................................................................................................................................................11-16
Pressure Relief Piping, Water Treatment Specications, Pipe Flushing.................................................................................18
Module Assembly, Standard Modules........................................................................................................................................19-21
Module Assembly, Total Access™ Modules......................................................................................................................................22
Frame and Enclosure Panel Installation............................................................................................................................................29
Start-Up Data Log...............................................................................................................................................................................31-32
This Multistack installation and operation manual will assist in the proper installation and operation of Multistack modular chillers. Review this
manual carefully.
• The information and illustrations contained in this manual are generalized. Consult with a Multistack representative to address specic
installation and operating details not covered in this manual.
• Good electrical and piping practices in accordance with all National and local codes must be followed.
• This equipment must not be installed near an open ame per local codes and ASHRAE specications.
• Personnel servicing Multistack modular chillers must have, at minimum, a Class II EPA certication.
• Questions regarding the content of this manual and Multistack products should be directed to an authorized Multistack representative or
to the Multistack Service Department at: (608) 366-2400 or via e-mail to info@multistack.com
Planning Ahead
To ensure all warranties and a successful installation, a Factory Authorized Technician is required to perform start-up of the Multistack Chiller. If start-up
is to be performed directly by Multistack, a minimum of two weeks notice is required. Please call the Multistack Service Department at (608) 366-2400 to
schedule.
Multistack has a policy of continual improvement and reserves the right to change product design, literature and
specications without notice.
This manual includes warnings, cautions and notes.
DANGER conveys serious hazards for injury or death.
WARNING indicates risk of injury or death.
CAUTION warns of possible injury or damage.
NOTE calls out work practices that can result in optimal operations.
Warnings, cautions and notes include:
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tag outs.
DANGER: Use extreme caution when working around electrical components, wiring and connections to avoid injury or death by electric shock.
DANGER: Never remove a lockout from equipment unless you placed it there. Each person shall place his/her own lock/tag when required to isolate
an energy source. Do not start any adjustment, service or repair without verifying that the tag/lock out switch or control cannot be by-passed or overridden. Verify that the locked-out switch or control cannot be overridden. Test the equipment to be certain that the locked-out switch is de-energized
and not simply malfunctioning. Press all start buttons to conrm that the equipment WILL NOT start. Conrm that the system being serviced or
repaired is the system that has been locked out. Before restarting equipment, verify all tools and other items have been removed, all machine guards
are in place, all electric systems are reconnected, and personnel are clear of equipment.
DANGER: During installation, testing, servicing and troubleshooting this product, it may be necessary to work with live electrical components. Only
qualied licensed electricians or other properly trained persons may perform these tasks. Failure to follow all electrical safety precautions can result in
death or serious injury. All HVAC equipment must be installed per the National Electric Code (NEC) and/or all applicable state/local codes.
DANGER: Incorrect handling of HVAC equipment can result in explosions, electrical shock or re, causing property damage, injury and/or fatality.
DANGER: HVAC liquids and chemicals can be dangerous if used incorrectly or if spills or accidents occur. Handle detergents and solvents with care to
avoid spills and burns.
DANGER: Danger of explosion. Refrigerant cylinders can explode causing serious injury and/or death if not handled and stored properly.
WARNING: Only qualied, licensed electricians with proper personal protection equipment should wire Multistack chillers. Injury or death my result
if not properly wired due to electric shock hazard
WARNING: Danger of electrical shock. Many types of HVAC equipment have switches and regulators with electrical current on even when other parts
of the equipment appear to be turned o. Main circuit breakers must be turned o before servicing equipment to avoid injury, fatality.
WARNING: Be sure to use lifting slings with lifting capacity to safely handle unit weight. Consult the unit’s as-built submittal drawings for unit
weight data.
WARNING: If welding on chiller water connections, use proper electrical grounding to avoid damaging the compressors or chiller controls. Never
weld directly on the heat exchanger shells. Only an authorized ASME-certied repair agency may weld directly on ASME-certied shells. After welding, an “R” stamp is required.
CAUTION: Working with HVAC equipment can be hazardous due to electricity, moving parts, chemicals, combustion and other hazards. Use safe work
habits including proper tools and personal protective equipment. Understand and heed all safety information, installation guidelines and operation
and maintenance procedures.
CAUTION: Pressurized application of cleaning substances or refrigerants must be done with the correct procedures to ensure the safety of technicians
and others, and avoid property damage.
NOTE: Use correct tools for HVAC equipment installation, maintenance and adjustment. Use the correct tools to make tight connections without strip-
ping threads or breaking screws and bolts. Use accurate refrigerant and electrical meters to properly maintain and diagnose HVAC equipment.
3
Page 4
Multistack Water-Cooled Modular Chillers
Multistack invented the modular chiller. Multistack modular
chillers are available in a wide range of capacities, and with two
independent scroll compressors. Modules can be mix-matched
and combined to create up to 15-module arrays and 1,275 tons of
cooling capacity using environmentally friendly R-410A. Multistack
modular chillers can help owners qualify for USGBC LEED points and
signicant utility rebates. Multistack’s innovative modular design
makes adding more capacity as easy as purchasing and installing
more modules.
Unit Nameplate
The chiller nameplate is located on the front of the control panel.
Use the unit model number nomenclature to identify specic
features and options of an Multistack chiller module.
Total Access™ Modular Chillers
With Total Access, heat exchangers are located on the outer edges of
the chiller frame to provide easy serviceability with a small equipment room footprint. Total Access options include 10- through 85-ton
modular chillers.
1- Standard, 2- Total Access, 3 - Evap extended headers, 4 - Cond extended headers, 5 - Both extended headers, V - others
3
A - 208/3/60, L - 230/3/60, H - 460/3/60, C - 575/3/60, D - 200/3/50, E - 400/3/50, F - 380/3/60, S - 220/230/1/60, V - other
4
A - Air Cooled split, C - Single module temp controller, D - Cond unit, F - Fluid cooler (high temp),H - Heat recovery, R - Heat pump, W - Water cooled
5
A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, V - Other
6
A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, E - Double wall brazed, V - Other
6
4
Page 5
Standard Modular Chiller Arrangement
High Voltage
High Pressure
Transducer
Panel
Scroll Compressors
Low Voltage
Panel
Unit
Nameplate
Isolation/Disconnect
Switch
Buss Bar
Duct
Leaving
Condenser
Water
Header
Entering
Condenser
Water
Entering Chilled
Water Header
Evaporator
Low Pressure
Transducer
Liquid Line
Sight Glass
Header
Leaving Chilled
Filter/Strainers
Water Header
Total Access™ Modular Chiller Arrangement
Multistack’s Total Access option makes maintenance and serviceability even easier by placing heat
exchangers at the outside of the module frame. Manual i
Access units only) between the heat exchangers and water supply mains for heat exchanger isolation and
removal without the need to remove a module or shut down the entire chiller while allowing access to all
serviceable components.
