Multiquip GLW-180H User Manual

PARTS AND OPERATION MANUAL
MULTIQUIP
Model GLW-180H
D.C. WELDER
A.C. GENERATOR
© COPYRIGHT 2004, MULTIQUIP INC.
Revision #5 (03/14/05)
MULTIQUIP INC
E-mail:mq@multiquip.com www:multiquip.com
Atlanta • Boise • Dallas • Houston • Newark Montreal, Canada • Manchester, UK Rio De Janiero, Brazil • Guadalajara, Mexico
..
. PARTS DEPARTMENT:
..
SERVICE DEPARTMENT/TECHNICAL ASSISTANCE:
WARNING
CALIFORNIA
Proposition 65 Warning
This product contains or produces chemicals known to the State of California to cause cancer and birth defects
(or other reproductive harm).
PAGE 2 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
DCL160
HERE'S HOW TO GET HELP
PLEASE HAVE THE MODEL AND SERIAL NUMBER ON-HAND WHEN CALLING
PARTS DEPARTMENT
800-427-1244 or 310-537-3700 FAX: 800-672-7877 or 310-637-3284
SERVICE DEPARTMENT/TECHNICAL ASSISTANCE
800-478-1244 or 310-537-3700 FAX: 310- 537-4259
WARRANTY DEPARTMENT
888-661-4279, or 310-661-4279 FAX: 310- 537-1173
MAIN
800-421-1244 or 310-537-3700 FAX: 310-537-3927
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 3
TABLE OF CONTENTS
Here's How To Get Help ............................................ 3
Table Of Contents ..................................................... 4
Parts Ordering Procedures ....................................... 5
Rules For Safe Operation ......................................... 6
Operation and Safety Decals .................................... 7
Specifications ............................................................ 8
General Information .................................................. 9
Multiquip GLW-180H — AC Generator And Welder
Controls and Indicators ........................................... 10
Instrumentation ....................................................... 11
Installation .......................................................... 12-13
Pre-Setup ........................................................... 14-15
Load Application ..................................................... 16
Operating Instructions (Generator) ........................ 17
Operating Instructions (Welder)......................... 18-19
Maintenance ........................................................... 20
Preparation For Long Term Storage ....................... 21
Wiring Diagram ....................................................... 22
Troubleshooting (Engine) ................................... 23-24
Troubleshooting (Generator/Welder) ................. 25-26
Explanation Of Codes In Remarks Column ............ 28
Suggested Spare Parts ........................................... 29
Generator Assembly .......................................... 30-31
Control Box Assembly ........................................ 32-33
Control Box Assembly ........................................ 34-35
Pipe Frame Assembly ........................................ 36-37
Muffler Assembly ............................................... 38-39
Nameplate and Decals....................................... 40-41
Honda GX340K1 Engine
Cylinder Head Assembly ....................................42-43
Recoil Starter Assembly.....................................44-45
Fan Cover Assembly .......................................... 46-47
Camshaft/Valves Assembly ................................ 48-49
Piston/Rings Assembly.......................................50-51
Air Cleaner Assembly.........................................52-53
Cylinder Barrel (Recoil) Assembly ..................... 54-55
Cylinder Barrel (Electric) Assembly ................... 56-57
Crankcase Cover/Governor Assembly ..............58-59
Flywheel/Fan Assembly .....................................60-61
Coil Assembly..................................................... 62-63
Crankshaft Assembly .........................................64-65
Electric Start Assembly ......................................66-67
Governor Controls Assembly ............................. 68-69
Carburetor Assembly .........................................70-71
Solenoid Assembly ............................................. 72-73
Fuel Cock Assembly ..........................................74-75
Terms and Conditions Of Sale — Parts .................. 76
NOTE
Specification and part number are subject to change without notice.
PAGE 4 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
PARTS ORDERING PROCEDURES
■■
Dealer account number
■■
■■
Dealer name and address
■■
■■
Shipping address (if different than billing address)
■■
■■
Return fax number
■■
■■
Applicable model number
■■
■■
Quantity, part number and description of each part
■■
■■
Specify preferred method of shipment:
■■
UPS Ground
UPS Second Day or Third Day*
UPS Next Day*
Federal Express Priority One (please provide us with your Federal
Express account number)*
Airborne Express*
Truck or parcel post
*Normally shipped the same day the order is received, if prior to 2PM west coast time.
