Multiquip DCA-45US1 User Manual

PARTS AND OPERATION MANUAL
OPERATION AND PARTS MANUAL
DCA-45USI
ULTRA-SILENT
PARTS LIST NO. M1871400004B
Revision #2 (04/22/05)
THIS MANUAL MUST ACCOMPANY
THE EQUIPMENT AT ALL TIMES.
TM
SERIES
PAGE 2 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
HERE'S HOW TO GET HELP
PLEASE HAVE THE MODEL AND SERIAL
NUMBER
MQ POWER CORPORATE OFFICE
18910 Wilmington Ave. 800-421-1244 Carson, CA 90746 Email: mqpower@multiquip.com Internet: www.mqpower.com
PARTS DEPARTMENT
800-427-1244 310-537-3700
SERVICE DEPARTMENT
800-835-2551 310-537-3700
TECHNICAL ASSISTANCE
800-478-1244
WARRANTY DEPARTMENT
800-835-2551, 310-537-3700,
ON-HAND
EXT.
279
EXT.
279
WHEN CALLING
FAX:
310-632-2656
FAX:
800-672-7877
FAX:
310-637-3284
FAX:
310-638-8046
FAX:
310-631-5032
FAX:
310-638-8046
© COPYRIGHT 2004, MULTIQUIP INC. Multiquip Inc, MQ Power Inc, Ultra-Silent series, the MQ logo and the MQ Power logo are registered trademarks of Multiquip Inc. and
may not be used, reproduced, or altered without written permission. All other trademarks are the property of thier respective owners and used with permission.
This manual should remain with the unit if resold.
The information and specifications included in this publication were in effect at the time of approval for printing. Illustrations are based on the the information published in this publication at any time without notice and without incurring any obligations.
MUST accompany the equipment at all times. This manual is considered a permanent part of the equipment and
DCA-45USI Ultra Silent Generator
. Multiquip Inc. reserves the right to discontinue or change specifications, design or
To find the latest revision of this
publication, visit our website at:
www.mqpower.com
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 3
TABLE OF CONTENTS
MQ POWER DCA-45USIMQ POWER DCA-45USI
MQ POWER DCA-45USI
MQ POWER DCA-45USIMQ POWER DCA-45USI AC GENERAAC GENERA
AC GENERA
AC GENERAAC GENERA
Here's How To Get Help ............................................. 3
Table Of Contents ....................................................... 4
Parts Ordering Procedures ........................................ 5
DCA-45USI Specifications .......................................... 6
Dimensions .................................................................. 7
Safety Message Alert Symbols ............................... 8-9
Rules for Safe Operation ..................................... 10-13
Installation ............................................................ 14-15
Towing Safety Precautions ....................................... 16
Trailer Specifications ................................................. 17
Generator Decals ................................................. 18-19
General Information .................................................. 20
Major Components ................................................... 21
Generator Control Panel........................................... 22
Engine Operating Panel............................................ 23
Output Terminal Panel Familiarization................. 24-26
Load Application........................................................ 27
Generator Outputs ............................................... 28-29
Gauge Reading ......................................................... 30
Output Terminal Panel Connections .................... 30-31
Pre-setup .............................................................. 32-35
Generator Start-up Procedure ............................36-38
Generator Shut-down Procedure ............................. 39
Maintenance......................................................... 40-41
Trailer Brakes Maintenance...................................... 42
Trailer Maintenance ............................................. 43-44
Trailer Wiring Diagram .............................................. 45
Engine Wiring Diagram ........................................ 46-47
Generator Wiring Diagram ....................................... 48
Generator Troubleshooting....................................... 49
Explanation of Codes in Remarks Column .............. 50
Suggested Spare Parts ............................................ 51
TORTOR
TOR
TORTOR
COMPONENT DRACOMPONENT DRA
COMPONENT DRA
COMPONENT DRACOMPONENT DRA
Generator Assembly ............................................ 52-53
Control Box Assembly .......................................... 54-57
Engine & Radiator Assembly ............................... 58-61
Output Terminal Assembly ................................... 62-63
Battery Assembly ................................................. 64-65
Muffler Assembly ................................................. 66-67
Fuel Tank Assembly ............................................. 68-69
Enclosure Assembly ............................................ 70-75
Rubber Seal Assembly ........................................ 76-77
Nameplate and Decals ........................................ 78-79
Terms and Condition of Sale — Parts ...................... 80
WINGSWINGS
WINGS
WINGSWINGS
NOTE
PAGE 4 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
Specification and part number are subject to change without notice.
