Multiplex CED-40 Operator’s Manual

COUNTER ELECTRIC & NON­CARBONATED POST-MIX DISPENSERS
CED-30 (6 valve) and CED-40 (8 valve)
INSTALLATION & SERVICE GUIDE
Part Number 5010146
Manitowoc Beverage Equipment
2100 Future Drive w Sellersburg, IN 47172-1868 Tel: 812.246.7000, 800.367.4233 Fax: 812.246.9922 www.manitowocbeverage.com
In accordance with our policy of continuous product development and improvement, this information is subject to change at any time without notice.
5010146 Revision July 22, 2003
Installation and Service Manual

FOREWORD

SerVend developed this manual as a reference guide for the owner/operator, service agent, and installer of this equipment. Please read this manual before installation or operation of the machine. Consult the troubleshooting guide within this manual for service assistance
If you cannot correct the service problem, call your SerVend Service Agent or Distributor. Always have your model and serial number available when you call.
Your Service Agent ____________________________________________________________
Service Agent Telephone Number _________________________________________________
Model Number _______________________________________________________________
Serial Number _______________________________________________________________
The model and serial numbers are located on the right side of the dispenser, just behind the drainpan.
Installation Date ______________________________________________________________
Your Local SerVend Distributor ___________________________________________________
Distributor Telephone Number ___________________________________________________
A qualified service technician should perform installation and start-up of this equipment.

UNPACKING AND INSPECTION

Note: The Unit was thoroughly inspected before leaving the factory. Any damage or irregularities should be noted at the time of delivery (or not later than 15 days from the date of delivery.)

WARRANTY INFORMATION

Consult your local SerVend Distributor for terms and conditions of your warranty. Your warranty specifically excludes all beverage valve brixing, general adjustments, cleaning, accessories and related servicing.
Your warranty card must be returned to SerVend to activate the warranty on this equipment. If a warranty card is not returned, the warranty period can begin when the equipment leaves the SerVend factory.
No equipment may be returned to SerVend without a written Return Goods Authorization (RGA). Equipment returned without an RGA will be refused at SerVend’s dock and returned to the sender at the sender’s expense.
Please contact your local SerVend distributor for return procedures.
5010146
Revision July 22, 2003
3
Installation and Service Manual

SAFETY INSTRUCTIONS

Installation and start-up of this equipment should be done by a qualified service technician. Operation, maintenance, and cleaning information in this manual are provided for the user/operator of the equipment.

DAILY CHECK LIST FOR THE OPERATOR

Check CO
the primary regulator gauge will point to a shaded area that reads “Low CO2” or “Change CO2 Cylin­der.”
Check Syrup supply.
supply. If CO2 supply is low, an arrow on
2
Clean drain pan, grid, and splash panel. See daily
cleaning instructions on page 18.
Clean the valve nozzles and diffusers. See daily
cleaning instructions on page 18.
4
Revision July 22, 2003
5010146
Installation and Service Manual

TABLE OF CONTENTS

FOREWORD ........................................................................................................ 3
UNPACKING AND INSPECTION ........................................................................ 3
WARRANTY INFORMATION ............................................................................... 3
SAFETY INSTRUCTIONS ................................................................................... 4
DAILY CHECK LIST FOR THE OPERATOR....................................................... 4
CED SERIES BEVERAGE DISPENSERS OVERVIEW ...................................... 7
COUNTER-ELECTRIC DESCRIPTION .................................................................................. 7
INTERNAL COLD (IC) CARBONATOR CED ......................................................................... 7
EXTERNAL CARBONATOR (EC) CED ................................................................................. 7
NON-CARBONATED CED .................................................................................................... 7
EQUIPMENT OVERVIEW .................................................................................... 8
INTERNAL COLD (IC) CARBONATOR ................................................................................. 8
EXTERNAL CARBONATOR (EC) ......................................................................................... 9
NON-CARBONATED UNITS ................................................................................................. 9
INSTALLATION OVERVIEW ............................................................................... 9
BIB INSTALLATION DIAGRAM ........................................................................................... 10
SELECTING LOCATIONS ..................................................................................11
ALL CEDS........................................................................................................................... 11
PLACING UNIT IN THE OPERATING POSITION ................................................................ 11
COUNTER MOUNT ............................................................................................................. 11
ISLAND MOUNT ................................................................................................................. 12
REFRIGERATION SYSTEM START.................................................................. 13
INCOMING WATER SUPPLY REQUIREMENTS ................................................................. 13
CONNECTING THE DRAIN PAN HOSE .............................................................................. 13
CONNECTING WATER SUPPLY LINE(S) TO THE CED ................................. 14
INTERNAL CARBONATOR ................................................................................................. 14
EXTERNAL CARBONATOR ............................................................................................... 14
NONCARBONATED UNIT................................................................................................... 14
5010146
Revision July 22, 2003
5
Installation and Service Manual
TABLE OF CONTENTS
CONNECTING SYRUP SUPPLY LINES TO ALL CEDS ................................... 14
CONNECTING CO2 SUPPLY LINE TO THE CED ............................................ 15
CED WITH INTERNAL CARBONATOR ............................................................................... 15
CED WITH EXTERNAL CARBONATOR ............................................................................. 15
NON-CARBONATED CED .................................................................................................. 15
SPECIFICATIONS FOR CED SERIES DISPENSERS ...................................... 16
CED - 30 SPECIFICATIONS ................................................................................................ 16
SPECIFICATIONS FOR CED SERIES DISPENSERS ...................................... 17
CED - 40 SPECIFICATIONS ................................................................................................ 17
OPERATION ...................................................................................................... 18
BAG-IN-BOX (BIB) START-UP ............................................................................................ 18
INSTALL DECALS .............................................................................................................. 18
CLEAN UP .......................................................................................................................... 18
SANITIZING AND CLEANING.......................................................................... 18
DAILY CLEANING ...............................................................................................................18
WATER BATH ..................................................................................................................... 18
PERIODIC SANITIZING OF THE DISPENSER .................................................................... 18
BAG-IN-BOX ....................................................................................................................... 19
FIGAL SYSTEM SANITIZING .............................................................................................. 19
CARBONATED/NON-CARBONATED CONVERSION...................................... 20
WIRING DIAGRAM 120 VOLT/60/1 ................................................................... 22
INTERNAL CARBONATOR ................................................................................................ 22
EXTERNAL CARBONATOR ............................................................................................... 22
WIRING DIAGRAM 220-240 VOLT/50/1 ........................................................... 23
INTERNAL CARBONATOR ................................................................................................. 23
EXTERNAL CARBONATOR ............................................................................................... 23
WIRING DIAGRAM 208-230 VOLT/60/1 ........................................................... 24
INTERNAL CARBONATOR ................................................................................................. 24
EXTERNAL CARBONATOR ............................................................................................... 24
TROUBLESHOOTING GUIDE........................................................................... 25
6
Revision July 22, 2003
5010146
Installation and Service Manual