Earn Extra Discounts when
you order by FAX!
All parts orders which include complete part numbers and are received by fax qualify for the following extra discounts:
Number of line items ordered Additional Discount
1-9 items 3%
10+ items** 5%
Get special freight allowances when you order 10 or more line items via FAX!**
■■
UPS Ground Service at no charge for freight
■■
■■
PS Third Day Service at one-half of actual freight cost
■■
No other allowances on freight shipped by any other carrier.
**Common nuts, bolts and washers (all items under $1.00 list price) do not count towards the 10+ line items.
Extra Fax DiscountExtra Fax Discount
Extra Fax Discount
Extra Fax DiscountExtra Fax Discount
for Domestic USAfor Domestic USA
for Domestic USA
for Domestic USAfor Domestic USA
Dealers OnlyDealers Only
Dealers Only
Dealers OnlyDealers Only
Now! Direct TOLL-FREE access
to our Parts Department!
Toll-free nationwide:
800-421-1244
Toll-free FAX:
*DISCOUNTS ARE SUBJECT TO CHANGE*
Fax order discount and UPS special programs revised June 1, 1995
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 5
800/6-PARTS-7 • 800-672-7877
RULES FOR SAFE OPERATION
CAUTION:
Failure to follow instructions in this manual may lead to serious injury or even death! This equipment is to be operated by trained and
qualified personnel only! This equipment is for industrial use only.
The following safety guidelines should always be used when operating the GLW-180H Generator/Welder:
GENERAL SAFETY
DO NOT operate or service this equipment before reading this entire manual.
This equipment should not be operated by persons under 18 years of age.
NEVER operate this equipment without proper protective clothing, shatterproof glasses, steel-toed boots and other protective devices required by the job.
This generator is a source of potentially LETHAL high voltage. Never permit unqualified personnel-especially children to operate the generator.
Always refuel in a well-ventilated area, away from sparks and open flames.
Always use extreme caution when working with flammable liquids. When refueling, stop the engine and allow it to cool.
DO NOT
could result from fuel vapors, or if fuel is spilled on a hot engine.
This generator is equipped with a protection. Always complete the grounding path from the generator to an external grounding source.
NEVER operate this generator, or handle any electrical equipment while standing in
hands are wet, or in the rain. Electrical shock could occur causing severe bodily harm or even death.
Keep electrical cords in good condition. Worn, bare or frayed wiring can cause electrical shock, leading to
even death.
This generator requires an adequate free flow of cooling air. Never operate the generator in any enclosed or narrow area where free flow of the air is restricted. If the air flow is restricted it will cause serious damage to the generator and may cause injury to people.
NEVER touch the hot exhaust manifold, muffler or cylinder. Allow these parts to cool before servicing generator.
smoke around or near the machine. Fire or explosion
ground terminal
for your
water, while bare foot, while
bodily harm or
Provide adequate ventilation when operating the generator. DO NOT operate the generator in any enclosed or narrow space. The generator's GLWsoline engine gives off DEADLY
carbon monoxide GLWs
NEVER operate the generator in an explosive atmosphere or near combustible materials. An explosion or fire could result causing severe
Always make sure that the generator is secure on level ground so that it cannot slide or shift around, endangering workers. Also keep the immediate area free of bystanders.
When using a concrete vibrator or a similar device that is immersed in a water based solution, make sure the device is equipped with short circuit protection.
Always use rubber boots and gloves when operating a concrete vibrator or similar device.
Use adequate size connecting cable for extension.
Maintain electrical cords in good condition and frequently replace the entire cable of the concrete vibrator with a new one.
High Temperatures – Allow the machine and engine to cool before adding fuel or performing service and maintenance functions. Contact with burns.
Emergencies
Always know the location of the nearest and
first aid kit
Also know the phone numbers of the nearest
doctor
invaluable in the case of an emergency.
Maintenance Safety
NEVER lubricate components or attempt service on a running machine.
Always allow the machine a proper amount of time to cool before servicing.
Keep the machinery in proper running condition.
Fix damage to the machine immediately and always replace broken parts.
Dispose of hazardous waste properly. Examples of potentially hazardous waste are used motor oil, fuel and fuel filters.
DO NOT use food or plastic containers to dispose of hazardous waste.
DO NOT pour waste, oil or fuel directly onto the ground, down a drain or into any water source
bodily harm or even death.
