PAGE 4 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
PARTS ORDERING PROCEDURES
Ordering parts has never been easier!
Choose from three easy options:
Effective:
January 1
st
, 2006
Best Deal!
Order via Internet (Dealers Only):
Order parts on-line using Multiquip’s SmartEquip website!
■
View Parts Diagrams
■
Order Parts
■
Print Specification Information
Goto www.multiquip.com and click on
Order Parts
to log in and save!
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax.
Domestic (US) Customers dial:
1-800-6-PARTS-7 (800-672-7877)
Non-Dealer Customers:
Contact your local Multiquip Dealer for
parts or call 800-427-1244 for help in
locating a dealer near you.
Order via Phone:
If you have an MQ Account, to obtain a
Username and Password, E-mail us at:
parts@multiquip.com.
To obtain an MQ Account, contact your
District Sales Manager for more information.
internet
Use the
on
Standard orders
and qualify for a 5% Discount
for all orders which include
complete part numbers.*
Fax
your order in and qualify for a 2% Discount
on
Standard orders
for all orders which include
complete part numbers.*
Domestic (US) Dealers Call:
1-800-427-1244
International Customers
their local Multiquip Representatives for
Parts Ordering information.
Note: Discounts Are Subject To Change
Note: Discounts Are Subject To Change
should contact
When ordering parts, please supply:
❒❒
❒
❒❒
Dealer Account Number
❒
❒❒
❒❒
❒
Dealer Name and Address
❒❒
❒❒
Shipping Address (if different than billing address)
❒
❒❒
❒❒
❒
Return Fax Number
❒❒
❒❒
❒
Applicable Model Number
❒❒
❒❒
❒
Quantity, Part Number and Description of Each Part
❒❒
All orders are treated as
Standard Orders
and will ship the same day if received prior
to 3PM PST.
www.multiquip.com
WE ACCEPT ALL MAJOR CREDIT CARDS!
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 5
Specify Preferred Method of Shipment:
❒❒
✓
UPS/Fed Ex
■
Priority One
■
Ground
■ Next Day
■
Second/Third Day
✓ DHL
✓
Tr u c k
RULES FOR SAFE OPERATION
■
CAUTION:
Failure to follow instructions in this manual
may lead to serious injury or even death! This
equipment is to be operated by trained and
qualified personnel only! This equipment is
for industrial use only.
The following safety guidelines should always be used when
operating the GDP-5000H Generator:
GENERAL SAFETY
■
DO NOT operate or service this equipment before reading
this entire manual.
■
This equipment should not be operated by persons under 18
years of age.
■
NEVER operate this equipment without proper protective
clothing, shatterproof glasses, steel-toed boots and other
protective devices required by the job.
■
This generator is a source of potentially LETHAL high voltage.
Never permit unqualified personnel-especially children to
operate the generator.
■
Always refuel in a well-ventilated area, away from sparks and
open flames.
■
Always use extreme caution when working with flammable
liquids. When refueling, stop the engine and allow it to cool.
DO NOT
could result from fuel vapors, or if fuel is spilled on a hot
engine.
■
This generator is equipped with a
protection. Always complete the grounding path from the
generator to an external grounding source.
■
NEVER operate this generator, or handle any electrical
equipment while standing in
hands are wet, or in the rain. Electrical shock could occur
causing severe bodily harm or even death.
■
Keep electrical cords in good condition. Worn, bare or frayed
wiring can cause electrical shock, leading to
even death.
■
This generator requires an adequate free flow of cooling air.
Never operate the generator in any enclosed or narrow area
where free flow of the air is restricted. If the air flow is restricted
it will cause serious damage to the generator and may cause
injury to people.
smoke around or near the machine. Fire or explosion
ground terminal
for your
water, while bare foot, while
bodily harm or
Provide adequate ventilation when operating the generator.
DO NOT operate the generator in any enclosed or narrow
space. The generator's gasoline engine gives off DEADLY
carbon monoxide gas.
■
NEVER operate the generator in an explosive atmosphere or
near combustible materials. An explosion or fire could result
causing severe
■
Always make sure that the generator is secure on level ground
so that it cannot slide or shift around, endangering workers.