Low Voltage
Panel
High Pressure
Transducer
Condenser
solation valves are factoryinstalled (Total
High Voltage
Panel
Isolation/Disconnect
Switch
Buss Bar
Duct
Evaporator
Condenser
Expansion
Valve
Scroll Compressors
Low Pressure
Transducer
Isolation
Valve
Expansion
Valve
Filter/Strainers
Condenser
5
Page 6
Chiller Components
Master Control Panel
Each chiller has a master control panel that can be mounted on top of any
of the module panels using provided knockouts. Sensors, cables and wiring
connect through the bottom of the master control. The master control box
includes built-in terminal strip inputs for ow switches, start/stop signal, alarm
output, and power phase monitor. As shipped, the Master Control also contains
the pLAN communication wire to be eld installed by the start-up technician.
Four temperature sensors and sensor wells are supplied by Multistack: entering
chilled water, leaving chilled water, entering condenser water, and leaving
condenser water. The sensors are to be installed in customer’s piping system.
Module Control Boards and Low Voltage Panel
The module control boards communicate individual module temperatures
and pressures to the master control. Each module has a switch labeled Auto/
O/ Manual. Normal operation is in the Auto mode. If there is a problem with
the master control, the selector switch can be changed to Manual to provide
individual module leaving chilled water temperature control that was pre-set
at the master control.
Module High Voltage Panel
The high voltage panel contains each compressor’s contactor, circuit breaker,
control relay and transformer. External to the panel is the single-module isolation switch to isolate the that module from high voltage supply power.
Master Controller
Module Slave
Controller
AUTO/OFF/MANUAL
Switch
Compressors, Sensors, Switches
• Standard modules use two scroll compressors with separate refrigeration
circuits.
• Each refrigerant circuit has a high pressure (HP) and low pressure (LP)
transducer that sends pressure signals to the module slave controller
board. Each compressor also includes an HP switch with a manual reset
button.
• Transducers are a 0-5V ratiometric type.
• Compressors include oil level sight glasses. Oil level should be at ⁄ - ¼
full during operation.
• Each circuit has its own leaving chilled water temperature sensor and
refrigerant suction temperature sensor.
• Compressor crankcase heaters are not standard on Multistack MS chiller
modules.
Chilled and Condenser Water Connections
• Water connections to the chilled and condenser side are standard 6-inch
grooved pipes on MS010X through 070X, and 8-inch on MS085X units.
• The upper header on the chilled water side is entering water to the
module.
• The bottom header is chilled water leaving the module.
• Water entering the condenser is on the bottom.
• Water leaving the condenser is on top.
• The entering header on both the evaporator and condenser contains a 30mesh lter strainer to prevent debris from entering the brazed plate heat
exchangers. This strainer should only be used as a nal lter stage.
• Proper ltration before the module should be installed for easy access to
cleaning, such as a ‘Y’ or a basket type of strainer.
Low Voltage
Terminal Strips
Low Voltage Panel
A Compressor
Isolation Switch
A Compressor
Contactor
High Voltage Panel
Control
Relay
Low Voltage
Circuit Breaker
High Voltage
Circuit Breaker
Transformer
Single
Circuit
Breaker
Control
Relay
B Compressor
Isolation
Switch
B Compressor
Contactor
6
Page 7
Expansion Valve, Subcooling, Liquid Line Sight Glass
• Each circuit on a module has a thermal expansion valve located
between the water header pipes on the condenser side. During
factory run testing the valves are adjusted to maintain 10-12
degrees superheat. Check the superheat periodically to maintain
this range. Subcooling should normally be in a 10-15 degree
range. No external subcooler is used.
• The liquid line sight glass shows green on the indicator bulb if
no moisture is present in the refrigerant circuit. Yellow indicates
potential moisture.
• Sight glasses should show full during normal operation.
• Flashing in the sight glass indicates possible under-charge of the
circuit.
• Refer to the unit nameplate for refrigerant charge information.
Variable Flow and Power Actuated Buttery Valves
For variable ow on the chilled or condenser water side, chiller modules must be ordered with power actuated buttery valves.
Note: The footprint of an array of standard modules will increase as
the valves add length. Total Access™ module footprint will not change.
1. Multistack recommends controlling the chiller pumps to maintain
pressure dierential across the chiller, not the system. Control
based on system pressure will provide erratic results.
2. Chiller minimum ow bypass for the system can be programmed
in the master controller.
Expansion
Valves
Sight
Glasses
Expansion Valves and Liquid Line Sight Glasses
(Standard unit.)
Power Actuated
Buttery Valve
Optional Manual Isolation Valves
Standard modules are not supplied with isolation valves. Manual or
electrically actuated valves may be ordered as an option from
Multistack. Total Access modules are supplied with manual isolation
valves from the factory and may be upgraded to electrically actuated
valves as an option. Multistack recommends exercising the isolation
valves as part of annual maintenance.
Optional Hot Gas Bypass
As an option, hot gas bypass valves (Sporlan HGBE-8) can be provided
for each circuit. The valve is adjustable from 75 to 150 psi with a
standard setting of 120 psig. A screw on the pilot valve handles the
adjustment. Turning clockwise increases the valve setting; counterclockwise rotation decreases the valve setting.
Buttery Valve Actuator for Variable Flow shown on
standard module with extended headers.
Hot Gas Bypass Valve
Heat Exchanger Isolation Valves on Total
Access™ Modular Chiller
7
Page 8
General Data Table
MS010XMS015XMS020XMS030XMS040XMS050XMS070XMS085X
Compressor TypeScroll
Dry Weight (lbs. each)89135135146280293390419
Normal Capacity (tons each)57.5101520253040
Compressor Quantity/Module22222222
Oil Charge (pints per compressor)3.56.96.96.99.59.513.313.3
NOTES: Figures in parentheses ( ) apply to Total Access™ conguration chillers.
Add 75 lbs. per module if equipped with enclosure panels.
Multistack has a policy of continual improvement and reserves the right to change product design, literature and specications without notice.
8
Page 9
Module Shipment Package
NOTE: Before accepting delivery of the Multistack chiller, check
the overall condition of the equipment for damage such as broken
copper lines, oil leaks, damaged controls and/or electrical component
housing, or any major component torn loose from its mounting. If
the Multistack modular chiller is damaged during shipping by the
transportation company or its agent, the installing contractor MUST
promptly le a claim with the transportation company and advise
Multistack. Any discrepancy or damage must be noted on the bill of
lading.
