Multiplex 11M Installation Manual

Model 11M Root Beer System
Refrigeration Unit
Installation, Use & Care Manual
This manual is updated as new information and models are released.
Visit our website for the latest manual. www.manitowocfsg.com
America’s Quality Choice in Refrigeration
Part Number 020001552 5/11
Safety Notices
As you work on Manitowoc equipment, be sure to pay close attention to the safety notices in this manual. Disregarding the notices may lead to serious injury and/ or damage to the equipment.
Throughout this manual, you will see the following types of safety notices:
Warning
!
Text in a Warning box alerts you to a potential personal injury situation. Be sure to read the Warning statement before proceeding, and work carefully.
Caution
!
Text in a Caution box alerts you to a situation in which you could damage the equipment. Be sure to read the Caution statement before proceeding, and work carefully.
Procedural Notices
As you work on Manitowoc equipment, be sure to read the procedural notices in this manual. These notices supply helpful information which may assist you as you work.
Throughout this manual, you will see the following types of procedural notices:
Read These Before Proceeding:
Caution
!
Proper installation, care and maintenance are essential for maximum performance and trouble-free operation of your Manitowoc equipment. Read and understand this manual. It contains valuable care and maintenance information. If you encounter problems not covered by this manual, do not proceed, contact Manitowoc Foodservice Group. We will be happy to provide assistance.
Important
Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Warning
!
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
NOTE: SAVE THESE INSTRUCTIONS.
Important
Text in an Important box provides you with information that may help you perform a procedure more efficiently. Disregarding this information will not cause damage or injury, but it may slow you down as you work.
NOTE: Text set off as a Note provides you with simple, but useful, extra information about the procedure you are performing.
We reserve the right to make product improvements at any time.
Section 1 General Information
Section 2 Installation
Table of Contents (continued)
Read This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How to Read a Model Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Special Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Attention: Marine Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Outdoor Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Serial Plate Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Unpacking and Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Dimensions and Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Blade Tower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Safe Installation Dos and Don’ts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Kitchen Equipment Installer Representative Responsibilities . . . . . . . . . . . 2-5
Requirements for Post Mix Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Installer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Minimum Circuit Ampacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Grounding Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Plumbing/Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Plumbing Potable Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Plumbing Requirements – General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Plumbing Circuit Diagrams — Model 11M Root Beer . . . . . . . . . . . . . . . . . 2-9
Part Number 020001552 5/11 i
Table of Contents (continued)
Refrigeration Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Positioning of Refrigeration Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Equipment Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Routing Insulated Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Connecting Insulated Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Connecting Supply Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Connect the drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Proper Use of John Guest Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Insulating Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Aeroquip Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Condenser and Pre-charged Lines Installation . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Remote Condenser Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Pre-charged Refrigeration Line Requirements . . . . . . . . . . . . . . . . . . . . . . 2-17
Installing the Multiplex Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Connecting the Pre-charged Refrigeration Lines . . . . . . . . . . . . . . . . . . . . 2-18
Testing CO2 Circuit for Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Testing Syrup Circuit (5 gallon tanks only) . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Preparing Ice Bank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Building an Ice Bank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
Section 3 Operation
Typical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
How the Multiplex Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Water Bath Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Pre-mix Refrigeration Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Placing Equipment in Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Placing the Carbonation System in Operation . . . . . . . . . . . . . . . . . . . . . . . 3-3
Equipment Setup and Close Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Equipment Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Equipment Close Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
ii Part Number 020001552 5/11
Section 4 Maintenance
Sanitizing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Back-flow Preventer Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Shipping, Storage and Relocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Section 5 Before Calling for Service
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Table of Contents (continued)
Beverage System Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Bag-In-Box System Sanitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Figal Beverage System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Part Number 020001552 5/11 iii
Table of Contents (continued)
THIS PAGE INTENTIONALLY LEFT BLANK
iv Part Number 020001552 5/11

Section 1 General Information

Section 1
General Information

Read This Manual

Manitowoc Food Service developed this manual as a reference guide for the owner/operator and installer of this equipment. Please read this manual before installation or operation of the machine. A qualified service technician must perform installation and start-up of this equipment, consult Section 5 within this manual for service assistance.
If you cannot correct the service problem, call your Manitowoc Beverage Equipment (MBE) Service Agent or Distributor. Always have your model and serial number available when you call.
Your Service Agent ____________________________ Service Agent Telephone Number_________________ Your Local MBE Distributor ______________________ Distributor Telephone Number____________________ Model Number _______________________________ Serial Number ________________________________ Installation Date ______________________________

Unit Inspection

Thoroughly inspect the unit upon delivery. Immediately report any damage that occurred during transportation to the delivery carrier. Request a written inspection report from a claims inspector to document any necessary claim.

Model Numbers

This manual covers the following models:
Post Mix Soda Refrigeration Unit
11MA04B

How to Read a Model Number

Condenser
Type
Model Prefix
Model Base
11M A 04 B
2803 & SC180 - 1/3 hp 11M & SC340 - 1/2 hp 44M & SC1000 - 1 hp 44E - 1 hp, TUV Approved 50M & SC2000 - 2.2 hp
A - Air-cooled AX - Air-cooled, international R - Remote RX - Remote, international W - Water-cooled WX - Water-cooled, international
B - Reserve Ice Bank T - TUV approved
Q/T - Quick Trip
04 - R404a refrigerant
Model Suffix
carbonator tank
Warning
!
PERSONAL INJURY POTENTIAL
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
Part Number 020001552 5/11 1-1
General Information Section 1

Accessories

Depending on store type and location, various optional equipment (such as CO2 Panel, water filter kit, water booster kit, etc.) may be added to this system. Install and connect any optional equipment in the desired location according to the installation instructions provided with these kits/equipment.

Special Applications

ATTENTION: MARINE INSTALLATIONS

Warning
!
This unit is for use on vessels over 66 ft (20 m) in length. This unit must not be installed in the engine space of a gasoline-powered ship.
NOTE: This unit must be secured to the vessel during installation. Models with part numbers beginning with the letters TS are NOT marine listed.

OUTDOOR APPLICATIONS

TS Multiplex Beverage Recirculating units are approved and listed by Underwriters Laboratories (UL). However they are not UL approved for weather exposure applications. These units must be installed in areas where adequate protection from the elements is provided, all other models are ETL listed.