CED SERIES BEVERAGE DISPENSERS OVERVIEW

IMPORTANT: TO THE USER OF THIS SERVICE MANUAL, THIS MANUAL IS A GUIDE FOR INSTALLING THIS EQUIPMENT. REFER TO THE TABLE OF CONTENTS FOR PAGE LOCATION FOR DETAILED INFORMATION PERTAINING TO QUESTIONS THAT ARISE DURING INSTALLATION AND START-UP OF THIS EQUIPMENT.
This section gives the Counter-Electric Dispenser de­scription, theory of operation, and service data for the 6 and 8 flavor Post Mix Dispensers (hereafter re­ferred to as CED.)

COUNTER-ELECTRIC DESCRIPTION

The CED s are small compact chillers with a high-im­pact and corrosion-resistant stainless steel housing and may be island mounted or installed on a front or rear counter. The refrigeration assemblies are the drop-in­type that can be removed for service and maintenance. Adjustable syrup flow regulators, located on the dispens­ing valves, are easily accessible to control the Water to
INTERNAL COLD (IC) CARBONATOR
CED
This CED Unit is equipped with a 1/3 H.P. refrigeration assembly and has a built-in cold carbonator. The car­bonator is located on the deck of the CED under the bonnet. The carbonator tank is located within the water tank. Installation requirements for operation are: Place­ment of CED on a countertop making sure the unit is level, installation of loose shipped parts, connection of drains, connection of plain water and syrup supplies, adjustment of CO2 regulators, fill water tank with water, and plug CED power cord into an electrical outlet.

EXTERNAL CARBONATOR (EC) CED

(Requires Connection to a Remote Carbonator)
This CED is equipped with a 1/3 H.P. refrigeration as­sembly and requires connection to an external Carbon­ator. Installation requirements for operation are: Place­ment of CED on a countertop making sure the unit is level, installation of loose shipped parts, connection of drain, connection of external carbonator, connection of plain water and syrup supplies, adjustment of CO2 regu­lators, fill water tank with water, and plug CED power cord into an electrical outlet.
Syrup Ratio (Termed Brix) of the dispensed product. All CEDs have electric dispensing valves.
5010146
Revision July 22, 2003

NON-CARBONATED CED

This CED is the same as the external carbonator unit, except no carbonator is required. Installation require­ments for operation are: Placement of CED on a countertop making sure it is level, installation of loose shipped parts, connection of drains, connection of plain water including a booster system if necessary, syrup/ juice supplies, possible adjustment of CO2 regulators, filling water tank with water, and plugging CED power cord into an electrical outlet.
7
Installation and Service Manual

EQUIPMENT OVERVIEW

NOTE: BEFORE SHIPPING, STORING, OR RELOCATING THIS CED, THE SYRUP SYSTEMS MUST BE SANITIZED AND ALL SANITIZING SOLUTION MUST BE PURGED FROM THE SYRUP SYSTEMS. ALL WATER MUST ALSO BE PURGED FROM THE PLAIN AND CARBONATED WATER SYSTEMS. A FREEZING AMBIENT ENVIRONMENT WILL CAUSE RESIDUAL WATER IN THE CED TO FREEZE CAUSING EXPANSION OF TUBING AND RESULTING IN DAMAGE TO INTERNAL COMPONENTS.