3
5
4
12
6
7
Pallet #1 — Typical Cabinetry Package (Optional)
1. Top Front Panel
2. Bottom Front Panel
3. Rear Panel/End Panel
4. Side End Panel
5. Master Controller Top Panel
6. Frame Pieces
7. Frame Connectors, Fasteners, Clips & Magnetic Tape
11
8
9
10
Pallet #2 — Buss Connections
8. Buss bar
9. Buss bar insulation
10. Ground strap
11. Junction Box leg
Multistack has a policy of continual improvement and reserves the right to change product design, literature and specications without notice.
9
Page 10
21
18
19
33
22
20
24
25
23
26
37
37
28
29
27
33
34
30
42
35
36
39
31
39
40
41
Pallet #3 — Typical Piping & Electrical
Package
18. Master Controller*
19. Junction Box
20. Junction Box Cover
21. Sensors / Cables
22. Junction Box Connector (Throat)
23. Power Phase Monitor
24. Buss bar Connector
25. Power Phase Monitor Wire
26. Buss bar Insulation Overlap
27. Phase Monitor Wire
28. Buss bar End Caps
29. Drain Valves & Fittings
30. Module Joining Bolts
31. End Cap for Multiush system (upper)
32. End Caps (evap)
33. Couplings
34. Multiush pipe
35. Solenoid for Multiush system
36. Pipe Stubs
37. End Cap Multiush system (lower)
38. Filter Stops
39. Pet Cock Valves
40. Drain Valves & Fittings
41. Sensor Wells
42. 30 Mesh Filter Strainer
* May be shipped separately to sales oce or job site.
** Shipped inside #19 - Junction Box
Multistack has a policy of continual improvement and reserves the right to change product design, literature and specications without notice.
Moving Chiller Modules
Caution: Modules Are Top Heavy
Module on Fork LiftModule on Pallet Jack
Multistack chiller modules MS010 through MS085 may be moved using a fork lift truck, pallet jack or similar equipment. Optional spreader bars for lifting
and factory-installed wheels are available from Multistack. Contact your Multistack representative. For unit weights see the table on Page 8 and the jobspecic as-built submittal drawings.
10
Page 11
Clearances
Diagram shows typical dimensions and the recommended clearances around the modular chiller. There must be a minimum of six inches clearance over the
top of the chiller, including the top of master controller if installed on top of the module.
For specic unit dimensions, refer to as-built submittal drawings.
11
Page 12
Width (A)Depth (B)Height (C)
Module Dimensions (No Panels)
Standard28”47 ⁄”64”
Total Access (MS010--050)32”56”67”
Total Access (MS070)34”56”67”
Extended Headers 28”62 ⁄”64”
B
C
Extended Headers 28”76 ⁄”64”
A
*Standardized drawing of sample customer installation
** Enclosure panels are optional
Standard Modules (Constant Flow Design)
12
Page 13
Width (A)Depth (B)Height (C)
B
Standard28”47 ⁄”64”
Extended Headers 28”62 ⁄”64”
Total Access (MS070)34”56”67”
Module Dimensions (No Panels)
*Standardized drawing of sample customer installation
**Enclosure panels are optional
Evaporators and Condensers
Standard Modules with Extended Headers on
Variable Flow Design for Chilled and Hot Water
Total Access (MS010--050)32”56”67”
Extended Headers 28”76 ⁄”64”
C
A
13
Page 14
Width (A)Depth (B)Height (C)
Standard28”47 ⁄”64”
Extended Headers 28”62 ⁄”64”
Total Access (MS070)34”56”67”
Module Dimensions (No Panels)
*Standardized drawing of sample customer installation
** Enclosure panels are optional
Total Access (MS010--050)32”56”67”
B
C
Extended Headers 28”76 ⁄”64”
A
Standard Modules with Extended Headers on Condensers
Variable Flow Design for Hot Water, Constant Flow for Chilled Water
14
Page 15
Width (A)Depth (B)Height (C)
Module Dimensions (No Panels)
Standard28”47 ⁄”64”
Total Access (MS010--050)32”56”67”
Total Access (MS070)34”56”67”
Extended Headers 28”62 ⁄”64”
B
C
Extended Headers 28”76 ⁄”64”
A
*Standardized drawing of sample customer installation
** Enclosure panels are optional
Standard Modules with Extended Headers on Evaporators
Variable Flow Design for Chilled Water, Constant Flow for Condenser Water
15
Page 16
Width (A)Depth (B)Height (C)
Module Dimensions (No Panels)
Standard28”47 ⁄”64”
Total Access (MS010--050)32”56”67”
Total Access (MS070)34”56”67”
Extended Headers 28”62 ⁄”64”
B
C
Extended Headers 28”76 ⁄”64”
A
*Standardized drawing of sample customer installation
** Enclosure panels are optional
Total Access Modules With or Without Variable Flow
16
Page 17
CONDENSER SIDEEVAPORATOR SIDE
Sensor Pockets, Sensors
Supplied by Multistack,
installed by others.
Pressure
Taps
Pressure
Taps
Isolation
Valves
Strainer
Flow/DP
Switch
Chilled Water
Pump
CHW In
CHW Out
To Cooling Tower
or Fluid Cooler
CW Out
CW In
3-Way
Bypass Valve
Flow/DP
Condenser
Pump
Switch
Isolation
Valves
Strainer
Sensor Pockets, Sensors
Supplied by Multistack,
installed by others.
Pressure
Taps
Items in This Area Included
with Chiller
Recommended Piping
All piping must be properly and adequately supported at coupling connections and suitable intervals along the piping runs. Hanger design must
provide for the weight of uids in the piping system when the chiller is in operation.
Multistack modules are equipped with brazed plate heat exchangers made of 316 stainless steel. Multistack recommends use of a 30-mesh system
strainer, Y-type basket or equal, in each condenser and evaporator inlet header.
It is the installing contractor’s responsibility to make sure the water systems have been ushed and the strainers are clean and clear of debris before
starting the chiller. Do not ush piping so as to push debris into or through the through the chiller heat exchangers.
Important
Be sure to install the supplied sensor wells in the system piping. The wells should be installed
a few feet from the chiller in the entering and leaving chilled water and entering and leaving
condenser water pipes.
Typical Sensor Wells
Flow Protection
Proof of chilled water and condenser water ow is required by the Master Controller inputs. Paddle-type or Dierential Pressure (DP) switches may
be used. Switches can be supplied by Multistack as an option, otherwise they are to be eld supplied and installed. Chillers purchased with chilled
or condenser water pump modules have a DP switch installed across the pump to verify operation. Multistack recommends a paddle-type switch be
installed in the leaving chilled water piping using a dierential pressure switch. Install it across the inlet and outlet water connections to the chilled
and/or condenser water piping connections.