Specifications

Model
11M One 6-valve soda tower or up
Number of Dispensing
Heads
to three 2-valve root beer
towers
Type of
Container
Bag-in-Box
1-2
Part Number 020001552 5/11
Section 1 General Information

Serial Plate Location

Warranty Information

Consult your local MBE Distributor for terms and conditions of your warranty. Your warranty specifically excludes all beverage valve brixing, general adjustments, cleaning, accessories and related servicing.
Your warranty card must be returned to MBE to activate the warranty on this equipment. If a warranty card is not returned, the warranty period can begin when the equipment leaves the MBE factory.
No equipment may be returned to MBE without a written Return Materials Authorization (RMA). Equipment returned without an RMA will be refused at MBE’s dock and returned to the sender at the sender’s expense.
Please contact your local MBE distributor for return procedures.
Part Number 020001552 5/11 1-3
General Information Section 1
THIS PAGE INTENTIONALLY LEFT BLANK
1-4
Part Number 020001552 5/11
Section 2
Installation

General

UNPACKING AND INSPECTING

Carefully inspect the refrigeration unit immediately upon unpacking. Verify the equipment and parts received against the Bill of Lading. Locate all items according to packing list and inspect for possible damage caused by shipping. Notify the appropriate carrier if necessary and contact MBE immediately for replacement of parts if discrepancies exist.
1. The Multiplex A&W Model 11 Refrigeration Unit is pre-assembled in the factory and requires minimum installation. Locate the following parts supplied with the unit.
Kit assembly includes:
- Tab clamps for conduit, syrup, and water coils.
- Bracket for drain hose and screws for mounting
- 6 ft (182.9 cm) drain hose
- Six (6) Adapter 1/2” Barb x 1/2” OD Tube
- Twelve (12) Adapter 3/8” Barb x 1/2” OD Stem
- One (1) Adapter 3/8” MPT x 1/2” OD Stem
2. Locate any of the optional Kit Assembly for mounting to match the type of mounting required. Install the kit as noted in the instructions supplied.
3. Record the Model Number, Serial Number and date of installation for future reference, or to be used when ordering parts.
Part Number 020001552 5/11 2-1
Installation Section 2

Dimensions and Clearances

Wall
Electrical
Junction Box
12"
(30.5 cm)
6" (15.2 cm) minimum
minimum
Electrical
J
Junction Box
Wall
3-7/8" (9.8 cm) Diameter
18" (45.7 cm) minimum
Wall
Control
Switches
Air Flow
6" (15.2 cm)
Diameter Chase minimum
Top View
Ceiling
Conduit to
Dispensing Towers
D
W
Incoming Water
Line
minimum
18" (45.7 cm)
Wall
Incoming CO2
Supply Line
Incoming Syrup
Supply Lines
P
Refrigeration units require stand or 6" (15.2 cm) legs. Refrigeration unit cannot be placed directly on floor.
Conduit can be run through floor or ceiling chase.
Model W D H
11M 35-1/2" (90.2
cm)
18-1/2" (47
cm)
Drain Connection
21-3/4"
(55.2 cm)
I
(with stand)
54"
(137.2 cm)
Wall
H
I
CO2 Regulator
Panel (Optional)
N
Front ViewSide View
Syrup supply can be located on stand or adjacent to refrigeration unit.
JKLMNP
11"
(28 cm)
5"
Drain Connection
Floor drain should be located
within 6 ft (183 cm) of unit
(12.7 cm)
(22.9 cm)
Wall
9"
2-2
Part Number 020001552 5/11
Section 2 Installation

REMOTE CONDENSER

OPTIONAL
38.00" (96.52 cm)
34.00" (86.36 cm)
30.00" (76.20 cm)
29.50"
(74.93 cm)
29.16"
(74.06 cm)
27.94"
(70.97 cm)
1.50"
(3.81 cm)
6.00"
(15.24 cm)

BLADE TOWER

.75"
(1.9 cm)
1.75"
(4.4 cm)
3.50"
(8.89 cm)
(10.16 cm)
4.00"
5"
(12.7 cm)
(18.8 cm)
6.50"
(16.51 cm)
(37.13 cm)
7.39"
14.62"
3" (7.6 cm)
3.29" (8.4 cm)
OPTIONAL
20.00" (50.80 cm)
16.00" (40.64 cm)
12.00" (30.48 cm)
11.86" (30.1 cm)
9.68" (24.6 cm)
(43.9 cm)
10.75"
(27.3 cm)
17.3"
4.88"
(12.4 cm)
Part Number 020001552 5/11 2-3
Installation Section 2

Safe Installation Dos and Don’ts

Warning
!
Read the following warnings before beginning an installation. Failure to do so may result in possible death or serious injury.
DO adhere to all National and Local Plumbing and Electrical Safety Codes.
DO turn OFF incoming electrical service switches when servicing, installing, or repairing equipment.
DO check that all flare fittings are tight. This check must be performed with a wrench to ensure a quality seal.
DO inspect pressure on regulators before starting up equipment.
DO protect eyes when working around refrigerants.
DO use caution when handling metal surface edges of all equipment.
DO handle CO2 cylinders and gauges with care. Secure cylinders properly against abrasion.
DO store CO2 cylinder(s) in well ventilated areas.
DO NOT exhaust CO
gas (example: syrup pump)
2
into an enclosed area, including all types of walk-in coolers, cellars, and closets.
DO NOT throw or drop a CO
cylinder. Secure the
2
cylinder(s) in an upright position with a chain.
DO NOT connect the CO2 cylinder(s) directly to the product container. Doing so will result in an explosion causing possible death or injury. It is best to connect the CO2 cylinder(s) to a regulator(s).
DO NOT store CO
cylinders in temperature above
2
125°F (51.7°C) near furnaces, radiator or sources of heat.
DO NOT release CO
gas from old cylinder.
2
DO NOT touch refrigeration lines inside units; some may exceed temperatures of 200°F (93.3°C).
NOTICE: All utility connections and fixtures must be sized, installed, and maintained in accordance with Federal, State, and Local codes.
2-4
Part Number 020001552 5/11
Section 2 Installation

Location Requirements

CLEARANCES

Warning
Control Side (Right) 18" (45.7 cm) Tower Connection Side (Left) 12" (30.5 cm) Back Side 6" (15.2 cm) Ceiling 18" (45.7 cm)

RATINGS

Model
Model 11M 5,150 BTUH
Evaporator Rating
at 20°F (-6.5°C)
1,159 kcal/hr
Heat Rejection (Max.)
8,638 BTUH 1,949 kcal/hr
Carbon Dioxide (CO2) displaces oxygen. Exposure to a high concentration of CO2 gas causes tremors, which are followed rapidly by loss of consciousness and suffocation. If a CO2 gas leak is suspected, particularly in a small area, immediately ventilate the area before repairing the leak. CO2 lines and pumps must not be installed in an enclosed space. An enclosed space can be a cooler or small room or closet. This may include convenience stores with glass door self serve coolers. If you suspect CO may build up in an area, venting of the BIB pumps and/or CO2 monitors must be utilized.
!
2
Select a location for the refrigeration unit that meets the requirements of the building plans, local codes, and personnel. The unit must be positioned for free airflow as well as for future service. The following requirements must be met:
100 GPH (379 LTR/hr) potable water supply
Beverage quality CO
gas (bulk or bottled supply)
2
with a minimum 3/8" (.96 cm) line
One Bag-In-Box (BIB) (or Figal) container of each post mix syrup flavor.
NOTE: Refer to nameplate on side of refrigeration unit for voltage and amperage specifications. Make all electrical connections at the junction box located at the top rear of unit. Optional equipment may require additional power supplies.
NOTE: Potable water connections to the equipment must comply with local plumbing code requirements, particularly the back-flow prevention requirements.