INTERNAL COLD (IC) CARBONATOR

The CED 30 is a 6 valve unit set up to dispense a non­carbonated drink from the NO. 3 dispensing valve. The CED 40 is an 8 valve unit set up to dispense a noncar­bonated drink from the No. 4 and 5 valves. The remain­ing dispensing valves on each unit are set to dispense carbonated beverages. Refer to the instructions on
page 21-22 to convert a valve from carbonated to non­carbonated or non-carbonated to carbonated.
A CO2 cylinder delivers carbon dioxide (CO2) gas through adjustable CO2 regulator to the syrup BIB pump and also to an internal carbonator. Plain water also enters the internal carbonator tank, and is carbonated by the regu­lated CO2 gas pressure. When a dispensing valve is opened, CO2 pressure exerted within the syrup BIB pump propels syrup from the BIB, through the CED Unit bev­erage coils, and into the dispensing valve. Carbonated water is forced from the carbonator tank by CO2 pres­sure which pushes cold carbonated water into the dis­pensing valve resulting in a carbonated drink being dis­pensed. A noncarbonated drink is dispensed in the same manner as a carbonated drink with the exception that plain water is substituted for carbonated.
The carbonator is replenished when the carbonated water level inside the tank drops, which in turn automati­cally starts the carbonator water pump. When the water level inside the tank has been replenished, carbonator water pump will stop.
8
Revision July 22, 2003
5010146
EQUIPMENT OVERVIEW
Installation and Service Manual

EXTERNAL CARBONATOR (EC)

The CED 30 is a 6 valve unit set up to dispense a non­carbonated drink from the No. 3 dispensing valve. The CED 40 is an 8 valve unit set up to dispense a noncar­bonated drink from the No. 4 and 5 valves. The remain­ing dispensing valves on each unit are set to dispense carbonated beverages. Refer to the instructions on
page 21-22 to convert a valve from a carbonated to non-carbonated or from non-carbonated to carbon­ated.
A CO2 cylinder delivers carbon dioxide (CO2) gas through adjustable CO2 regulators to the syrup BIB pump and also to an external carbonator. Plain water also enters the remote carbonator tank, and is carbonated by the regulated CO2 gas pressure. When a dispensing valve is opened, CO2 pressure exerted within the syrup BIB pump propels syrup from the BIB, through the CED bev­erage coils, and into the dispensing valve. Carbonated water is forced from the carbonator tank by CO2 pres­sure which pushes carbonated water through the CED cooling coils, and into the dispensing valve. Syrup and carbonated water meet simultaneously and mix at the nozzle of the dispensing valve resulting in a carbonated drink being dispensed. A noncarbonated drink is dis­pensed in the same manner as a carbonated drink with the exception that plain water is substituted for carbon­ated.
INSTALLATION
OVERVIEW
This section covers unpacking, inspecting, select­ing location, installing the CED, and preparing for operation.
1. After the unit has been unpacked, remove the keys. The key will be needed to perform brixing of valves. Hold onto the keys until such time to forward them to the respective owner/operator. Remove tape (which secures grid in place in drain pan) from grid and other packing material.
2. Make sure all items are present and in good con­dition. Loose shipped items in the carton include the drain kit parts, S/S “U” tube, John Guest fitting and the instructions.
3. Inspect CED for any external damages.
The Carbonator is replenished when the carbonated water level inside the tank drops, which in turn automati­cally starts the carbonator water pump. When the water level inside the tank has been replenished, carbonator water pump will stop.

NON-CARBONATED UNITS

A CO2 cylinder delivers carbon dioxide (CO2) gas through adjustable CO2 regulators to the syrup/juice BIB pump. When a dispensing valve is activated, pressure exerted upon the syrup BIB pump propels syrup/concentrate from the BIB, through the cooling coils, and into the dispensing valve. Plain water enters the CED and passes through the cooling coils to the dispensing valve. Syrup/concentrate and plain water meet simultaneously in the dispensing valve and mix at the nozzle resulting in a still (noncarbonated) drink being dis­pensed. For noncarbonated BIB syrup(s)/concentrate(s) to be delivered at ambient temperature, refer to the conversion instructions for bypassing the cooling coil.
5010146
Revision July 22, 2003
9
Installation and Service Manual

BIB INSTALLATION DIAGRAM

The internal carbonator in the post-mix system has two inlets and one outlet connection. The internal carbonator is pre-plumbed at the factory. The inlets for CO2 and water are located behind the splash panel. There are two inlets for water and one inlet for CO2. If you have questions refer to the plumbing diagram on your equipment.
The outlet of the syrup supply (either BIB pump or Figal tank) connects to the appropriate syrup inlet fitting. The syrup flows through the icebath to be chilled on its way to the valves. The water flows through the icebath to the internal carbonator then back through the icebath chilling the carbonated water on its way to the valves. When both fluids leave the beverage valve they are mixed in the nozzle of the valve. Out comes a properly cooled, properly ratioed soft drink.
When starting a new beverage system of either type, be sure the electrically operated valves are turned off. Assure all connections are made, turn the water supply on to the dispenser. Open CO2 tank valve and set all pressures. Turn the refrigeration on and allow the refrigeration coils to fill with ice. After the beverage has achieved a 40 degree F temperature, the ratio of the syrup-to-water (brix) on a post-mix system may then be set.
10
Revision July 22, 2003
5010146

SELECTING LOCATIONS

Installation and Service Manual
The CED may be island-mounted or installed on a front or rear counter. Locate the CED so the following require­ments are satisfied: CED is for indoor use only and must NOT be placed in an area where a water jet or similar high pressure sprayer could be used.
1. CED must be installed near a properly grounded electrical outlet with proper electrical requirements fused at proper amperage or circuit connected through an equivalent HACR circuit breaker with ELCB (GFCI). REFER TO UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE. Hz AND THE MINIMUM CIRCUIT AMPACITY OF THE CED. No other electrical equip­ment should be connected to this circuit. ALL ELEC­TRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES. MAIN PLUG MUST BE ACCESSIBLE FOR DISCONNECTION. The key switch is able to be mounted on either side of the CED. When the location for the CED is se­lected, make sure the key switch is mounted where it will be most accessible.
2. CED must be open at the top and on both sides with at least 6-inches clearance at the rear. CED has top air outlet and is to remain free of all objects. Do not place anything on top of the CED . The rear grill of the CED must be unobstructed to allow air to enter the hood.
3. Place CED close to a permanent drain in order to route the drain pan hose to the permanent drain. Water tank overflow hose goes into the drain pan.