System Water Volume
A properly sized chilled water system must have enough time (at least three minutes) to properly control and respond to changes in load and to
prevent short cycling of the chiller. To ensure the system water volume is adequate, a general rule of thumb is:
7-10 gallons of water per ton or Acceptable Chilled Water Volume = Chilled Water Design GPM X 3
If the system heat exchangers, piping and components cannot hold the necessary chilled water volume, a properly sized chilled water storage tank
should be added.
Condenser Water Temperature Control
For installations where entering condenser water temperature could be lower than 65°F Multistack recommends installing a three-way tower bypass
valve to maintain a minimum of 65°F entering condenser water temperature. This is based on a 10°F Delta-T system.
17
Page 18
Pressure Relief Piping and Refrigerant Monitoring
Multistack chiller modules use a small refrigerant charge (typically 0.6 lbs. per ton) and are often exempt from many requirements of ASHRAE 15 Standard.
Pressure relief valves are not standard on water-cooled modules and must be special ordered if required by local codes.
Water Treatment / Specications
Supply water for both the chilled water and condenser water circuits must be analyzed and treated by a professional water treatment specialist familiar
with the operating conditions and construction materials used in Multistack modular chiller heat exchangers, headers and associated piping. Water quality
for modular chillers using 316 stainless steel brazed plate heat exchangers and carbon steel headers must be maintained within the following parameters:
Water Specications Specications with 25 Percent Glycol
ph >7 and <9 ph >7 and <9
Total Dissolved Solids (TDS) Less than 1000 ppm Total Dissolved Solids 1,000 - 10,000 ppm
Hardness as CaCO3 30 to 500 ppm Conductivity 1,000 - 15,000 ppm
Alkalinity as CaCO3 30 to 500 ppm Hardness as CaCO
Chlorides Less than 200 ppm Alkalinity as CaCO
3
> 500 ppm
3
30 - 500 ppm
Sulfates Less than 200 ppm Chlorides < 200 ppm
Sulfates < 200 ppm
Pipe System Flushing Procedure
Before connecting the chiller to the condenser and chilled water loop, the piping loops must be ushed with a detergent and hot water (110-130º F) mixture to remove any dirt and organic residue. After removing residue, continue ushing with a dilute phosphoric acid, sulfamic acid or citric acid and water
mixture to remove inorganic scale in the pipe. Cleaning chemicals such as Nu-Calgon “Imperial Grade” Scale Remover part number 4360-84 or equivalent
suitable for both organic residue and scale removal may be substituted. Otherwise detergents and acids shall not be combined unless approved by the
chemical manufacturers. Only chemicals compatible with 316 stainless steel, copper and carbon steel shall be used. (Any concentrations of hydrochloric or
sulfuric acid or chloride containing chemicals shall not be allowed to come in contact with copper brazed 316 stainless steel heat exchangers).
Caution: The use of unapproved chemicals in the chilled or condenser water supplies may damage the heat exchangers. These chemicals in-
clude, but are not limited to, hydrochloric acid, sulfuric acid, muriatic acid, and household bleach. Damage caused by the use of these and other
unapproved chemicals is not covered by warranty. The only approved chemicals for heat exchanger cleaning are phosphoric or sulfamic acids in
concentrations of 10 percent or less by volume. For more information contact your Multistack representative.
While ushing, 30-mesh Y-strainers (or equivalent) must be in place in the system piping and examined periodically as needed to remove collected residue.
The ushing process shall take no less than six hours, or until the strainers are clean after ushing. Old pipe systems with heavy encrustation shall be
ushed a minimum of 24 hours and may require as much as 48 hours before the lters run clean. Detergent and acid concentrations shall be used in strict
accordance with the respective chemical manufacturers instructions. After ushing with the detergent and/or dilute acid concentrations, the system loop
shall be purged with clean water for at least an hour to ush out all residual cleaning chemicals.
18
Page 19
Module Assembly
Multistack chiller modules and multiple module chiller arrays are designed to be mounted on steel rails.
Opposite End
Same End
1. Determine the entering and leaving evaporator and condenser connection arrangement before setting mounting rails and modules modules in place. Connections may be at the same end or opposite ends, depending upon jobsite requirements.
2. Chiller modules are to be mounted on 4- x 4- x 4-inch steel
rails or equivalent , 21 inches center-to-center.
4. Lubricate rails with vegetable shortening or other non-petroleum
lubricant to facilitate installation.
Vibration Pads
3. Place 4- x 4- x 3/8-inch wae type vibration pads every 22 inches
under rails. 50 PSI maximum loading.
Note: Seismic restraint information available from Multistack.
19
Page 20
Module Assembly
5. Place rst module on the rails.
7. Place subsequent modules onto rails.
6. Slide module into position.
8. Leave sucient space between modules to install
coupling gaskets.
9. Lubricate gaskets with solid vegetable shortening or
other non-petroleum based lubricant.
11. Install top joining bolts.
20
10. Slide modules together lining up footing holes. Install
bottom joining bolts.
12. Starting with the lower header, install pipe couplings. Position coupling bolts at one and seven o’clock positions as shown for proper frame
installation. Note: Assure proper strainer placement.
Page 21
Module Assembly
13. If adjustment is needed when tightening bolts, loosen the center
header bolt.
15. Install the header blank ends, starting at bottom,
then move to the top blank that includes drain valves
(evaporator shown).
14. The grooved heat exchanger couplings may also be loosened if
adjustment is required.
16. Install lter stop rings on module closest to piping take-o. The 9-inch
long pipe stubs supplied by Multistack are to be installed at the take-o ends
of the chiller.
B
A
17. The 3/4-inch drain valve (A), should be located on bottom
header and petcock valve (B) installed in each contractor pipe stub.
21
Page 22
Module Assembly - Total Access™ Modules
Multistack Total Access modular chillers are assembled into chiller arrays in the same manner as non-Total Access modules as shown on Pgs. 19-21.
Grooved ange water connections on Total Access chiller modules
joined into a chiller array.
Condenser side view of Total
Access chiller modules assembled into a chiller array. .
Evaporator side view of Multistack Total Access™ modules. (Optional enclosure panels not shown.)
22
Page 23
Multiush System Assembly
The following procedure describes installation of the Multiush automatic debris removal system. This system is
used periodically to remove dirt and debris from the from the chiller heat exchangers.
1. Attach Multiush pipe to module header pipe.2. Insert 30-mesh lter into header.
NOTE: See Pallet #3 for Multiush components, Page 10.
3. Install large grooved pipe couplings. Leave loose - do not tighten. 4. Attach Multiush pipe ttings using grooved couplings
5. Install manual or solenoid valve at end of Multiush header.
6. Tighten all ttings.
as shown.
