Multiquip DCA125USJ User Manual

PARTS AND OPERATION MANUAL
OPERATION AND PARTS MANUAL
®
MODEL DCA125USJ
60 Hz GENERATOR
(JOHN DEERE 6068TF 275 DIESEL ENGINE)
PARTS LIST NO. M3870400004
Revision #2 (01/27/11)
publication, visit our website at:
www.multiquip.com
THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.
PAGE 2 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
NOTE PAGE
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 3
TABLE OF CONTENTS
MQ POWER DCA12USJMQ POWER DCA12USJ
MQ POWER DCA12USJ
MQ POWER DCA12USJMQ POWER DCA12USJ AC GENERAAC GENERA
AC GENERA
AC GENERAAC GENERA
California Proposition 65 Warning ..................................... 2
Here's How To Get Help ....................................................3
Table Of Contents ............................................................. 4
Parts Ordering Procedures ............................................... 5
Specifications ................................................................... 6
Dimensions (Top, Side, Front) .......................................... 7
Safety Information ....................................................... 8-13
Generator Decals....................................................... 14-15
Installation ................................................................. 16-17
General Information ........................................................ 18
Major Components ......................................................... 19
Generator Control Panel ................................................. 21
Engine Operating Panel ............................................. 22-23
Output Terminal Panel Familiarization ........................ 24-26
Load Application ............................................................. 27
Generator Outputs .......................................................... 28
Gauge Reading ............................................................... 29
Output Terminal Panel Connections ........................... 30-31
Pre Setup .................................................................. 32-35
Generator Start-up Procedure (Manual) ..................... 36-37
Generator Start-up Procedure (Auto Mode) .................... 38
Generator Shut-Down Procedure .................................... 39
Maintenance .............................................................. 40-42
Trailer Brakes Maintenance ............................................ 43
Trailer Maintenance .................................................... 44-45
Trailer Wiring Diagram ..................................................... 46
Generator Wiring Diagram ............................................... 47
Engine Wiring Diagram ................................................... 48
Generator Troubleshooting .............................................. 49
Engine Controller Troubleshooting ................................... 50
Explanation of Code in Remarks Column ....................... 52
Suggested Spare Parts .................................................. 53
TORTOR
TOR
TORTOR
COMPONENT DRACOMPONENT DRA
COMPONENT DRA
COMPONENT DRACOMPONENT DRA
Generator Assembly .................................................. 54-55
Control Box Assembly ............................................... 56-59
Engine & Radiator Assembly ..................................... 60-63
Output Terminal Assembly ......................................... 64-65
Battery Assembly ...................................................... 66-67
Muffler Assembly ...................................................... 68-69
Fuel Tank Assembly .................................................. 70-71
Enclosure #1 Assembly ............................................ 72-75
Enclosure #2 Assembly ............................................ 76-77
Rubber Seals Assembly ............................................ 78-79
Nameplate and Decals .............................................. 80-81
Terms and Condition of Sale — Parts ............................ 82
Specification and part
NOTE
number are subject to change without notice.
WINGSWINGS
WINGS
WINGSWINGS
PAGE 4 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
PARTS ORDERING PROCEDURES
r
Ordering parts has never been easier!
Choose from three easy options:
January 1
Effective:
st
, 2006
Best Deal!
Order via Internet (Dealers Only):
Order parts on-line using Multiquip’s SmartEquip website!
View Parts Diagrams
Order Parts
Print Specification Information
Goto www.multiquip.com and click on
Order Par ts
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax. Domestic (US) Customers dial: 1-800-6-PARTS-7 (800-672-7877)
Non-Dealer Customers: Contact your local Multiquip Dealer for parts or call 800-427-1244 for help in locating a dealer near you.
to log in and save!
Order via Phone:
If you have an MQ Account, to obtain a Username and Password, E-mail us at: parts@multiquip.
com.
To obtain an MQ Account, contact you District Sales Manager for more information.
Use the internet and qualify for a 5% Discount on Standard orders for all orders which include complete part numbers.*
Fax your order in and qualify for a 2% Discount on Standard orders for all orders which include complete part numbers.*
Domestic (US) Dealers Call:
1-800-427-1244
International Customers should contact their local Multiquip Representatives for Parts Ordering information.