PARTS ORDERING PROCEDURES
When ordering parts,
please supply the following information:
❒❒
Dealer account number
❒❒ ❒❒
Dealer name and address
❒❒ ❒❒
Shipping address (if different than billing address)
❒❒ ❒❒
Return fax number
❒❒ ❒❒
Applicable model number
❒❒ ❒❒
Quantity, part number and description of each part
❒❒ ❒❒
Specify preferred method of shipment:
❒❒
FedEx or UPS Ground FedEx or UPS Second Day or Third Day FedEx or UPS Next Day Federal Express Priority One DHL Tr u c k
Note: Unless otherwise indicated by customer, all orders are treated as “Standard Orders”, and will ship within 24 hours. We will make every effort to ship “Air Shipments” the same day that the order is received, if prior to 2PM west coast time. “Stock Orders” must be so noted on fax or web forms.
Here’s how to get help...
Please have the model and serial number on hand when calling.
MQ POWER CORPORATE OFFICE
18910 Wilmington Ave. 800-421-1244
FAX:
Carson, CA 90746 Email: mqpower@multiquip.com Internet: www.mqpower.com
PARTS DEPARTMENT
800-427-1244 310-537-3700
SERVICE DEPARTMENT
800-835-2551 310-537-3700
TECHNICAL ASSISTANCE
800-478-1244
WARRANTY DEPARTMENT
800-835-2551, 310-537-3700,
EXT. EXT.
279 279
310-632-2656
FAX:
800-672-7877
FAX:
310-637-3284
FAX:
310-638-8046
FAX:
310-631-5032
FAX:
310-638-8046
Place Your Parts Order Via Web or Fax
For Even More Savings!
(Domestic USA Dealers Only)
Extra Discounts!
All parts orders which include complete part numbers and are received by our automated web parts order system, or by fax qualify for the following extra discounts:
Ordered Standard Stock orders
via orders ($750 list and above)
Fax 3% 10%
Web 5% 10%
Special freight allowances when you order 10 or more line items via Web or Fax!**
FedEx Ground Service
No other allowances on freight shipped by any other carrier. **Common nuts, bolts and washers (all items under $1.00
list price) do not count towards the 10+ line items.
at no charge for freight
NOTE: DISCOUNTS ARE SUBJECT TO CHANGE
MQPOWER
A Division of Multiquip Inc.
POST OFFICE BOX 6254 CARSON, CA 90749 310-537-3700 • 800-421-1244 FAX: 310-632-2656 E-MAIL: mqpower@multiquip.com INTERNET: www.mqpower.com
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 5
Direct TOLL-FREE access
to our Parts Department:
Toll-free nationwide — 800-427-1244
Toll-free FAX — 800-6-PARTS-7
(800/672-7877)
DCA-45USI — SPECIFICATIONS
ledoMISU54-ACD
snoitacificepSrotareneG.1elbaT
epyT
A
esahP
deepS
noitcennoCerutamr
3elgniS
tuptuOybdnatS
tuptuOemirP
egatloV
ycneuqerF
rotcaFrewoP
rewoPCA.xuA
egatloV
tuptuO
roV042V021/042
8.01
lartueNhtiwratSgaZgiZ
)WK8.73(AVK3.74WK3.72
)WK63(AVK54WK62
V084
rotareneg
zH06
mpr008,1
zH06,esahPelgniS
CAV021
xWK4.2(WK8.4
)2
suonorhcnysepytdetcetorpnepo,detalitnevfles,dleifgnivloveR
snoitacificepSenignE
ledoMT1GJ4-BBUZUSI
epyT
srednilyCfo.oN
roB
ekortSxe
tuptuOdetaR
tnemecalpsiD
gnitratS
yticapaCtnalooC
yticapaCliOebuL
ag6.2 daollluf tarh/)L74.7(.lag79.1 daol4/3
noitpmusnoCleuF
yrettaB
leuF
srednilyc4
)mm701xmm4.59(.ni12.4x.ni67.3
mpr008,1/PH3.55
)cc950,3(.ni.uc781
elE
cirtc
)sretil7.31(.lag6.3
)sretil0.01(.lag46.2
tarh/)L48.9(.l
tarh/)L24.5(.lag34.1 daol2/1 tarh/)L3.3(.lag78.0 daol4/1
2puorGICB-V21
7
leuFleseiD2#
degrahcobrut,noitcejnitcerid,delooc-retaw,elcyC4
PAGE 6 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — DIMENSIONS (SIDE AND FRONT)
Figure 1. Dimensions
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 7
DCA-45USI — SAFETY MESSAGE ALERT SYMBOLS
FOR YOUR SAFETY AND THE SAFETY OF OTHERS!