Also keep the immediate area free of bystanders.
■
When using a concrete vibrator or a similar device that is
immersed in a water based solution, make sure the device is
equipped with short circuit protection.
■
Always use rubber boots and gloves when operating a
concrete vibrator or similar device.
■
Use adequate size connecting cable for extension.
■
High Temperatures – Allow the machine and engine to cool
before adding fuel or performing service and maintenance
functions. Contact with
burns.
Emergencies
■
Always know the location of the nearest
and
first aid kit
Also know the phone numbers of the nearest
doctor
invaluable in the case of an emergency.
Maintenance Safety
■
NEVER lubricate components or attempt service on a running
machine.
■
Always allow the machine a proper amount of time to cool
before servicing.
■
Keep the machinery in proper running condition.
■
Fix damage to the machine immediately and always replace
broken parts.
■
Dispose of hazardous waste properly. Examples of potentially
hazardous waste are used motor oil, fuel and fuel filters.
■
DO NOT use food or plastic containers to dispose of
hazardous waste.
■
DO NOT pour waste, oil or fuel directly onto the ground,
down a drain or into any water source
bodily harm or even death.
. Know the location of the nearest telephone.
and
fire department
hot
components can cause serious
fire extinguisher
ambulance
. This information will be
,
■
NEVER touch the hot exhaust manifold, muffler or cylinder.
Allow these parts to cool before servicing generator.
PAGE 6 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
OPERATION AND SAFETY DECALS
Machine Safety Decals
The GDP-5000H portable generator is equipped with a number of safety decals. These decals are provided for operator safety and
maintenance information. The illustration below shows these decals as they appear on the machine. Should any of these decals
become unreadable, replacements can be obtained from your dealer.
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 7
GDP5000H — SPECIFICATIONS
snoitacificepS.1elbaT
LEDOMH0005-PDG
epyTdleiFgnivloveRepyTsselhsurB,elop-2
tuptuO.xaMWk0.4
tuptuOdetaRWk6.3
egatloVdetaRV042/021
rotareneGelcyC06
1
enignE
rotareneGelcyC08
)HXWXL(noisnemiDmm015X065X007
thgieWteNyrDsbl5.132
esahP)eriw4(esahPelgniS
esahP)eriw4(esahPeerhT
aRMPR0063
epyTrednilycdenilcni52HVOekorts4delooc-riA
leuFenilosaGelibomotuAdedaelnU
tnerruCdetaRA0.51/0.03
ycneuqerFzH06
deepSdetaRMPR0063
rotcaFrewoP%001
tuptuO.xaMAVk5
tuptuOdetaRAVk5
egatloVdetaRV032
tnerruCdetaRA5.21
ycneuqerFzH081
deepSdet
rotcaFrewoP%08
ledoM043XGadnoH
ekortSXeroBmm46Xmm28
ltnemecalpsiDcc733
tuptuOxaM.M.P.R0063/.P.H0.11
tuptuOdetaR.M.P.R0063/.P.H0.8
yticapaCknaTleuFsnollaG.S.U5.x
yticapaCliOebuLstnip4/31
dohteMlortnoCdeepSepyTthgiew-ylFlagufirtneC
do
hteMgnitratStratSlioceR
orppA
Effects of Altitude and Heat
The maximum output of the engine listed above is applicable to supplying electrical power for continuous service at ambient
conditions in accordance with SAE Test cord J607. The above ambient conditions are at standard sea level, with a barometric
reading of 29.92 inches and a temperature of 60 degrees fahrenheit.
°°
°
°°
Generally, the engine output power will decrease 3 1/2% for each 1000 feet of altitude above sea level, and 1% for each 10
°°
°
Fahrenheit above the standard temperature of 60
°°
F
F
PAGE 8 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — GENERAL INFORMATION
WARNING:
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
(transfer) switch.
Serious injury or death may result without
this transfer switch.
GDP-5000H FAMILIARIZATION
Generator
The Multiquip Model GDP-5000H generator has been
designed as a portable dual purpose power source for 60
Hz (single phase) lighting facilities, power tools, submersible
pumps and other industrial and construction machinery. In
addition the Model GDP-5000H has been designed as a
power source for 180 Hz, 3-phase concrete vibrators.