Note: Discounts Are Subject To Change
Note: Discounts Are Subject To Change
Dealer Account Number
Dealer Name and Address
Shipping Address (if different than billing address)
Return Fax NumberApplicable Model Number
Quantity, Part Number and Description of Each Part
www.multiquip.com
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 5
When ordering parts, please supply:
Specify Preferred Method of Shipment:UPS/Fed Ex ✓ DHL
Priority One Tr uck
Ground
Next Day
Second/Third Day
NOTICE
All orders are treated as Standard Orders and will
ship the same day if received prior to 3PM PST.
WE ACCEPT ALL MAJOR CREDIT CARDS!
1
DCA-125USJ — SPECIFICATIONS
ledoMJSU521ACD
snoitacificepSrotareneG.1elbaT
epyT
AlartueNhtiwratSgaZgiZ
esahP
deepS
noitcennoCerutamr
3elgniS
tuptuOybdnatS
tuptuOemirP
egatloV
ycneuqerF
rotcaFrewoP
rewoPCA.xuA
egatloV
tuptuO
042V021/042
8.01
)WK011(AVK731WK97
)WK001(AVK521WK27
V084roV
rotareneg
zH06
mpr0081
zH06,esahPelgniS
V021
(WK8.4
)2xWK4.2
snoitacificepSenignE.2elbaT
suonorhcnysepytdetcetorpnepo,detalitnevfles,dleifgnivloveR
ledoM
epyT
srednilyCfo.oN
kortSxeroB
e
tuptuOdetaR
tnemecalpsiD
gnitratS
yticapaCtnalooC
yticapaCliOebuL
epyTleuF
apaCknaTleuF
ytic
tarh/)L0.92(.lag7.7 daollluf tarh/)L9.12(.lag8.5 daol4/3
noitpmusnoCleuF
h/)L5.41(.lag8.3 daol2/1 tarh/)L3.9(.lag5.2 daol4/1
tar
yrettaB
srednilyc6
1cirtcelE
572FT8606EREEDNHOJ
degrahc-obrut,noitcejnitcerid,delooc-retaw,elcyc4
)mm721xmm601(.ni5x.ni91.4
mpr0081/PH051
)cc008,6(.ni.uc514
CDV2
)sretil8.61(.lag4.4
)sretil9.81(.lag3.5
leuFleseiD2#
)sretil046(.lag961
64puorGICBV21
PAGE 6 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — DIMENSIONS (TOP, SIDE AND FRONT)
Figure 1. Dimensions
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 7
1
DCA-125USJ — SAFETY INFORMATION
Do not operate or service the equipment before reading the entire manual. Safety precautions should be followed at all times when operating this equipment. Failure to read and understand the safety messages and operating instructions could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you about potential hazards that could injure you or others. The safety messages specifically address the level of exposure to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION or NOTICE.
SAFETY SYMBOLS
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
Potential hazards associated with the operation of this equipment will be referenced with hazard symbols which may appear throughout this manual in conjunction with safety messages.
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.
CAUTION
Indicates a hazardous situation which, if not avoided, COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
PAGE 8 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — SAFETY INFORMATION
.
GENERAL SAFETY
CAUTION
NEVER operate this equipment without proper protective
clothing, shatterproof glasses, respiratory protection, hearing protection, steel-toed boots and other protective devices required by the job or city and state regulations.
NEVER operate this equipment when not feeling well due to fatigue, illness or when under medication.
NEVER operate this equipment under the influence of drugs or alcohol.
ALWAYS check the equipment for loosened threads or bolts before starting.
DO NOT use the equipment for any purpose other than its intended purposes or applications.
NEVER use accessories or attachments that are not recommended by Multiquip for this equipment. Damage to the equipment and/or injury to user may result.
ALWAYS know the location of the nearest fire extinguisher.
ALWAYS know the location of the nearest first aid kit.
ALWAYS know the location of the nearest
phone or keep a phone on the job site. Also, know the phone numbers of the nearest ambulance, doctor and fire department. This information will be invaluable in the case of an emergency.
GENERATOR SAFETY
DANGER
NEVER operate the equipment in an explosive
atmosphere or near combustible materials. An explosion or fire could result causing severe
bodily harm or even death.
WARNING
NOTICE
This equipment should only be operated by trained and qualified personnel 18 years of age and older.
Whenever necessary, replace nameplate, operation and safety decals when they become difficult read.
Manufacturer does not assume responsibility for any accident due to equipment modifications. Unauthorized equipment modification will void all warranties.
