This manual is updated as new information and models
are released. Visit our website for the latest manual.
America’s Quality Choice in Refrigeration
Part Number STH13 9/10
www.manitowocfsg.com
Safety Notices
!
Warning
!
Caution
Important
As you work on Manitowoc equipment, be sure to pay
close attention to the safety notices in this handbook.
Disregarding the notices may lead to serious injury
and/or damage to the equipment.
Throughout this handbook, you will see the following
types of safety notices:
Text in a Warning box alerts you to a potential
personal injury situation. Be sure to read the
Warning statement before proceeding, and work
carefully.
Text in a Caution box alerts you to a situation in
which you could damage the equipment. Be sure
to read the Caution statement before proceeding,
and work carefully.
Procedural Notices
As you work on Manitowoc equipment, be sure to read
the procedural notices in this handbook. These notices
supply helpful information which may assist you as
you work.
Throughout this handbook, you will see the following
types of procedural notices:
Text in an Important box provides you with
information that may help you perform a
procedure more efficiently. Disregarding this
information will not cause damage or injury, but it
may slow you down as you work.
NOTE: T ext set off as a Note provides you with simple,
!
Caution
Important
! Warning
We reserve the right to make product
improvements at any time. S pecifications and
design are subject to change without notice.
but useful, extra information about the procedure you
are performing.
Read These Before Proceeding:
Proper installation, care and maintenance are
essential for maximum performance and troublefree operation of your Manitowoc equipment. If
you encounter problems not covered by this
handbook, do not proceed, contact Manitowoc
Foodservice Group. We will be happy to provide
assistance.
Routine adjustments and maintenance
procedures outlined in this handbook are not
covered by the warranty.
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been
misused, abused, neglected, damaged, or
altered/modified from that of original
manufactured specifications.
Depending on store type and location, various optional
equipment may be added to this system. Install and
connect any optional equipment in the desired location
according to the installation instructions provided with
these kits/equipment.
Special Applications
ATTENTION: MARINE INSTALLATIONS
This unit is for use on vessels over 66 ft (20 m) in
length. This unit must not be installed in the
engine space of a gasoline-powered ship.
NOTE: This unit must be secured to the vessel during
installation. Models with part numbers beginning with
the letters TO are NOT marine listed.
OUTDOOR APPLICATIONS
TO Multiplex Beverage Recirculating units are
approved and listed by Underwriters Laboratories
(UL). However they are not UL approved for weather
exposure applications. These units must be installed in
areas where adequate protection from the elements is
provided, all other models are ETL listed.
Personal Injury Potential
Do not operate equipment that has been misuse d,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
Model/Serial Number Location
These numbers are required when requesting
information from your local Manitowoc Distributor,
service representative, or Manitowoc Foodservice.
The model and serial number are listed on the
OWNER WARRANTY REGISTRATION CARD. They
are also listed on the MODEL/SERIAL NUMBER
DECAL affixed to the unit.
10Part Number STH13 9/10
Warranty Information
Consult your local distributor for terms and conditions
of your warranty. Your warranty specifically excludes
all beverage valve brixing, general adjustments,
cleaning, accessories and related servicing.
Your warranty card must be returned to activate the
warranty on this equipment. If a warranty card is not
returned, the warranty period can begin when the
equipment leaves the factory.
No equipment may be returned without a written
Return Materials Authorization (RMA). Equipment
returned without an RMA will be refused at the dock
and returned to the sender at the sender’s expense.
Please contact your local distributor for return
procedures.
Part Number STH13 9/1011
Complete System Overview
BEER PROPERTIES
General Information
The object of every establishment serving draught
beer is to deliver the same high quality of beer to the
customer that is delivered to it by the beer distributor.
Unfortunately, this objective may be more difficult to
achieve than the vendor or proprietor realizes,
especially if he is not thoroughly familiar with the
relationships that exist between temperature,
pressure, and beer delivery systems, all of which have
a major effect on the quality of the beer delivered to
the customer. A brief discussion of these factors may
prove helpful in understanding why a problem exists
and what corrective action is required.
Beer is a unique liquid; no two barrels (even of the
same brand) are exactly alike. There are large
variations between brands. Chemically speaking, beer
is a “supersaturated” liquid. Simply stated, beer
contains excess carbon dioxide (CO2) which
dissipates or “out gasses” if allowed to stand in an
open container for a period of time. If this were to
happen, the beer would go “flat”. The presence of CO
gives beer its effervescent quality and distinct flavor.
There are several factors that affect the level of
carbonation, and therefore the quality and flavor of the
beer that is delivered to the customer.
Pressure
Beer is pressurized in the keg by the brewer to his
exact specifications, which ar e op ti mized for the best
possible flavor. For example, under pressurized beer
will taste flat and over pressurized beer will taste bitter.
It therefore follows that the vendor must carefully
balance his system to the beer specifications of the
brewer in order to dispense the beer with the best
possible flavor to his customers. Failure to do so can
result in poor tasting or foamy beer. This is why it is
strongly recommended that each keg or beer supply
be regulated by its own pressure regulator.
The optimum pressure for most domestic beer,
dispensed at normal temperatures and at sea level, is
12 to 14 pounds per square inch (psi) keg pressure.
2
12Part Number STH13 9/10
Some domestic beers require slightly higher pressure
and some imported beers require lower pressure,
which explains the need for separate pressure
regulators for each brand. This information is readily
available from the beer distributor. Areas with higher
elevations will require higher keg pressure, specifically
one psi for each 2,000 ft (609.6 m) elevation above
sea level. This increase in keg pressure is necessary
to retain the correct carbonation level in the beer itself,
since the carbonation level is a function of the
“absolute pressure” and not the difference in pressure
between keg and atmospheric (which is the pressure
maintained by the pressure regulator on the beer
system).
The applied CO
forcing the beer from the keg through the beer lines
pressure is also the vehicle for
2
and into the glass at the dispensing point. Many
operators mistakenly believe that this is the only
function, or at least the major function, of the applied
pressure, and therefore the pressure m ay be
decreased or increased at will to facilitate a desired
dispensing rate (flow rate). Because of the effects on
the carbonation level of the beer, and therefore the
quality of the beer itself, the pressure must not be
changed to achieve a desired change in the flow rate.
The only acceptable method for adjusting the flow rate
is by changing the amount of the restriction or “drag” in
the system with respect to the flowing beer. The
amount of additional restriction may be adjusted by
adding or removing lengths of the main beer lines, or
adding or removing shorter portions of smaller sized
tubing (choker lines) to the beer lines.
Part Number STH13 9/1013
In some beer systems the walk-in cooler or storage
room is located remotely and on different levels from
the dispensing points. Under these conditions, even
with large size beer lines it is often not feasible to
dispense beer at an adequate flow rate with normal
keg pressures since the drag, or resistance of the
lines, as well as vertical lift that may be required can
be sufficient to reduce the flow greatly at these
standard pressures. In these cases it is often
necessary to pressurize the keg as much as two or
three times the normal keg pressure in order to
provide an acceptable flow rate at the dispensing
point. This type of system is commonly known as a
“long draw” or “remote” system. Manufacturers of
these systems recommend using a blend of gasses or
beer pumps (usually a mixture of CO
and nitrogen) to pressurize the system without over
and air or CO2
2
carbonating the beer. The refrigerated chamber
containing the kegs can be located more than 450 ft
(91.4 m) away from the serving location using these
long draw techniques.
Natural Keg Pressures at Sea Level (Pounds/
Square inch)
Brewing
Company
Anheuser Busch11121314
Adolph Coors
(requires 1/4"
Ported Shanks)
Miller12.513.514.515.5
Schlitz/Stroh’s12131415
Add 1 psi to adjust for altitude for every 2,000 ft above sea level.
An additional 1 psi may be required for “Light” beers.
Cooler Temperature
36°F38°F40°F42°F
14.515.516.517.5
14Part Number STH13 9/10
TEMPERATURE
26 ft (7.9 m)
T o tal Conduit Length:
50 ft (15.2 m)
Altitude:
1,000 ft (304.8 m)
Walk-in Cooler
38°F
(3.3°C)
8 ft
(2.4 m)
8 ft
(2.4 m)
5 ft
(1.5 m)
4 ft
(1.2 m)
The effects of temperature are manifested in several
ways. The temperature itself is very significant. A
temperature between 36°F (2.2°C) and 38°F (3.3°C)
gives the best dispensing results, and is generally
favored by most people as providing the best taste. If
the beer is cooled below 36°F (2.2°C), more CO
absorbed and a greater tendency to out gas may
occur when the beer is released to atmospheric
pressure by dispensing, thereby producing more foam.
The greater absorption of CO2 also imparts a slightly
more bitter taste to the beer, which is objectionable to
most beer drinkers.
Above 38°F (3.3°C) the CO
a higher energy level and can escape more easily.
contained in the beer is at
2
Therefore out gassing and foaming can occur more
readily. This energy level continues to increase at
higher temperatures, resulting in a rapid increase in
the beer’s tendency to foam.
An increase in temperature in the beer lines or the
faucet itself can result in “fracturing” (out gassing)
when the beer is dispensed. This generally occurs
when un-refrigerated beer lines extend outside of the
beer cooler and the ambient temperature surrounding
the lines is at a higher temperature than the cooler
itself. This can also occur in the beer “tower” at which
the faucets are connected when an insufficient amount
of coolant is circulated in the tower. The general result
is that the first glass dispensed after a delay of several
minutes will experience significant fracturing, resulting
is
2
Part Number STH13 9/1015
in a larger head of foam. To maintain the correct
temperature in the tower, care must be taken to ensure
that a sufficient amoun t of coolant is delivered to this
area.