This generator is powered by a HONDA gasoline engine.
The alternator, a brushless revolving-field type, is
permanently aligned to the engine through rigid coupling.
The generator is mounted on rubber vibration isolators that
have a steel base backplate which is attached to the
protective steel pipe carrying frame. The protective carrying
frame is made of steel tubing and fully wraps around the
generator to protect against damage.
This portable generator is supplied with a electrical
box
. To reduce vibration caused by the engine, the control
box is also placed on rubber isolators.
control
Excitation System
The GDP-5000H-series generators use a magnet attached
to a flywheel to produce AC voltage from a lamp coil beneath
the flywheel. As the magnetic passes the coil it produces
approximately 19-22 AC volts.
This voltage (19-22 VAC) is then sent to the control box that
contains three rectifying diodes:
z
Excitation (diode 1)
z
Battery (diode 2)
z
Slow Down (diode 3)
The AC voltage will pass through the excitation diode that
converts the voltage to DC power.
This DC power is then sent to the excitation windings housed
within the main windings commonly called the "stator".
This voltage is then transferred into the rotor through
induction. The rotor contains two diodes within it which rectify
the DC voltage and send it out through the main windings,
as AC voltage.
Engine
The four-cycle air-cooled HONDA gasoline engine is designed
to meet every performance requirement of this generator.
Reference Table 1, page 8 for engine specifications
Figure 1 (page 11) shows the basic controls and indicators
for the GDP-5000H generator.
Control Box
The control box is provided with the following:
z
Three 240V output receptacles (three phase).
z
One 120V output output receptacle (single phase).
z
One 120/240V output output receptacle (single phase).
z
One 120V output receptacle, GFIC (single phase).
z
One main 60 Hz (single phase) circuit breaker.
z
One main 180 Hz (three phase) circuit breaker.
z
AC Voltmeter
z
Ground Terminal
z
Full Power Switch
z
Idle Control Switch
z
Operation Switch
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 9
NOTE
In keeping with Multiquip's policy of
constantly improving its products, the
specifications quoted herein are subject
to change without prior notice.
GDP-5000H — CONTROLS AND INDICATORS
Figure 1. Controls and Indicators
PAGE 10 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — INSTALLATION
Outdoor Installation
Install the generator in a location where it will not be exposed to
rain or sunshine. Make sure that the generator is on secure level
ground so that it cannot slide or shift around. Also install the
generator in a manner so that the exhaust will not be discharged
in the direction of nearby homes.
The installation site must be relatively free from moisture and
dust. All electrical equipment should be protected from excessive
moisture. Failure to do will result in deterioration of the insulation
and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials
have a tendency to cause excessive wear, not only to the engine
parts, but also to the alternator parts.
CAUTION :
Pay close attention to ventilation when
operating the generator inside confined
areas. The engine exhaust contains
noxious elements.
Indoor Installation
Exhaust gases from gasoline engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
Eliminate the danger of deadly carbon monoxide gas.
Remember that exhaust fumes from any gasoline engine
are very poisonous if discharged in a closed room, but
harmless if allowed to mix with the outside air. If the generator
is installed indoors, you must make provisions for venting
the engine exhaust to the outside of the building.
CAUTION :
Preventing electrical shock. Pay close
attention to handling when operating
concrete vibrators. Always use rubber
boots and gloves to insulate the body from
a short circuit.
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 11
GDP-5000H — PRE-SETUP
General Inspection Prior to Operation
This generator has been thoroughly inspected prior to
Ground the Tool
Ground the tool (load) in the same manner as the generator.
shipment from the factory. However, be sure to check for
damaged parts or components, or loose nuts and bolts, which
could have occurred in transit.
Ground
Circuit Breaker
To protect the generator from an overload,
provided for both 60 and 180 phases on the control box.
Make sure to switch the circuit breakers to the "OFF" position
The nut and ground terminal on the generator should always
prior to starting the engine.
be used to connect the generator to a suitable ground. The
ground path should be of #8 size wire.