. Know the location of the nearest telephone.
and
fire department
.
hot
components can cause serious
fire extinguisher
ambulance
. This information will be
,
PAGE 6 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
OPERATION AND SAFETY DECALS
Machine Safety Decals
The GLW-180H portable generator is equipped with a number of safety decals. These decals are provided for operator safety and maintenance information. The illustration below shows these decals as they appear on the machine. Should any of these decals become unreadable, replacements can be obtained from your dealer.
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 7
GLW-180H — SPECIFICATIONS
H081-WLGsnoitacificepS.1elbaT
tnerruC.xaMspmA081
egatloVdetaRstloV4.62
redleW
rotareneGelcyC06
elcyCytuD%05
egnaRtnerruCelbatsujdAspmA081-05
tnerruCdetaRspmA0
eziSedortcelEelbacilppA"23/5-"46/5
rotanretlAepyT dleiFgnivloveRepyTsselhsurB,elop-2
ptuO.xaMsttaW0054
tu
)suounitnoc(tuptuOdetaRsttaW0004
egatloVdetaRCAV021
tnerruCdetaRspmA3.33
esahP )eriw-3(esahP
ycneuqerFzH06
deepSdetaRMPR0063
rotcaFrewoP%001
ledoMDV1K043XGadnoH
epyT rednilycdednilcni°52HVOek
ekortSXeroB
orts4delooc-riA
61
elgniS
.ni25.2X.ni32.3
)mm46Xmm28(
tnemecalpsiDcc36.02
enignE
)HXWXL(noisnemiD
gieWteNyrD
th
tuptuOxaM.M.P.R0063/.P.H0.8
paCknaTleuF snollaG.S.U4/3-3.xorppA
ytica
leuF enilosaGelibomotuAdedaelnU
yticapaCliOebuLstnip4/3-1
deepS epyTthgiew-ylFlagufirtneC
dohteMlortnoC
dohteMgnitratStratSlioceR
.ni22x22x5.13
).mm065x065x008(
).gK531(.sbl792
Effects of Altitude and Heat
The maximum output of the engine listed above is applicable to supplying electrical power for continuous service at ambient conditions in accordance with SAE Test cord J607. The above ambient conditions are at standard sea level, with a barometric reading of 29.92 inches and a temperature of 60 degrees fahrenheit.
°°
°
°°
Generally, the engine output power will decrease 3-1/2% for each 1000 feet of altitude above sea level, and 1% for each 10
°°
°
fahrenheit above the standard temperature of 60
°°
F .
F
PAGE 8 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — GENERAL INFORMATION
WARNING:
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch.
Serious injury or death may result without this transfer switch.
GLW-180H FAMILIARIZATION Generator/Welder
The Multiquip Model GLW-180H generator has been designed as a portable lightweight power source for 60 Hz (single­phase) vibrators, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
This generator is powered by a HONDA GLWsoline engine. The alternator, a brushless revolving-field type, is permanently aligned to the engine through rigid coupling.
The generator is mounted on rubber vibration isolators that have a steel base backplate which is attached to the protective steel pipe carrying frame. The protective carrying frame is made of steel tubing and fully wraps around the generator to protect aGLWinst damage.
This portable generator is supplied with a electrical
box
. To reduce vibration caused by the engine, the control
box is also placed on rubber isolators.
control
Excitation System
All GLW-series generators use a magnet attached to a flywheel to produce AC voltage from a lamp coil beneath the flywheel. As the magnet passes the coil it produces approximately 19-22 AC volts.
This voltage (19-22 VAC) is then sent to the control box that contains three rectifying diodes:
z
Excitation (diode 1)
z
Battery (diode 2)
z
Slow Down (diode 3)
The AC voltage will pass through the excitation diode that converts the voltage to DC power.
This DC power is then sent to the excitation windings housed within the main windings commonly called the "stator".
This voltage is then transferred into the rotor through induction. The rotor contains two diodes within it which rectify the DC voltage and send it out through the main windings, as AC voltage.
Engine
The four-cycle air-cooled HONDA GLWsoline engine is designed to meet every performance requirement of this generator. Reference Table 1, page 8 for engine specifications.
Figure 1 (page 10) shows the basic controls and indicators for the GLW-180H generator.