THE TEMPERATURE/PRESSURE COMBINATION
Since carbonation of the beer is related to both
pressure and temperature, it is important to
understand this relationship in order to assure that the
highest quality beer product is delivered to the
customer. Higher than normal temperatures require
higher than normal pressures in order to maintain
carbonation. Specifically, in order to maintain proper
carbonation, the CO
when there is an increase in the beer temperature. For
pressure must be increased
2
example, a typical American beer that would be
properly carbonated at 12 psi (0.8 bar) at a
temperature of 38°F (3.3°C) would require an increase
in pressure to maintain the same level of carbonation
at a temperature of 39°F (4.2°C). Conversely, lowering
the temperature requires a corresponding decrease in
CO
pressure to prevent over-carbonation. In actual
2
practice pure CO
16.5 psi (1.1 bar) (at sea level) should be avoided at
pressures above approximately
2
normal temperature (36°F [2.2°C] to 38°F [3.3°C]) to
avoid an unacceptable level of over carbonation which
leads to foaming problems. When the pressures
above this level are required for good dispensing, the
operator should switch to a blend of CO
for pressurization or beer pumps.
and nitrogen
2
The beer faucet itself is surrounded by normal ambient
room air and will warm slightly over a period of several
minutes. Since a small amount of beer is trapped
behind the faucet, there is a likelihood that this small
amount of beer will also warm slightly. The result will
be that this trapped beer will fracture and produce
foam on the first beer dispensed after an extended idle
time. When all of the slightly warmed beer has been
depleted from the faucet and the beer line, subsequent
beers drawn immediately following the first should
produce about the same amount of foam or head, but
less than the first beer.
In long draw or remote systems as described above, it
is essential to refrigerate the beer lines throughout
16Part Number STH13 9/10
their entire length at about the same temperature as
the beer in the cooler. Most manufacturers of these
systems agree that it is not possible to adequately
refrigerate these lines using cold air over distances
greater than about 15 ft (4.6 m). Therefore, these
systems utilize a liquid refrigerant line continuously
cycling propylene glycol at a temperature below 30°F
(-1.1°C) (or other suitable liquid coolant) in physical
contact with beer lines and with the overall assembly
contained in a flexible, insulated housing. These
systems, when properly designed and installed,
generally offer the best and most consistent draught
beer product. On the other hand, an improperly
designed, installed, or maintained system (even a
rough or damaged gasket) can produce “shots” of
foam, continuous foam, or continuously warm and
therefore, foamy beer.
NOTE: A properly designed, installed, and maintained
draught dispensing system should deliver beer at 1.75
to 2.0 ounces per second. The beer should be
dispensed at 38°F (3.3°C) or less. The beer should
flow in a solid, clear column smoothly (neither falling or
pushing) from the faucet to the glass.
Part Number STH13 9/1017
Multiplex Beermaster™ Beer Dispensing
System
The beer keg is kept in a refrigerated cooler at the proper
temperature for dispensing. The pressure system
supplies pressurized gas to the kegs at a specific
pressure for each keg, this pressure is determined by the
installer taking into consideration the distance, vertical
rise and fall of the conduit (insulated bundle of tubing),
along with the natural pressure in the keg. The beer is
pushed through the lines in the conduit from the cooler to
the dispensing valve. T o maintain the cold temperature in
the conduit the refrigeration system uses the Multiplex
Beermaster™ refrigeration unit which chills a glycol bath.
This glycol, which is adjusted to below 30°F (-1.11°C), is
circulated through the conduit up to the dispensing faucet
and back where it is re-chilled in the bath. These chilled
glycol lines are touching the beer lines in the conduit,
maintaining the cold temperature of the beer. The beer is
then brought up to the dispensing system where the
conduit tubing is restricted down to a smaller diameter
tube of a length, calculated by the installer, that’s
designed to give a 1.75 ounce per second flow of a
perfectly dispensed beer.
18Part Number STH13 9/10
PRESSURE SYSTEM
The pressure system supplies the pressurized gas to
the kegs at a specific pressure for each keg. This
consists of a high pressure regulator to reduce the
CO
or mixed gas pressure from the high pressure
2
cylinder to 40 psi (2.8 bar). This gas is fed to the
secondary regulators to beer pumps or the optional
blender which may nitrogen with the CO
reduce the chance of providing extra carbonation to
to help
2
the beer. The secondary regulators are adjusted to the
installer calculated pressure, calculated for each keg.
This pressure is calculated to push the beer through
the conduit to the dispensing faucets and flow at a
desired 1.75 oz per second flow rate.
Part Number STH13 9/1019
REFRIGERATION SYSTEM
The refrigeration system consists of the Multiplex
Beermaster™ refrigeration unit which chills a food
grade glycol to below 30°F (-1.11°C). This glycol is
circulated through an insulated bundle of tubing
(conduit) by a 70 GPH circulating pump and returned
to the refrigeration unit for re-chilling. This very cold
glycol is continually circulating through independent
lines in the conduit. The beer lines (which are also in
the conduit) are in contact with the glycol lines which
will maintain the temperature of the beer. This ensures
that the product is dispensed at the beer cooler
temperature. The refrigeration compressor will cycle
ON and OFF as needed to maintain the consistent
temperature of glycol. Each size of Beermaster™
Refrigeration Unit is rated for a maximum total conduit
length to keep the beer dispensing at a consistently
cold temperature, maintaining the proper temperature
and taste of the beer.
20Part Number STH13 9/10
DISPENSING SYSTEM
The dispensing system consists of one of the many
different styles and sizes of dispensing towers which
can have any number of dispensing faucets used to
dispense the beer into the glass, mug or pitcher. As
the beer comes out of the conduit it must be adjusted
to give a maximum 2 oz per second flow rate to reduce
the chance of foaming and to dispense a proper glass
of beer. The proper way to adjust the flow rate of the
beer is to reduce the diameter of the tubing, using an
installer calculated length, of 3/16" diameter restrictor
tubing. The beer then flows through an aluminum or
stainless steel heat exchanger, that is kept in contact
with the very cold glycol lines, to maintain the cold
temperature all the way to the dispensing faucet and
into the glass.
Part Number STH13 9/1021
BALANCING THE SYSTEM
Keg Temperature/Pressure
Applied Keg Pressure
Tubing Resistance
Tubing Lift/Fall
Length of Restrictor Line
To keep the proper amount of carbon dioxide gas in
solution in the beer to maintain the proper taste
throughout the life of the keg, the system must have
the proper balance of temperature, applied pressure to
the keg and rate of flow at the faucet.
The installer must calculate, taking into consideration
the static resistance in the conduit (amount of vertical
rise and fall) as well as frictional resistance (the length
of the conduit itself), the internal pressure of the keg
according to the Brewmaster, the altitude at the
location as well as the temperature of the beer in the
cooler. The object is to dispense the beer as fast as
possible (2 oz per second) with the proper gas
pressure (CO
adjusted so it will not change the carbonation or taste
or mixed gas) applied to the keg and
2
of the beer. The installer must determine the proper
pressure applied to the keg as well as the length of the
restrictor attached to the dispensing faucet giving a
consistent properly dispensed beer.
22Part Number STH13 9/10
Installation
Wall
6" (15.2 cm)
Diameter Chase
minimum
Air
Flow
Control
Switches
18"
(45.7 cm)
minimum
J
Electrical
Junction Box
6" (15.2 cm) minimum
12"
(30.5 cm)
minimum
Wall
Wall
Top View
Side View
P
Wall
Electrical
Junction Box
Incoming
Water Line
Incoming CO
2
Supply Line
Incoming Syrup
Supply Lines
Drain Plug
D
General
•Refrigeration units require a stand or 6" (15.2 cm)
legs. Refrigeration unit cannot be placed directly
on floor.
•Conduit can be run through floor or ceiling chase.
Dimensions and Clearances — All
Models
Part Number STH13 9/1023
Front View
W
Ceiling
Wall
18" (45.7 cm)
minimum
I
H
CO2 Regulator
Panel (Optional)
N
Drain Plug
Wall
Conduit to
Dispensing
Towers
24Part Number STH13 9/10
ModelWDH
I
(with stand)
JNP
7527-3/4"
(70.5 cm)
16-1/4"
(41.3 cm)
18-3/4"
(47.7 cm)
——19-3/4"
(50.2 cm)
5-1/2"
(14.0 cm)
15036-1/4"
(92.1 cm)
19-1/2"
(49.5 cm)
21-1/2"
(54.6 cm)
—11"
(28 cm)
5"
(12.7 cm)
9"
(22.9 cm)
30039-3/4"
(101 cm)
24-3/4"
(62.9 cm)
28-1/4"
(72.4 cm)
60-3/4"
(154.3 cm)
11"
(28 cm)
6"
(15.2 cm)
12"
(30.5 cm)
45042-1/4"
(107.3 cm)
28-1/4"
(71.8 cm)
32-1/4"
(81.9 cm)
66-3/4"
(169.5 cm)
11"
(28 cm)
8-1/2"
(21.6 cm)
14"
(35.6 cm)
Part Number STH13 9/1025
REMOTE CONDENSER
!
Warning
OPTIONAL
38.00" (96.52 cm)
34.00" (86.36 cm)
30.00" (76.20 cm)
29.50"
(74.93 cm)
29.16"
(74.06 cm)
6.00"
(15.24 cm)
3.50"
(8.89 cm)
4.00"
(10.16 cm)
14.62"
(37.13 cm)
6.50"
(16.51 cm)
OPTIONAL
20.00" (50.80 cm)
16.00" (40.64 cm)
12.00" (30.48 cm)
1.50"
(3.81 cm)
27.94"
(70.97 cm)
Safe Installation Do’s and Don’ts
Read the following warnings before beginning an
installation. Failure to do so may result in
possible death or serious injury.
•DO adhere to all National and Local Plumbing and
Electrical Safety Codes.
•DO turn OFF incoming electrical service switches
when servicing, installing, or repairing equipment.