ALL CEDS

Remove the Bonnet by removing the two screws
holding it in place.
PLACING UNIT IN THE OPERATING
POSITION
The CED must be level horizontally from right to left and front to rear.
CED inlet supply lines, power cord, and drain pan hose must either be routed out of the CED

COUNTER MOUNT

Place the CED in location on the countertop. Route CED inlet supply lines, power cord, and drain pan hose out of the base back access hole. Area around inlet supply lines at flanged hole behind front access panel must be closed and sealed.
Unit base back access hole, or if island-mounted, through a hole cut in the countertop under the CED Unit. Pro­ceed to applicable installation procedure.
5010146
Revision July 22, 2003
To comply with NSF requirements within the United States, the CED base must be sealed to the countertop unless the optional 4” legs are installed (see above).
All access holes to the base must be sealed. If the 4” legs are installed, proceed to step E, otherwise proceed as follows to seal the CED base.
11
Installation and Service Manual

ISLAND MOUNT

SELECTING LOCATIONS
Place the CED in location on the countertop flush with the countertop edge. Mark CED’s center line on the edge of the countertop, then move the CED to one side. Starting at the center line mark on the edge of the countertop, mea­sure back 12-inches for the location of a hole at least 4 inches to be cut into the countertop. Cut at least a 4 inch hole in the countertop where indicated. Place the CED in position over the hole. Route the inlet supply lines, power cord, and drain pan hose down through the hole in the countertop. Install the line outlet plug, provided with the CED in the base back access hole. The area around the inlet supply lines at the flanged hole behind the front ac­cess panel must be closed and sealed.
A. Tilt CED up to expose bottom of base.
B. Liberally apply silastic sealant such as Dow
Corning RTV 731 or equivalent on the base bottom edges.
C. Lower the CED into operating position on the
counter top to complete the seal of the base to the countertop.
Note: Do not move CED after positioning or the seal between the base and the countertop will be bro­ken.
Fill Water Tank and Start Refrigeration System
1. Make sure the plug in the water tank drain hose is secure.
2. Remove the plug from the water fill hole located on the carbonator pump deck. Fill the water tank with clean water until water flows out of the tank over­flow. Use a funnel if necessary. Caution: Be care-
ful not to spill water on any electrical fitting or connection. Do not use distilled water.
Note: An alternative method to fill the water tank would be to temporarily splice the incoming water line into the water tank drain hose, turn on the water and fill the tank until water comes out the overflow drain. Turn off the water and plug the water tank drain hose.
D. Apply additional sealant around the bottom of
the base. The seal must be a minimum of 1/4 inch to prevent crevices and to ensure a com­plete seal.
E. Close and seal all access holes to the inside
of the CED base.
12
3. Install plug in water fill hole.
4. Place CED refrigeration system switch and the agita­tion switch, located on the side of the control box, in “OFF” position ON A CED WITH AN INTERNAL COLD CARBONATOR, DISCONNECT THE POWER SUP­PLY TO THE CARBONATOR AT THIS POINT. OTH­ERWISE WATER PUMP DAMAGE WILL OCCUR.
5010146
Revision July 22, 2003

REFRIGERATION SYSTEM START

WARNING: CED must be electrically grounded to avoid possible fatal electrical shock or serious injury to the op­erator. 120V CED power cord is equipped with a three­prong plug. If supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. If a grounded electrical outlet is not available, use an approved method to ground the CED.
A. Plug CED power cord into an accessible properly
grounded electrical outlet.
Installation and Service Manual
INCOMING WATER SUPPLY
REQUIREMENTS
NOTE: SerVend International Inc. recommends that a water shutoff valve and water filter be installed in the incoming water supply line.
The incoming water source to the equipment shall be installed with adequate backflow protection to com­ply with applicable National, State, and local codes.
Water pressure should be a minimum of 45 PSI or you will starve the pump of water and damage it. The maximum water pressure should be 55 psi or you will affect the quality of the carbonation.
The carbonator pump should be located within 6 feet of a 1/2 inch water source. A minimum 3/8 inch ID water line must be used. Before connection the water source should be flushed of approximately 5 gallons of water to purge the system of any sedi­ments, especially in areas of new construction.
B. Place CED refrigeration system switch and agita-
tion switch located on the side of the control box, in “ON” position. Compressor, condenser fan motor, and agitator motor will start and begin forming an ice bank. NOTE: The refrigeration system on the
50 Hz CED is equipped with a 4-minute time de­lay. Whenever power to the compressor is inter­rupted, the time delay will take effect. When a full
ice bank has been formed, the compressor and con­denser fan motor will stop, but the agitator motor will continue to operate, circulating ice bath water in the water tank. Turn the key switch to the “ON” posi­tion to check all beverage valves for operation. Check for water, syrup, and CO2 leaks in the supply system. Replace the bonnet with the two screws provided.
Recommended: Beverage pour temperature should be main­tained at a constant 40o F or below for optimum brixing value. Time required to reach the proper temperature will be subject to water and ambient air temperatures.