Connect the terminal of the ground wire between the lock
washer and the nut and tighten the nut fully. Connect their
end of the wire to a suitable ground.
Extension Cable
When electric power is to be provided to various tools or loads at
some distance from the generator, extension cords are normally
used. Cables should be sized to allow for distance in length and
amperage so that the voltage drop between the generator and
Ground the Generator
Ground the generator from its ground connector so that the
point of use (load) is held to a minimum. Use the cable selection
chart (Tables 2 and 3) as a guide for selecting proper cable size.
resistance to ground is 500 ohms or less.
tnerruC
ni
serepmA
021tA
stloV
sttaWnIdaoLhtgneLelbaCelbawollAmumixaM
042tA
stloV
eriW01#eriW21#eriW41#eriW61#
circuit breakers are
)noitarepoesahpelgnis,zH06(noitceleSelbaC.2elbaT
daoL
5.2003006.tf0001.tf006.tf573.tf052
50060021.tf005.tf003.tf002.tf521
5.
70090081.tf053.tf002.tf521.tf001
0100210042.tf052.tf051.tf001
5100810063.tf051.tf001.tf56
0200420084.tf521.tf57.tf05
olmorftlusernacegamadtnempiuqE:NOITUAC
htgneL).tf(
.egatlovw
05001051002052003
AVk3ni1300.0
AVk2ni1300.0
2
2
2
ni1300.0
2
ni1300.0
2
ni1300.0
2
ni1300.0
2
ni4500.0
2
ni1300.0
)noitarepoesahp-3,zH081(noitceleSelbaC.3elbaT
2
ni4500.0
2
ni1300.0
2
ni5800.0
2
ni4500.0
AVk1ni1300.0
2
2
ni1300.0
2
ni1300.0
2
ni1300.0
2
ni1300.0
PAGE 12 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
2
ni1300.0
GDP-5000H — PRE-SETUP
Lubrication Oil
Fill the engine crankcase with lubricating oil through the filler
hole, but do not overfill. Make sure the generator is level.
With the dipstick inserted all the way, but without being
Fuel
Close the fuel cock before filling the tank. Fill the fuel tank
with clean and fresh unleaded gasoline. Do not fill the tank
beyond capacity.
screwed into the filler hole, verify that the oil level is
maintained between the two notches on the dipstick.
Pay attention to the fuel tank capacity when replenishing
fuel. Refer to the fuel tank capacity listed on page 8
The oil listed in Table 4 is recommended to ensure better
Specification Table 1.
engine performance. Use class SC or higher grade motor
oil.
woleB)°51-(C°503-W01EASroW01EAS
liOrotoMdednemmoceR.4elbaT
erutarepmeT
egnaR
F°32~F°401
)C°5-~C°04(
F°5~F°32
)C°51-~C°5-(
03EAS
easro02EAS
liOepyT
03-W01
The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does not have
a spout, use a funnel.
CAUTION :
Never fill the fuel tank while the engine is
running or in the dark. Gasoline spillage
on a hot engine can cause a fire or
explosion. If gasoline spillage occurs, wipe
up the spilled gasoline completely to
prevent fire hazards.
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 13
GDP-5000H — INSTRUMENTATION
Power Outlets
The generator has the following single and 3-phase
receptacles.
zz
z
Single Phase
zz
One Duplex NEMA (GFCI) 5-20R (120V, 30 Amp)
One Twist Lock NEMA L5-30R (120V, 30 Amp)
One Twist Lock NEMA L6-20R (240V, 20 Amp)
zz
z
3- Phase
zz
ThreeTwist Lock NEMA 7410 (240V, 30 Amp)
Full Power Switch
The unit is provided with a full power switch. Figures 2 and 3
show simplified wiring diagrams of the dual voltage system.
When the full power switch is in the 120 volt (up) position,
you can take up
volts from the single duplex receptacle, single locking type
120 volt receptacle, or a combination of these receptacles
as long as the total load does not exceed the generating set
capacity.
full rated power
of the generator at 120
CAUTION :
60 Hz Circuit Breaker
This breaker protects the generator from short circuiting or
overloading from the 60 Hz single phase load.