Control Box
The control box has the following: (all outputs are 60 Hz, single phase)
z
One 120V output receptacle.
z
One 120V output receptacle (GFCI protected).
z
One main 40 amp circuit breaker.
z
AC Voltmeter
z
Idle Control Switch
z
Operation Switch
z
Output Terminals (Welding)
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 9
Idle Control Switch
DO NOT use the idle control switch in conjunction with AC
electro-magnetic switches relays etc. Using the idle control switch with these devices will cause the idle control device not to actuate. If any of these devices are being used, leave the idle control switch in the
When running capacitor start motors such as submersible pumps, the idle control switch should Disconnect the pump or tool from the power source by switching OFF the main circuit breaker.
OFF
position.
NOT BE USED.
NOTE
In keeping with Multiquip's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
GLW-180H — CONTROLS AND INDICATORS
Figure 1. Controls and Indicators
PAGE 10 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — INSTRUMENTATION
CAUTION :
When using a combination of dual receptacles, total load should not exceed the rated capacity of the generating.
The definitions below describe the controls and functions of the of the GLW-180 H Generator/Welder.
1. Ground Terminal Equipment – If required ground equipment (power tools etc,) to this ground terminal. This ground is not
2. 120 VAC Twist Lock Receptacle – This unit is supplied with one
EARTH
Twist Lock
output receptacle.
3. 120 VAC GFCI Receptacle – This unit is supplied with one
Duplex
NEMA (GFCI) 5-20R (120V, 20 Amp) output
receptacle.
4. AC Voltmeter – This voltmeter indicates (with a mark) the rated 60 Hz, 120 VAC addition the voltmeter can also be used as a diagnostic tool.
ground.
NEMA L5-30R (120V, 30 Amp)
single phase output voltage
7. Current Regulator – Use this dial to adjust the welder's
output to the desired setting.
8. Idle Control Switch – This unit is provided with an automatic idle control for noise suppression and reduced fuel consumption. The automatic idle control automatically enGLWges under a no-load condition.
With the automatic idle control switched “ON”, the engine revolutions will automatically drop to about 2500 rpm (low­speed operation) within 3 seconds after the load stops.
When the operation is resumed, the engine speed is automatically increased to about 3600 rpm (high-speed operation) as soon as the load is connected.
9. Current Regulator Selector Switch – Two position switch,
left
amps), (max.-180).
10. DC Output Terminals – Connect the welder's (+) and (-) welding cables to these terminals.
11. Fuel Tank – The fuel GLWuge is located on the fuel tank
. In
and allows easy monitoring of the fuel level.
12. Chassis Ground – Connect earth ground ( to this lug. See Figure 3.
position selects minimum current output (min.-130
right
position selects maximum current output
ground rod
)
If the voltmeter indicator (needle) is below the rated voltage, engine problems may exist (low/high RPM's). To prevent damage to the generator or power tools turn the generator OFF and consult your authorized Multiquip service dealer.
5. Circuit Breaker – This single-pole, 40 amp breaker is provided to protect both 120 VAC output receptacles from overload.
6. Operation Switch – Must be in the up position ( normal operation. To turn-off generator place this switch in
OFF
the down position (
).
ON
) for
CAUTION :
NEVER turn the load ON or OFF by
connecting and disconnecting the load power cord from the generator's AC output receptacle. ALWAYS turn the circuit breaker OFF to remove power from the 120 AC recepracles (load).
CAUTION :
When AC power is required, ALWAYS place the current regulator dial in the
power using range
Figure 2. Current Regulator Switch
AC Power Range
.
AC
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 11
GLW-180H — INSTALLATION
Outdoor Installation
Install the generator in a location where it will not be exposed to rain or sunshine. Make sure that the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.
The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear, not only to the engine parts, but also to the alternator parts.
CAUTION :
Pay close attention to ventilation when operating the generator inside confined areas. The engine exhaust contains noxious elements.
Indoor Installation
Exhaust GLWses from GLWsoline engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves
CAUTION :
Generator Grounding
To guard aGLWnist electrical shock and possible damage to the equipment, it is important to provide a good ground.
Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building (Figure 3) as close to the point of cable entry as practical.
NEC articles 250-91a and 250-95 set the following grounding requirements:
1. Use one of the following wire types to connect the generator to earth ground.
a. Copper - 10 AWG (5.3 mm2) or larger. b. Aluminum - 8 AWG (8.4 mm2) or larger.