Leak Testing
NOTE: Before leak testing make sure the four sensor wells have been installed.
After all piping connections are complete, make a static leak pressure test and seal
any leaks. When the leak test has proved satisfactory, start the chiller system pumps
and purge any air from the system. Seal any remaining leaks before proceeding.
23
Page 24
Electrical Installation
Field wiring must comply with all federal, state and local regulations. Circuit breakers, fuses, wiring and wire size must be installed per the National Electric
Code (NEC). Voltage applied to Multistack chillers must be within plus/minus 10 percent of nameplate voltage. Voltage imbalance between phases may
not exceed two percent. According to NEMA Standard MG-1-1998, a two percent voltage imbalance will cause a current imbalance of six to 10 times the
voltage imbalance. Voltage imbalance between electrical phases must be kept to a minimum. Most Multistack chillers come with a single point of electrical
connection (up to 500 amps) to simplify installation. The main electrical conduit feeding the power junction box may enter from either the top, bottom,
or left side of the panel when facing the panel. Chillers requiring more than 500 amps will have multiple electrical connection points (per the 500 amp
requirement).
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tagouts.
Optional Single Module Field Connection
For single module installations, the power junction box can be deleted, but a power phase monitor must be installed. The main electrical feed can connect
directly to the module circuit breaker.
NOTE: There is a dedicated chiller ground in this panel that must connect to a true earth ground.
Junction Box SupportElectrical Junction Box
1. Attach the electrical junction box support. Line up the orange posts to ensure support is not backwards. The threaded plate slides in between frame.
2. The electrical junction box may be installed on either end of the chiller module.
3. Remove cover plate on appropriate end of the junction box, then bolt junction box to the support.
4. Cut the junction box support leg to length and fasten to the bottom of box and then to the oor, if necessary.
5. Three-phase wire and the ground wire, sized according to the nameplate rating, should be run through the junction box.
Junction Box Support Leg
Buss bar Installation
NOTE: Contact the local Multistack representative before installing the buss bar. Depending on the start-up representative’s policy, the attachment of
the buss bar system, and power phase monitor to the electrician’s wire and lugs may be the responsibility of the electrician or the Multistack authorized start-up technician.
1. Remove the buss duct covers.2. Remove the isolation switch cover
24
Page 25
3. Install the three buss bar connector wires to the isolation
switch at each module. The wires are shipped with each
module.
5. After connecting the Line 3 lugs for all modules, cut the
orange insulation to t between the lugs. Install the lug
cover and snap the buss bar into the plastic holders.
4. Remove the orange insulation and install the buss bar
for Line 3 (back). Connect lug for Line 3 on each module.
6. Single-phase power for the modules should be taken o
two lines of the buss bar. Multistack recommends using
7. Follow the procedure in Step 5 to complete installation of
Lines 1 and 2.
Lines 1 and 3.
8. Follow the procedure in Step 5 to complete installation
of Lines 1 and 2.
9. With all three lines installed, use the provided overlap
pieces to cover any open buss bar areas.
DANGER: During installation, testing, servicing and troubleshooting this product, it may be necessary to work with live electrical components. Only
qualied licensed electricians or other properly trained persons may perform these tasks. Failure to follow all electrical safety precautions can result in
death or serious injury. All HVAC equipment must be installed per National Electric Code (NEC) and all applicable state/local codes.
25
Page 26
10. The ground bar must be drilled, then attached to the module
ground lug.
11. Reinstall the buss duct and isolation switch covers. Install
the main power connectors as shown.
12. Install the power phase monitor as shown. When correctly
installed the lettering on the power phase monitor is inverted.
Wires are run to the normally open contact of the power phase
monitor and connect to the master control.
NOTE: IT IS THE ELECTRICIAN’S RESPONSIBILITY TO CONNECT
MAIN POWER TO THIS CONNECTOR.
Single Point Power
On water cooled chillers with single point power, optional wire whips may be ordered and
substituted for the standard buss bar. The conduit, wiring and junction box are shipped as part
of the loose parts package. The wire and conduit are then connected to the junction box as the
modules are installed. Each wire and circuit breaker is marked for correct connection.
Each wire and circuit breaker is marked for correct
connection.
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tagouts.
26
Module wiring connections to the power junction
box must be completed by a qualied electrician.
NOTE: Be sure to replace all protective covers
after completing wiring connections.
Page 27
Typical Interconnecting Wiring. Consult the Specic, As-Built Submittal Wiring Diagrams
Multistack has a policy of continual improvement and reserves the right to change product design, literature and specications without notice.
DANGER: To avoid the risk of electrical shock, personal injury or death,
disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply. Assume all
electrical wires are live, energized wires. Use lockout/tagouts.
27
Page 28
System Wire & Fuse Sizing Specications
Compressor Rated Load Amps (RLA) and Locked Rotor Amps (LRA) Data
Standard and Total Access™ Modules
RLA/LRA
VOLTAGE208230460575
MS010X*13.1/13611.8/1365.9/66.14.7/55.3
MS015X24.8/24022.4/24011.9/1309.1/93.7
MS020X28.1/24025.4/24013.9/14010.7/107.6
MS030X49.8/34045.0/34022.5/17318.0/132
MS040X54.0/53849.0/53823.5/22919.5/180
MS050X67.0/60560.0/60530.0/27224.0/215
MS070X89.0/59980.0/59940.0/31032.0/239
MS085X112.8/943 102.0/943 51.0/40837.6/375
* MS010X units are also available for single-phase power (230/1/60 )
applications and have an RLA of 19.5 amps and LRA of 178 amps.
2. Fuse Sizing: Maximum Fuse (MF), Type RK5 Fuse
MF= (2.25 x RLA1*) + RLA2 + RLA3
Where MF does not equal a standard size fuse, the next larger size fuse should be used.
NOTES:
A. *RLA1 = RLA of the largest compressor in the system. RLA2 & RLA3 = RLA of the other compres-
sors in the system.
B. Total system Minimum Circuit Ampacity (MCA) shall not exceed 500A.
C. Wire sizing is based on the National Electrical Code (NEC) rating for 75°C copper wire, with 3
wires per conduit.
D. Wiring distance from branch circuit shall not exceed 100 feet.
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all
electrical power to the unit before performing any maintenance or service. The unit may have
more than one electrical power supply. Assume all electrical wires are live, energized wires. Use
lockout/tagouts.
28
Page 29
Frame & Panel Installation
Attachment of the optional enclosure panels is the responsibility of the Multistack authorized start-up technician. Typical installation is shown.
1. Install panel clips and spindle posts on the
outside four corners of module frame.
4. Install two long frames over spindle posts
vertically in rear (buss bar side). Attach top
frames to corner joints (use special frames
with seven holes for end modules only). Attach 20-inch horizontal frames, two in front,
one in rear.