KITCHEN EQUIPMENT INSTALLER REPRESENTATIVE RESPONSIBILITIES

Prior to scheduling Multiplex Equipment installer, the following steps listed below must be completed:
1. Usable floor sewer drain.
2. A 120 VAC, 3-wire, 1 Phase, 60 Hz Electrical Power Supply (minimum 30 Amp capacity).
- International Models are 50 Hz
3. Usable potable water.
4. CO2 Gas (bulk or bottled supply); minimum 3/8" line.
5. One 5 gallon (19 L) container or Bag-In-Box container of each post mix syrup flavor.
6. A 120 VAC, 3-wire, 1 Phase, 60 Hz dual wall receptacle for optional electrical equipment (domestic only).
NOTE: Do not schedule the authorized Multiplex Equipment Installer until all of the above have been completed. It will only result in charge-backs to you for the unnecessary trips.

REQUIREMENTS FOR POST MIX UNITS

Conduit can be run through floor or ceiling chase.
60°F (15.6°C) minimum and 105°F (40.5°C) maximum operating ambient conditions.
For indoor installation only.
Syrup supply can be located on stand or adjacent to refrigeration unit.
Part Number 020001552 5/11 2-5
Installation Section 2

Installer Instructions

Important
The remainder of these instructions is to be completed by an authorized Multiplex Installer.
These equipment instructions are intended to assist qualified personnel in the unpacking, locating and the initial operation of the Multiplex Beverage Equipment Post Mix Refrigeration Unit.
Important
This publication must be saved for future reference. Read instructions before attempting installation.

PREPARATION

The Multiplex Beverage Equipment Post Mix Refrigeration Unit is pre-assembled in the factory and requires minimum installation.
For future reference or to be used when ordering parts, record the Model Number, Serial Number, Part Numbers of Unit, Condenser (if remote), Towers, etc., and Date of Installation on the inside of this Manual. Leave manual on site in a safe place. Do not discard manual.
Ambient Location Requirement
This equipment is rated for indoor use only. It will not operate in sub-freezing temperature. In a situation when temperatures drop below freezing, the equipment must be turned off immediately and properly winterized. Contact the manufacturer for winterization process.

Electrical

GENERAL

Warning
!
All wiring must conform to local, state and national codes.

MINIMUM CIRCUIT AMPACITY

The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the beverage/ice machine’s running amp load.) The wire size (or gauge) is also dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.

ELECTRICAL REQUIREMENTS

Refer to Ice Machine Model/Serial Plate for voltage/amperage specifications.

SPECIFICATIONS

Model Volt/Cycle/Phase Minimum Circuit Amps Breaker Compressor
11M 120/60/1
230/50/1
21.5
10.7
30A 16A
1/2 hp
.97 kW
2-6
Part Number 020001552 5/11
Section 2 Installation

GROUNDING INSTRUCTIONS

Warning
!
Warning
!
The beverage/ice machine must be grounded in accordance with national and local electrical codes.
This appliance must be grounded. In the event of malfunction or breakdown, grounding provides a path of least resistance for electric current to reduce the risk of electric shock. This appliance is equipped with a cord having an equipment-grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
NOTE: The 208/230V units are not equipped with a cord.
Warning
!
Improper connection of the equipment-grounding conductor can result in a risk of electric shock. The conductor with insulation having an outer surface that is green with or without yellow stripes is the equipment grounding conductor. If repair or replacement of the cord or plug is necessary, do not connect the equipment-grounding conductor to a live terminal. Check with a qualified electrician or serviceman if the grounding instructions are not completely understood, or if in doubt as to whether the appliance is properly grounded. Do not modify the plug provided with the appliance — if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
When using electric appliances, basic precautions must always be followed, including the following:
a. Read all the instructions before using the
appliance.
b. To reduce the risk of injury, close supervision is
necessary when an appliance is used near
children. c. Do not contact moving parts. d. Only use attachments recommended or sold by
the manufacturer. e. Do not use outdoors.
f. For a cord-connected appliance, the following
shall be included:
• Do not unplug by pulling on cord. To unplug, grasp the plug, not the cord.
• Unplug from outlet when not in use and before servicing or cleaning.
• Do not operate any appliance with a damaged cord or plug, or after the appliance malfunctions or is dropped or damaged in any manner. Contact the nearest authorized service facility for examination, repair, or electrical or mechanical adjustment.
g. For a permanently connected appliance — Turn
the power switch to the off position when the appliance is not in use and before servicing or cleaning.
h. For an appliance with a replaceable lamp —
Always unplug before replacing the lamp. Replace the bulb with the same type.
i. For a grounded appliance — Connect to a
properly grounded outlet only. See Grounding Instructions.
Part Number 020001552 5/11 2-7
Installation Section 2

Plumbing/Water Supply

PLUMBING POTABLE WATER

Required
Model
11M 40 – 70 psig
Water
Pressure
(2.8 – 4.9 bar)
A 1" (2.54 cm) ID copper inlet water line equipped with a 3/4" (1.905 cm) FPT sweat adapter with shut-off must be supplied by plumber at rear of equipment. Appropriate floor drains must be provided within 6 ft (183 cm) of each unit installed.
NOTE: The carbonator in this unit is provided with a dual check valve type back-flow preventer, which conforms to ASSE 1032.
Potable water connections to the equipment must comply with the basic plumbing code of the Building Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the Food and Drug Administration. Verify local plumbing code requirements.