Safety precautions should be followed at all times when operating this equipment. Failure to read and understand the Safety Messages and Operating Instructions could result in injury to yourself and others.
This Owner's Manual has been
NOTE
Before using this GENERATOR, ensure that the operating individual has read and understands all instructions in this manual.
developed to provide complete instructions for the safe and efficient operation of the MQ Power
DCA45USI ULTRA-SILENT™ GENERATOR.
Model
HAZARD SYMBOLS
SAFETY MESSAGE ALERT SYMBOLS
The three (3) Safety Messages shown below will inform you about potential hazards that could injure you or others. The Safety Messages specifically address the level of exposure to the operator, and are preceded by one of three words: DANGER,
WARNING, or CAUTION.
Lethal Exhaust Gases
Engine exhaust gases contain poisonous carbon monoxide. This gas is colorless and
odorless, and can cause death if inhaled. NEVER operate this equipment in a confined area or enclosed structure that does not
provide ample free flow air.
Explosive Fuel
Diesel fuel is extremely flammable, and its vapors can cause an explosion if ignited. DO NOT start the engine near spilled fuel or combustible fluids. DO NOT fill the fuel tank while the engine is running or hot. DO NOT overfill tank, since spilled fuel could ignite if it comes into contact with hot engine parts or sparks from the ignition system. Store fuel in
approved containers, in well-ventilated areas and away from sparks and flames. NEVER use fuel as a cleaning agent.
DANGER: You WILL be KILLED or
SERIOUSLY injured if you DO NOT follow directions.
WARNING: You CAN be KILLED or
SERIOUSLY injured if you DO NOT follow directions.
CAUTION: You CAN be injured if you
DO NOT follow directions.
Potential hazards associated with trowel operation will be referenced with " this manual, and will be referenced in conjunction with Safety "
Message Alert Symbols
Hazard Symbols
".
" which appear throughout
Burn Hazards
Engine components can generate extreme heat. To prevent burns, DO NOT touch these areas while the engine is running or immediately after operations. NEVER operate the engine with heat shields or heat guards removed.
Rotating Parts
NEVER operate equipment with covers, or
guards removed. Keep and
clothing
prevent injury.
fingers, hands, hair
away from all moving parts to
PAGE 8 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — SAFETY MESSAGE ALERT SYMBOLS
Accidental Starting
ALWAYS place the engine ON/OFF switch
in the OFF position, when the trowel is not in use.
Over Speed Conditions
NEVER tamper with the factory settings of the
engine governor or settings. Personal injury and damage to the engine or equipment can result if operating in speed ranges above maximum allowable.
This
NOTE
the surrounding environment could be damaged if you do not follow instructions.
generator
, other property, or
Respiratory Hazard
ALWAYS wear approved respiratory protection.
Sight and Hearing hazard
ALWAYS wear approved eye and hearing
protection.
Equipment Damage Messages
Other important messages are provided throughout this manual to help prevent damage to your trowel, other property, or the surrounding environment.
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 9
DCA-45USI — RULES FOR SAFE OPERATION
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
The following safety guidelines should always be used when operating the DCA-45USI Generator:
GENERAL SAFETY
DO NOT operate or service this equipment before reading this entire manual.
This equipment should not be operated by persons under 18 years of age.
NEVER operate this equipment without proper protective clothing, shatterproof glasses, steel­toed boots and other protective devices required by the job.
:
Failure to follow instructions in this manual may lead to serious injury or even death! This equipment is to be operated by trained and qualified personnel only! This equipment is for industrial use only.
NEVER touch the hot exhaust manifold, muffler or cylinder. Allow these parts to cool before servicing engine or generator.
High Temperatures – Allow the engine to cool before performing service and maintenance functions. Contact with
hot!
components can cause serious burns.
The engine of this generator requires an adequate free flow of cooling air. operate the generator in any enclosed or narrow area where free flow of the air is restricted. If the air flow is restricted it will cause serious damage to the generator or engine and may cause injury to people. The generator engine gives off DEADLY carbon monoxide gas.
NEVER
NEVER operate this equipment when not feeling well due to fatigue, illness or taking medicine.
NEVER operate this equipment under the influence or drugs or alcohol.
NEVER use accessories or attachments, which are not recommended by MQ Power for this equipment. Damage to the equipment and/or injury to user may result.
Manufacture does not assume responsibility for any accident due to equipment modifications.
Whenever necessary, replace nameplate, operation and safety decals when they become difficult read.
ALWAYS check the machine for loosened threads or bolts before starting.