2. Attach panel supports on outside of end modules.
3. Attach front frame section on module
(33-1⁄8 -inch pieces on bottom). Use “T”
connectors in front middle. The four corner
connectors go on top, front and rear.
5. Once the frame is assembled, attach the black fasteners and magnetic tape (or Velcro™ strips) to front
of support panels.
6. With the rst module frame and panels
complete, install the additional enclosures.
29
Page 30
INSTALLATION CHECKLIST & REQUEST FOR AUTHORIZED START-UP ENGINEER
CUSTOMER ORDER NO.: ________________________________
CHILLED WATERYesNoN/A
Piping complete and connected to Multistack Units.
Water system lled and vented.
Pumps installed (Rotation checked).
Recommended strainers installed.
Controls (3-way valves & by-pass valves, etc.) operable.
Water system operated and ow balanced to meet unit design requirements.
Strainers checked for unusual debris.
Flow or dierential pressure switch installed.
CONDENSER WATERYesNoN/A
Piping complete and connected to Multistack Units.
Cooling tower ushed, lled and vented.
Pumps installed (Rotation checked).
Recommended strainers installed.
Controls (3-way valves and by-pass valves, etc.) operable.
Cooling tower fans wired and operable.
Condenser water system operated.
Condenser & evaporator strainers must be checked, cleaned and free of debris.
Flow or dierential pressure switch installed.
ELECTRICALYesNoN/A
Power wiring complete and in accordance with nameplate rating on Multistack unit and prepared for connection in accordance with installation manual.
NOTE: No power is to be applied to unit prior to inspection by Multistack engineer.
All interlock wiring complete between control panel and complies with Multistack specications and with
applicable codes.
MISCELLANEOUSYesNoN/A
Thermometer wells, thermometer gauges, control, etc. installed.
A minimum system load of 50% of total building load is available for testing and
adjusting controls.
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
qqq
We understand that authorized representatives of the installing electrical and piping contractor must be available during the start-up period and that
coordination is our responsibility.
We further understand that the services of Multistack Authorized Start-up Engineer will be furnished for a period of not more than sixteen (16) consecutive
normal working hours and we agree that a charge for time and expenses will be made by Multistack if services are required for longer than sixteen (16)
consecutive normal working hours or if repeat calls are required through no fault of Multistack.
SignedTitle
Company Name, Company Location and Company Telephone
WATER SIDE AND INSTALLATION CHECKLIST CIRCLE CORRECT RESPONSE
1. Chiller mounted on rails and isolators? YES NO
2. Any visible damage, oil or refrigerant leaks? YES NO
If yes, detail: ________________________________________
3. All pipe work independently supported from chiller? YES NO
4. System sensor wells installed: CHILLED: IN OUT CONDENSER: IN OUT
5. Flow or dierential switches installed: CHILLED: ____ CONDENSER: ____
6. Operation of ow or dierential switches with reduction of 50%. P __________
8. Condenser 3-way by-pass valve? YES NO
If yes, Temperature set point: _____ °F
9. System strainers installed? CONDENSER: YES NOEVAPORATOR : YES NO
10. Install System sensors and apply thermal paste? YES NO
DESIGN PARAMETERS
1. ECHW ____________________
2. LCHW ____________________
3. CHW GPM ____________________
4. CHW P DROP ____________________
5. ECW ____________________
6. LCW ____________________
7. CW GPM ____________________
8. CW P DROP ____________________
ELECTRICAL AND CONTROLS CHECKLIST
1. All electrical connections tight and correct? YES NO
2. Power wiring sucient to carry F.L.A.? YES NO
3. Voltage levels: PHASES: 1 + 2 _______ 2 + 3 ________ 1 + G _______ 2 + G ________ 3 + G ________
4. Set module board addresses, run communication wire, do factory reset on Master Control? YES NO
5. Program system variable to site connections, date and time? YES NO
6. Verify demand for cooling? YES NO
7. Check temperature and pressure sensors through microprocessor display? YES NO
8. Check interlock operation: Stop chilled water pump? YES NO
Stop condenser water pump? YES NO
9. Provide training to contractor or owner? YES NO
9. Leave system in full operation? YES NO
10. Notify contractor of any problems? YES NO
Start-up Service Technician Owner or Contractor Acceptance
31
Page 32
Start-Up Data Log, Cont’d
Actual Setpoints
1. ECHW (Upset) ____________________
2. LCHW (Loset) ____________________
3. VSP __________________________
4. Control ________________________
5. TDIFF _________________________
6. Flush Dur. ______________________
*PC0 Program Version _________________
(Go to main menu screens then push PRG & UP buttons)
Measured Readings
1. CHW P Drop _____________________
2. CW P Drop ______________________
CURRENTTEMPERATURE
MODULE
ABCSuctLoChwSYS LCHWECHW
A
1
B
Factory Setup
1. Program Type __________________
C. CHW Bypass _________________
2. Chiller Type ___________________
D. CHW Min Output ______________
3. Refrigerant ___________________
E. CW Output __________________
4. Flow Faults: CHW ________________
F. CW Bypass __________________
CW _________________
G. CW Set point_________________
5. Circuit Type ___________________
H. CW Min Output _______________
6. Variable Flow __________________
I. CW PID ____________________
A. Valve Display ________________
J. CHW PID ___________________
B. CHW Output _________________
HPLP
10
2
A
B
A
3
B
A
4
B
A
5
B
A
6
B
A
7
B
A
8
B
A
9
B
A
B
11
A
B
A
12
B
32
Page 33
Operation
The Multistack chiller provides chilled water to an external load, based on return water temperature to the Multistack Master Control. When the entering
chilled water temperature sensor sends a signal to the master controller that cooling is needed, compressors will start and begin to produce chilled water.
A compressor start is determined by the entering chilled water (ECHW) upper set point and the variable set point setting in the Master Control System
Variables menu. When the ECHW sensor senses that the chilled water temperature has dropped below the set point, compressors will begin to cycle o.
Chiller modules equipped with modulating buttery valves on the chilled water side are controlled from the leaving chilled water set point (lower set point)
in the System Variables menu. The module slave board(s) send a 2-10 VDC output to each actuator to modulate the water valve to maintain lower set point.
When a module is not running, valves close to prevent bypassing water at the operating chiller modules.
For variable ow applications one or more valves may remain open at all times to provide minimum ow through the chiller. The valve that stays open will
always be the lead compressor for that day, eliminating the need for an external bypass installed at the chiller. If modulating buttery valves are used on
the condenser side of each module, the valves will control to a discharge pressure setting selected from the Factory Setup menu. This is also a 2-10 VDC
output each module board sends to the valve actuator. If the condenser pump cycles o while no modules are running, minimum ow doesn’t need to be
considered. If the condenser pump runs at minimum ow, the condenser bypass should be enabled in the Factory Setup menu.