CONNECTING THE DRAIN PAN HOSE

NOTE: Connection of the drain pan hose to a per­manent drain is recommended. A drain pan hose routed to a waste container is not recommended due to sanitation problems.
1. Remove the plug from the drain pan nipple.
2. Connect drain pan hose to the nipple on the drain pan.
3. Install drain pan in position on the CED, then place grid in the drain pan.
4. Route lower end of drain pan hose to a permanent drain and connect according to local codes.
NOTE: If no permanent drain is available the drain pan may be emptied manually. Some CED’s come equipped with a drain pan that may be removed by sliding it for­ward. Nothing else needs to be removed to take the drain pan off, empty it and replace it on the CED. If this drain pan is hooked to a permanent drain, the drain nipple must be opened and connected to the drain hose as described on page 12 of this manual.
5010146
Revision July 22, 2003
13
Installation and Service Manual

CONNECTING WATER SUPPLY LINE(S) TO THE CED

INTERNAL CARBONATOR

Connect plain water supply line to the CED at the plain water inlet line, and the non-carbonated water inlet.

EXTERNAL CARBONATOR

Connect carbonated water supply line from the external carbonator to the CED at the carbonated water inlet line.
Connect plain water supply line to the CED at the non­carbonated water inlet line.

NONCARBONATED UNIT

Connect plain water supply lines to the CED at the plain water inlet line and the non-carbonated water inlet.
CONNECTING SYRUP SUPPLY
LINES TO ALL CEDS
Connect syrup supply lines to the CED at the correspond­ing syrup inlet lines. Syrup inlet line #1 will correspond with the right hand dispensing valve. The valves are numbered in sequence from right to left.
14
Revision July 22, 2003
5010146
Installation and Service Manual

CONNECTING CO2 SUPPLY LINE TO THE CED

CED WITH INTERNAL
CARBONATOR
1. Connect CO2 supply to the CO2 inlet at the CED.
2. Open pressure relief valve. (Red arm should be in the upright position).
3. Turn water supply on and fill the carbonator tank until water can be seen coming out the pressure relief valve.
4. Close the pressure relief valve.
5. Activate a dispensing valve until a good flow of plain water is established.
6. Check for water leaks.
7. Turn on the CO psi.
8. Activate a valve until all the water has been forced out of the system by the CO2.
9. Check for any leaks.
10. Connect the power to the carbonator.
bottle and adjust the regulator to 75
2
CED WITH EXTERNAL
CARBONATOR
1. Connect CO2 supply to the CO2 inlet on the carbon­ator tank.
2. Connect carbonated water outlet line to the dispens­ing system. To avoid contamination of potable liq­uids, do not connect copper tubing or fittings between the discharge fitting on the carbonator and the dis­pensing valve.
3. Open pressure relief valve. (Red arm should be in the upright position).
4. Turn water supply on and fill the carbonator tank until water can be seen coming out the pressure relief valve.
5. Close the pressure relief valve.
6. Activate a dispensing valve until a good flow of plain water is established.
7. Check for water leaks.
8. Turn on the CO 100 psi.
bottle and adjust the regulator to
2
11. Operate the valves until the carbonator cycles several times and there is a good flow of carbon­ated water from each valve.
9. Activate a valve until all the water has been forced out of the system by the CO2.
10. Check for any leaks.
11. Plug in the carbonator.
12. Operate the valves until the carbonator cycles several times.

NON-CARBONATED CED

1. Open plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose con­nections.
2. Operate each dispensing valve until the system is flushed and water flows smoothly from each valve.
5010146
Revision July 22, 2003
15
Installation and Service Manual

SPECIFICATIONS FOR CED SERIES DISPENSERS

CED - 30 SPECIFICATIONS

Dimensions:
20 1/2” W x 27 3/8” D x 28 1/4” H
51.435 cm W x 69.53 cm D x 72.4 cm H
Ice Bank Size:
30 lbs/13.636 kg
Valves:
Six beverage valves
Standard Voltage:
120/60/1 6 - foot (1.82m) three-wire cord and plug provided.
Fuse Size:
Minimum 20 amp
Amperage:
8.2 Operating amps 13 FLA
Other voltage available:
220/240 Volts - 50 Hz - 1 Ph 208/230 Volts - 60 Hz - 1 Ph Fuse Size: Minimum 10 amp
Amperage:
4.5 Operating amps
6.5 FLA
Compressor:
1/3 HP 50 Hz refrigeration system is equipped with a four minute time delay.
Refrigerant:
R-134a 120 V Unit 8.5 oz. 208/230 V Unit 7.75 oz. 220/240 V Unit 11 oz.
Always check serial plate for exact charge
Ship Weight:
EC Approximately 143 lbs/65 kg. IC Approximately 158 lbs/71.8 kg
Cabinet:
Stainless Steel
Drain:
Single pre-installed 3/4” PVC (NPT) drain fitting extends from the drain pan.
Service:
Beverage valves, inlet connections, drain connection, and electrical components are front accessible.
Optimum Ambient Conditions are:
Between 50 o and 95oF (10oC and 35oC).
16
Revision July 22, 2003
5010146
Installation and Service Manual
SPECIFICATIONS FOR CED SERIES DISPENSERS