•DO check that all flare fittings are tight. This check
must be performed with a wrench to ensure a
quality seal.
•DO inspect pressure on regulators before starting
up equipment.
•DO protect eyes when working around
refrigerants.
26Part Number STH13 9/10
•DO use caution when handling metal surface
edges of all equipment.
•DO handle CO
Secure cylinders properly against abrasion.
cylinders and gauges with care.
2
•DO store CO2 cylinder(s) in well ventilated areas.
•DO NOT exhaust CO2 gas (example: syrup pump)
into an enclosed area, including all types of walk-in
coolers, cellars, and closets.
•DO NOT throw or drop a CO
cylinder(s) in an upright position with a chain.
cylinder. Secure the
2
•DO NOT connect the CO2 cylinder(s) directly to
the product container. Doing so will result in an
explosion causing possible death or injury. It is
best to connect the CO
regulator(s).
•DO NOT store CO
above 125°F (51.7°C) near furnaces, radiator or
cylinder(s) to a
2
cylinders in temperature
2
sources of heat.
•DO NOT release CO
gas from old cylinder.
2
•DO NOT touch refrigeration lines inside units;
some may exceed temperatures of 200°F
(93.3°C).
NOTE: All utility connections and fixtures must be
sized, installed, and maintained in accordance with
Federal, State, and Local codes.
Part Number STH13 9/1027
Location Requirements
!
Warning
Select a location for the refrigeration unit that meets
the requirements of the building plans, local codes,
and personnel. The unit must be positioned for free
airflow as well as for future service. The following
requirements must be met:
•Beverage quality CO
with a minimum 3/8" (.96 cm) line
NOTE: Refer to serial plate on front of refrigeration
unit for voltage and amperage specifications. Make all
electrical connections at the junction box located at the
top rear of unit. Optional equipment may require
additional power supplies.
gas (bulk or bottled supply)
2
Carbon Dioxide (CO2) displaces oxygen.
Exposure to a high concentration of CO
causes tremors, which are followed rapidly by
loss of consciousness and suffocation. If a CO
gas leak is suspected, particularly in a small area,
gas
2
2
immediately ventilate the area before repairing
the leak. CO
installed in an enclosed space. An enclosed
lines and pumps must not be
2
space can be a cooler or small room or closet.
This may include convenience stores with glass
door self serve coolers. If you suspect CO2 may
build up in an area, venting of the BIB pumps
and/or CO
Prior to scheduling Multiplex Equipment
installer, the following steps listed below
must be completed:
1. Electrical power supply meeting the requirements
for the unit to be installed. (See the specification
in this section or refer to the unit’s serial plate).
Gas (bulk or bottled supply); minimum 3/8"
2. CO
2
line.
3. A 120 VAC, 3-wire, 1 Phase, 60 Hz dual wall
receptacle for optional electrical equipment
(domestic only).
NOTE: Do not schedule the authorized Multiplex
Equipment Installer until all of the above have been
completed. It will only result in charge-backs to you for
the unnecessary trips.
REQUIREMENTS FOR REFRIGERATION UNITS
•Conduit can be run through floor or ceiling chase.
•60°F (15.6°C) minimum and 105°F (40.5°C)
maximum operating ambient conditions.
•For indoor installation only.
•Beer supply can be located on stand or floor in a
walk-in adjacent to refrigeration unit.
Part Number STH13 9/1029
Installer Instructions
!
Warning
AMBIENT LOCATION REQUIREMENT
This equipment is rated for indoor use only. It will not
operate in sub-freezing temperature. In a situation
when temperatures drop below freezing, the
equipment must be turned off immediately and
properly winterized. Contact the manufacturer for
winterization process.
Electrical
GENERAL
All wiring must conform to local, state and
national codes.
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (Minimum circuit
ampacity is not the beverage/ice machine’s running
amp load.) The wire size (or gauge) is also dependent
upon location, materials used, length of run, etc., so it
must be determined by a qualified electrician. See
Specifications section.
30Part Number STH13 9/10
GROUNDING INSTRUCTIONS
!
Warning
!
Warning
The unit must be grounded in accordance with
national and local electrical codes.
This appliance must be grounded. In the event of
malfunction or breakdown, grounding provides a path
of least resistance for electric current to reduce the risk
of electric shock. This appliance is equipped with a
cord having an equipment-grounding conductor and a
grounding plug. The plug must be plugged into an
appropriate outlet that is properly installed and
grounded in accordance with all local codes and
ordinances.
Improper connection of the equipment-grounding
conductor can result in a risk of electric shock.
The conductor with insulation having an outer
surface that is green with or without yellow stripes
is the equipment grounding conductor. If repair or
replacement of the cord or plug is necessary, do
not connect the equipment-grounding conductor
to a live terminal. Check with a qualified
electrician or serviceman if the grounding
instructions are not completely understood, or if
in doubt as to whether the appliance is properly
grounded. Do not modify the plug provided with
the appliance — if it will not fit the outlet, have a
proper outlet installed by a qualified electrician.
Part Number STH13 9/1031
!
Warning
When using electric appliances, basic precautions
must always be followed, including the following:
a. Read all the instructions before using the
appliance.
b. To reduce the risk of injury, close
supervision is necessary when an
appliance is used near children.
c. Do not contact moving parts.
d. Only use attachments recommended or
sold by the manufacturer.
e. Do not use outdoors.
f. For a cord-connected appliance, the
following shall be included:
• Do not unplug by pulling on cord. To
unplug, grasp the plug, not the cord.
• Unplug from outlet when not in use and
before servicing or cleaning.
• Do not operate any appliance with a
damaged cord or plug, or after the
appliance malfunctions or is dropped or
damaged in any manner. Contact the
nearest authorized service facility for
examination, repair, or electrical or
mechanical adjustment.
g. For a permanently connected appliance —
Turn the power switch to the off position
when the appliance is not in use and
before servicing or cleaning.
h. For an appliance with a replaceable lamp —
Always unplug before replacing the lamp.
Replace the bulb with the same type.
i. For a grounded appliance — Connect to a
properly grounded outlet only. See
Grounding Instructions.
32Part Number STH13 9/10
Conduit
FLOOR CHASES
Before pulling beer conduit through a floor chase,
ensure the floor chase contains the following:
•6" (15 cm) minimum PVC conduit chase
•Chase openings should extend 6" (15 cm) above
floor
•Wide sweep elbows (2 ft [0.6 m] radius minimum)
•Chase must be clean and dry — no foreign
materials
Part Number STH13 9/1033
Beermaster™
Refrigeration Unit
Walk-in Cooler
Dispensing
Station
Beer Conduit
6" (15.2 cm) PVC
Conduit Chase minimum
Wide Sweep Elbows 2 ft
(61 cm) Radius minimum
34Part Number STH13 9/10
Pulling Conduit Through Floor Chase
1. Determine the most convenient way of routing
conduit, starting at the end which offers adequate
room for installation. The conduit installation
process requires the assistance of at least two (2)
qualified personnel.
2. Route the steel fish tape through chase opening.
Push fish tape through entire chase until it
appears at opposite end.
3. Locate an appropriate length of rope and tie to
end of fish tape (end which was routed through
chase in step 2). Approximately 2 ft (0.6 m) from
steel fish tape/rope connection, secure a swab to
rope (use mop heads or a bundle of rags for
swab).
4. Pull end of fish tape from starting point through
chase with rope and swab. The swab will clean
any construction materials, moisture, or debris
that may exist in floor chase. Continue to swab
the chase until the swab exits the chase clean and
dry.
5. After floor chase has been cleaned, remove steel
fish tape and swab from rope. Locate bundle of
beer conduit and unspool conduit to allow
unrestricted feed during installation process.
6. Locate rope through floor chase opening and
connect to proper end of beer conduit.
NOTE: The beer conduit is designed to be pulled
through floor chase in the direction of arrows printed
on conduit.
Part Number STH13 9/1035
7. After rope has been connected, tape end of
conduit, including rope, and form conduit end to a
point (see figure above). Tape will ensure that no
contaminants enter conduit tubes during
installation.
8. Place pointed end of the conduit through chase
opening. While one person pushes the conduit
through chase, another person should be pulling
the conduit through the chase with rope at the
opposite end.
9. Once the conduit has been routed through the
chase, pull enough conduit through the openings
to ensure an adequate supply at each end of the
chase for connections.
36Part Number STH13 9/10
OVERHEAD INSTALLATION
Beermaster™
Refrigeration Unit
Walk-in Cooler
Dispensing
Station
Ceiling Tiles
Conduit Hanger
Beer Conduit
Part Number STH13 9/1037
Refer to the figure above for the following:
1. Determine the correct location for routing the beer
conduit. Be sure to avoid heat ducts, hoods, grills,
or any sharp objects that may exist above drop
ceiling tile.
2. Unspool the beer conduit to allow unrestricted
feed.
3. Route the conduit above ceiling tiles and connect
to ceiling and/or pipes using the appropriate
conduit hangers. Be sure the conduit is
suspended above ceiling tiles, not lying on the
tiles. Care should be taken when determining
appropriate method of handing conduit securely.
Hangers must not crush or pinch insulation. This
will reduce cooling efficiency.
4. Once the conduit has been routed, ensure an
adequate supply of conduit is provided at each
end to make all connections.
38Part Number STH13 9/10
BASEMENT CONSTRUCTION
Beermaster™
Refrigeration Unit
Walk-in Cooler
Dispensing
Station
Conduit Hanger
Beer
Conduit
Refer to the figure above for the following:
1. Unspool the beer conduit to allow unrestricted
feed during installation process.
2. Route the conduit up basement wall and secure
with appropriate conduit hangers.
3. After routing the conduit up the basement wall,
route conduit overhead on the basement ceiling.
Connect to the basement ceiling using
appropriate conduit hangers.
Part Number STH13 9/1039
4. Once the conduit has been routed, ensure an
!