Sequence of Operation, Leaving Chilled Water Temperature Control
The Multistack chiller is equipped with a microprocessor based supply water temperature controller. The chiller operates in response to leaving chilled
water (LCHW) set points.
AUTO (Toggle switch on machine)
In AUTO mode, the compressors operate as needed to maintain the LCHW set point. Cooling temperature control with CONTROL TO: set to LEAVING is based
on: LCHW SET POINT
LCHW OFFSET LCHW STAGE OFF
1. The Leaving Chilled Water (LCHW) set point default is 45 degrees F with a 35 to 80 degree ranges. The controller maintains this value within __ +/- of
the LCHW Oset.
2. The LCHW Oset default is 2 degrees F with a range of 0.5 to 10 degrees. This is the value above and below the LCHW Set point that compressors are
staged on and o.
3. The LCHW Stage O delay is defaulted to 30 seconds with a 5 to 180 second range. This allows for a delay between the shutting o of compressors in
Leaving Chilled Water control. If the system leaving temperature drops too far too quickly (2 degrees below where the previous compressor was to
shut o) the controls will allow one more compressor to shut o within that 30 seconds. That should be enough to back o the leaving temperature
so the over shoot condition doesn’t continue.
Modulating valves on the modules will control to the following in AUTO MODE:
The SYSTEM VARIABLE of CONTROL TO: Set to a value of LEAVING.
Evaporator valve will control to the LCHW SET POINT.
Variable Flow Chilled Water and/or Variable Flow Condenser Water
Motorized actuating valves for varying water ow through the evaporators and or condensers are factory installed on each heat exchanger. To accomplish
VFD chilled water and/or condenser water ow the system must control the chilled water pump and/or condenser water pump based on pressure drop
across the chiller. As a compressor starts a valve is opened and pressure drop decreases. The pump should then speed up to match the desired pressure
drop. Control of the pump is external to the chiller. Additionally, the chilled water loop must have a minimum ow bypass at the end of the loop (by others)
to maintain minimum ow through the chiller.
The valves on a Multistack chiller are dual purpose. First, a user dened number of valves can be programed to remain open at all times as a minimum
ow bypass through the chiller. This is selectable at the master controller or through the BAS with an optional web-portal. Second, the motorized valves
modulate to maintain leaving chilled water temperature control out of each heat exchanger. The bypass valve(s) will follow the lead compressor and
remain locked in a bypass position and rotate with the lead compressor. Remaining valves will open when corresponding compressors start. The compressor will then modulate for leaving water temperature control. Valves close when corresponding compressors shut o. When there is no demand for cooling
all valves are closed with only the pre-selected number of bypass valves remaining open for a minimum ow chiller bypass.
If all evaporators and condensers are equipped with variable ow valves the master controller, in conjunction with each corresponding slave controller, will
modulate the valves for simultaneous leaving chilled water and condenser head pressure control from each heat exchanger (with the exception of the heat
exchanger(s) programmed as the minimum ow chiller bypass).
33
Page 34
Factory Setup/Commissioning
Go to the System Variables Menu and select Factory Settings to access the program type and other setup information. Setup is to be done by the Multistack
authorized startup technician. Setup parameters are factory set to default values. Jobsite conditions must be congured at startup. To change these settings requires a password that is available to authorized service technicians by calling Multistack at (608-366-2400).
The Standard Program should be used on applications where no glycol is used in the chilled water side. In this mode the chilled water temperature cutout is
set at 34°F.
The Low Temperature Program should only be used in applications that have a minimum of 25 percent glycol in the chilled water loop. Cutout on low water
temperature in this mode is 20°F and the suction temperature cutout setting (with R-410A refrigerant) is set at 15°F.
Condenser Water Set-Point: If power-actuated buttery valves are used on the condenser side, this value should be set for the desired discharge pressure.
Depending on the condenser water inlet temperature this will adjust the valve to maintain the desired pressure.
Variable Flow: Select ENABLE if doing variable ow on the chilled or condenser side. If not, select DISABLE. To do variable ow, water control valves must
be installed on each module between the water header pipe and heat exchanger.
Bypass: Select ENABLE to leave the valve on the lead module open for minimum ow bypass. Select CHILLED WATER or CONDENSER WATER bypass. If no
valves are installed on the module keep this variable in the DISABLE MODE.
For information on basic control setup of the modules see the Multistack Comput 600 User manual.
Pressure Readings
The operating suction and discharge pressures in the system are directly related to water ow, condenser temperature, chilled water set-point, and system
cleanliness. Standard operating conditions with 95°F leaving condenser water and 45°F leaving chilled water temperature are discharge pressure at 325
psig ( 102°F saturated) and suction pressure at 114 psig (38°F saturated).
All water-cooled modules have a high pressure (HP) cutout safety device and a backup HP cutout switch. The HP cutout is 475 psig for a standard watercooled module with R-410A.
Each module also includes a low pressure (LP) safety cutout. The LP cutout is set in the module program at 50 psig.
If circuits are experiencing HP faults rst check to see that the cooling tower fan is operating. Next, verify proper water ow to the brazed plate heat
exchanger and conrm the strainer and lters are clean and free owing.
A LP fault is an indication of low refrigerant charge in the system. If a circuit trips out on a LP fault check the static pressure of the system while the circuit
is in the o mode. If pressures are low, check the circuit for possible leaks. The circuit can be pressurized to 15 psig with refrigerant and topped to 160 psig
with dry Nitrogen.
Maintenance
Use proper safety equiment, tools and procedures when operating and servicing this equipment. Be sure to review all safety warnings, cautions and notes
found on Pg. 3 of this manual.
Preventive Maintenance
Multistack publication MAINT-002-0416 provides heat exchanger preventative maintenance guidelines. Contact your Multistack representative for more
information. Multistack water cooled chillers, especially those with brazed plate heat exchangers, require careful control of the chilled and condensing
water circuits to prevent heat exchanger fouling. Refer to Multistack publication MAINT-001-0416 for water sample collection information.
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tagouts.
34
Page 35
Strainer Cleaning, Heat Exchanger Cleaning
All Multistack modules have a 30-mesh lter strainer in the condenser and evaporator inlet headers. The purpose of the strainer is to prevent debris from
entering the heat exchanger. An external “Y” or basket type system strainer should also be installed as a pre-lter to the Multistack strainers. There is
no pre-determined time for cleaning the strainer cartridges. The frequency of this process is dependant on the water quality in the condenser and/or
evaporator loop. Normally, debris in a water loop is takes the path of least resistance and accumulates in the last modules to receive water.