CED - 40 SPECIFICATIONS

Dimensions:
25 1/4” W x 27 3/8” D x 28 1/4” H
63.1 cm W x 69.53 cm D x 72.4 cm H
Ice Bank Size:
Up to 40 lbs/18.182 kg
Valves:
Eight beverage valves
Standard Voltage:
120/60/1 6 - foot (1.82m) three-wire cord and plug provided.
Fuse Size:
Minimum 20 amp
Amperage:
8.2 Operating amps 13 FLA
Other Voltage Available:
208/230 Volts -60 Hz - 1 Ph
Fuse Size:
Minimum 10 amp
Amperage:
4.5 Operating amps
6.5 FLA
Compressor:
1/3 HP
Refrigerant:
R-134a 120 V Unit 11 oz. 208/230 V Unit 10.25 oz
Always check serial plate for exact charge.
Ship Weight:
EC Approximately 160 lbs/72.7 kg. IC Approximately 175 lbs/79.5 kg
Cabinet:
Stainless Steel
Drain:
Single pre-installed 3/4” PVC (NPT) drain fitting extends from the drain pan.
Service:
Beverage valves, inlet connections, drain connection, and electrical components are front accessible.
Optimum Ambient Conditions are:
Between 50 o and 95oF (10oC and 35oC).
5010146
Revision July 22, 2003
17
Installation and Service Manual

OPERATION

BAG-IN-BOX (BIB) START-UP

All lines should be properly flushed and sanitized before starting the CED. Sanitizing instructions can be found be­ginning on page 18 of the Installation Manual.
1. Connect each BIB connector to the appropriate BIB.
2. Gradually adjust the secondary regulator to 70 psi. Never run a BIB pump without the BIB installed as the pump could be damaged. Set final secondary regulator pres­sure 70 -75 psi depending on the line size and the dis­tance of the run.
3. Operate each dispensing valve until the syrup flows smoothly from the valve.
Adjust Syrup to Water Ratio (Brix) of Dispensed Product.
1. Adjust water flow rate on each dispensing valve to
2.5 ounces per second.
2. Adjust dispensing valves for water-to-syrup ratio (brix) as recommended by the syrup distributor.

INSTALL DECALS

Install decals (provided with CED ) on the dispensing valve covers.

DAILY CLEANING

Drain pan
Grid
Splash Panel
Valve Nozzles
Diffusers
You will need: Warm clean water, a mild nonabrasive soap, and a clean cloth.
1. Lift the grid and remove it from the drain pan.
2. Using warm water, mild soap, and a clean cloth, wash the drain pan and splash panel. After cleaning, rinse with clean, warm water.
3. Allow plenty of warm (not hot) tap water to run down the drain of the drain pan to remove any syrup residue that can clog the drain opening.
4. Wash the grid, then rinse with clean water. Place the grid back in the drain pan.
5. Wash all exterior surfaces of the CED with warm water and a clean cloth. Wipe again with a clean, dry cloth.
6. Remove the nozzles and diffusers from the dispens­ing valves.
7. Clean both the nozzles and the diffusers with soap and water to remove syrup residue, then rinse with warm, clean water.
8. Replace the diffusers and the nozzles on the valves.

CLEAN UP

Clean up all work areas. Dispose of all packing material, ex­cess tubing and trash properly.

SANITIZING AND CLEANING

Note: Scheduled cleaning must be in compliance with local health codes. The CED must not be cleaned with a water jet. This cleaning schedule is a recommendation.

WATER BATH

It is recommended that the water bath be drained at least twice a year. Turn off the refrigeration. Completely melt the ice bank. Refill the water bath with fresh water until water runs out the overflow tube. Turn on the refrigeration.
PERIODIC SANITIZING OF THE
DISPENSER
Note: Sanitize the dispenser at initial start-up in addition to periodic sanitizing.
18
Revision July 22, 2003
5010146
Installation and Service Manual

BAG-IN-BOX

BEVERAGE SYSTEM SANITIZING
(for trained personnel only)
You will need: Three clean, empty five-gallon buckets to be used for the rinse, detergent, and sanitizing buckets, and a con­tainer to be placed under soda valves to carry away detergent and sanitizing agents which will be flushed through the valves.
1. Disconnect the bag-in-box connectors.
2. Prepare the following in three clean buckets:
A. Rinse bucket - fill bucket with clean tap water.
(Refill as necessary.)
B. Detergent bucket - mix approved beverage
system cleaner with warm water as recommended.
C. Sanitizing bucket - mix a solution of 1 ounce
of liquid, unscented household bleach (5.25% Cl Na O concentration) with two gallons of tap water. The mixture should supply 200 PPM of available chlorine.
3. Remove the cap located opposite the tubing connection on the bag-in-box connector.
4. Place bag-in-box connector in rinse bucket (step 2A). Draw clean tap water through the system and out the beverage valve until all syrup is flushed from the system.
5. Place bag-in-box-connector in the detergent bucket (step 2B). Draw detergent solution through the system and out the beverage valve for 2 minutes. Then, allow the remain­ing detergent to stay in the system for 5 minutes.
6. Remove the valve nozzle and diffuser, as described in the daily cleaning instructions. Using a clean cloth or a soft brush, scrub the nozzle, the diffuser, the bottom of the dis­pensing valve, and the cup lever, if applicable.
7. Place the valve diffuser and nozzle in sanitizing solution for 20 minutes, then replace them on the beverage valve.
8. Place bag-in-box connector in the sanitizing bucket (step 2C). Draw sanitizing solution through the system and out the valve for 5 minutes. Allow the sanitizing solution to remain in the system for a minimum of 20 minutes.
9. Place the bag-in-box connector in the rinse bucket (step 2A). Draw clean rinse water through the system and out the valve for 2 minutes, flushing the sanitizing solution from the system.
10.Repeat Step 8 and Step 9.
11. Replace the plastic cap opposite the tubing connection on the bag-in-box connector.
12.Reconnect the bag-in-box connector to the beverage syrup bag-in-box.
13.Repeat the above steps for each beverage valve, or follow this procedure with any number of valves concurrently.