NEVER disconnect any emergency or safety devices. These devices are intended for operator safety Disconnection of these devices can cause severe injury, bodily harm or even death. Disconnection of any of these devices will void all warranties.
CAUTION
NEVER lubricate components or attempt service on a
running machine.
NOTICE
ALWAYS ensure generator is on level ground before use.
ALWAYS keep the machine in proper running condition.
Fix damage to machine and replace any broken parts immediately.
ALWAYS store equipment properly when it is not being used. Equipment should be stored in a clean, dry location out of the reach of children and unauthorized personnel
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 9
DCA-125USJ — SAFETY INFORMATION
r
ENGINE SAFETY
DANGER
The engine fuel exhaust gases contain poisonous carbon monoxide. This gas is colorless and odorless, and can cause death if inhaled.
The engine of this equipment requires an adequate free flow of cooling air. NEVER operate this equipment in any enclosed or narrow area where free flow of the air is restricted. If the air flow is restricted it will cause injury to people and property and serious damage to the equipment or engine.
WARNING
DO NOT place hands or fingers inside engine
compartment when engine is running.
NEVER operate the engine with heat shields or guards removed.
Keep fingers, hands hair and clothing away from all moving parts to prevent injury.
DO NOT remove the radiator cap while the engine is hot. High pressure boiling water will gush out of the radiator and severely scald any persons in the general area of the generator.
DO NOT remove the coolant drain plug while the engine is hot. Hot coolant will gush out of the coolant tank and severely scald any persons in the general area of the generator.
DO NOT remove the engine oil drain plug while the engine is hot. Hot oil will gush out of the oil tank and severely scald any persons in the general area of the generator.
CAUTION
NEVER touch the hot exhaust manifold,
muffler or cylinder. Allow these parts to cool before servicing equipment.
NOTICE
NEVER run engine without an air filter or with a dirty air filter. Severe engine damage may occur. Service air filte frequently to prevent engine malfunction.
NEVER tamper with the factory settings of the engine or engine governor. Damage to the engine or equipment can result if operating in speed ranges above the maximum allowable.
Wet stacking is a common problem with diesel engines which are operated for extended periods with light or no load applied. When a diesel engine operates without sufficient load (less than 40% of the rated output), it will not operate at its optimum temperature. This will allow unburned fuel to accumulate in the exhaust system, which can foul the fuel injectors, engine valves and exhaust system, including turbochargers, and reduce the operating performance.
In order for a diesel engine to operate at peak efficiency,
it must be able to provide fuel and air in the proper ratio and at a high enough engine temperature for the engine to completely burn all of the fuel.
Wet stacking does not usually cause any permanent
damage and can be alleviated if additional load is applied to relieve the condition. It can reduce the system performance and increase maintenance. Applying an increasing load over a period of time until the excess fuel is burned off and the system capacity is reached usually can repair the condition. This can take several hours to burn off the accumulated unburned fuel.
State Health Safety Codes and Public Resources Codes specify that in certain locations, spark arresters must be used on internal combustion engines that use hydrocarbon fuels. A spark arrester is a device designed to prevent accidental discharge of sparks or flames from the engine exhaust. Spark arresters are qualified and rated by the United States Forest Service for this purpose. In order to comply with local laws regarding spark arresters, consult the engine distributor or the local Health and Safety Administrator.
PAGE 10 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — SAFETY INFORMATION
FUEL SAFETY
DANGER
DO NOT start the engine near spilled fuel or combustible
fluids. Diesel fuel is extremely flammable and its vapors can cause an explosion if ignited.
ALWAYS refuel in a well-ventilated area, away from sparks and open flames.
ALWAYS use extreme caution when working with flammable liquids.
DO NOT fill the fuel tank while the engine is running
or hot.
DO NOT overfill tank, since spilled fuel could ignite if it comes into contact with hot engine parts or sparks from the ignition system.
Store fuel in appropriate containers, in well-ventilated areas and away from sparks and flames.
NEVER use fuel as a cleaning agent.
DO NOT smoke around or near the
equipment. Fire or explosion could result from fuel vapors or if fuel is spilled on a hot engine.
TOWING SAFETY
CAUTION
Check with your local county or state safety towing regulations, in addition to meeting
Department of Transportation (DOT) Safety Towing Regulations, before towing
your generator.
Refer to MQ Power trailer manual for additional safety information.
In order to reduce the possibility of an accident while transporting the generator on public roads, ALWAYS make sure the trailer that supports the generator and the towing vehicle are mechanically sound and in good operating condition.