Caution
Butterfly Cutter
Razor Knife
adequate supply of conduit is on hand to make all
connections.
CONNECTING BEER CONDUIT
Only an approved cutting tool should be used to
cut polyethylene tubing. The cutting tool should
contain a razor sharp cutting blade so that the
tubing will not be crushed when cutting. A razor
blade knife or butterfly tubing cutter is sufficient
(see figures). Multiplex packs a butterfly cutter
with each Beermaster Glycol Chiller.
NOTE: The 3/8" I.D. poly line used in the beer conduit
is thin wall tubing. Barbed fittings should not be used.
The usage of barbed fittings causes thin wall tubing to
split or crack and leaks will result.
40Part Number STH13 9/10
Beermaster™
Refrigeration Unit
Walk-in Cooler
Dispensing
Station
Main Beer
Conduit - 6”
Minimum Dia.
Beer Conduit to Walk-in
Cooler
Part Number STH13 9/1041
CONDUIT KIT
Kit Contents
Four (4) and Seven (7) line conduit kits
•Three (3) Return bends
•Eight (8) Elbows
•29 Unions
•Five (5) Tail pieces
•Five (5) Beer nuts
•One (1) 60 ft of PVC tape
•One (1) 60 ft of foil
•One (1) Spanner wrench
10 and 14 line conduit kits
•Four (4) Return bends
•15 Elbows
•42 Unions
•Eight (8) Tail pieces
•Eight (8) Beer nuts
•One (1) 60 ft of PVC tape
•One (1) 60 ft of foil
•One (1) Spanner wrench
42Part Number STH13 9/10
INSTALLING THE CONDUIT KIT
Connections Preview
Review the three illustrations under “Circuit Diagrams”
in the Diagrams section to determine which best
illustrates your particular installation. Consider the
following while examining the drawings:
Beer conduits have been designed to achieve the
proper cooling of each encased beer line. In order to
function properly, you must follow these guidelines:
should flow directly to the dispensing towers before
returning to the remote Glycol Chiller Unit. After
examining the drawings determine the desired glycol
circuit to be achieved and illustrate on paper for
referral. Do the same for the assignment of the beer
supply lines.
Part Number STH13 9/1043
Connecting Main Beer Conduit at Walk-in Cooler
John Guest
Adapter Tail
Piece
Washer
Wall
Bracket
Fitting
To Beer Keg
Beer Nut
Beer Line to
Tower
1/2" John
Guest Union
1. At the top of each beer wall bracket fitting, found
on the dual secondary regulator, secure a Beer
Nut, John Guest adapting tail piece, washer, and
1/2" John Guest union (see the following image).
2. Identify the appropriate beer lines to be
connected to each of the wall bracket fittings, cut
to length and insert into the proper John Guest
1/2" connector as shown below.
44Part Number STH13 9/10
Connecting Beer Conduit to the Tower
3/16" Barb
x 1/2"
John
Guest
Adapter
1/2" John
Guest Union
1/2" John
Guest Union
Beer
Line
Beer
Conduit
Glycol
Line
Glycol
Manifold
Adapter
Restrictor
Lines
Adjustable
Clamp
See
“Calculating
Restriction”
for Length
Dispenser TowerDispenser Tower
Dispenser Tower
Glycol lines in
1. Peel the insulation back from the end of the beer
conduit to expose all lines. Locate the appropriate
glycol circuit lines, cut to length and attach a 1/2"
John Guest union to each line (see the “Tower
Connections” image).
2. Attach the opposite end of each 1/2" John Guest
union to the 1/2" adapter located at the base of
the dispensing tower.
Part Number STH13 9/1045
Tower Connections
NOTE: If conduit contains more than one glycol circuit
it will be necessary to attach U-bends for each of the
additional circuits. Use a 1/2" U-bend quick connect
fitting or the U-bend can be built by attaching two (2)
1/2" John Guest elbows to one another by means of a
2" length of 1/2" tubing.
BEER RESTRICTOR LINES
1. Refer to the section on “Balancing the System” in
this manual for determining the required length of
restrictor line. Calculate the required length for
each faucet. Cut each restrictor line to the
calculated length and carefully insert the 3/16"
Barb x 1/2" John Guest adapter and clamp
securely with the adjustable clamps provided (see
the “To wer Connections” figure).
2. Identify the beer line to be connected to each of
the appropriate restrictor line, cut the beer lines to
length and attach a 1/2" John Guest Union to
each. Neatly wrap the excess restrictor line
securely around the glycol supply lines to ensure
good heat exchange. Connect the adapter from
each restrictor to the 1/2" connector of each of the
appropriate beer lines.
Connecting Main Beer Conduit to Branch Beer
Conduit
1. At the required point of connection carefully split
open and fold back the insulation on the main
beer conduit and identify the correct set of glycol
lines (circuit) to connect to the branch beer
conduit. Cut the glycol line(s) and attach the
appropriate 1/2" elbow or union connections that
are best suited to connecting with the main beer
conduit (see the “Main Beer Conduit Connections”
figure).
2. Peel the insulation back from the end of the
branch beer conduit to expose all lines. Locate
the glycol circuit lines, cut to length and insert
each line into the open end of the previously
attached 1/2" connectors at the main beer conduit
(see the “Main Beer Conduit Connections” figure).
46Part Number STH13 9/10
3. Locate the appropriate beer line(s) in the main
!
Caution
1/2" John
Guest Union
1/2" John
Guest Elbow
Branch Beer
Conduit
Main Beer
Conduit
beer conduit to be connected to the branch
conduit. Cut desired beer line(s) long so that they
can be pulled back and then routed in a smooth
curve into the branch conduit. Attach appropriate
beer line(s) from main beer conduit to beer line(s)
in branch beer conduit with 1/2" John Guest
Union(s).
To a void agitation use only straight unions when
splicing beer lines.
Main Beer Conduit Connections
Part Number STH13 9/1047
Balancing the System
DETERMINING RESTRICTOR LINE LENGTH AND
APPLIED KEG PRESSURE
In order to ensure a proper, foam-free, beer flow from
each faucet, the following instructions and calculations
must be completed. Use the formulas found in this
section to determine the required restrictor line length
and applied keg pressure needed for each beer line. In
order to complete these calculations the following
information will be needed:
•Brands of beer to be dispensed (if blended gas is
used to push the beer, this is not required).
•Temperature of the Walk-In Cooler (default 38°F
[3.3°C]).
•Altitude (Distance above sea level).
•Total line length for each beer line.
•Overall lift or drop for each beer line.
To determine the appropriate Applied Keg pressures
and Restrictor Line Lengths see attached work sheets
and refer to examples A and B.
To prope rly determine the required restrictor line
lengths and applied keg pressure to be used for each
beer follow the instructions below.
1. First determine which brands of beer will be
dispensed at which faucet. Use the “System
Calculators” to record data (see the Charts
section).
2. Determine keg temperature at cooler.
3. Once the brand and keg temperature are known
the Internal Keg Pressure can be found by
referring to the “Natural Keg Pressures Chart” in
the Charts section.
4. Determine the number of feet above sea level to
adjust natural keg pressure for particular location.
5. If required adjust for “Lite” or “Light” beer by
adding 1 psi to natural keg pressure. Check with
local beer wholesaler for additional information.
48Part Number STH13 9/10
Example:
-Budweiser on faucet number 1
-Walk-in cooler for kegs at 38°F
-Anheuser Busch (Budweiser) at 38°F=12 psi
-Altitude adjustment at 1,000 ft (1 psi/2,000 ft
above sea level)=0.5 psi
(pressure the secondary regulator will be
adjusted at)
6. Determine the total line length and tubing
diameter from bottom of keg to faucet. This must
be done for each individual beer line (refer to the
figures below for proper method of determining
line length).
7. Once the run length is known calculate the
amount of restriction.
Example:
50 ft (length of conduit)
x 0.07 (restriction 3/8" ID poly) = 3.5 psi
Part Number STH13 9/1049
EXAMPLE A
EXAMPLE B
26 ft (7.9 m)
Total Conduit Length:
50 ft (15.2 m)
Altitude:
1,000 ft (304.8 m)
Walk-in Cooler
38°F
(3.3°C)
8 ft
(2.4 m)
8 ft
(2.4 m)
5 ft
(1.5 m)
4 ft
(1.2 m)
26 ft (7.9 m)
T o tal Conduit Length:
50 ft (15.2 m)
Altitude:
1,000 ft (304.8 m)
Walk-in Cooler
38°F
(3.3°C)
19 ft
(5.8 m)
5 ft
(1.5 m)
50Part Number STH13 9/10
Restriction (pounds per square inch)
Restrictor Line: 3/16" ID @ ft=3.0 psi
Beer Supply Line: 3/8" ID @ ft=0.07 psi
8. Determine the lift or drop restriction by taking the
total vertical lift in feet and subtracting the total
vertical drop in feet and multiplying the remainder
by 0.5 psi.
Add 1/2 psi for every foot of vertical lift. Subtract
1/2 psi for every foot of vertical drop.
Equal lifts and drops cancel one another.
Example:
13 ft lift - 8 ft drop = 5 ft of lift
5 ft of lift x 0.5 psi = 2.5 psi lift*
*This figure will be negative if the drop exceeds
the lift.
9. Determine the total line restriction by adding each
of the previously calculated restriction factors.
Example:
3.5 psi (length of run restriction) + 2.5 psi (lift/drop
restriction) = 6.0 psi (total line restriction)
10. Determine the required psi of restriction that will
be required by taking the Applied Keg Pressure
and subtracting the T otal Line Restriction.
If this figure is greater than or equal to 6.0 psi
proceed to the instructions outlined in step A.
below. If this figure is less than 6.0 psi proceed to
the instructions outlined in step B. below.