FIGAL SYSTEM SANITIZING

1. Prepare the following in three clean Figal tanks:
a Rinse tank - fill with room temperature water.
b Detergent tank - mix approved beverage system
cleaner with warm water as directed.
c Sanitizing tank - mix a solution of 1 ounce of
unscented household bleach (5.25% Cl Na O concentration) to two gallons of tap water. The mixture should supply 200 PPM available chlo­rine.
2. Locate the Figal syrup tank for the circuit to be sani­tized. Remove both quick disconnects from the Fi­gal syrup tank. Rinse quick disconnects in warm tap water.
3. Connect rinse tank to the syrup line. Draw clean rinse water through the valve until syrup is flushed from the system.
4. Connect detergent tank to the syrup line and draw detergent through the valve for 2 minutes. Then, al­low remaining detergent to stay in the system for 5 minutes.
5. Follow steps 6 and 7 in the bag-in-box sanitizing in­structions to clean and sanitize the beverage valve nozzle and diffuser.
6. Connect sanitizing tank to the syrup line and draw sanitizing solutions through the valve for 5 minutes. Allow sanitizing solution to remain in the system for a minimum of 20 minutes.
7. Connect rinse tank to the syrup line. Draw clean rinse water through the system for two minutes to flush the sanitizing solution from the system.
8. Repeat Step 6 and Step 7.
9. Reconnect syrup lines.
5010146
Revision July 22, 2003
19
Installation and Service Manual

CARBONATED/NON-CARBONATED CONVERSION

To change a valve from carbonated to non-carbonated:
1. Turn off the water and CO2 to the CED.
2. Disconnect the syrup box to the valve you want to change.
3. Bleed the pressure from the valve.
4. Remove the plug from the back of the John Guest ”Y” fitting on the non-carbonated water line behind valve #4.
5. Remove the plug from the back of the John Guest ”Y” fitting on the carbonated water line behind valve #3.
6. Install the stainless steel “U” tube between the 2 John Guest “Y” fittings.
7. Remove the carbonated water supply line from the back of the John Guest “Y” fitting behind valve #3.
8. Install a plug into the “Y” fitting.
9. Install a John Guest union and plug on the carbon­ated water supply line that was removed from the “Y” fitting.
10.Turn on the water and CO2 to the CED.
11.Follow the sanitizing instructions to clean the old syrup from the line.
12.Hook up a fresh box of the syrup to be used.
13.Set the valve to the proper ratio of syrup to water.
14CED 40 converts the same way between valve num-
bers 5 & 6.
20
Revision July 22, 2003
5010146
Installation and Service Manual
CARBONATED/NON-CARBONATED CONVERSION
To change a valve from non-carbonated to carbonated:
1. Turn off the water and CO2 to the CED.
2. Disconnect the syrup box to the valve you want to change.
3. Bleed the pressure from the valve.
4. Remove the John Guest union and plug from the carbonated water line that is stubbed out behind valve #4.
5. Remove the plain water line from the John Guest “Y” fitting going into valve #4.
6. Install the union and plug removed from the carbon­ated water line into the plain water line.
7. Insert the carbonated water line into the John Guest “Y” fitting behind the #4 valve.
8. Turn on the water and CO2 to the CED.
9. Follow the sanitizing instructions to clean the old syrup from the line.
10.Hook up a fresh box of the syrup to be used.
11.Set the valve to the proper ratio of syrup to water.
12,CED-40 converts the same way, but the valve num-
bers are 4 & 5.
5010146
Revision July 22, 2003
21
Installation and Service Manual