ALWAYS shutdown engine before transporting
Make sure the hitch and coupling of the towing vehicle are rated equal to, or greater than the trailer “gross vehicle weight rating.”
ALWAYS inspect the hitch and coupling for wear. NEVER tow a trailer with defective hitches, couplings, chains, etc.
Check the tire air pressure on both towing vehicle and trailer. Trailer tires should be inflated to 50 psi cold. Also check the tire tread wear on both vehicles.
ALWAYS make sure the trailer is equipped with a safety chain.
ALWAYS properly attach trailer’s safety chains to towing
vehicle.
ALWAYS make sure the vehicle and trailer directional, backup, brake and trailer lights are connected and working properly.
DOT Requirements include the following:
 s#ONNECTANDTESTELECTRICBRAKEOPERATION
 s3ECUREPORTAB
wraps.
The maximum speed for highway towing is 55 MPH unless posted otherwise. Recommended off-road towing is not to exceed 15 MPH or less depending on type of terrain.
Avoid sudden stops and starts. This can cause skidding, or jack-knifing. Smooth, gradual starts and stops will improve towing.
Avoid sharp turns to prevent rolling.
Trailer should be adjusted to a level position at all times when towing.
Raise and lock trailer wheel stand in up position when towing.
Place chock blocks underneath wheel to prevent rolling while parked.
Place support blocks underneath the trailer’s bumper to prevent tipping while parked.
Use the trailer’s swivel jack to adjust the trailer height to a level position while parked.
LEPOWERCABLESINCABLETRAYWITHTIE
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 11
DCA-125USJ — SAFETY INFORMATION
ELECTRICAL SAFETY
DANGER
DO NOT touch output terminals during
operation. Contact with output terminals during operation can cause electrocution,
electrical shock or burn.
The electrical voltage required to operate the generator can cause severe injury or even death through physical contact with live circuits. Turn generator and all circuit breakers OFF before performing maintenance on the generator or making contact with output terminals.
NEVER insert any objects into the output receptacles during operation. This is extremely dangerous. The possibility exists of electrical shock, electrocution or death.
Backfeed to a utility system can cause
electrocution and/or property damage. NEVER connect the generator to a
building’s electrical system without a transfer switch or other approved device. All installations should be performed by a licensed electrician in accordance with all applicable laws and electrical codes. Failure to do so could result in electrical shock or burn, causing serious
injury or even death.
Make sure power cables are securely connected to the generator’s output receptacles. Incorrect connections may cause electrical shock and damage to the generator.
NOTICE
ALWAYS make certain that proper power or extension cord has been selected for the job. See Cable Selection Chart in this manual.
Grounding Safety
DANGER
ALWAYS make sure that electrical circuits are properly
grounded to a suitable earth ground (ground rod) per the National Electrical Code (NEC) and local codes before operating generator. Severe injury or death by electrocution can result from operating an ungrounded generator.
NEVER use gas piping as an electrical ground.
Power Cord/Cable Safety
DANGER
NEVER let power cords or cables lay in water.
NEVER stand in water while AC power from the
generator is being transferred to a load.
NEVER use damaged or worn cables or cords when connecting equipment to generator. Inspect for cuts in the insulation.
NEVER grab or touch a live power cord or cable with wet hands. The possibility exists of electrical shock,
electrocution or death.
PAGE 12 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — SAFETY INFORMATION
BATTERY SAFETY
DANGER
DO NOT drop the battery. There is a possibility that the
battery will explode.
DO NOT expose the battery to open flames, sparks, cigarettes, etc. The battery contains combustible gases and liquids. If these gases and liquids come into contact with a flame or spark, an explosion could occur.
WARNING
ALWAYS wear safety glasses when handling
the battery to avoid eye irritation. The battery contains acids that can cause injury to the eyes and skin.
Use well-insulated gloves when picking up the battery.
ALWAYS keep the battery charged. If the battery is not charged, combustible gas will build up.
ENVIRONMENTAL SAFETY
NOTICE
Dispose of hazardous waste properly. Examples of potentially hazardous waste are used motor oil, fuel and fuel filters.
DO NOT use food or plastic containers to dispose of hazardous waste.
DO NOT pour waste, oil or fuel directly onto the ground, down a drain or into any water source.
ALWAYS recharge the battery in a well-ventilated environment to avoid the risk of a dangerous concentration of combustible gasses.