PLUMBING REQUIREMENTS – GENERAL

Incoming water supply must be provided before installation of the refrigeration unit and must comply with local plumbing requirements.
1. A minimum 1" (2.54 cm) water supply line with a manual shut-off valve must be plumbed at least 6 ft (183 cm) from the unit. The incoming water supply pressure must not exceed 70 psi static (4.8 bar) and be no less than 40 psi (2.8 bar) dynamic. If supply water pressure is greater than 70 psi (5 bar), a water regulator will be required.
2. Locate the drain hose, bracket, and two screws provided in the installation kit. Attach the drain hose to the water bath overflow tube located on the bottom of the refrigeration unit.
3. Connect the water manifold supply line, located on the bulkhead panel in the motor compartment to the main water supply. The main water supply shut-off valve must remain in the OFF position. If a water filter is to be installed, connect the line to the outlet fitting of the filter. Plumb according to applicable plumbing codes.
Drain
Connections
3/4" ID
within 6 ft (2 m)
Water
Supply
3/8" ID
EVA Line
Bracket
Bottom
of Unit
Screw
Drain Hose
Drain Hose Connection
4. When a water cooled condenser is installed, a copper supply line (not supplied with unit) must be plumbed to the 3/8" (.965 cm) male flare fitting installed in the water shut-off assembly. The shut-off must be placed in the OFF position. A copper drain line (not supplied) is to be connected to the outlet fitting of the water cooled condenser and routed to the floor drain.

WATER SUPPLY

1. Use the built in fill valve that is already plumbed into the unit.
2. An appropriate floor drain is required within 6 ft (2 m) of the unit.
3. Potable water connections to the equipment must comply with the basic plumbing code of the Building Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the Food and Drug Administration. Verify local plumbing code requirements.
2-8
Part Number 020001552 5/11
Section 2 Installation
PLUMBING CIRCUIT DIAGRAMS — MODEL 11M ROOT BEER Single Tower Plumbing
Installation Kit
(020001441)
020001403
00861302
Carb Tank
Primary
Carb
Pump
Pressurized
Filtered
Water
Supply
Circ
Pump
Part Number 020001552 5/11 2-9
Installation Section 2
Model 11M Root Beer Dual Tower Plumbing
Installation Kit
(020001441)
020001403
00861302
Tee Kit
(020001411)
Carb Tank
Primary
Carb
Pump
Pressurized
Filtered
Water
Supply
Circ
Pump
2-10
Part Number 020001552 5/11
Section 2 Installation
Model 11M Root Beer Three Tower Plumbing
Installation Kit
(020001441)
020001403
00861302
Tee Kit
Tee Kit
(020001411)
(020001411)
Primary
Carb
Pump
Carb Tank
Circ
Pump
Pressurized
Filtered
Water
Supply
Part Number 020001552 5/11 2-11
Installation Section 2

Refrigeration Unit Installation

POSITIONING OF REFRIGERATION UNIT

Before proceeding with installation, verify that all requirements for roof mounted Remote Condenser Units have been satisfied (if applicable). Refer to the instructions on installing the Remote Condenser supplied with the unit.
If unit is to rest on floor, locate four 6" (15.2 cm) adjustable legs (optional). Screw and tighten legs into the bottom of the refrigeration unit. Set unit in desired location and adjust legs until unit is level and sturdy. If unit is to be mounted on stand, position stand and secure unit to stand. If unit is to be installed on a wall mount bracket, install wall mount bracket and position unit on bracket at this time. Fasten unit to bracket with bolts provided.

EQUIPMENT PLACEMENT

NOTE: All Refrigeration Units must be mounted on either 6" legs or optional stand.
1. Move the stand/refrigeration unit to the designated area and position it near the wall at a distance of at least 6" (15.2 cm) for air circulation in air-cooled units, or at a distance required by local code.
2. Level the stand/unit by adjusting the leg levelers provide on the legs or stand.
3. If unit is equipped with optional stand, lift the Refrigeration Unit onto the stand. Position the unit in the center of the stand. Be sure to orientate the drain of the refrigeration unit with the drain access hole of the stand. Secure with 5/8”-11 x 1" bolts supplied in kit, use two (2) bolts diagonally. Schedule the plumber and electrician to connect the water supply and electrical service if you have not already done so (refer to Electrical Requirements and Plumbing Requirements for plumbing and electrical requirements listed in these instructions).
4. Mount any optional equipment at this time. Follow the installation instructions for each kit required.

ELECTRICAL CONNECTIONS

Caution
!
Make sure power supply to unit is turned off.
NOTE: The electrician must refer to the nameplate and wiring schematic on the refrigeration unit for correct electrical requirements. All wiring must comply with all safety codes. Make sure all refrigeration unit power switches are in the OFF position.
1. Remove junction box cover.
2. Connect the circuit electrically. (120VAC 30amp circuit) Refer to chart. Route and connect power supply to leads in the electrical junction box at the top rear of the motor compartment.
NOTE: Be sure to connect ground wire(s) to ground screw located on back panel of junction box.
3. Replace junction box cover.

TOWER INSTALLATION

1. Locate placement of tower on the countertop per restaurant design. Verify counter has been prepared to accept the tower via mounting holes. Refer to tower specs for verification.
2. Mount tower with mounting hardware.
Connect the product lines from the Bag-In-Box or tank. See the plumbing diagrams for the tower setup that pertains to your installation.
Connect the product lines either from the bag-in-box or tank (#1 regular root beer & #2 diet root beer). See the plumbing diagrams for the tower setup that pertains to your installation.

ROUTING INSULATED CONDUIT

1. Before connecting conduit, evaluate store situation and lay out how the conduit will be routed. Be sure to route conduit away from traffic areas, moving parts, and heat.
2. Physically route conduit per evaluated plan. Examine conduit routing and check for neatness, kinks, and interferences.
2-12

CONNECTING INSULATED CONDUIT

NOTE: List what color line was connected to which product so it can be connected correctly at the towers.
1. Route the conduit to the front opening and into the unit. Cut the insulation back from the lines inside the water bath.
Part Number 020001552 5/11
Section 2 Installation
2. Connect the circulating water by connecting one line to the circulating pump outlet line (3/8” barb) and clamp in place. Connect the other line to the bulkhead return fitting located by the agitator motor (3/8” barb) and clamp in place.
3. Connect the conduit lines. Two (2) carbonated water lines and two (2) product output lines (#1 regular rootbeer & #2 diet rootbeer)