A. To convert the psi of restriction needed to
inches of required 3/16" ID restriction line,
use the following equation:
Number psi needed ÷ 0.25 psi = number of inches
of restrictor
Example B) reflects an increased vertical lift
factor of 24 ft (19 ft of lift + 5 ft of lift=24 ft). It
requires a lift/drop restriction of 12 psi (24 x
Since the restriction factor in this example is less
than 6.0 psi, a 24" fixed restrictor length will be
required.
Volumes (liquid oz per linear ft)
3/16" ID @ ft = 0.181/4" ID @ ft = 0.33
5/16" ID @ ft = 0.513/8" ID @ ft = 0.73
1/2" ID @ ft = 1.31
The Adjusted Applied Keg Pressure (the pressure
the secondary regulator will be adjusted to) can
now be determined by taking the To tal Line
Restriction and adding 8 psi.
STARTING UP THE SYSTEM
Before Starting Up the System
Each of the steps below should be done 24 hours prior
to the tapping or dispensing of any beer.
1. Place all kegs in a walk-in cooler at 36°F to 38°F
and allow them to temper properly.
2. Turn ON the Beermaster Glycol Chiller circulating
glycol pump(s).
52Part Number STH13 9/10
3. After leak testing all glycol and beer supply lines,
wrap the lines firmly with foil (to ensure a good
heat exchange) and then insulate all lines; to
ensure a minimum of 1" insulation over al l are as
of exposed beverage line.
4. After glycol has circulated through system for
approximately one hour, remove the strainer from
the glycol bath. Flush the strainers clean with
fresh water and reinstall.
Pressure Setting and Start-up
1. Adjust the primary CO
secure the lock nut.
regulator to 40 PSI and
2
2. If a blender is utilized proceed with adjustments
provided with blender kit.
3. Adjust the secondary regulators. It is
recommended that when applied keg pressures
exceed 20 PSI the secondary regulators be
adjusted 2 PSI below the calculated pressure. If
more pressure is required after tapping keg,
increase as needed.
4. Tap the kegs and proceed to draw beer from each
valve one at a time. Ensure each brand is
properly drawing before proceeding to the next.
The proper flow rate for beer at each valve is
2 ounces per second. Beer should be flowing
clear with a full flow from the dispensing faucet (a
considerable amount of dispensing may be
needed).
5. Secure all secondary regulator lock nuts and
complete the information label, identifying the
product and its applied keg pressure for each
appropriate regulator.
6. Instruct operator on proper maintenance and
operating requirements.
Part Number STH13 9/1053
Beermaster Wine Dispensing Kit
To dispense chilled wine through the Beermaster™
system, the following components are required:
•Wine Dispensing Kit (P.N. 00211504)
•Nitrogen Regulator (P.N. 00219381)
•Wine Tank, Stainless Steel with general
disconnects
INSTALLING
Single Faucet
1. Select faucet on beer tower for wine and remove
metal beer faucet. Replace metal beer faucet with
plastic wine faucet.
2. Locate product line connected to this faucet at
walk-in cooler. If connected to beer wall bracket,
disconnect and remove beer nut, tail piece, and
John Guest tube connector.
3. Assemble 1/2" x 3/8" John Guest tube connector,
appropriate length of 3/8" O.D. poly, to reach
location of wine tank, 3/8" x 1/4" FF John Guest
connector, and liquid disconnect.
4. Connect nitrogen regulator to nitrogen tank and
connect gas line to regulator outlet.
5. Connect empty wine tank and turn on nitrogen
tank. Adjust to 30 PSI and pressurize system to
check for leaks.
6. Turn OFF nitrogen and depressurize system.
Determine system pressure resistance and reset
regulator for desired flow.
Multiple Faucets from Same Tank
In addition to component required for single faucet
installation, each additional faucet requires:
•Faucet (P.N. 00211885)
•Tee (P.N. 00210862)
1. Install faucets at desired locations.
2. Install tees at appropriate places in 1/2" O.D. poly
wine line.
54Part Number STH13 9/10
POSITIONING OF REFRIGERATION UNIT
Before proceeding with installation, verify that all
requirements for roof mounted Remote Condenser
Units have been satisfied (if applicable). Refer to the
instructions on installing the Remote Condenser
supplied with the unit.
If the unit is to rest on the floor, locate the four 6" (15.2
cm) adjustable legs (optional). Screw and tighten the
legs into the bottom of the refrigeration unit. Set the
unit in desired location and adjust legs until the unit is
level and sturdy. If the unit is to be mounted on a
stand, position stand and secure the unit to stand. If
the unit is to be installed on a wall mount bracket,
install the wall mount bracket and position the unit on
the bracket at this time. Fasten the unit to the bracket
with bolts provided.
EQUIPMENT PLACEMENT
NOTE: All Refrigeration Units must be mounted on
either 6" legs or optional stand.
1. Move the stand/refrigeration unit to the
designated area and position it near the wall at a
distance of at least 6" (15.2 cm) for air circulation
in air-cooled units, or at a distance required by
local code.
2. Level the stand/unit by adjusting the leg levelers
provide on the legs or stand.
3. If the unit is equipped with optional stand, lift the
Refrigeration Unit onto the stand. Position the unit
in the center of the stand. Be sure to orientate the
drain of the refrigeration unit with the drain access
hole of the stand. Secure with 5/8"-11 x 1" bolts
supplied in kit, use two bolts diagonally. Schedule
the electrician to connect the electrical service if
you have not already done so (refer to Electrical
Requirements for requirements listed in these
instructions).
4. Mount any optional equipment at this time. Follow
the installation instructions for each kit required.
Part Number STH13 9/1055
ELECTRICAL CONNECTIONS
!
Caution
Make sure power supply to unit is turned off .
NOTE: The electrician must refer to the nameplate
and wiring schematic on the refrigeration unit for
correct electrical requirements. All wiring must comply
with all safety codes. Make sure all refrigeration unit
power switches are in the OFF positi on .
5. Route and connect power supply to leads in the
electrical junction box at the top rear of the motor
compartment.
NOTE: Be sure to connect ground wire(s) to ground
screw located on back panel of junction box.
56Part Number STH13 9/10
INSULATING CONNECTIONS
Aerosol
Foam
Chase
1. Make sure all exposed lines are well insulated on
towers to conduit, conduit junctions, refrigeration
unit to conduits.
2. To insulate the above, use the leftover conduit
sections and tape.
3. Cut the conduit sections to fit snugly over the
exposed lines and fittings. A little extra time spent
doing a thorough job initially will eliminate a call
back in several days to make corrections.
NOTE: Do not inject foam material directly on the
connections where the tubing connects to the barb
fittings or directly on poly tubing.
4. A can of foam is to be used to fill the openings
between the conduit insulation and the inside
diameter of the floor chases. The purpose is to
provide an air tight seal at the floor level to
prevent foreign matter from entering the chases.
Please read the foam manufacturer’s instructions
carefully. We recommend using the adapter with
the right angle extension.
5. Insert the adapter into the openings
approximately 1" to 2" (2.5 to 5.1 cm) while
depressing the adapter.
6. Move the extension around throughout the area
where the foam is to be placed. Do not over fill,
allow room for expansion. If the chase opening is
too deep insert a section of the leftover conduit
insulation in the opening prior to using the foam
insulation.
Part Number STH13 9/1057
Aeroquip Connection
Important
1. Lubricate male half diaphragm and synthetic
rubber seal with refrigerant oil.
2. Thread male coupling to its proper female half by
hand to ensure proper mating of threads.
3. Use proper wrenches (on coupling body hex and
its union nut) and tighten union nut until coupling
bodies “bottom”.
NOTE: You must use a wrench on the body to keep
the body from turning while tightening the nut with the
second wrench. If the body turns excessively, the
piercing seal will be damaged.
4. Use proper wrenches to tighten an additional 1/4
turn (90°). This final 1/4 turn is necessary to
ensure the formation of a leak proof joint.
Alternately, use a torque wrench to tighten the
1/2" coupling to 40 ft-lbs and 3/8" fitting to
11 ft-lbs.
5. Leak check all your connections. If you detect any
leaks, repair and recheck.
Condenser and Pre-charged Lines
Installation
Before proceeding with installation, verify that all
requirements for roof mounted remote condenser units
(if applicable) have been satisfied. If unit has a remote
condenser, refer to the instructions on installing the
remote condenser supplied with the condensing unit
and refer to the section on installation of remote
refrigeration line sets.
If you are installing a remote unit, there is a
refrigeration king valve located behind the
compressor. This valve must be back seated
prior to starting the compressor. Failure to do so
will short cycle and may damage the compressor.
1. Installation and maintenance are to be performed
only by qualified refrigeration personnel. These
technicians must have EPA certification (USA),
are familiar with local codes and regulations, and
are experienced with this type of remote
refrigeration equipment.
2. As a condition of the warranty, the check, test and
start-up procedure must be performed by qualified
personnel. Because of possible shipping damage,
check both the condensing unit and refrigeration
unit(s) for refrigerant leaks.
3. If the refrigeration unit is located on a roll out
platform, you must coil up to one round between
the back of the stand and the wall. This allows pull
out of the refrigeration unit for servicing.
4. If the refrigeration unit is located in a stationary
location, you must remove excess refrigeration
tubing as described below.
1. Both the discharge and liquid remote condensing
lines must be kept to a minimum distance for
maximum performance. All Multiplex systems are
capacity rated to 100 ft (30.5 m) tubing distance
between the compressor and condenser.
2. Any vertical rise 25 ft (7.62 m) or greater must
have a manufactured or installed trap (bend), in
the discharge refrigeration line from the
compressor to the remote condenser. A trap is
necessary for every additional 25 ft (7.62 m)
vertical rise. When excessive vertical rise exists,
this trap allows oil to reach the condenser and
return to the compressor.
3. The easiest method to create a trap is to bend the
tubing (smoothly, no kinks) into the trap form.