The 180 Hz Leakage Breaker
The 180 Hz leakage breaker (Figure 4) is a earth leakage
breaker with the following conditions:
z
The circuit is broken when the load side shorts or there
is over current.
z
During use it detects when there is defective insulation
on the load side and breaks the circuit in response.
Idle Control Switch (both 60 and 180 Hz)
The unit is provided with an automatic idle control for noise
suppression and fuel cost reduction. The automatic idle
control automatically engages under a no-load condition.
When using a combination of dual
receptacles, total load should not exceed
the rated capacity of the generator.
With the automatic idle control switched “ON”, the engine
revolutions will automatically drop to about 2500 rpm (lowspeed operation) within 3 seconds after the load stops. When
the operation is resumed, the engine speed is automatically
increased to about 3600 rpm (high-speed operation) as soon
Figure 2. 120 V Simplified Diagram (Switch Up)
NOTE
When the switch is in the 120 V position, the
locking type 240 volt receptacle cannot be used.
When the switch is in the 240 volt (down) position, you can
take up to half of the rated power of the generating set at
120 volts from the duplex receptacle and up to half of the
rated power of the set at 120 volts from the locking type 120
volt receptacle; or full rated power of the set at 240 volts
from the locking type 240 volt receptacle.
as the load is connected.
Fuel Gauge
The fuel gauge is located on the fuel tank and allows easy
monitoring of the fuel level.
AC Voltmeter
This voltmeter indicates output voltage for both 60 and 180
Hz phases. In addition this voltmeter can also be used as a
diagnostic tool.
If the voltmeter indicator (needle) is elow the rated voltage,
engine problems may exist (low/high RPM's). To prevent
damage to the generator or power tools turn the generator
OFF and consult your authorized Multiquip service dealer.
Figure 3. 120/240V Simplified Diagram (Sw Dn.)
PAGE 14 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — LOAD APPLICATION
Single Phase Load — 60 Hz
CAUTION:
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage and
frequency requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require 130—
150% more wattage than the rating on the nameplate, as
the wattage is influenced by the efficiency, power factor and
starting system of the equipment.
NOTE
If wattage is not given on the equipment's
name plate, approximate wattage may be
determined by multiplying nameplate
voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
To determine the running wattage for your load, multiply the
running wattage as indicated by steps 1, 2, and 3 below:
An inadequate size connecting cable which cannot carry
the required load can cause a voltage drop which can burn
out the appliance or tool and overheat the cable.
The idle control is operated at minimum load capacity of
100W. If the load capacity is less than 100W, throw the idle
control switch to the OFF position.
CAUTION:
Three Phase Load — 180 Hz
Motors and motor-driven equipment draw
much greater current for starting than
during operation.
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
(transfer) switch. Serious injury or death
may result without this transfer switch.
1.INCANDESCENT LOADS
Lights, heaters and similar appliances.
Total the running wattage and multiply by 1.
Example:
29 light bulbs @ 100W each = 2.9 KW
use a 3 KW generator.
2.SMALL MOTORS
Drills and other small power tools.
Total the running wattage and multiply by 2.
Example:
A 1 inch drill runs at 1 KW
use a 2 KW generator.
3.LARGE MOTORS
Submersible pumps, table saws etc.
Total the running wattage and multiply by 3.
Example:
A conveyor belt runs at 8 KW
use a 24 KW generator.
180 cycle, three phase, 230V, motor-in-head vibrators can
be operated with this generator. When operating more than
one concrete vibrator, the ON/OFF switch of each concrete
vibrators shall be turned on one at a time.
If they are switched on simultaneously, the circuit breaker
may trip or the engine may be overloaded.
NOTE
If output (kVA) is not given on the vibrators
nameplate, approximate output may be
determined by multiplying voltage by
amperage by .
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 15
GDP-5000H — LOAD APPLICATION
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
z
Always use a vibrator with short circuit
protection.
z
Always use rubber boots and gloves
when operating the vibrator.
z
Use adequate size connecting cable
for extension.
z
Maintain electrical cords in good
condition and frequently replace the
entire cable of the vibrator with a new
one.