NEVER operate the generator in an explosive atmosphere or near combustible materials. An explosion or fire could result causing severe
bodily harm or even death.
ALWAYS make sure generator is properly grounded. NEVER use gas piping as an electrical ground. DO NOT place hands or fingers inside generator engine
compartment when engine is running.
ALWAYS make sure generator installation is accordance with
national and local electrical codes
ALWAYS have a qualified electrician perform the generator
wiring installation.
NEVER power cables or cords NEVER
is being transfer to a load. NEVER use a defective or frayed power cable. Check the
cable for cuts in the insulation. NEVER use a extension cord that is frayed or damaged where
the insulation has been cut. ALWAYS make certain that proper extension cord has been
selected for the job See Table 5. The electrical voltage required to operate the generator can
cause severe injury or even death through physical contact with live circuits. performing maintenance on the generator.
stand in water
while AC power from the generator
Turn all circuit breakers OFF before
.
lay in wate
r.
PAGE 10 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — RULES FOR SAFE OPERATION
ALWAYS make sure that electrical circuits are properly
grounded
codes before operating generator. Severe electrocution can result from operating an ungrounded generator.
ALWAYS be sure the operator is familiar with proper safety precautions and operations techniques before using generator.
ALWAYS store equipment properly when it is not being used. Equipment should be stored in a clean, dry location out of the reach of children.
ALWAYS read, understand, and follow procedures in Operator’s Manual before attempting to operate equipment.
DANGERDANGER
DANGER
DANGERDANGER
securely connected to the generator’s output terminals, insufficient tightening of the terminal connections may cause damage to the generator and electrical shock.
DANGERDANGER
DANGER
DANGERDANGER
DANGERDANGER
DANGER
DANGERDANGER
per the
National Electrical Code
(NEC) and local
injury
or
death!
:
Never use damaged or worn cables when
connecting equipment to the generator.
Make sure power connecting cables are
WET
HANDS
:
NEVER grab or
touch a live power cord with
wet hands , the possibility exists
of electrical shock, electrocution, and even
death!
POWER
CORD
(POWER ON)
:
.
DANGERDANGER
DANGER
DANGERDANGER
by
Backfeed to a utility system can cause property damage. DO NOT connect to any building's electrical system except through an approved device or after building main switch is opened. ALWAYS have a licensed electrician perform the installation
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Radiator
1. Radiator Cap - Removing the radiator cap while the engine
2. Coolant Drain Plug - Removing the coolant drain plug
3. Engine Oil Drain Plug - Removing the engine oil drain
Maintenance Safety
:
electrocution
and or
:
DO NOT touch or open any of the below
mentioned components while the generator is running. Always allow sufficient time for the engine and generator to cool before performing maintenance.
is hot will result in high pressurized, boiling water to gush out of the radiator, causing severe scalding to any persons in the general area of the generator.
while the engine is hot will result in hot coolant to gush out of the coolant drain plug, therefore causing severe scalding to any persons in the general area of the generator.
plug while the engine is hot will result in hot oil to gush out of the oil drain plug, therefore causing severe scalding to any persons in the general area of the generator.
NEVER lubricate components or attempt service on a running machine.
NEVER touch output terminals during operation. This is extremely dangerous. ALWAYS stop the machine and place the circuit breaker in the “OFF” position when contact with the output terminals is required. There exists the possibility of
which can cause severe bodily harm or even death
electrocution, electrical shock or burn,
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 11
!
ALWAYS allow the machine a proper amount of time to cool before servicing.
Keep the machinery in proper running condition. Fix damage to the machine immediately and always replace
broken parts.
DCA-45USI — RULES FOR SAFE OPERATION
NEVER run engine without air filter. Severe engine damage may occur.
ALWAYS service air cleaner frequently to prevent engine malfunction.
ALWAYS disconnect the performing service on the generator.
ALWAYS be sure the operator is familiar with proper safety precautions when operating the generator set.
ALWAYS store equipment properly when not in use.
DO NOT leave the generator running in the unattended.
DO NOT allow unauthorized people to operate this equipment.
ALWAYS read, understand, and follow procedures in Operator’s Manual before attempting to operate equipment.
Refer to the technical questions or information.
DANGER:DANGER:
DANGER:
DANGER:DANGER:
engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.
Generator Grounding
To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.
Article 250 (Grounding) of the (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.