2. When grounding the generator (Figure 3) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.
3. NEC article 250-83c specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.
An
electric shock
vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from a short circuit.
is apt to happen when
EARTH
Eliminate the danger of deadly carbon monoxide GLWs. Remember that exhaust fumes from any GLWsoline engine are very poisonous if discharged in a closed room, but harmless if allowed to mix with the outside air. If the generator is installed indoors, you must make provisions for venting the engine exhaust to the outside of the building.
PAGE 12 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.
NOTE
Grounding
GLW-180H — INSTALLATION
Figure 3. Generator Ground Rod Application
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 13
GLW-180H — PRE-SETUP
General Inspection Prior to Operation
This generator has been thoroughly inspected and accepted prior to shipment from the factory. However, be sure to check for damaged parts or components, or loose nuts and bolts, which could have occurred in transit.
Ground
The nut and ground terminal on the generator should always be used to connect the generator to a suitable ground. The ground path should be of #8 size wire.
Connect the terminal of the ground wire between the lock washer and the nut at the base of the generator and tighten the nut fully. Connect the other end of the ground wire to a
grounding rod
as shown in Figure 3.
Circuit Breaker
To protect the generator from an overload,
amp circuit breaker is provided on the control box. Make sure to switch this circuit breaker to the "OFF" position prior to starting the engine.
Extension Cable
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 2 ) as a guide for selecting the proper extension cable size.
a single-pole 40
)noitarepOesahPelgniS,zH06(noitceleSelbaCnoisnetxE.2elbaT
nIdaoL
nitnerruC
serepmA
sttaW
021tA
stloV
eriW01#eriW21#eriW41#eriW61#
htgneLelbaCelbawollAmumixaM
5.2003.tf0001.tf006.tf573.tf052
5006.tf005.tf003.tf002.tf521
5.7009.tf
053.tf002.tf521.tf001
010021.tf052.tf051.tf001
510081.tf051.tf001.tf56
020042.tf521.tf57.tf05
amadtnempiuqE:NOITUAC
.egatlovwolmorftlusernaceg
PAGE 14 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — PRE-SETUP
Lubrication Oil
Fill the engine crankcase with lubricating oil through the filler hole, but do not overfill. Make sure the generator is level. With the dipstick inserted all the way, but without being screw
Fuel
Close the fuel cock before filling the tank. Fill the fuel tank with clean and fresh unleaded GLWsoline. DO NOT fill the tank beyond capacity.
into the filler hole, verify that the oil level is maintained between the two notches on the dipstick.
Pay attention to the fuel tank capacity when replenishing fuel. Refer to the fuel tank capacity listed on page 8
The oil listed in Table 3 is recommended to ensure better
Specification Table 1.
engine performance. Use class SC or higher grade motor oil.
egnaRerutarepmeTliOepyT
F°32~F°401
)C°5-~C°04(
F°5~F°32
)C°51-~C°5-(
woleB)°51-(C°503-W0
liOrotoMdednemmoceR.3elbaT
03EAS
03-W01easro02EAS
1EASroW01EAS
The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does not have a spout, use a funnel.
CAUTION :
Never fill the
fuel tank
while the engine is running or in the dark. GLWsoline spillage on a hot engine can cause a fire or explosion. If GLWsoline spillage occurs, wipe up the spilled GLWsoline completely to prevent fire hazards.
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 15
GLW-180H — LOAD APPLICATION
Single Phase Load
Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.
Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.
NOTE
If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
To determine the running wattage for your load, multiply the running wattage as indicated by steps 1, 2, and 3 below:
CAUTION:
An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable.
The idle control is operated at minimum load capacity of 100W. If the load capacity is less than 100W, throw the idle control switch to the OFF position.
Motors and motor-driven equipment draw much greater current for starting than during operation.
1. INCANDESCENT LOADS Lights, heaters and similar appliances. Total the running wattage and multiply by 1. Example: 29 light bulbs @ 100W each = 2.9 KW use a 3 KW generator.
2. SMALL MOTORS Drills and other small power tools. Total the running wattage and multiply by 2. Example: A 1 inch drill runs at 1 KW use a 2 KW generator.
3. LARGE MOTORS Submersible pumps, table saws etc. Total the running wattage and multiply by 3. Example: A conveyor belt runs at 8 KW use a 24 KW generator.