Earth Leakage Breaker (180 Cycle)
The 180 Hz leakage breaker (Figure 4) is an earth leakage
breaker, so please use it after carefully reading the following:
WARNING:
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
(transfer) switch.
Serious injury or death may result without
this transfer switch.
How to Use
Always conduct the following in order that the earth leakage
breaker will operate safely. Also, if the leakage breaker should
for some reason actuate, first stop the generator and then
repair or eliminate the source of the earth leakage before
resetting the leakage breaker. When setting up the generator
perform the following:
Ground the Generator
Ground the generator from its ground connector so that
resistance to ground is 500 ohms or less.
Ground the Tool
Ground the tool (load) in the same manner as the generator.
Figure 4. Earth Leakage Breaker
Test Operation
For safety’s sake, the operation of the earth leakage breaker
should be tested periodically according to the following
NOTE
Before operating generator press
earth leakage test button.
The earth leakage breaker's earth leakage detection
sensitivity is 30 mA, and the actuation time is 0.1 sec.
procedure:
1.Start the engine and set it to high speed.
2.Turn the leakage breaker ON.
3.During normal operation, press the earth leakage indicator
4.Push the indicator button back in when resetting
NOTE
Simply because the generator is equipped
with a earth leakage breaker does not mean
that grounding of the load can be neglected,
please be sure to properly ground load
equipment.
test button on the front of the generator and observe
that indicator button pops out and the leakage breaker
trips.
.
PAGE 16 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — OPERATING INSTRUCTIONS
Before Starting
1.Be sure to disconnect the electrical load and switch
both main circuit breakers (60 and 180 Hz) to the “OFF”
position prior to starting the engine.
2.Never start the engine with the main circuit breaker “ON”.
3.Check the lubricating oil level prior to starting the engine.
Make sure the generator is level. The oil level must be
maintained between two notches on the dipstick.
4.When there is not enough lubricating oil, fill the crankcase
with high grade motor oil. Use a high quality detergent
oil classified SC, SD or SE. (See Table 4 on page 13)
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
z
NEVER start the engine when the oil level
is below the lower mark on the dipstick.
z
Check the fuel level on the fuel gauge.
When fuel is low, fill the fuel tank with
clean fresh unleaded automotive gasoline.
z
If gasoline spillage occurs, completely
wipe up the spilled gasoline.
Starting
1.Open the fuel cock located below the fuel tank. The fuel
starts to flow when the fuel cock is turned downward.
2.Place the idle control switch in the “ON” (up) position.
Warm up
1.When the engine starts, open the choke slowly.
2.Run the engine at low speed for 3 minutes without load
until the engine warms up.
3.Turn the idle control switch to the "OFF" (down) position
and check the voltage by referring to the voltmeter on
the control box.
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
1.Check the generator for abnormal noise and smells. Then
connect the load to the receptacles of the generator.
2.Switch both main circuit breakers (60 and 180 Hz) to
the “ON” position and turn the idle control switch to the
“ON” (down) position for normal (load) engine operation.
Operation
Check the voltage by referring to the voltmeter on the control
box. When the voltmeter indicates 120 volts, 120 volts from
the 120V receptacles and 240 volts from the 240V receptacle
can be obtained at the same time. Refer to Figure 1, Controls
and Indicators, item 7 on page 10.
DO NOT change the engine speed control
lever which has been set at the factory prior
to shipping.
3.Close the choke. Adjust the opening of the choke valve
according to operating conditions. When the engine is
warm or the air temperature is high, close the choke
valve halfway or open it all the way.
4.Confirm that both main circuit breakers (60 and 180 Hz)
on the generator control box are in the “OFF” position.
5.Set the operation switch to the “ON” position and grasp
the starting knob and slowly pull it out. The resistance
becomes hardest at a certain position, corresponding
to the compression point. Rewind the rope a little from
that point and pull out sharply.
6.If the engine fails to start, repeat the procedure.
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
z
DO NOT pull the starter rope all the way
to the end.
z
DO NOT release the starter rope after
pulling. Allow it to rewind as soon as
possible.