WIRING DIAGRAM 120 VOLT/60/1

INTERNAL CARBONATOR

EXTERNAL CARBONATOR

22
Revision July 22, 2003
5010146
Installation and Service Manual

WIRING DIAGRAM 220-240 VOLT/50/1

INTERNAL CARBONATOR

EXTERNAL CARBONATOR

5010146
Revision July 22, 2003
23
Installation and Service Manual

WIRING DIAGRAM 208-230 VOLT/60/1

INTERNAL CARBONATOR

EXTERNAL CARBONATOR

24
Revision July 22, 2003
5010146

TROUBLESHOOTING GUIDE

NOITIDNOC NOITAGITSEVNI KCEHC NOITCERROC
Installation and Service Manual
sknirdmraW?gninnurrosserpmocehtsI
.metsysnoitaregirfer
.ffohctiwsrewoP"no"othctiwsevoM
.oN
lortnocknabecIlortnocecalper/kcehC
daolrevorosserpmoCdaolrevoecalper/kcehC
yalertratSyalerecalper/kcehC
rosserpmoCecalper/kcehC
?gninnurrosserpmocehtsI
.seY
ytridresnednoCretlifrianaelC
dekcolbresnednoCnoitcurtsboevomeR
gninnurtonnaFrotomnafecalpeR
noitatigAoNrellepmiecalper/kcehC
wolleveltnaregirfeRhtiwegrahc,kaelriapeR
noitisop
)BetoNees(
rosserpmoc
tnaregirferehtdeneposimetsysnoitaregirferehtemitynatahtrebmemerottnatropmisitI:AetoN
ehtotnidehgiewtnaregirferfoegrahcreporpehtdnadellatsnireirdwena,derevocerebdluohs
noitatigaecalper/kcehC
rotom
.tnaregirfer AetoneeS
.evoba
sagropurys,retawoN
.gnisnepsid
?hctiws
?hctiws
?nezorftinusIwollevelretaWhtabecillifer/kcehC
.tinUDECeht
?tinuehtotrewoperehtsIrewopoNteserrotinunigulP
yekhguorhtgnimocrewopsI
yekehtotrewoperehtsI
"ffo"hctiwsyeK"no"hctiwsyeknruT
evitcefedhctiwsyeKhctiwsyekecalpeR
ehthguorhtrewopoN
remrofsnart
lortnocknabecI.lortnocecalper/kcehC
rekaerb
remrofsnartecalper/teseR
.wolebBetoNeeS
7dna5seborpneewtebecnatsiserehtkcehctsumuoylortnocknabeciehtkcehcotredronI:BetoN
detcetedsismhoK54nahtsselecnatsiseranehwtratslliwtinunoitaregirferehT.7&6neewtebdna
lliwhcihw,seborpehtllasrevocknabeciehtnehwpotslliwtinunoitaregirferehT.7&5seborpssorca
reporpehtsretsigereborpehtfI.7&6seborpneewtebsmhoK58nahtretaergecnatsiseraetaerc
seodeborpehtfI.eludomlortnocehtecalper,dilossezeerfroetaregirfert'nowDECehtdnaecnatsiser
knabeciehT.eludomlortnocknabeciehtdnaeborpehtecalper,ecnatsiserreporpehtretsigerton
tuohtiwdecalperebyamtI.kcednoitaregirferehtnoxoblortnocehtnidetnuomsieludomlortnoc
ehtgnivomerybdesseccaebyameborplortnocknabeciehT.htabretawehtmorfeborpehtgnivomer
morfkcednoitaregirferehtgnivomertuohtiwdevomerdnadewahtebnaceborpehT.kcedrotanobrac
5010146
Revision July 22, 2003
25
Installation and Service Manual
TROUBLESHOOTING GUIDE
NOITIDNOC
gnisnepsidylnoretaWerusserpoNfotuo)s(rotalugeR
-AGITSEVNI
NOIT
KCEHC NOITCERROC
)s(rotalugertsujda/kcehC
tnemtsujda
OCfotuO
2
knathserfllatsnI
)s(rotalugerevitcefeD)s(rotalugerecalper/riaper/kcehC
OC
2
detcurtsbo
OCdnapuryS
ylno
2
gnisnepsid
rotanobraCrewopoNrotanobracnigulP.ylppusrewopkcehC
rodeknik,dehcnipenil
OCecalper/riaper/kcehC
enil
2
.rekaerbteserro
ylppusretaW"no"denrutsiretawerusekaM
retlifretawecalpeR
reniartspmupecalper/naelc/kcehC
evlavkcehcretawriaper/naelc/kcehC
.enilretawnezorfrofkcehC lanretnI
.ylnotinurotanobraC
rotanobracevitcefeD,pmuprotanobracecalper/riaper/kcehC
.lortnocleveldiuqilroedortcele,rotom
gnisnepsidylnopurySretaw/adossI
lortnocknabecievitcefeD.lortnocknabeciecalpeR .BetoneeS
?nezorfenil
retawnialpdnapuryS
gnisnepsidylno
erusserpoNOCfotuO
2
fotuorotalugerPH
knathserfllatsnI
gnittesreporpehtotrotalugerPHtsujdA
tnemtsujda
rotalugerPHevitcefeDrotalugerPHecalper/riaper/kcehC
OC
2
detcurtsbo
tonlliwevlavenO gnihtynaesnepsid
rewoperehtsI
?evlavehtot
noitcennoc
rodeknik,dehcnipenil
esoolroeriwnekorB
OCecalper/riaper/kcehC
enil
2
rotcennocroeriwriaper/ecalpeR
hctiwsorcimdaBhctiwsorcimecalpeR
teewsootsi
desnepsidegareveB
?tcerroc
)xirb(oitarehtsI
knirdehtfo
OCwoL
2
skael
fotuolortnocwolF
lortnocwolfehttsujdA
tnemtsujda
oteudwolfadostneiciffusnI
erusserprotanobracwol
oteuderusserp
roretawehtninoitcurtsbO
OCtsujdA
2
OCriapeR
skael
2
knatehtegnahcroerusserp
senilehttuonaelC
enilados
hguone
teewstonsiegareveB
?tcerroc
)xirb(oitarehtsI
knirdehtfo
tnemtsujda
fotuolortnocwolF
hgihootwolfadoSOCteseR
lortnocwolfehttsujdA
2
yrassecenfi
rotalugerecalperroerusserp
enilpurysninoitcurtsbOenilpurysehttuonaelC
gnimaoferasknirDmetsyserA
serusserp
?tcerroc
noitanobracrevOOCkcehC
sevlav/senilytriDmetsyseritneezitinas/naelC
2
yrassecenfirotalugerecalper
roerusserpteseR.ylppus
26
Revision July 22, 2003
5010146
Manitowoc Beverage Equipment
2100 Future Drive w Sellersburg, IN 47172-1868 Tel: 812.246.7000, 800.367.4233 Fax: 812.246.9922 www.manitowocbeverage.com
In accordance with our policy of continuous product development and improvement, this information is subject to change at any time without notice.
5010146 Revision July 22, 2003
Loading...