Isuzu Engine Owner's Manual
Pay close attention to
ventilation when operating the generator inside tunnels and caves. The
negative battery terminal
manual mode
for engine
National Electrical Code
before
Battery
The battery contains acids that can cause injury to the eyes and skin. To avoid eye irritation, Use well insulated gloves when picking up the battery. Use the following guidelines when handling the battery:
1. DO NOT drop the battery. There is the possibility of risk that the battery may explode.
2. DO NOT expose the battery to open flames, sparks, cigarettes etc. The battery contains combustible gases and liquids. If these gases and liquids come in contact with a flame or spark, an explosion could occur.
3. ALWAYS keep the battery charged. If the battery is not charged a buildup of combustible gas will occur.
4. ALWAYS keep battery charging and cables in good working condition. Repair or replace all worn cables.
5. ALWAYS recharge the battery in an vented air environment, to avoid risk of a dangerous concentration of combustible gases.
6. In case the battery liquid (dilute sulfuric acid) comes in contact with immediately with plenty of water.
7. In case the battery liquid (dilute sulfuric acid) comes in contact with your eyes, rinse eyes immediately with plenty of water, then contact the nearest doctor or hospital, and seek medical attention.
Transporting
ALWAYS shutdown engine before transporting.
Tighten both fuel tank caps securely.
always
clothing or skin
, rinse skin or clothing
wear safety glasses.
ALWAYS be sure to use the ground terminal (green wire) when connecting a load to the UVWO output terminals.
PAGE 12 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
If generator is mounted on a trailer, make sure trailer complies with all local and state safety transportation laws. See next page “ basic towing techniques.
Towing Safety Precautions
” for
DCA-45USI — RULES FOR SAFE OPERATION
Towing Safety Precautions
CAUTION:CAUTION:
CAUTION:
CAUTION:CAUTION:
Conform to (DOT)
towing generator.
To reduce the possibility of an accident while transporting the generator on public roads, always make sure the trailer that supports the generator and the towing vehicle are in good operating condition and both units are mechanically sound.
The following list of suggestions should be used when towing your generator:
Make sure the hitch and coupling of the towing vehicle are rated equal to, or greater than the trailer "gross vehicle weight rating" (GVWR) of 6,000 lbs.
ALWAYS inspect the hitch and coupling for wear. NEVER tow a trailer with defective hitches, couplings, chains etc.
Department of Transportation
Safety Towing Regulations
before
Avoid sharp turns.
Trailer should be adjusted to a level position at all times when towing.
Raise and lock trailer wheel stand in up position when transporting.
DOT Requirements include the following:
z z
Emergencies
ALWAYS know the location of the nearest
ALWAYS know the location of the nearest and
Connect and test electric brake operation. Secure portable power cables in cable tray with tie wraps.
fire extinguisher
first aid kit
.
.
Check the tire air pressure on both towing vehicle and trailer. Also check the tire tread wear on both vehicles.
ALWAYS make sure the trailer is equipped with a "Safety Chain".
ALWAYS attach trailer’s safety chains to towing vehicle properly.
ALWAYS make sure the vehicle and trailer directional, backup, brake, and trailer lights are connected and working properly.
The maximum speed for highway towing is 55 MPH unless posted otherwise. Recommended off-road towing is not to exceed 15 MPH or less depending on type of terrain.
Place while parked.
Use the trailer’s swivel jack to adjust the trailer height to a level position while parked.
Avoid sudden stops and starts. This can cause skidding, or jack-knifing. Smooth, gradual starts and stops will improve towing.
Trailer tires should be inflated to 50 psi cold.
chock blocks
underneath wheel to prevent rolling,
In emergencies
nearest phone or Also know the phone numbers of the nearest
ambulance, doctor
information will be invaluable in the case of an emergency.
always
know the location of the
keep a phone on the job site
and
fire department
.
. This
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 13
DCA-45USI — INSTALLATION
Figure 2. Typical Generator Grounding Application
PAGE 14 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — INSTALLATION
Outdoor Installation
Install the generator in a clear area. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.
The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
:
Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.
Generator Grounding
To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.
Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground. a. Copper - 10 AWG (5.3 mm2) or larger. b. Aluminum - 8 AWG (8.4 mm2) or larger.
2. When grounding the generator (Figure 2) connect the
ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground
rod should be buried aminimum of 8 ft. into the ground.
Indoor Installation
Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.
Mounting
The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.
NOTE
When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 15
DCA-45USI — TOWING SAFETY PRECAUTIONS
Towing Safety Precautions
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
To reduce the possibility of an accident while transporting the generator on public roads, always make sure the trailer (Figure 3) that supports the generator and the towing vehicle are in good operating condition and both units are mechanically sound.