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 17
Stopping the Engine
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
1.Remove the load from the generator. Place the circuit
breaker in the “OFF” position (See Figure. 3 on page 9).
Run the engine (no-load) with the idle control switch set
to the ON position for three to five minutes, then stop
the engine.
2.Turn the START/STOP switch to the “STOP” position.
3.Never stop the engine suddenly while running at high
speed.
4.After the engine has stopped, close the fuel cock.
NEVER stop the engine suddenly while
running at high speeds.
GDP-5000H — MAINTENANCE
General Inspection
At least daily or prior to each use, the generating set should
be cleaned and inspected for deficiencies. Check for loose,
missing or damaged nuts, bolts or other fasteners. Also check
for fuel or oil leaks.
Engine Side (Refer to the Engine Instruction Manual)
Check Oil Level
Check the crankcase oil level prior to each use, or when the
fuel tank is filled. Make sure the generating set is level. The
oil level must be between the two notches on the dipstick.
Changing Oil
Change oil after the first 20 hours of operation. Drain and
refill the engine crankcase every 50 operating hours or once
a week thereafter. Drain crankcase oil into a suitable container
while engine is still warm. Replace the drain plug tightly. Add
oil through the filler hole.
Air Cleaner
Every 50 hours: Remove air cleaner element (std. or heavy
duty types), and wash in kerosene or liquid detergent and
hot water. Wrap foam element in a cloth and squeeze dry.Wipe
heavy duty paper element dry with toweling. Saturate element
with kerosene; squeeze excess from foam element. Wipe
excess from heavy duty paper element.
Service Daily
If engine is operating in very dusty and dry grass conditions.
A clogged air cleaner will result in high fuel consumption,
loss of power and excessive carbon build-up in the
combustion chamber.
Cleaning the Fuel Strainer
Clean the fuel strainer if it contains dust or water. Remove
dust or water in the strainer cap and wash it in gasoline.
Securely fasten the fuel strainer cap so that fuel will not
leak. Check the fuel strainer every 200 hours of operation or
once a month.
Spark Plug
Remove carbon build-up on the spark plug (Figure 5) with a
wire brush. Set the spark plug gap to 0.6—0.7 mm (0.024-
0.028 inch). Tighten with a spark plug socket wrench. Clean
the spark plug every 50 operating hours or once a week.
Figure 5. Spark Plug Gap
PAGE 18 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — PREPARATION FOR LONG -TERM STORAGE
Generator Storage
For storage of the generating set for over 30 days, the
following is required:
z
Drain the fuel tank completely.
z
Run the engine until the gasoline in the carburetor is
completely consumed.
z
Completely drain the oil from the crankcase and refill
with fresh oil.
z
Remove the spark plug, pour 2 or 3 cc of SAE 30 oil
into the cylinder and crank slowly to distribute the oil.
z
Slowly rotate the engine a few times with the starter
Rope and install a new plug.
z
Pull out the starter rope slowly and stop at the
compression point.
z
Clean all external parts of the generating set with a cloth.
z
Cover the generating set and store in a clean, dry place.
GDP-5000H A.C. GENERATOR — OPERATION AND PARTS MANUAL — REV. #2 (07/23/08) — PAGE 19
GDP-5000H — WIRING DIAGRAM
PAGE 20 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — TROUBLESHOOTING (ENGINE)
Practically all breakdowns can be prevented by proper
handling and maintenance inspections, but in the event of a
breakdown, please take a remedial action following the
diagnosis based on the Engine Troubleshooting (Table 6)
information shown below and on the proceeding page. If the
problem cannot be remedied, please leave the unit just as it
is and consult our company's business office or service
plant.
PAGE 22 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)
GDP-5000H — TROUBLESHOOTING (GENERATOR)
Practically all generator breakdowns can be prevented by
proper handling and maintenance inspections, but in the event
of a breakdown, please take a remedial action following the
diagnosis based on the Generator Troubleshooting (Table 7)
information shown below and on the preceding page. If the
problem cannot be remedied, please leave the unit just as it
is and consult our company's business office or service
plant.