Part Number STH13 9/1059
4. The trap(s) must be of minimum height of 3"
To the
Condenser
Discharge Line Trap Every
25 Vertical ft. (7.62 m)
3 ft (.9 m) (minimum) of Discharge
Line Trap at the Compressor
Compressor
3" (7.6 cm) x 6" (15.2 cm)
Maximum Trap Area
Discharge Line
Condenser Trap
(7.6 cm) and a width of 6" (15.2 cm) to minimize
oil accumulation. The traps can also be bent out
of the refrigeration tubing. Carefully bend the
tubing down 12", and then sweep the tubing back
up.
5. It is critical that the Multiplex remote condensing
line size specifications for the specific model be
maintained. The specifications are 1/2" discharge
and 3/8" liquid lines.
INSTALLING THE MULTIPLEX REMOTE
CONDENSER
The Multiplex remote condensing units have a
208-230 Volt, 50/60 HZ, 1 PH fan motor that includes a
permanent split capacitor and internal overload
protection. The electrical wires from the refrigeration
unit wire to the condenser. The electrical installation
must be in accordance with local codes, National
Electrical Code and regulations.
1. Determine a position for installation that will allow
access for maintenance and is free from
obstruction. Verify hot air discharge from other
condensers does not interfere with the inlet of this
condenser.
2. Install the four legs to the sides of the condenser
using the mounting bolts provided.
60Part Number STH13 9/10
3. The General Contractor or Owner must secure
3" Pitch Pot
Roof
two treated lumber 4" x 4" x 36" (or longer). You
may then mount the remote condenser to the
treated lumber.
4. The General Contractor or Owner must install a 3"
pitch pot in the roof. Then seal for weather
protection.
5. Locate the pre-charged refrigeration lines shipped
with the system. These lines must be a correct
length for the building design. Avoiding any kinks,
neatly route these lines from the remote
condenser to the refrigeration unit. Excess
refrigeration tubing must be handled in one of two
ways. When coiling the excess tubing, make sure
the inlet to the coil is at the top of the coil and the
exit is the bottom of the coil. There can be no
more than one turn to the coil. If you have more
Part Number STH13 9/1061
tubing, you must cut out the excess before
!
Caution
connecting the ends. When cutting the tubing, you
must first evacuate the refrigerant (line sets have
a positive refrigerant holding charge of two to
three ounces). After shortening and welding the
tubing together again, you must evacuate the
tubing to 250 microns. Then recharge the tubing
with 4 ounces of appropriate refrigerant.
Excess refrigeration tubing must be properly
cared for before being connected to either the
remote condenser or the refrigeration unit.
CONNECTING THE PRE-CHARGED
REFRIGERATION LINES
NOTE: Before connecting the pre-charged
refrigeration lines, the refrigeration unit must be
properly located, leveled, and the water bath filled 1"
(2.5 cm) below the installed drain pipe.
1. Attach low side gauge set to service port on each
line set to verify positive pressure within the line
set.
NOTE: If for any reason the lines are damaged and/or
leaking or the lines no longer charged, refer to “How to
Re-charge the Line Sets”. If the line set is too long for
the application, refer to “How to Shorten the Line
Sets”.
2. Always make the connections at the condenser
first, using the end of the pre-charged lines with
the valve ports.
3. Connect the condenser side with the quick
connectors (discharge and liquid) up to
condenser. Refer to the section titled “Aeroquip
Connection” in these instructions.
4. Connect the refrigeration unit side with the quick
connects (discharge and liquid). Make sure to
provide a discharge trap at back of refrigeration
unit, or bend discharge line down 12" and then up
smoothly (no kinks) to provide a trap.
62Part Number STH13 9/10
5. If a low refrigerant charge is detected, recover
and recharge the system adding the unit name
plate charge.
6. Repair any damages to the line sets before
proceeding.
HOW TO SHORTEN THE LINE SETS
1. Do not connect either end of the tubing to the
system before everything is set in place. Standard
refrigeration practices must be followed regarding
the tubing installation.
2. Excess refrigeration tubing must be handled in
one of two ways. With a short amount of excess
tubing (about 10 feet), you may coil that amount
vertically between the condenser and refrigeration
unit. When coiling the excess tubing, make sure
the inlet to the coil is at the high side of the coil
and the exit is the low side of the coil. There can
be no more than one turn to the coil. The coil must
continue in a downward spiral with no overlaps,
similar to a cork screw. If you have more tubing,
you must cut out the excess before connecting
the ends. When cutting the tubing, you must first
evacuate the refrigerant.
3. After shortening the tubing and welding together
again, you must vacuum the tubing to 250
microns.
4. Recharge the tubing with the appropriate
refrigerant at 4 ounces per length of tubing.
HOW TO RE-CHARGE THE LINE SETS
NOTE: This procedure to be used only with damaged
or evacuated line sets or with unknown refrigerant
type.
1. With the remote condenser lines properly hooked
and sealed to the condenser, evacuate to 250
microns for 1 hour, using both Schrader ports on
the service line set.
2. For units with model numbers beginning with
“SS”, charge the condenser and line set as
described here. Add 0.72 oz/ft (0.067 kg/m) of
remote line set (one way run distance) plus
condenser name plate charge.
Part Number STH13 9/1063
Example:
45 ft of line set
45 x 0.72 oz = 32.4 oz
32.4 oz + condenser charge = Total charge
If the line set and the main refrigeration unit are
connected, you must also add that refrigerant
charge.
For units with part numbers beginning with “TS”,
charge according to the nameplate charge on the
refrigeration unit. That is enough refrigerant for up
to 100 feet of tubing plus the Multiplex condenser.
If you have another brand condenser, please add
additional charge for the condenser (example: up
to three pounds for a MAC condenser).
3. Connect line sets to the proper discharge and
liquid mating connectors on the refrigeration unit
using quick connects. Refer to the section titled
“Aeroquip Connection” in these instructions.
4. Be sure to observe proper refrigeration
techniques when running the line set.
A. The discharge line must loop down at the
compressor end to trap liquid from returning
to the compressor, unless you are coiling
refrigeration tubing behind the unit.
B. The discharge line must loop above
discharge connector at the condenser to
resist liquid returning to the compressor. Any
excess tubing must be removed from the line
set before the line set is connected to any
equipment.
C. The discharge line must have one P trap
every 25 ft (7.6 m) of vertical rise to allow oil
to stair-step up to the condenser and
eventually return to the compressor.
NOTE: When the connections are made, the seal in
the couplings are broken, and if removed for any
reason, the refrigerant charge will be lost.
64Part Number STH13 9/10
!
Caution
Relays and terminal block are energized from
!
Caution
To the
Condenser
Discharge Line Trap Every
25 Vertical ft. (7.62 m)
3 ft (.9 m) (minimum) of Discharge
Line Trap at the Compressor
Compressor
3" (7.6 cm) x 6" (15.2 cm)
Maximum Trap Area
Discharge Line
Condenser Trap
each remote unit. Turn OFF switches on each
unit before opening quick disconnect switch on
condensing unit. On the completion of the wiring
of the remote condenser make sure the
electrician placed the switch lever in the ON
position. This switch must be ON before turning
ON the refrigeration toggle switch on the unit.
Also, the water bath must be filled with water.
Relays and terminal block are energized from
each remote unit. Turn OFF switches on each
unit before opening quick disconnect switch on
condensing unit. On the completion of the wiring
of the remote condenser make sure the
electrician placed the switch lever in the ON
position. This switch must be ON before turning
ON the refrigeration toggle switch on the unit.
Also, the water bath must be filled with water.
Part Number STH13 9/1065
Preparing Glycol
!
Caution
!
Caution
MIXING GLYCOL SOLUTION
1. Inspect the glycol reservoir tank for dirt and/or
foreign debris. The tank must be clean before
mixing glycol solution.
2. Locate the glycol kit:
Model 753 Gallons (19 ltr) Glycol
Model 1505 Gallons (19 ltr) Glycol
Model 30015 Gallons (57 ltr) Glycol
Model 45020 Gallons (75 ltr) Glycol
3. Pour the glycol into the reservoir tank.
Do not turn on the circulating pump(s) until
system installation is complete.
4. Add water until level of glycol/water solution
reaches the “Fill Here” mark located on tank wall.
NOTE: The glycol/water solution in the water bath is
now mixed to the proper ratio.
5. Push the switches marked “Compressor” and
“Agitator” if equipped to the ON position. After
compressor cycles OFF, check to ensure glycol
solution reads 27°F (-2.7°C) to 29°F (-1.6°C).
Glycol water ratio should be maintained at a 3 to
1 ratio (17-22 Refractometer). Additional water
will be required after starting pumps and solution
fills circulation system.
66Part Number STH13 9/10
NOTE: Verify that the pump box holding tank is full
Drain Plug
Overflow
Tube
Glycol Bath
Tank
Tab
Clamp
before proceeding.
6. Turn on the circulator. The circulator must run
continuously. Verify that glycol is retu rning to the
glycol bath through the return bulk head fitting.
Part Number STH13 9/1067
Additional Glycol Circulating Pump and
Carriage Bolts
(Later Units)
Mounting Studs
(Early Units)
5/16" - 18 Hex Nut
Motor Kit
Pump and Motor Kit
Motor Installation
NOTE: Only two fasteners required.
68Part Number STH13 9/10
Tube Installation
End Panel
1/2" O.D. x 1/2" O.D.
John Guest Elbow
1/2" O.D. Red
Connecting Tube
Circulating Pump
Discharge Cooling Coil
Part Number STH13 9/1069
INSTALLING THE GLYCOL CIRCULATING PUMP
AND MOTOR KIT
1. Remove the lid from the Beermaster refrigeration
unit.
2. Install the glycol circulating motor with pump to
the motor shelf located in the Beermaster Glycol
Unit motor compartment (see “Motor Installation”
figure).