The following list of suggestions should be used when towing your generator:
Make sure the hitch and coupling of the towing vehicle are rated equal to, or greater than the trailer "gross vehicle weight rating" (GVWR).
ALWAYS inspect the hitch and coupling for wear. NEVER tow a trailer with defective hitches, couplings, chains etc.
Check the tire air pressure on both towing vehicle and trailer. Also check the tire tread wear on both vehicles.
ALWAYS make sure the trailer is equipped with a "Safety Chain".
:
Check with your local county or state safety towing regulations before towing your generator.
ALWAYS attach trailer’s safety chain to bumper of towing vehicle.
ALWAYS make sure the vehicle and trailer directional, backup, brake, and trailer lights are connected and working properly.
The maximum speed for highway towing is 55 MPH unless posted otherwise. Recommended off-road towing is not to exceed 15 MPH or less depending on type of terrain.
Place rolling, while parked.
Place prevent tipping, while parked.
Use the trailer’s hand winch to adjust the height of the trailer, then insert locking pin to lock wheel stand in place, while parked.
Avoid sudden stops and starts. This can cause skidding, or jackknifing. Smooth, gradual starts and stops will improve gas milage.
Avoid sharp turns to prevent rolling.
Remove wheel stand when transporting.
DO NOT transport generator with fuel in tank.
chocked blocks
support blocks
underneath wheel to prevent
underneath the trailer’s bumper to
NOTE
Figure 3. Generator with Trailer
PAGE 16 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
Generator w/trailer illustration is for reference only.
DCA-45USI — TRAILER SPECIFICATIONS
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Explanation of Chart:
This section is to provide the user with trailer service and maintenance information. The service and maintenance guidelines referenced in this section apply a wide range of trailers. Remember periodic inspection of the trailer will en­sure safe towing of the equipment and will prevent damage to the equipment and personal injury.
It is the purpose of this section to cover the major mainte­nance components of the trailer. The following trailer com­ponents will be discussed in this section:
Brakes
Tires
Lug Nut Torquing
Suspension
Electrical
Brake Troubleshooting Tables
Use the following definitions when reading Table 2.
1. Fuel Cell - Provides an adequate amount of fuel for the equipment in use. Fuel cells must be empty when trans­porting equipment.
2. Braking System - System employed in stopping the trailer. Typical braking systems are electric, surge, hy­draulic, hydraulic-surge and air.
3. GVWR- Gross Vehicle Weight Rating (GVWR), is the maximum number of pounds the trailer can carry, in­cluding the fuel cell (empty).
:
ALWAYS make sure the trailer is in good
operating condition. Check the tires for proper inflation and wear. Also check the wheel lug nuts for proper tightness.
5. Frame Width - Measurement is from fender to fender
6. Jack Stand - Trailer support device with maximum pound requirement from the tongue of the trailer.
7. Coupler - Type of hitch used on the trailer for towing.
8. Tire Size - Indicates the diameter of the tire in inches (10,12,14, etc.), and the width in millimeters (175,185,205, etc.). The tire diameter must match the diameter of the tire rim.
9. Tire Ply - The tire ply (layers) number is rated in letters; 2-ply,4-ply,6-ply, etc.
10. Wheel Hub - The wheel hub is connected to the trailer’s axle.
11. Tire Rim - Tires mounted on a tire rim. The tire rim must match the size of the tire.
12. Lug Nuts - Used to secure the wheel to the wheel hub. Always use a torque wrench to tighten down the lug nuts. See Table 17 and Figure 67 sequence.
13. Axle - Indicates the maximum weight the axle can sup­port in pounds, and the diameter of the axle expressed in inches (see Table 2). Please note that some trailers have a double axle. This will be shown as 2-6000 lbs., meaning two axles with a total weight capacity of 6000 pounds.
14. Suspension - Protects the trailer chassis from shocks transmitted through the wheels. Types of suspension used are leaf, Q-flex, and air ride.
15. Electrical - Electrical connectors (looms) are provided with the trailer so the brake lights and turn signals can be connected to the towing vehicle.
16. Application - Indicates which units can be employed on a particular trailer.
or lug nut tightening and
4. Frame Length - Measurement is from the ball hitch to the rear bumper (reflector).
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 17
DCA-45USI — GENERATOR DECALS
The DCA-45USI generator is equipped with a number of safety decals. These decals are provided for operator safety and maintenance information. The illustration below and on the preceding page show the decals as they appear on the machine. Should any of these decals become unreadable, replacements can be obtained from your dealer.