If the battery liquid (dilute sulfuric acid) comes into contact with clothing or skin, rinse skin or clothing immediately with plenty of water.
If the battery liquid (dilute sulfuric acid) comes into contact with eyes, rinse eyes immediately with plenty of water and contact the nearest doctor or hospital to seek medical attention.
CAUTION
ALWAYS disconnect the NEGATIVE battery terminal
before performing service on the generator.
ALWAYS keep battery cables in good working condition. Repair or replace all worn cables.
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 13
DCA-125USJ — GENERATOR DECALS
The DCA-125USJ generator is equipped with a number of safety decals (Figures 2 and 3). These decals are provided for operator safety and maintenance information. The illustration below and on the preceding page show the decals as they appear on the machine. Should any of these decals become unreadable, replacements can be obtained from your dealer.
Figure 2. Generator Decals
PAGE 14 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — GENERATOR DECALS
Figure 3. Generator Decals (Cont.)
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 15
1
DCA-125USJ — INSTALLATION
Figure 4. Typical Generator Grounding Application
PAGE 16 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — INSTALLATION
Outdoor Installation
Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.
The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.
CAUTION - EXHAUST HAZARD
Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.
Indoor Installation
Generator Grounding
To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.
Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following grounding requirements:
1. Use one of the following wire types to connect the generator to earth ground.
a. Copper - 10 AWG (5.3 mm2) or larger.
b. Aluminum - 8 AWG (8.4 mm2) or larger.
2. When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground rod should be buried aminimum of 8 ft. into the ground.
Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.
Mounting
The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.
NOTE
When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 17
DCA-125USJ — GENERAL INFORMATION
DCA-125USJ Series Familiarization Generator
The MQ Power Model DCA-125USJ is a 100 kW (Figure 5) that is designed as a high quality portable (requires a trailer for transport) power source for telecom sites, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
Tachometer
Water Temperature Gauge
Oil Pressure Gauge
Charging Ammeter Gauge
Fuel Level Gauge
Pre-heat Lamp
Panel Light/Panel Light Switch
Auto ON/OFF Engine Controller (MPEC)
Fuel Leak Detected Alarm Lamp
Generator Control Panel
The “Generator Control Panel” is provided with the following:
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter Change-Over Switch
Voltmeter Change-Over Switch
Voltage Regulator
3-Pole, 300 amp Main Circuit Breaker
Control Box
The “Control Box”, located behind the
Panel
, is provided with the following:
Automatic Voltage Regulator
Current Transformer
Over-Current Relay
Voltage Rectifer
Starter Relay
Engine Controller (Computer Controlled)
Voltage Selector Switch
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
Three 120/240V output receptacles (CS-6369), 50A
Three auxilliary circuit breakers, 50A
Two 120V output receptacles (GFCI), 20A
Two GFCI circuit breakers, 20A
Five output terminal lugs (3Ø power)
Battery Charger (Optional)
Water Heater (Optional)
Generator Control
generator
Open Delta Excitation System
The DCA-125USJ generator is equipped with the state of the art " system consist of an electrically independent winding wound among stationary windings of the AC output section.
There are four connections of the open delta A, B, C and D. During steady state loads, the power from the voltage regulator is supplied from the parallel connections of A to B, A to D, and C to D. These three phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.
When a heavy load, such as a motor starting or a short circuit occurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C. This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation current, offering maximum motor starting capabilities. The excitation does not have a " according the demands of the required load.
Engine
The DCA-125USJ is powered by a 4 cycle, water cooled, direct injection, turbocharged JOHN DEERE
6068TF275 Diesel Engine
every performance requirement for the generator. Reference Table 1 for engine specifications.
In keeping with MQ Power's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
Electric Governor System
The electric governor system controls the RPMs of the engine. When the engine demand increases or decreases, the governor system regulates the frequency variation to ±.25%.
Extension Cables
When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 5) as a guide for selecting proper extension cable size.