CONNECTING SUPPLY LINES

Braided CO2
Gas Line Black Water Supply Line
Color Coded
Syrup Lines
Connect water supply inside unit.
Water Supply & Regulator
Connect CO2 supply inside unit.
CO2 Supply & Gauge
Connecting conduit at the refrigeration unit
1. Connect the product lines either from the bag-in-box or tank (#1 regular rootbeer & #2 diet rootbeer). See the plumbing diagrams for the tower setup that pertains to your installation.
2. Insert the Multipar conduit into the outlet opening on the left hand side of unit. Conduit insulation must extend inside of opening in unit for proper operation of equipment.
Pre-installation of towers is required and the appropriate syrup supply must be connected to the corresponding tower.
Proceed with the Following Tests
Ensure that overflow tube is firmly seated, not leaking.
Check conduit for proper support and insulation.
Cycle carbonator “A” momentarily.
Cycle circulating Motor “A” momentarily.
Cycle compressor momentarily.
Ensure that agitator motor is running.
Ensure that ice bank control probe is securely attached to evaporator coil.
Insulated
Beverage
NOTE: Multipar conduit is color coded for easy identification of lines. When making connections always attach lines requiring the longest connection from the insulation first. The remaining lines can be trimmed as required to make the routing neat and secure.
3. Locate the two blue carbonated water lines of the Multipar conduit. Attach one of the blue lines to the tee fitting located on top of the carbonator tank. Attach the other blue line to John Guest elbow fitting on the stainless coil labeled “8”.
4. Locate the black plain water line of the Multipar conduit. Attach this line to the elbow fitting on the stainless coil labeled “W”.
5. The remaining lines of the Multipar conduit are syrup supply lines and must be attached to the appropriate elbow fittings on stainless steel syrup coils. Note the numbered lines attached to the opposite end of each syrup coil when making connections.
Part Number 020001552 5/11 2-13
Installation Section 2

Connect the drain

Locate the drain hose, bracket and the two (2) screws provided in the installation kit. Attach the drain hose to the water bath overflow tube located on the bottom of the refrigeration unit. Route drain hose to a floor drain (See Below).
Bracket
Bottom of
Screw
Drain Hose

PROPER USE OF JOHN GUEST FITTINGS

NOTE: This unit has a compression type tube connector. The following are step-by-step instructions on how to properly use these fittings. For connecting purposes, all connections are furnished with a 3/8” barb connector.
1. Before inserting tubing into a John Guest fitting, be sure end of tubing is cleanly and squarely cut).
Correct
Unit
Wrong
6. Route the numbered syrup lines to the syrup supply (syrup tanks, Bag-In-Box, or bulk syrup). Do not attach lines to syrup supply at this time. Lines will be attached to syrup supply after system is tested for leaks.
7. Attach the braided CO CO
supply. Use nylon water provided in installation kit.
2
line with swivel nut to a regulated
2
Note: do not turn ON CO2 supply to system at this time.
8. Connect the conduit lines. Two (2) carbonated water lines and two (2) product output lines (#1 regular rootbeer & #2 diet rootbeer).
Wrong
Tubing
Tube Stop
Collet
Collet Cover
Correct
Tubing
Tubing Tubing
Proper Tubing Cut
2. Lubricate O-ring with water. Insert tubing into John Guest fitting. Push tubing firmly through fitting until it rests against the tube stop in the fitting’s main body housing. The tubing is now locked into the John Guest fitting.
3. To release tubing from John Guest fitting, slide collet cover up tube and push in collet. Pull tubing out.
4. Neatly route syrup lines, braided CO
gas line and the
2
black incoming water line through the inlet opening on the left side of the refrigeration unit. Do not allow any of these lines to rest on the agitator motor or any other surface that may become hot.
5. Attach the black water supply line to the water filter or a filtered water supply. A 3/8” Barb fitting and tab clamp, reducer bushing and 3/8” male pipe x 1/2” OD John Guest tube adapter are provided in the installation kit for making this connection.
Collet
Collet Cover
Proper John Guest Fitting Installation
2-14
Part Number 020001552 5/11
Section 2 Installation
Model 11M Connections
Opening for Conduit Supply Lines
John Guest Fittings
Drain Hose
Part Number 020001552 5/11 2-15
Control Switches
Installation Section 2

INSULATING CONNECTIONS

1. Make sure all exposed carbonated water and syrup lines are well insulated on towers to conduit, conduit junctions, refrigeration unit to conduits, and drivethrough junction.
2. To insulate the above, use the leftover conduit sections and tape.
3. Cut the conduit sections to fit snugly over the exposed lines and fittings. A little extra time spent doing a thorough job initially will eliminate a call back in several days to make corrections.
NOTE: Do not inject foam material directly on the connections where the tubing connects to the barb fittings or directly on poly tubing.
Aerosol Foam
Chase
NOTE: You must use a wrench on the body to keep the body from turning while tightening the nut with the second wrench. If the body turns excessively, the piercing seal will be damaged.
4. Use proper wrenches to tighten an additional 1/4 turn (90°). This final 1/4 turn is necessary to ensure the formation of a leak proof joint. Alternately, use a torque wrench to tighten the 1/2” coupling to 40 ft-lbs and 3/8” fitting to 11 ft-lbs.
5. Leak check all your connections. If you detect any leaks, repair and recheck.

Condenser and Pre-charged Lines Installation

Before proceeding with installation, verify that all requirements for roof mounted remote condenser units (if applicable) have been satisfied. If unit has a remote condenser, refer to the instructions on installing the remote condenser supplied with the condensing unit and refer to the section on installation of remote refrigeration line sets.
Important
If you are installing a remote unit, there is a refrigeration king valve located behind the compressor. This valve must be back seated prior to starting the compressor. Failure to do so will short cycle and may damage the compressor.
4. The can of foam is to be used to fill the openings between the conduit insulation and the inside diameter of the floor chases. The purpose is to provide an air tight seal at the floor level to prevent foreign matter from entering the chases. Please read the foam manufacturer’s instructions carefully. We recommend using the adapter with the right angle extension.
5. Insert the adapter into the openings approximately 1" to 2" (2.5 to 5.1 cm) while depressing the adapter.
6. Move the extension around throughout the area where the foam is to be placed. Do not over fill, allow room for expansion. If the chase opening is too deep insert a section of the leftover conduit insulation in the opening prior to using the foam insulation.

Aeroquip Connection

1. Lubricate male half diaphragm and synthetic rubber seal with refrigerant oil.
2. Thread male coupling to its proper female half by hand to ensure proper mating of threads.
3. Use proper wrenches (on coupling body hex and its union nut) and tighten union nut until coupling bodies “bottom”.