PAGE 18 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — GENERATOR DECALS
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 19
DCA-45USI — GENERAL INFORMATION
DCA-45USI FAMILIARIZATION Generator
The MQ Power Model DCA-45USI (Figure 4) is a 36 kW
generator
that is designed as a high quality portable (requires a trailer for transport) power source for telecom sites, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
z
Tachometer
z
Water Temperature Gauge/ Alarm Lamp
z
Oil Pressure Gauge/ Alarm Lamp
z
Charging Ammeter Gauge
z
Pre-Heat Lamp
z
Panel Light
z
Panel Light Switch
z
Ignition/Preheat Switch
z
Fuel Gauge
z
Fuel Filter Water Level Alarm Lamp
Generator Control Panel
The “Generator Control Panel” is provided with the following:
z
Output Voltage Adjustment Knob
z
Frequency Meter (Hz)
z
AC Ammeter (Amps)
z
AC Voltmeter (Volts)
z
Ammeter Change-Over Switch
z
Voltmeter Change-Over Switch
z
Voltage Regulator
z
3-Pole, 110 amp Main Circuit Breaker
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
Open Delta Excitation System
The DCA-45USI generator is equipped with the state of the art
Open-Delta
" an electrically independent winding wound among stationary windings of the AC output section.
There are four connections of the open delta A, B, C and D. During steady state loads, the power from the voltage regulator is supplied from the parallel connections of A to B, A to D, and C to D. These three phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.
When a heavy load, such as a motor starting or a short circuit occurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C. This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation current, offering maximum motor starting capabilities. The excitation does not have a " the required load.
Engine
The DCA-45USI is powered by a 4 cycle, water cooled, turbocharged Isuzu BB-4JG1T every performance requirement for the generator. Reference Table 1 for engine specifications.
In keeping with MQ Power's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
The basic controls and indicators for the DCA-45USI generator are addressed on the following pages.
" excitation system. The open delta system consist of
fixed ceiling
" and responds according the demands of
diesel
engine. This engine is designed to meet
z
Three 120/240V output receptacles (CS-6369), 50 amps
z
Three auxilliary circuit breakers, @50 amps
z
Two 125 VAC output receptacles, (GFCI), 20 amps
z
Two GFCI circuit breakers @ 20amps
z
Five output terminal lugs (3Ø power)
Control Box
The “Control Box” is provided with the following:
z
Automatic Voltage Regulator
z
Current Transformer
z
Emergency Relay
z
Over-Current Relay
PAGE 20 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
Mechanical Governor System
The mechanical governor system control the RPM of the engine. When the engine demands increase or decrease, the mechanical governor system regulates the frequency variation to within ±.5%. The electronic governor option decreases the frequency variation to within ±0.25%.
Extension Cables
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 5 ) as a guide for selecting proper extension cable size.
DCA-45USI — MAJOR COMPONENTS
Figure 4. Major Components
3elbaT. stnenopmoCrojaMrotareneG
.ONMETINOITPIRCSED
1ylbmessArelffuM
2ylbmessAenignE
3ylbmessArenaelCriA
4ylbmessArotareneG
5ylbmessAlanimreTtupt
6ylbmessAknaTleuF
7ylbmessAyrettaB
8ylbmessAlenaPlortnoCrotareneG
9ylbmessAlenaPgnitarepOenignE
uO
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 21
Figure 5. Generator Control Panel
DCA-45USI — GENERATOR CONTROL PANEL
The definitions below describe the controls and functions of the DCA-45USI "
1. Main Circuit Breaker – This three-pole, 110 amp main breaker is provided to protect the
Terminal Lugs
2. AC Ammeter – Indicates the amount of current the load
is drawing from the generator per leg selected by the ammeter phase-selector switch.
3. Ammeter Change-Over Switch – This switch allows the AC ammeter to indicate the current flowing to the load connected to any phase of the output terminals, or to be switched off. This switch does not effect the generator output in any fashion, it is for current reading only.
4. Voltmeter Change-Over Switch – This switch allows the AC voltmeter to indicate phase to phase voltage between any two phases of the output terminals or to be switched off.
5. Voltage Regulator Control – Allows ±15% manual adjustment of the generator’s output voltage.
6. Frequency Meter – Indicates the output frequency in hertz (Hz). Normally 60 Hz ±1 Hz .
7. AC Voltmeter – Indicates the output voltage present at the
U,V, and W Output Terminal Lugs
Generator Control Panel
" (Figure 5).
U,V, and W Output
from overload.
.
Located behind the generator control panel is the
Control Box
electronic components required to make the generator function.