PAGE 16 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — GENERATOR OPERATING INSTRUCTIONS
Before Starting
1. Be sure to disconnect the electrical load and switch the main circuit breaker to the “OFF” position prior to starting the engine.
2. Never start the engine with the main circuit breaker “ON”.
3. Check the lubricating oil level prior to starting the engine. Make sure the generator is level. The oil level must be maintained between two notches on the dipstick.
4. When there is not enough lubricating oil, fill the crankcase with high grade motor oil. Use a high quality detergent oil classified SC, SD or SE. (See Table 3 on page 15)
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
z
NEVER start the engine when the oil level is below the lower mark on the dipstick.
z
Check the fuel level on the fuel GLWuge. When fuel is low, fill the fuel tank with clean fresh unleaded automotive GLWsoline.
z
If GLWsoline spillage occurs, completely
Starting
1. Place the idle control switch in the “ON” (up) position.
2. Close the choke. Adjust the opening of the choke valve according to operating conditions. When the engine is warm or the air temperature is high, close the choke valve halfway or open it all the way.
3. Confirm that the main circuit breaker on the generator control box is “OFF”.
wipe up the spilled GLWsoline.
Warm up
1. When the engine starts, open the choke slowly.
2. Run the engine at low speed for 3 minutes without load until the engine warms up.
3. Turn the idle control switch to the "OFF" (down) position and check the voltage by referring to the voltmeter on the control box.
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
1. Check the generator for abnormal noise and smells. Then connect the load to the receptacles of the generator.
2. Switch the main circuit breaker to the “ON” position and turn the idle control switch to the “ON” (down) position for normal (load) engine operation.
Operation
Check the voltage by referring to the voltmeter on the control box. When the voltmeter indicates 120 volts, 120 volts from the 120V receptacles and 240 volts from the 240V receptacle can be obtained at the same time. Refer to Figure 1, Controls and Indicators, item 4 on page 10.
Stopping the Engine
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
DO NOT change the engine speed control
lever which has been set at the factory prior to shipping.
4. Set the operation switch to the “ON” position and grasp the starting rope and slowly pull it out. The resistance becomes hardest at a certain position, corresponding to the compression point. Rewind the rope a little from that point and pull out sharply.
5. If the engine fails to start, repeat the procedure.
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
z
DO NOT pull the starter rope all the way to the end.
z
DO NOT release the starter rope after
pulling. Allow it to rewind as soon as possible.
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 17
1. Remove the load from the generator. Place the circuit breaker in the “OFF” position. Refer to Figure 1, item 5 on page 10. Run the engine (no-load) with the idle control switch set to the ON position for three to five minutes, then stop the engine.
2. Turn the START/STOP switch to the “STOP” position.
3. Never stop the engine suddenly while running at high speed.
4. Close the fuel cock.
NEVER stop the engine suddenly while running at high speeds.
GLW-180H — WELDER OPERATING INSTRUCTIONS
Welding Cables and Polarities
Connect the welding cables (Figure 4) to the welder's output terminals located on the control panel. The output terminals have (+) and (-) polarities. Select the appropriate polarities according to the application (See Welding Application, Table 5).
NOTE
Attach terminal connectors at the end of each cable. NEVER connect exposed wires (Figure 5) directly to the terminal. Exposed wiring may cause shocks or di-electric breakdown from poor contact.
Figure 4. Welding Cable Connection
(Correct)
YTIRALOPDOHTEMGNIDLEWSNOITACILPPALACIPYT
...
)+(
ytiraloPthgiartS
ytiraloPesreveR
...
)+(
nidraugeR:etoN
.rekameriwehtmorfsnoitcurtsni
Figure 5. Welding Cable Connection
(Incorrect)
snoitacilppAgnidleW.4elbaT
)lateMesaB(gnidnuorG
redloHredleW...)-(yol
redloHredleW...)+(
setalpniht
)lateMesaB(gnidnuorGleetssselniatsfognidlewcrA
larenegrofslairetamleetsgnidleW
.setalpssenkcihtdna,serutcurts
lareppocrofgnidlewcrA
fognidlewCRA,gnidlewpu-dliuB
ehtwollof,scitretcarahcVCehtniytiralopehtfonoitcelesehtg
PAGE 18 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — WELDER OPERATING INSTRUCTIONS
Welding Cables
The required cable welding size is governed by this simple rule: The longer the welding cable, or the greater the welding
Duty Cycle
The duty cycle for the generator/welder is based on 10 minute intervals. See Table 6 below.
current, the thicker (copper strands) the calbe must be.