REMOTE CONDENSER REQUIREMENTS

APPROVED CONDENSERS
Multiplex Condenser - TS0895-271
MAC Multi-Pass Condensers
1. Installation and maintenance are to be performed only by qualified refrigeration personnel. These technicians must have EPA certification (USA), are familiar with local codes and regulations, and are experienced with this type of remote refrigeration equipment.
2. As a condition of the warranty, the check, test and start­up procedure must be performed by qualified personnel. Because of possible shipping damage, check both the condensing unit and refrigeration unit(s) for refrigerant leaks.
3. If the refrigeration unit is located on a roll out platform, you must coil up to one round between the back of the stand and the wall. This allows pull out of the refrigeration unit for servicing.
4. If the refrigeration unit is located in a stationary location, you must remove excess refrigeration tubing as described below.
2-16
Part Number 020001552 5/11
Section 2 Installation

PRE-CHARGED REFRIGERATION LINE REQUIREMENTS

Important
If you have a MAC Multi-Pass condenser please add three (3) pounds additional charge.
1. Both the discharge and liquid remote condensing lines must be kept to a minimum distance for maximum performance. All Multiplex systems are capacity rated to 100 ft (30.5 m) tubing distance between the compressor and condenser. If you have another brand condenser, please add additional charge for the condenser (example: up to three (3) pounds for a MAC condenser).
2. Any vertical rise 25 ft (7.62 m) or greater must have a manufactured or installed trap (bend), in the discharge refrigeration line from the compressor to the remote condenser. A trap is necessary for every additional 25 ft (7.62 m) vertical rise. When excessive vertical rise exists, this trap allows oil to reach the condenser and return to the compressor.
3. The easiest method to create a trap is to bend the tubing (smoothly, no kinks) into the trap form.
Discharge Line
Condenser Trap
1. Determine a position for installation that will allow access for maintenance and is free from obstruction. Verify hot air discharge from other condensers does not interfere with the inlet of this condenser.
2. Install the four legs to the sides of the condenser using the mounting bolts provided.
3. The General Contractor or Owner must secure two treated lumber 4" x 4" x 36" (or longer). You may then mount the remote condenser to the treated lumber.
4. The General Contractor or Owner must install a 3" pitch pot in the roof. Then seal for weather protection.
3" Pitch
Roof
To the
Condenser
3" (7.6 cm) x 6" (15.2 cm)
Maximum Trap Area
Compressor
3 ft (.9 m) (minimum) of Discharge
Discharge Line Trap Every
25 Vertical ft. (7.62 m)
Line Trap at the Compressor
4. The trap(s) must be of minimum height of 3" (7.6 cm) and a width of 6" (15.2 cm) to minimize oil accumulation. The traps can also be bent out of the refrigeration tubing. Carefully bend the tubing down 12", and then sweep the tubing back up.
5. It is critical that the Multiplex remote condensing line size specifications for the specific model be maintained. The specifications are 1/2” discharge and 3/8” liquid lines.

INSTALLING THE MULTIPLEX REMOTE CONDENSER

The Multiplex remote condensing units have a 208-230 Volt, 50/60 HZ, 1 PH fan motor that includes a permanent split capacitor and internal overload protection. The electrical wires from the refrigeration unit wire to the condenser. The electrical installation must be in accordance with local codes, National Electrical Code and regulations.
5. Locate the pre-charged refrigeration lines shipped with the system. These lines must be a correct length for the building design. Avoiding any kinks, neatly route these lines from the remote condenser to the refrigeration unit. Excess refrigeration tubing must be handled in one of two ways. When coiling the excess tubing, make sure the inlet to the coil is at the top of the coil and the exit is the bottom of the coil. There can be no more than one turn to the coil. If you have more tubing, you must cut out the excess before connecting the ends. When cutting the tubing, you must first evacuate the refrigerant (line sets have a positive refrigerant holding charge of two to three ounces). After shortening and welding the tubing together again, you must vacuum the tubing to 250 microns. Then recharge the tubing with the appropriate refrigerant at 4 ounces per length of tubing.
Caution
!
Excess refrigeration tubing must be properly cared for before being connected to either the remote condenser or the refrigeration unit.
Part Number 020001552 5/11 2-17
Installation Section 2

CONNECTING THE PRE-CHARGED REFRIGERATION LINES

NOTE: Before connecting the pre-charged refrigeration lines, the refrigeration unit must be properly located, leveled, and the water bath filled 1" (2.5 cm) below the installed drain pipe.
1. Attach low side gauge set to service port on each line set to verify positive pressure within the line set.
NOTE: If for any reason the lines are damaged and/or leaking or the lines no longer charged, refer to “How To Re-charge the Line Sets”. If the line set is too long for the application, refer to “How to Shorten the Line Sets” in Section 3.
2. Always make the connections at the condenser first, using the end of the pre-charged lines with the valve ports.
3. Connect the condenser side with the quick connectors (discharge and liquid) up to condenser. Refer to the section titled “Aeroquip Connection” in these instructions.
4. Connect the refrigeration unit side with the quick connects (discharge and liquid). Make sure to provide a discharge trap at back of refrigeration unit, or bend discharge line down 12" and then up smoothly (no kinks) to provide a trap.
5. If a low refrigerant charge is detected, recover and recharge the system adding the unit name plate charge.
6. Repair any damages to the line sets before proceeding.

TESTING CO2 CIRCUIT FOR LEAKS

It is advisable to test the system for leaks before turning ON the water supply to the carbonator and connecting the syrup tanks. If a leak does exist, it will be easier and faster to make any correction.
1. Turn ON the CO2 supply and adjust the primary regulator to 90 psi (6.2 bar).
2. Position the CO2 tank changeover valve handle (if applicable) toward this regulator.
3. Move the air/CO2 changeover valve to the CO2 position (if applicable).
4. Allow the CO2 gas to enter the system.
5. Wait for 2 or 3 minutes before turning OFF the CO2 tank valve. This will allow the lines to expand under pressure.
6. Turn OFF the CO2 tank valve. Observe the pressure on the high pressure gauge (not the 90 psi [6.2 bar]
operating gauge). The needle may drop approximately 1 psi (.09 bar), but must remain constant and not lose pressure. Wait for several minutes.
If pressure continues to fall, this indicates there is a leak in the system which must be corrected.
The greater the leak, the faster the pressure will drop. The smaller the leak, the slower the gauge will drop.
It may be necessary to use a soap solution at all connections to locate a very small leak.
CO2 gas must be present on all valves of the tower(s) NOTE: All soap solution must be rinsed thoroughly from
tubing upon completion of testing.