Open-Delta
" excitation system. The open delta
fixed ceiling
" and responds
Model
. This engine is designed to meet
PAGE 18 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — MAJOR COMPONENTS
Figure 5. Major Components
3elbaT. stnenopmoCrojaMrotareneG
.ONMETINOITPIRCSED
1ylbmessArelffuM
2ylbmessAenignE
3ylbmessAerusolcnE
4ylbmessArotareneG
5ylbmessAlanimreTtuptu
6ylbmessAknaTleuF
7ylbmessAyrettaB
8ylbmessAlenaPlortnoCrotareneG
9ylbmessAlenaPgnitarepOenignE
O
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 19
NOTE PAGE
PAGE 20 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
Figure 6. Generator Control Panel
DCA-125USJ — GENERATOR CONTROL PANEL
The definitions below describe the controls and functions of the DCA-125USJ
1. Main Circuit Breaker – This three-pole, 300A main
breaker is provided to protect the the
Terminal Lugs
2. Frequency Meter – Indicates the output frequency in
hertz (Hz). Normally 60 Hz.
3. AC Ammeter – Indicates the amount of current the load
is drawing from the generator per leg selected by the ammeter phase-selector switch.
4. Ammeter Change-Over Switch – This switch allows
the AC ammeter to indicate the current flowing to the load connected to any phase of the output terminals, or to be switched off. This switch does not effect the generator output in any fashion, it is for current reading only.
5. AC Voltmeter – Indicates the output voltage present at
the
U,V, and W Output Terminal Lugs
6. Voltmeter Change-Over Switch – This switch allows
the AC voltmeter to indicate phase to phase voltage between any two phases of the output terminals or to be switched off.
Generator Control Panel
(Figure 6).
U,V, and W Output
from overload.
.
Located behind the generator control panel is the
Control Box
electronic components required to make the generator function.
The Control Box is equipped with the following major components:
Over-Current Relay
Voltage Rectifer (AVR)
Starter Relay
Current Transformer
Voltage Selector Switch
NOTE
In the event of a short circuit or over current condition, it will automatically trip the 60 amp main breaker.
To restore power to the
reset
button on the overcurrent relay and place the
circuit breaker in the
Generator
. This box contains some of the necessary
Remember the
relay
monitors the current
flowing from the
Output Terminal Lugs
load.
Output Terminal Panel
overcurrent
U,V, and W
to the
, press the
main
closed
position (ON).
7. Voltage Regulator Control – Allows ±15% manual
adjustment of the generator’s output voltage.
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 21
1
DCA-125USJ — ENGINE OPERATING PANEL
Figure 7. Engine Operating Panel
PAGE 22 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — ENGINE OPERATING PANEL
The definitions below describe the controls and functions of the DCA-125USJ
1. Panel Light – Normally used in dark areas or at night
time. When activated, panel lights will illuminate. When the generator is not in use be sure to turn the panel light switch to the OFF position.
2. Panel Light Switch – When activated will turn on control
panel light.
3. Oil Pressure Gauge – During normal operation this
gauge be should read between 35 to 65 psi. When starting the generator the oil pressure may read a little higher, but after the engine warms up the oil pressure should return to the correct pressure range.
4. Water Temperature Gauge – During normal operation
this gauge be should read between 180° and 221°F.
5. Charging Ammeter Gauge – Indicates the current
being supplied by the engine’s alternator which provides current for generator’s control circuits and battery charging system.
6. Fuel Gauge - Indicates amount of diesel fuel available.
7. Tachometer – Indicates engine speed in RPM’s for 60
Hz operation. This meter should indicate 1800 RPM’s when the rated load is applied. In addition a built in hour meter will record the number of operational hours that the generator has been in use.
8. Pre-Heat Lamp – As the engine cranks, this lamp will
illuminate to indicate automatic preheating of the engine. When the lamp turns off, the engine has been preheated and will start automatically.
9. Fuel Leak Detected Alarm Lamp – This lamp will
illuminate when a leak in the fuel tank containment enclosure is detected.
10. Auto On/Off Engine Controller (MPEC) –
This controller has a vertical row of status LED's (inset), that when lit, indicate that an engine malfunction (fault) has been detected. When a fault has been detected the engine controller will evaluate the fault and all major faults will shutdown the generator.
Engine Operating Panel
(Figure 7).
During engine for 10 seconds before disengaging. If the engine does not engage (start) by the third attempt, the engine will be shutdown by the engine controller’s mode. If the engine engages at a speed (RPM's) that is not safe, the controller will shutdown the engine by initializing the
Also the engine controller will shut down the engine in the event of low oil pressure, high coolant temperature, low coolant level, and loss of magnetic pickup. These conditions can be observed by monitoring the LED status indicators on the front of the controller module.