NOTE: Motor must be installed with the glycol pump
facing away from the glycol bath.
3. Locate the pickup tube and discharge tube
assemblies. Slide one piece of insulation over
each of the tube assemblies (see “Tube
Installation” figure).
4. Attach the pickup tube to the inlet side of the
glycol pump making sure the opposite end from
the pump is submerged in glycol bath.
5. Attach the discharge tube to the outlet side of the
glycol pump.
6. Slide the 1/2" x 1/2" John Guest Elbow, supplied
in kit, onto the end of the discharge tube at pump
motor assembly.
7. Locate the circulator pump discharge cooling
tube, supplied with kit, and insert into the water
bath area. Insert straight end of tube into the John
Guest elbow fitting as shown.
8. Insert the two 1/2" O.D. John Guest bulkhead
unions, supplied in kit, into the pre-punched holes
located in the end of the refrigeration unit.
9. Locate the two 1/2" O.D. tube retaining collets,
provided in kit, and insert into each of the John
Guest bulkhead unions.
10. Insert the free end (bent end) of the circulator
pump coil tube into the lower John Guest
bulkhead union.
NOTE: Do Not discard the condensation cover over
the reservoir tank. It is necessary to prevent excessive
condensation from diluting the water-glycol mixture.
70Part Number STH13 9/10
11. Locate the 1/2" O.D. x 4" or 8" plastic tube,
1/2" O.D. John
Guest Bulkhead
1/2" O.D. x 8"
Plastic Tube
1/2" O.D. Tube
Retaining Collet
Circulator Pump
Discharge Cooling
Tube
Pickup Tube
2 ft x 1/2" I.D.
Insulation
1/2" x 1/2" John
Guest Elbow
Strainer Plate
12. Locate the 8 ft piece of cork tape, provided with
13. Remove and discard safety plug from connector
14. Installation of glycol circuit pump is now complete.
15. The added glycol circulating pump can now be
NOTE: After starting the new circulator pump, it may
be necessary to top off the glycol bath with the proper
propylene glycol/water mixture to maintain marked
level in tank.
Part Number STH13 9/1071
provided with kit. Insert one end of this tube into
the upper bulkhead fitting. Insert opposite end of
this tube into hole of strainer plate (see “Pump
Connections” figure).
Pump Connections
kit, and insulate the glycol pump and all exposed
connections to prevent condensation.
of wire harness coming from control box. Attach
connector of glycol pump motor to connector of
wire harness coming from control box.
The Beermaster refrigeration unit can now be
turned ON.
controlled by a switch located on the switch box.
-For Model 450, the CIRC #4 switch will control
added pump.
Beermaster Dispensing Towers
!
Caution
INTRODUCTION
The following instructions will cover installation
procedures required for properly installing Beermaster
Dispensing Towers. Kit includes one (1) Template, (1)
Beermaster Dispensing Tower, (4) Mounting Screws
(for Wooden Counter Top), (1) Gasket, (2) 3/8" MF x
1/2" John Guest Adapters, (1) 3/16" Barb x 1/2" John
Guest Adapter, and (1) Adjustable Clamp.
1. Determine desired location of beer tower.
2. Using the template provided, locate and mark the
center of the tower column.
3. Cut a 3" (7.6 cm) hole and place the tower o v er
the hole to locate and mark the mounting screw
positions.
4. Drill appropriate holes for mounting (1/8" diameter
when using screws provided, if mounting in
wood).
NOTE: If more than one tower is being installed, use
only the tower intended for each location to mark the
mounting screw positions.
5. Position gasket over top of 3" (7.6 cm) access
hole and align holes for mounting screws. It is
recommended that a small bead of silicon
caulking be placed on both sides of the gasket at
this point.
6. Route beer tower beverage lines through 3" (7.6
cm) hole and secure dispensing tower base to
counter with mounting hardware.
7. Ensure lines are neatly sealed and wrapped until
the necessary beer and glycol connections can be
made, as outlined in the Conduit Kit Installation
Kit section.
The 6 ft beer restrictor lines for beer tower should
not be trimmed until completely reviewing the
instructions for conduit kits.
72Part Number STH13 9/10
DISPENSING TOWER TEMPLATE FOR
3"
(7.6 cm)
Cut Out
3" (7.6 cm)
Diameter
BEERMASTER DISPENSING TOWER
NOTE: This template is 50% of actual size.
High Pressure CO2 Regulator (00211500)
INTRODUCTION
The following instructions will cover procedures
required for properly installing the Beermaster high
pressure CO
KIT CONTENTS
•(1) Beermaster High Pressure CO
with seal
•20 ft of 5/16" I.D. tubing
•(6) # 8 screws
•(6) tie mounts
•(6) self locking cable ties
•(4) tab clamps
Installation should only be performed by qualified
personnel.
2
regulator.
Gas Regulator
2
Part Number STH13 9/1073
INSTALLING
Primary High
Pressure CO
2
Regulator
To CO
2
Blender or
Secondary Regulator
Assembly
Seal
1. Determine the location where the beer system
CO
tank(s) will be located. CO2 tanks must be
2
chained securely in place.
2. Attach the primary regulator to the CO
seal provided in kit (see the “Attaching Regulator”
tank. Use
2
figure).
3. Neatly route the 5/16" I.D. vinyl tubing from the
primary regulator(s) to the secondary regulator in
the beer keg cooler or to the optional blender.
4. Secure the vinyl tubing in place with tie mounts
and cable ties provided in kit (see the “Securing
Vinyl Tubing” figure).
NOTE: At start-up the primary regulator should be
adjusted to 40 PSI (2.8 bar) and locked.
Attaching Regulator
74Part Number STH13 9/10
Securing Vinyl Tubing
Tie Mount
Cable Tie
#8 Screw
Dual Secondary Regulator Kit (00211400)
INTRODUCTION
The following instructions cover the installation of a
Multiplex secondary regulator panel kit. Each dual
secondary regulator kit will handle two beer kegs.
Additional dual secondary regulator kits can be placed
in series to handle additional beer kegs.
KIT CONTENTS
•(1) dual secondary regulator assembly with wall
bracket
•CO
•Beer lines
•12 ft - 5/16" I.D. black vinyl tubing
•(10) boss coupling washers
•(8) tab clamps
•(1) 1-1/4" MPT pipe plug
•6 ft - 3/8" I.D. clear vinyl line assembly
gas lines
2
Part Number STH13 9/1075
INSTALLING
Beer Keg
Black Vinyl Tubing
from Primary
Regulator or Gas
Blender
Tab
Clamps
5/16" Barb x
1/4" MPT
VIEW
A
Plug
Black Vinyl
(Attach to Next
Regulator
Assembly)
Lock Bar
Tab Clamp
Boss Coupling
Washer
4 ft Clear Vinyl
Beer Line
Tavern
Head
Refer to the “Secondary Regulator Installation” figure
for the following procedures:
1. Mount the dual secondary regulator panel in a
convenient location above the area where beer
kegs will be stored.
2. Route the CO
pressure regulator (or gas blender) and attach to
gas line from the primary high
2
the 5/16" Barb fitting of the secondary regulator.
Use two tab clamps.
Secondary Regulator Installation
76Part Number STH13 9/10
3. Cut the black vinyl CO2 gas line looped between
Primary High
Pressure CO
2
Regulator
To CO
2
Blender
or Secondary
Regulator
Assembly
Seal
the two regulators. Attach each CO
the 5/16" inlet of the tavern head (not provided).
gas line to
2
Use one tab clamp per connection.
4. Attach each of the clear vinyl beer lines to the
beer outlet of the tavern head. Use one boss
coupling washer, 3/8" nipple and hex nut
(provided in kit) at each connection.
5. Additional dual secondary regulator kits can be
placed in series from the first regulator panel. To
plug the last regulator in a series of regulators,
remove the Barb fitting from the regulator outlet
and install the 1/4" MPT plug, provided in kit (see
the “Secondary Regulator Installation” figure,
View A).
NOTE: Do not adjust pressure regulators at this point.
See “Conduit Kit” section for regulator adjustments.
Part Number STH13 9/1077
Beermaster Blenders
Outlet for Mixed Gas
(most beers)
Outlet for Mixed Gas
(Guiness)
Secondary
Regulators
Use
reinforced
tubing
suitable for
70-150 PSI
Primary CO
2
Regulator
Primary N2
Regulator
Use
reinforced
tubing
suitable for
70-150 PSI
Secondary
Regulators
N
2
Tank
CO
2
Tank
N2/CO2 BLENDER (SINGLE — 00520182, DUAL —
00520183)
Installing
1. Decide where the N
mounted.
NOTE: Be sure the panel is on a wall in a well
ventilated, accessible indoor area that is out of harm’s
way.
2. Mount the panel on the wall.
3. Hook-up panel using thread sealant on threads
and a back-up wrench on panel fittings.
NOTE: Do not use fittings with check valve on inlets.
Do not remove 1/4" female threaded fittings from
panel, as they contain filters.
4. Test all fitting s for leaks.
5. Use regulators and tubing suitable for 70 –
150 PSI.
NOTE: Regulators set at 50 PSI are suitable on a
50 PSI blender.
6. Secure all cylinders to the wall.
NOTE: Store cylinders in a well ventilated, accessible
area.
/CO2 Blender Kit will be
2
78Part Number STH13 9/10
Beermaster Low CO2 Alarm Kit
Beermaster
Glycol Chiller
Pump Assembly
Air
Compressor
Mounting
Channel
Support
Stand
The following instructions cover the installation
procedures for installing the Beermaster Low CO
Alarm Kit. Installation should be performed by qualified
personnel.