TESTING SYRUP CIRCUIT (5 GALLON TANKS ONLY)

Before connecting the syrup tanks to the system, the syrup circuits must be tested for leaks with CO2 gas.
1. Connect an empty syrup tank to pre-mix syrup circuits.
2. Connect one of the CO2 gas quick disconnects to this tank. Allow the tank to fill with CO2 gas.
3. Observe the pressure of the primary CO2 tank regulator (not the 90 psi [6.2 bar]).
4. Allow the CO2 tank pressure to remain ON for a few seconds. This will allow the lines to expand to operating conditions.
5. Turn OFF the CO2 tank cylinder.
6. Check all connections from the syrup tank through the connections in the water bath area to all fittings at rear of tower.
7. Check syrup circuitry on the tower by activating the valve.
8. Follow the same procedure for the diet pre-mix beverage circuit.
If no leaks are found in the syrup circuits and the carbonated water circuit, the system is ready to be insulated and placed in operation.
2-18
Part Number 020001552 5/11
Section 2 Installation

Start-Up

1. Turn on main water supply, set incoming regulator to 25 PSI (must be lower than CO2 supply pressure). Once water is supplied to the unit air needs to be purged from the carbonator tank. Do so by lifting press relief valve tab until water comes out of relief valve.
Set Incoming Water to
Regulator to 25 psi
NOTE: Always set the water pressure to 25 psi first and only when no CO2 pressure is present. The CO2 pressure will bleed back and raise the water pressure gauge.
2. Turn on main CO
2 supply, set regulator initially to 26 psi,
can raise incrementally to 30 psi if their is no excessive foaming.
3. Set bag-in-box or syrup tank push pressure CO2 regulator to 35-40 psi.
Main CO2 Supply Set to 26-30 PSI

Preparing Ice Bank

BUILDING AN ICE BANK

1. At this time, fill the unit water bath tank to the top, or within 1/2” (1.3 cm) of the top minimum, of the overflow tube. Use a garden hose or another water supply to do this.
NOTE: A manual fill valve is incorporated into the water circuit to the carbonator tank. This valve can be used to manually add water lost for any reason. Do not leave this valve ON constantly, only use it for filling and topping off. The water bath must be drained, flushed, and refilled every six months.
2. Turn ON the switch labeled “Refrigeration”. Allow unit to run for about 15 minutes before proceeding to step 3.
3. Turn ON the switch labeled “Agitator”.
Note: Turn this switch OFF to perform any operations in the water bath area.
With water bath water temperature of 65°F (18°C), ice must begin to form on the evaporator coils in approximately 2 hours. The unit will build a full ice bank in approximately 4 to 6 hours (depending on ambient water temperature).
Water Bath
Tank
Overflow Tube
Tab Clamp
Drain Tube
4. Before turning on the carbonator or circulator switch, verify that the pump box assembly has been mounted and connected to the unit and the appropriate syrup and water has been supplied.
5. Turn on the main water supply to the booster assembly. Verify the booster is plugged in and that the accumulator tank valve is open. (If the system has an optional “Out­of-Syrup” device, verify that it is unplugged.)
6. Verify the pump is running. Place the valve on the right side of the pump box in the purge position until all air bubbles have passed through the line. Turn the valve back to “dispense”. Plug the Out-of-Syrup device power cord into an appropriate wall outlet at this time (if supplied).
NOTE: Verify that the pump box holding tank is full before proceeding.
7. Turn on the circulator and carbonator switches. The carbonator must run for approximately 1 to 3 minutes and shut off. The circulator must run continuously. Verify that water is returning to the water bath through the return bulk head fitting.
Important
Wait until a thin layer of ice has begun to form on the evaporator before proceeding any further.
8. Go to the tower(s) and brix the valves. Using a syrup separator and volume cup, adjust the flow rate of the carbonated water to two fluid ounces per second. Then, using the separator and a brix cup, adjust the syrup flow rate for a ratio of carbonated water to syrup to 5 to 1.
Part Number 020001552 5/11 2-19
Installation Section 2

Installation Checklist

Check all fittings and conduit attachments for leaks. Check all insulated connections to make sure that they are sealed.
Observe the pump operations for leaks.
Check the water bath for full ice bank.
The stabilized water bath operating temperature must be maintained at 33°F (.6°C) to 35°F (1.7°C).
Close water bath feeder valve completely.
2-20
Part Number 020001552 5/11

Section 3 Operation

Section 3
Operation

Typical System

Conduit (In Wall)
6 Valve Soda Tower
Water Booster
BIB Pumps
8 Valve Soda Tower
Air Compressor
Tank
CO
2
Conduit
Bag-In-Box
(BIB) Syrup
CO
Panel
2
Multiplex
Refrigeration
Unit
Water Filters
BIB Rack
Multiplex Pre-mix Beverage System Operation and Layout
Part Number 020001552 5/11 3-1
Operation Section 3

How the Multiplex Works

The Model 11M is a 1/2 HP refrigeration unit that will provide premix carbonated beverages and chilled carbonated water for up to 12 gal (45 L) of syrup/day or 560 drinks/day (4,000 gal/year) with a 100 ft (30 m) maximum conduit length. This is a remote refrigeration unit that derives its peak draw capacity from the reserve ice bank produced from a capillary tube refrigeration system. This system is controlled to cycle ON and OFF by the operation of the ice bank control. The sensing bulb that controls the ice bank is located on an adjustable bracket in the water bath.

WATER BATH ACCESS

• Has a round hole in the front and back panels with no edge trim to protect lines.
• End panel has two ovals in the rear of the panel with edge trim to help protect conduit lines.

Sequence of Operation

PRE-MIX REFRIGERATION UNIT Ice Bank Is Required
1. Check water bath for full ice bank.
2. The stabilized water bath operating temperature must be maintained at 33°F (0.6°C) to 35°F (1.7°C).
The following is a sequence of operations for the Multiplex Pre-mix Beverage equipment.
1. Once a drink is dispensed, the following will occur:
A. For a Syrup Tank System, the Pre-mix syrup is
manually mixed at the store. Pre-mix beverage is then transferred to a holding tank for supply to the Multiplex system.
B. For a Bag-In-Box System, pre-mix syrup is
drawn from a Bag-In-Box by means of a gas driven syrup pump.
2. The brix pump mixes a 5:1 ratio pre-mixer syrup and water into a 3 gallon holding tank located in the pump box (the 3 gallon tank is vented to atmosphere).
3. The carbonator pump (stainless) pulls the 5:1 pre-mix out of the 3 gallon holding tank and injects it into the pre-mix carbonator tank where the CO pressure is 35 psi (2.4 bar) on the tank.
4. The circulator pump runs continuously and circulates water bath water through the conduit to provide cooling for all drinks.
2

SERVICE ACCESS

• Front panel was solid and did not allow easy access for service.
• Switch panel was mounted flush to end panel.
3-2
Part Number 020001552 5/11
Section 3 Operation