A. MPEC Control Switch – This switch controls the
B. Low Oil Pressure – Indicates the engine pressure has
C. High Coolant Temperature – Indicates the engine
D. Overcrank Shutdown – Indicates the unit has
E. Overspeed Shutdown – Indicates the engine is running
F. Engine Running – Indicates that engine is running at
cranking cycle
Over Speed Protection
running of the unit. If this switch is set to the OFF/RESET position, the unit will not run. When this switch is set to the MANUAL position, the generator will start immediately.
If the generator is to be connected to a building's AC power source via a transfer switch (isolation), place the switch in the AUTO position. In this position the generator will monitor the AC line output from the building's power source.
fallen below 15 psi. The oil pressure is detected using variable resistive values from the oil pressure sending unit. This is considered a
temperature has exceeded 239F. The engine temperature is detected using variable resistive values from the temperature sending unit. This is considered a
major
attempted to start a pre- programmed number of times, and has failed to start. The number of cycles and duration are programmable. It is pre-set at 3 cycles with a 10 second duration. This is considered a fault.
at an unsafe speed. This is considered a
a safe operating speed.
fault.
, The MPEC will attempt to crank the
Over Crank Protection
mode.
major
fault.
major
major
fault.
1
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 23
DCA-125USJ — OUTPUT TERMINAL PANEL FAMILIARIZATION
Output Terminal Panel
The
Output Terminal Panel
on the right-hand side (left from control panel) of the generator. Lift up on the cover to gain access to receptacles and terminal lugs.
NOTE
(Figure 8) shown below is located
Terminal legs “O” and “Ground” are considered
bonded grounds
Output Terminal Familiarization
The “
Output Terminal Panel
following:
Three (3) 120/240V output receptacles @ 50 amp
Three (3) Circuit Breakers @ 50 amps
Two (2) 120V GFCI receptacles @ 20 amp
.
Two (2) GFCI Circuit Breakers @ 20 amps
Five (5) Output Terminal Lugs ( U, V, W, O, Ground)
” (Figure 8) is provided with the
Figure 8. Output Terminal Panel
PAGE 24 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)
DCA-125USJ — OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the UVWO terminals.
Pressing the being tripped. Pressing the " the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.
reset
button resets the GFCI receptacle after
voltage selector switch
Test Button
" (See Figure 9) in
Each auxilliary receptacle is protected by a 50 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the
Output Terminal Lugs
Turn the control panel to obtain the desired voltage. Turning the knob clockwise will clockwise will
Figure 11. Voltage Regulator Control Knob
Removing the Plastic Face Plate (Hard Wire Hookup Panel)
The
Output Terminal Lugs
plate cover (Figure 12). Un-screw the securing bolts and lift the plastic terminal cover to gain access to the terminal enclosure.
.
voltage regulator control knob
increase
decrease
the voltage, turning the knob counter-
the voltage.
are protected by a plastic face
(Figure 11) on the
After the load wires have been securely attached to the terminal lugs, reinstall the plastic face plate.
Figure 9. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 120/240V, 50 amp auxilliary twist-lock (CS-6369) recepacles (Figure 10) provided on the output terminal panel.These receptacles can when the voltage selector switch is placed in the
only
be accessed
single-
phase 240/120 position.
Figure 12. Plastic Face Plate (Output Terminal Lugs)
Figure 10. 120/240V Twist-Lock
Auxiliary Receptacles
DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 25
1
DCA-125USJ — OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the
Lugs
or the convienience receptacles. (See Figure 13). Make sure to read the operation manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a
main
3-pole, 300A switch ALL circuit breakers to the OFF position prior to starting the engine.
circuit breaker is provided. Make sure to
Ouput Terminal
Blower Fan
This unit has an intake fan located at the rear of the machine to draw outside air into the cabinet to cool the engine. The fan has a 10 amp AC fuse located beneath the
Selector Switch
CAUTION - ELECTRICAL SHOCK HAZARD
Voltage
(Figure 15).
Figure 15. Blower Fan Fuse
Figure 13. Connecting Loads
Over Current Relay
An
over current relay
circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the rent relay must be pressed. The over current relay is lo­cated in the control box.
(Figure 14) is connected to the main
reset button
on the over cur-
The blower fan fuse has current running through it any time the engine is operating. This fuse IS NOT connected to the main circuit breaker of the generator. Attempting to replace the fuse with the engine and/or generator operating could result in
harm
. ALWAYS turn the unit completely off before
attempting to replace or handle the fuse.
electrocution
and
severe bodily
Figure 14. Over Current Relay
PAGE 26 — DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11)