The Control Box is equipped with the following major components:
z
Over-Current Relay
z
Voltage Rectifer
z
Starter Relay
z
Engine Controller (Computer Controlled)
z
Current Transformer
z
Voltage Selector Switch
NOTE
In the event of a short circuit or over current condition, it will automatically trip the 60 amp main breaker.
To restore power to the
reset
button on the overcurrent relay and place the
circuit breaker in the
Generator
. This box contains some of the necessary
Remember the
relay
monitors the current
flowing from the
Output Terminal Lugs
load.
Output Terminal Panel
overcurrent
U,V, and W
to the
, press the
main
closed
position (ON).
PAGE 22 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — ENGINE OPERATING PANEL
The definitions below describe the controls and functions of the DCA-45USI "
1. Panel Light - Normally used in dark places or at night. When activated, panel will luminate. When the generator is not in use, turn the panel light switch to the OFF position.
2. Panel Light Switch- When activated, will turn on control panel light.
3. Oil Pressure Lamp - Indicates that the oil pressure is too low and will shut down the engine.
4. Water Temperature Lamp - Indicates that the water temperature is too hot and will shut down the engine.
5. Fuel Filter Water Level Alarm Lamp - This lamp turns on when water in the filter is detected. Drain the water in the fuel filter strainer to correct the problem.
6. Pre-heat Lamp - This indicates when the engine has been preheated and is ready for starting. In cold weather conditions, it may be several minutes before the lamp illuminates.
Engine Operating Panel
" (Figure 6).
7. Fuel Leak Detected Alarm – This indicates that liquid is present in the fuel tank containment basin. Drain the containment basin and repair any leaks.
8. Tachometer – Indicates engine speed in RPM’s for 60 Hz operation. This meter should indicate 1800 RPM’s when the rated load is applied. In addition a built in hour meter will record the number of operational hours that the generator has been in use.
9. Fuel Gauge - Indicates amount of diesel fuel available.
10. Charging Ammeter Gauge – Indicates the current being supplied by the engine’s alternator which provides current for generator’s control circuits and battery charging system.
11. Water Temperature Gauge – During normal operation this gauge be should read between 165o F to 203o F.
12. Oil Pressure Gauge – Normal operation should be about 28 to 71 psi. When starting the generator the oil pressure may read a bit higher, but after the engine warms up the oil pressure should return to normal.
13. Starter Switch – Three position switch, stop, preheat/run and start. Insert ignition key to start and stop engine.
Figure 6. Engine Operating Panel
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 23
DCA-45USI — OUTPUT TERMINAL PANEL FAMILIARIZATION
Output Terminal Panel
The
Output Terminal Panel
on the right-hand side (left from control panel) of the generator. Lift up on the cover to gain access to receptacles and terminal lugs.
NOTE
(Figure 7) shown below is located
Terminal legs “O” and “Ground” are considered
bonded grounds
Output Terminal Familiarization
The “
Output Terminal Panel
following:
z
Three (3) 120/240V output receptacles, 50 amp
z
Three (3) Circuit Breakers 240V @50 amps
z
Two (2) 120V GFCI receptacles, 20 amp
z
.
Two (2) GFCI Circuit Breakers @ 20 amps
z
One Main Circuit Breaker @110 amps
z
Five (5) Output Terminal Lugs ( U, V, W, O, Ground)
” (Figure 7) is provided with the
Figure 7. Output Terminal Panel
PAGE 24 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the UVWO terminals.
Pressing the being tripped. Pressing the " the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.
reset
button resets the GFCI receptacle after
voltage selector switch
Test Button
" (See Figure 8) in
Each auxilliary receptacle is protected by a 50 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the
Output Terminal Lugs
Turn the control panel to obtain the desired voltage. Turning the knob clockwise will clockwise will
Figure 10. Voltage Regulator Control Knob
Removing the Plastic Face Plate (
The
Output Terminal Lugs
plate cover (Figure 11). Un-screw the securing bolts and lift the plastic terminal cover to gain access to the terminal enclosure.
.
voltage regulator control knob
increase
decrease
the voltage, turning the knob counter-
the voltage.
(Figure 10) on the
Output Terminal Lugs
are protected by a plastic face
)
After the load wires have been securely attached to the
Figure 8. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 120/240 VAC, 50 amp auxilliary twist-lock (CS-6369) recepacles (Figure 9) provided on the output terminal panel.These receptacles can when the voltage selector switch is placed in the
only
be accessed
single-
Output Terminal Lugs
phase 240/120 position.
Figure 11. Plastic Face Plate (UVWO Terminals)
, reinstall the plastic face plate.
Figure 9. 240 VAC Twist-Lock
Auxiliary Receptacles
DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05) — PAGE 25