Select a welding cable with adequate thickness according to the cable length and welding amperage (current) as listed in Table 5.
seziSelbaCredleW.5elbaT
tuptuOredleW
tnerruC
001
htgneLelbaCeziSelbaC
053.oN
0013.oN
5213.oN
0513.oN
0023.oN
0523.oN
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
1. Connect the welding cables (electrodes) to the
0033.oN
053.oN
0013.oN
5213.o
051
0513.oN
0022.oN
0521.oN
N
generator's output terminals (Figure 4). For welding current (min-130 amps), use an eyelet terminal connector with a 5/64" to 1/8" diameter, for welding current (110 - max amps), use an eyelet terminal connector with a 3/32" to 5/32" diameter
2. Set the current
panel (Figure X) to the desired setting. The is for
gnidleW
tnerruC
ytuD
%elcyC
NEVER switch
low
current, the
elcyCytuD.6elbaT
ro011
sseL
00108060504
switch the
521541061081
current range selector
during any welding operation.
minimum
maximum
regulator control switch
on the control
inner
outer
scale is
high
current output.
scale
0031.oN
053.oN
0013.oN
5213.oN
002
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
0512.oN
0021.oN
0520/1.oN
0030/1.oN
Figure 6. Current Regulator/Range Switches
To prevent serious accidents, ALWAYS turn off the generator/welder ( operation switch) and set the main circuit breaker to the OFF position.
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 19
3. Set the current
low
or
high
range control switch
. DO NOT change the position of this switch
while welding.
(Figure 7) to either
GLW-180H — MAINTENANCE
General Inspection
At least daily or prior to each use, the generating set should be cleaned and inspected for deficiencies. Check for loose, missing or damaged nuts, bolts or other fasteners. Also check for fuel or oil leaks.
Engine Side (Refer to the Engine Instruction Manual)
Check Oil Level
Check the crankcase oil level prior to each use, or when the fuel tank is filled. Make sure the generating set is level. The oil level must be between the two notches on the dipstick.
Changing Oil
Change oil after the first 20 hours of operation. Drain and refill the engine crankcase every 50 operating hours or once a week thereafter. Drain crankcase oil into a suitable container while engine is still warm. Replace the drain plug tightly. Add oil through the filler hole.
Air Cleaner
Every 50 hours: Remove air cleaner element (std. or heavy duty types), and wash in kerosene or liquid detergent and hot water. Wrap foam element in a cloth and squeeze dry. Wipe heavy duty paper element dry with toweling. Saturate element with kerosene; squeeze excess from foam element. Wipe excess from heavy duty paper element.
Service Daily
If engine is operating in very dusty and dry grass conditions. A clogged air cleaner will result in high fuel consumption, loss of power and excessive carbon buildup in the combustion chamber.
Cleaning the Fuel Strainer
Clean the fuel strainer if it contains dust or water. Remove dust or water in the strainer cap and wash it in GLWsoline. Securely fasten the fuel strainer cap so that fuel will not leak. Check the fuel strainer every 200 hours of operation or once a month.
Spark Plug
Remove carbon build-up on the spark plug (Figure 5) with a wire brush. Set the spark plug GLWp to 0.6—0.7mm (0.024-
0.028 inch). Tighten with a spark plug socket wrench. Clean the spark plug every 50 operating hours or once a week.
Figure 5. Spark Plug GLWp
PAGE 20 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — PREPARATION FOR LONG -TERM STORAGE
Generator Storage
For storage of the generating set for over 30 days, the following is required:
z
Drain the fuel tank completely.
z
Run the engine until the GLWsoline in the carburetor is completely consumed.
z
Completely drain the oil from the crankcase and refill with fresh oil.
z
Remove the spark plug, pour 2 or 3 cc of SAE 30 oil into the cylinder and crank slowly to distribute the oil.
z
Slowly rotate the engine a few times with the starter Rope and install a new plug.
z
Pull out the starter rope slowly and stop at the compression point.
z
Clean all external parts of the generating set with a cloth.
z
Cover the generating set and store in a clean, dry place.