2
INSTALLING THE LOW CO
1. Turn OFF CO
pressure from line.
at the CO2 tank and bleed all
2
ALARM KIT
2
2. Locate the 1/4" x 1/4" x 1/4" stainless steel tee
supplied with the alarm kit. Install this tee in the
pressure line between the high pressure
CO
2
regulator and the medium pressure regulator. Use
two tab clamps per connection (refer to the figure
below).
NOTE: If beer system is equipped with an blender, tee
must be installed upstream of the blender.
3. Locate the alarm box and transformer supplied
with kit. Mount the alarm box in a convenient
location near the CO
slide switch on face of alarm box to “Beeper off”
pressure switch. Place
2
position.
Part Number STH13 9/1079
4. Neatly route the two conductor cables of the
CO2 Supply
CO
2
Low
Pressure Switch
Assembly
1/4" x 1/4" x 1/4"
Stainless Steel Tee
Low CO
2
Alarm Box
Primary Regulator
set at 40 psig
120 VAC
Outlet
Transformer
alarm box to the low pressure switch and attach to
the terminal of the pressure switch (refer to the
figure below).
NOTE: Gray cable connector may be shortened.
5. Plug alarm box transformer into 120 VAC, 60 Hz
outlet. The CO
illuminate.
6. Turn ON CO
40 psig. Slide the switch to “Normal Operation”
alarm “Low Pressure” light should
2
at the CO2 tank. Adjust pressure to
2
position; beeper will sound. Press switch to
“Test/Reset” position; light will extinguish and
beeper will stop.
7. Installation is complete.
80Part Number STH13 9/10
Component Identification
N2
Tan k
CO2
Tan k
CO2
Alarm
Refrigeration
Unit
Kegs
Cooler
Regulators
Tower
Conduit
Tower
Blender
Typical System
Part Number STH13 9/1081
Compressor
FUNCTION OF THE COMPRESSOR
Refrigeration pump which draws a low pressure gas
on the cooling side of the refrigeration cycle and
squeezes or compresses the gas into high pressure
on the condensing side of the cycle.
FAILURE OF THE COMPRESSOR
An inoperative or weak compressor would adversely
affect the capability of the unit to chill glycol.
82Part Number STH13 9/10
Condenser
FUNCTION OF THE CONDENSER
A heat exchanger which transfers heat from the
refrigerant to the surrounding air.
FAILURE OF THE CONDENSER
A non-operational fan/motor or restricted condenser
will reduce the cooling efficiency of the refrigeration
unit.
Air Cooled Condenser
Part Number STH13 9/1083
Cap Tube or Expansion Valve
Compressor
Condenser
Water Bath
Receiver
FUNCTION OF THE CAP TUBE OR EXPANSION
VALVE
The cap tube or the expansion valve controls the
refrigerant flow. Both controls allow the reduction of
liquid refrigerant from high pressure to its evaporating
pressure. The expansion valve is better suited for
varying temperature conditions.
FAILURE OF THE CAP TUBE OR EXPANSION
VALVE
A defective expansion valve or cap tube will not
properly regulate the flow of refrigerant.
84Part Number STH13 9/10
Evaporator Coil
FUNCTION OF THE EVAPORATOR COIL
Coil in the glycol bath in which refrigerant vaporizes
and absorbs heat, chilling the bath.
FAILURE OF THE EVAPORATOR COIL
This copper tube assembly is extremely reliable.
Part Number STH13 9/1085
Glycol Bath
FUNCTION OF THE GLYCOL BATH
Water and glycol reservoir, providing an efficient
method of removing heat.
FAILURE OF THE GLYCOL BATH
If not maintained and glycol is allowed to dilute, ice
may form, reducing efficiency.
NOTE:
•Three parts water to one part glycol (3:1)
•17° to 22° on a sugar refractometer
•-10°F on an antifreeze tester
86Part Number STH13 9/10
Agitator
FUNCTION OF THE AGITATOR
Agitates the glycol in the glycol bath to distribute heat
load and keep the bath a consistent temperature.
FAILURE OF THE AGITATOR
An inoperative agitator will warm beer during busy
times, causing foaming at the dispensing faucet.
Part Number STH13 9/1087
Circulating Pump/Motor
Strainer Plate
1/2" O.D. John
Guest Bulkhead
1/2" O.D. Tube
Retaining Collet
Circular Pump
Discharge Cooling
Tube
2 ft x 1/2" I.D.
Insulation
1/2" x 1/2" John
Guest Elbow
1/2" O.D. x 8"
Plastic Tube
Pickup Tube
FUNCTION OF THE CIRCULATING PUMP/MOTOR
Circulates glycol from the glycol bath through the
conduit, up to the dispensing faucet and back to the
bath, maintaining the temperature of the beer.
FAILURE OF THE CIRCULATING PUMP/MOTOR
A weak or defective circulating pump or motor will
cause warm beer and foaming at the dispensing
faucets.
NOTE:
•Brass Pump
•No strainers in pumps
•70 GPH pumps
88Part Number STH13 9/10
Glycol Bath Strainer
FUNCTION OF THE GLYCOL BATH STRAINER
Keeps debris from continually recirculating throughout
the glycol system.
FAILURE OF THE GLYCOL BATH STRAINER
Can restrict the flow of glycol back into the water bath,
overflowing the strainer.
Part Number STH13 9/1089
Conduit
FUNCTION OF THE CONDUIT
Insulated beverage tubing used to move and maintain
cold beer and glycol from the refrigeration unit to the
dispensing station.
FAILURE OF THE CONDUIT
Temperature will not be maintained an d condensation
may develop if the conduit is improperly insulated or if
the insulation becomes saturated.
90Part Number STH13 9/10
John Guest Fittings
Collet
Collet Cover
Wrong
Right
Tubing
Collet
Collet Cover
Tubing
FUNCTION OF THE JOHN GUEST FITTINGS
Provide a “same inside diameter” connection for the
beer lines, causing a minimal or no amount of agitation
to the beer, reducing foaming. Also are used for the
glycol lines in series with the conduit tubing to provide
quick and easy connections for the glycol circuit.
FAILURE OF THE JOHN GUEST FITTINGS
These are very reliable fittings when installed properly.
The tubing must be cut with a razor type blade to
ensure tubing will not be crushed when cutting. The
tubing must be pushed completely into the fitting.
Part Number STH13 9/1091
Restriction Line
FUNCTION OF THE RESTRICTION LINE
Reduces the flow of beer from the faucet. Used with
the pressure adjustment to the keg to balance the
system, giving a proper foam-free beer flow from each
dispensing faucet.
FAILURE OF THE RESTRICTION LINE
If the length is not correct will cause foaming at the
dispensing faucets.
NOTE: If too long can cause slow flow. Standard flow
rate is 2 oz/sec.
92Part Number STH13 9/10
Dispensing Faucet
FUNCTION OF THE DISPENSING FAUCET
To dispe nse cold beer with very little agitation and the
proper head.
FAILURE OF THE DISPENSING FAUCET
Will dispense inferior beer with excessive foam.
NOTE: If dirty inside or worn or swollen gaskets can
cause foaming.
Part Number STH13 9/1093
Heat Exchanger
FUNCTION OF THE HEAT EXCHANGER
Provides the heat exchange between the glycol circuit
and the dispensing faucet keeping every beer cold.
FAILURE OF THE HEAT EXCHANGER
If heat exchanger is not in direct contact with the
dispensing faucet and the glycol circuit, it could cause
warm beer after slow or quiet periods.
94Part Number STH13 9/10
High Pressure Regulator
!
Caution
FUNCTION OF THE HIGH PRESSURE
REGULATOR
Regulates the CO
constant 40 psi (2.8 bar) to the secondary regulators,
to push the beer from the kegs.
FAILURE OF THE HIGH PRESSURE REGULATOR
Low pressure or a sluggish regulator can ca use
pressure variations and different flow rates at the
dispensing faucet. High pressure or a creeping
regulator will cause the relief valve to relieve.
tank pressure to maintain a
2
NOTE: 55 psi (3.8 bar) relief
Soda regulators should never be used for beer.
Part Number STH13 9/1095
Secondary Regulator
!
Caution
FUNCTION OF THE SECONDARY REGULATOR
Regulates the CO
gas used to push the beer.
FAILURE OF THE SECONDARY REGULATOR
Any fluctuations in pressure will cause beer to be
dispensed with excessive foam.
NOTE: 55 psi (3.8 bar) relief
or blended CO2 and air or blended
2
Soda regulators should never be used for beer.
96Part Number STH13 9/10
Tavern Head
FUNCTION OF THE TAVERN HEAD
Attaches to the keg and provides the pressure inlet
and beer outlet from the keg.
FAILURE OF THE TAVERN HEAD
If defective or worn will leak and/or not allow beer to
leave the keg properly.
Part Number STH13 9/1097
Keg
FUNCTION OF THE KEG
Container that holds the pressurized beer.
FAILURE OF THE KEG
Must be properly chilled and not agitated before
dispensing.
98Part Number STH13 9/10
Wall Bracket
FUNCTION OF THE WALL BRACKET
A wall mounted connection point for the tubing coming
from the flexible tavern head, connecting to the fixed
beer line in the conduit.
FAILURE OF THE WALL BRACKET
This metal fitting is extremely reliable.
Part Number STH13 9/1099
Blender
26%
23%
GPM Air
40 41 42 43 44 45 46 47 48 49 50
GPM
CO
2
20
19
18
17
16
15
14
13
12
11
10
FUNCTION OF THE BLENDER
Metering device that blends air or nitrogen with CO
supply pressure to the beer, reducing the chance of
changing the amount of carbonation in the beer.
FAILURE OF THE BLENDER
If not blended properly could cause over or under
carbonation in the beer.
to
2
NOTE:
•Air and CO
•Desired Air/CO
. The graph on the right can be used as a
CO
2
guide to determine if setting falls in the
recommended range.
100Part Number STH13 9/10
adjusted to 40 psi (2.8 bar).
2
mixture should have 23% to 26%
2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.