Multistack modules include the Multiush automatic blow down system installed on the condenser side of the last module in the chiller array. The
Multiush system is controlled by a timer in the Master Control and opens once a day to remove debris from the loop. Multiush does not eliminate the
need to pull and clean the strainers, but reduces the frequency.
The eect of debris buildup in the condenser water inlet lter cartridge will create nuisance HP (high pressure) faults. By checking the pressure dierential
between the inlet and outlet of the condensers, it can be determined if the strainers are contaminated. Refer to the MS 010-085X Product Data Catalog for
correct pressure drop of your model. For an MS070X module with a 10° F Delta T, the condenser side pressure drop should be 17’ / 7.4 psi; for chilled water
16’ / 7 psi. To keep HP faults from repeating, the strainers will need to be pulled and cleaned. If HP faults still occur after cleaning the strainer cartridges
the condenser pump should be checked for proper ow. If ow is not a problem the heat exchangers may need to be cleaned. Refer to Multistack Heat
Exchanger Cleaning Bulletin (MAINT-003-0416). Use this procedure to remove and clean the lter cartridges on the condenser side.
1. Turn o the chiller, shut down the condenser pump, and close the buttery/gate valves to the condenser.
2. Drain the water remaining in the condensers and header pipes by opening the drain valve in the pipe stubs or by removing the end grooved tting cap
on the Multiush system.
3. Remove the rst lter in the Multiush and remove all remaining lters in the bottom condenser header pipes.
4. Slowly open the top buttery / gate valve, allowing water to ow through the condensers and onto the oor for approximately 30 seconds. This will
push out any debris trapped in the bottom of the heat exchanger as the lters are removed.
5. Clean the lters with a hose, power washer, or wire brush as needed and re-install. Slide lters in until contacting the lter stop ring on the rst
module. Keep an extra set of strainers for quick re-installation. These lters are available for purchase through Multistack representatives.
6. Close the system by installing any grooved tting clamps previously removed.
7. Open the ¼-inch petcock bleed valves on the pipe stubs.
8. Fill the system by opening the bottom buttery/gate valve and lling from the bottom up. Close the ¼-inch petcock valves and open the top
buttery/gate valve after air has been bled from the system.
9. Start the condenser pump. Bleed any remaining air in the system once the pump has started and start the chiller.
If circuits trip out on Low Suction Temperature, or Low Chilled Water Temperature, check the chilled water inlet lter cartridge. The strainers are located
in the top header on the chilled water side. The previous instructions on condenser strainer removal do not need to be exactly followed. If the strainers
are clean the fault may be caused by a low ow condition or a low set point in the Master Control. If these possibilities are eliminated the evaporator heat
exchangers may need cleaning.
Compressor Oil Level
All compressors on water-cooled modules have an oil level sight glass on each compressor. Each module is run tested and the oil level is set at the factory.
R-410A scroll compressors are single stage and oil level is set at ⁄ – ¼ full sight glass. The compressor uses POE oil. Use Copeland type 998-E022 or Nu
Calgon 32-3MA. Call Multistack service at (608)366-2400 for factory oil charge for each compressor.
Refrigerant Charge / Evacuation
All water-cooled modules are factory charged to recommended refrigerant volumes. Prior to charging, each circuit is evacuated to 150 microns and held
15 minutes. The proper refrigerant charge for each module can be found on the module data plate. For proper charge on water-cooled modules, the circuit
should be charged until the sight glass clears.
Model Refrigerant Lbs. Per Circuit Oil Charge Per Circuit (in Pints)*
Multistack modules contain very short piping runs to the major components. Only a micro refrigerant charge (0.6 lbs. per ton) is used, and all circuits are
evacuated to 150 microns. For this reason a liquid line lter drier is not factory installed in the unit. When changing a major component in the system,
a replaceable core suction line lter kit can be added to reduce contamination. The suction lter kit can be purchased from Multistack through your local
representative.
Superheat/Subcooling
Subcooling is necessary in the system to prevent ash gas as the refrigerant enters the expansion valve. Multistack uses a mechanical-type expansion valve
on all modules. Clockwise adjustment of the valve increases superheat. On water-cooled modules, superheat is set at 10°-12°F during the factory run test.
Multistack condensers are sized so that liquid refrigerant subcooling occurs without a separate subcooler. The general range of subcooling is 10°-20°F.
Daily Log Sheet
Log sheets foud at the back of this manual can be used daily, weekly or as desired to record operation characteristics of the chiller. The information recorded
on the log sheet can also help diagnose potential system problems.
Annual Maintenance
DANGER: To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tagouts.
Annual maintenance requirements for Multistack Chillers involve proper shut-down of the machine and cleaning of the heat exchangers. The Preventative
Maintenance bulletin (MAINT-002-0416) and Heat Exchanger Cleaning bulletin (MAINT-003-0416) describe the recommended procedures for both
processes. Multistack makes available the 151A Cleaning Kit to assist with this process. Refer to the 151A Cleaning Kit bulletin for more details.
Also check annually:
• All electrical components (contactors, fuses, relays, etc.) to identify any signs of excessive wear. Check for tight connections.
• Superheat, pressure gauges, oil levels, Master Controller condition, and sensor accuracy should also be checked.
• Exercise all isolation valves, manual or power operated.
Compressors
In the event of a compressor failure, determine the cause. A motor burn due to a fault in the motor insulation is quite rare. Most burnouts are actually
caused by a mechanical condition or lubrication problem. In the event of a burnout, proper clean up procedures should be followed.
1. Check all electrical components of the circuit (contactors, fuses, wires, etc.)
2. If necessary do a system clean up. Nu-Calgon RX-11 ush, or Sporlan System Cleaner work well.
3. Install a suction lter drier with burnout core.
4. Evacuate the system to a minimum of 500 microns and hold for 20 minutes.
5. Charge the circuit with virgin refrigerant. Charge with liquid into the discharge side. See proper refrigerant charge on nameplate data of unit.
6. Run the system 2-3 weeks with burnout lter core. Replace with standard core drier
Heat Exchanger Cleaning
Multistack publication MAINT-003-0416 provides procedures for cleaning heat exchangers. Contact your Multistack representative for more information.
36
Page 37
Troubleshooting
Multistack modular chillers use the Carel PCO3 master control. A user manual for the PCO3 controller is supplied with the submittal package. The user
manual details the dierent status screens and explanations of system or module faults. Use the following guide to troubleshoot modules and the PC03
controller.
FaultSolutionFaultSolution
• Turn chiller on
• Check sensors
• Check load limit setting in system variables
• Check VSP setting is system variables
• Check entering CHW sensor location
• Look for system problem (low water Volume,
low load)