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 21
GLW-180H — WIRING DIAGRAM GENERATOR/ ENGINE
GENERATOR
ENGINE
PAGE 22 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
GLW-180H — TROUBLESHOOTING (ENGINE)
Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, please take a remedial action following the
diagnosis based on the Engine Troubleshooting (Table 7) information shown below and on the proceeding page. If the problem cannot be remedied, please leave the unit just as it is and consult our company's business office or service plant.
MOTPMYS MELBORPELBISSOP NOITULOS
?tignihcaersi
?leuFoN leuFddA
?knatleufniretaW .knatleufecalperrohsulF
?deggolcretlifleuF retlifleufecalpeR
?roterubrackcutS .msinahcemtaolfkcehC
gnitratsrooP
?dersigulpkrapS .tinunoitingirotsinartkcehC.deluofsigulpkrapS
leuffieesotroterubractcepsnI
?etihw-eulbsigulpkrapS
GNITOOHSELBUORTENIGNE.7ELBAT
enilleufkcehC
erastejroterubraC.gnikaelriadetcejni,noisserpmoctneiciffusnI
.)wolfrevo(deggolc
?gulp
?liooN .deriuqersalioddA
?gnitratsnopu
?esool
"noisserpmoc
"noisserpmoc"
on"tuptuorewoptneiciffusnI
?esoolsigulpkrapS .gulpkrapsecalpeR
?sgnirnotsipnroW .sgnirnotsipecalpeR
tuptuorewoptneiciffusnI
?daeh
krapsfopittatneserpkrapsoN
sknilbpmalmralaerusserpliO
?revonruttonlliwenignE .tniojlexayrassecenfidnanotsipdnarednilycecalpeR
stlobgnitcennocdaehrednilyC
?degamadteksagdaehrednilyC .teksagdaehrednilycecalpeR
?taesevlavfonoitcnuflaM .sevlavtaes-eR
renaelc-rianinoitcnuflaM
?deggolcretlifria,metsys
ecafretnimorfnignikaelriA
rednilycdnaroterubracneewteb
/tratS
.stlobgnitcennocdaehrednilycnethgiT
.retlifriaecalperronaelC
.teksagdaehrednilyc
.deluoffigulpkrapsecalpeR.nekorbhctiwspotS
."rosneslio"tiucricnwodtuhscitamotuAkcehC
.nekorbrodekcarcdrocegatlovhgih,nekorbtinunoitingirotsinarT
ecalpeR.daehrednilycdnaroterubracneewtebstlobnethgiT
?metsysleufninoitcnuflaM
.retlifleufecalperronaelC
.roterubracecalperronaelC
.taolfroterubrackcehC
GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05) — PAGE 23
GLW-180H — TROUBLESHOOTING (ENGINE)
)DEUNITNOC(GNITOOHSELBUORTENIGNE.7ELBAT
MOTPMYS MELBORPELBISSOP NOITULOS
tuptuorewoptneiciffusnI
staehrevodna"noisserpmoc"
leufhcumotsnruB
ylsuoinitnocsiroloctsuahxE
"ETIHW"
ylsuoinitnocsiroloctsuahxE
"KCALB"
?stcudorp
?ytisocsiv
?sgnirnroW sgnirecalpeR
?nafgniloocninoitcnuflaM .nafgniloocecalperrokcehC
?deggolcretlifekat-niriA .retlifekat-niriaecalperronaelC
tsuahxefonoitalumuccarevO
?gulpkrapsgnorW .gulpkrapsepytdetseggusserutcafunamhtiwgulpkrapsecalpeR
gnorwsiliognitacirbuL
?deggolcrennaelcriA .renaelcriaecalperronaelC
tesneebtonsahevlavekohC
?noitisoptcerrocehtot
nolaes,evitcefedroterubraC
?nekorbroterubrac
tnemtsujdaroterubracrooP
?hcirootsnurenigne"
.sevlavkcehcdnanaelC
.yrassecenfiecalper,relffumkcehC
.ytisocsivtcerrochtiwliognitacirbulecalpeR
.noitisoptcerrocehtotevlavekohctsujdA
.laesroroterubracecalpeR
.roterubractsujdA
PAGE 24 — GLW-180H A.C. GENERATOR/WELDER — PARTS & OPERATION MANUAL — REV. #5 (03/14/05)
Loading...
+ 54 hidden pages