Start-up

PLACING EQUIPMENT IN OPERATION

Before placing equipment in operation, verify that all requirements for roof mounted Remote Condenser Units (if applicable) have been satisfied. Refer to the instructions on installing the Remote Condenser.
1. Fill the refrigeration unit water bath tank with water to within 1/2” (1.27 cm) of the top of the overflow tube.
2. Open the manual water shut-off valve to the water cooled condenser (if applicable).
3. Turn ON the rocker switch labeled “Refrigeration” to begin building an ice bank.
4. Turn ON the rocker switch labeled “Agitator”.
5. Ice will begin to form on the evaporator coils in approximately 2 hours.
6. The refrigeration unit will build an ice bank in approximately 4 to 6 hours.
7. If optional CO installed on the refrigeration unit, refer to the installation instructions for operation and testing the circuits for leaks.
8. The carbonation circuits “A” and “B,” as well as the syrup circuits must be checked for leaks and possible cross circuits before turning ON the water supply to carbonator pumps.
9. Turn on main water supply. Set incoming regulator to 55 psi on the CO2 panel; 25 psi for the Model 11M root beer system’s internal regulator (must be lower than CO2 supply pressure). Once water is supplied to the unit, air needs to be purged from the carbonator tank. Do so by lifting press relief valve tab until water comes out of relief valve.
10. Turn on main CO2 supply. Set regulator initially to 90 – 100 psi. For the Model 11 Root Beer system, set regulator initially to 26 psi; it can be raised incrementally to 30 psi if there is excessive foaming.
11. Set bag-in-box syrup tank push pressure CO2 regulator to 65 – 70 psi. For the Model 11 Root Beer system, set push pressure CO2 regulator to 35 – 40 psi.

PLACING THE CARBONATION SYSTEM IN OPERATION

1. Open the CO2 gas supply valve at CO2 tanks or bulk tank. Adjust the CO2 pressure to 90 psi (6.2 bar).
2. Open relief valve on top of the carbonator tank for 4 seconds to bleed off air in tank.
3. Turn ON the water supply to unit.
/Water Control Panel has been
2
4. Turn ON the switch labeled “Carbonator Pump”. Allow carbonator to run and cycle OFF.
5. Activate all valves until a smooth, continuous flow or carbonated water and non-carbonated water appear at the valves.
6. Turn ON switch labeled “Circulator”.
7. Allow at least 1 hour before proceeding to calibration instructions. You may complete the sanitizing instructions during this period.

Equipment Setup and Close Procedure

EQUIPMENT SETUP PROCEDURE

1. Ensure that all valve nozzles are attached to the valves.
2. Observe pressure of CO 500 psi (34 bar) or more, or bulk CO2 tank of 150 psi or more. Primary regulator set at 90 psi (6 bar) and the secondary regulator set at 35 psi (2.4 bar).
3. Observe the control panel to verify that all pressure gauges are set at correct operating pressures.
4. Check the syrup tanks to make sure a sufficient number of tanks are connected in series to satisfy business volume.
5. Clean syrup inlet and outlet quick disconnects at the same time tanks are replaced. Rinse disconnects in clean potable water.

EQUIPMENT CLOSE PROCEDURE

1. Clean the underside of the dispensing tower around the nozzle area with a clean damp towel.
2. Pour at least 60 oz (1.8 liters) of warm water down the drain openings.
high pressure tank of
2
Part Number 020001552 5/11 3-3
Operation Section 3
THIS PAGE INTENTIONALLY LEFT BLANK
3-4
Part Number 020001552 5/11

Section 4 Maintenance

Section 4
Maintenance

Sanitizing

BEVERAGE SYSTEM CLEANING

Warning
!
Flush sanitizing solution from syrup system. Residual sanitizing solution left in system could
create a health hazard.
Warning
!
When using cleaning fluids or chemicals, rubber gloves and eye protection must be worn.
Sanitize the beverage system at initial start-up as well as regularly scheduled cleaning. The drain pan must be in place under soda valves, to carry away detergent and sanitizing agents that will be flushed through valves.
BAG-IN-BOX SYSTEM SANITATION The procedure below is for the sanitation of one
syrup circuit at a time. Repeat to sanitize additional circuits.
You will need the following items to clean and sanitize the Bag-in-Box (BIB) beverage system:
Three (3) clean buckets
Plastic brush or soft cloth
Mild detergent
Unscented bleach (5% Na CL O) or Commercial sanitizer
Bag-In-Box bag connector
1. Prepare the following in the buckets:
Bucket 1 — warm to hot tap water for rinsing.
Bucket 2 — mild detergent and warm to hot water.
Bucket 3 — mix a solution of unscented bleach (5% Na CL O) or commercial sanitizer and warm to hot water. Mixture should supply 100 PPM available chlorine (1/4 oz. bleach to 1 gallon water).
2. Disconnect the “syrup-line side” of the BIB connector.
Bag side
connector
3. Rinse connector with warm tap water.
4. Connect syrup connector to BIB connector and immerse both into Bucket 1. A “bag-side” connector can be created by cutting the connector from an empty disposable syrup bag.
Part Number 020001552 5/11 4-1
Maintenance Section 4
5. Draw rinse water through system until clean water is dispensed. Most beverage valves allow the syrup side to be manually activated by depressing the syrup pallet.
6. Connect Bucket 2 to system.
7. Draw detergent solution through system until solution is dispensed.
8. Repeat steps 2-7 until all syrup circuits contain detergent solution.
9. Allow detergent solution to remain in the system for 5 minutes.
10. Connect Bucket 3 to system.
11. Draw sanitizing solution through system until solution is dispensed.
12. Repeat step 11 until all syrup circuits contain sanitizer solution.
13. Allow sanitizer solution to remain in system for 15 minutes.
14. Remove nozzles and diffusers from beverage valves.
15. Scrub nozzles, diffusers and all removable valve parts (except electrical parts) with a plastic brush or a soft cloth and the detergent solution.
16. Soak nozzles, diffusers and removable valve parts (except electrical parts) in sanitizer for 15 minutes.
17. Replace nozzles, diffusers and valve parts.
18. Connect Bucket 1 to system.
19. Draw rinse water through system until no presence of sanitizer is detected.
20. Attach syrup connectors to BIBs.
21. Draw syrup through system until only syrup is dispensed.
22. Discard first 2 drinks.

FIGAL BEVERAGE SYSTEM

1. Prepare the following in three clean Figal tanks:
Rinse tank - fill with room temperature tap water.
Detergent tank - mix approved beverage system cleaner with warm water as directed.
Sanitizing tank - mix a solution of unscented bleach (5% Na CL O) or commercial sanitizer and warm to hot water. Mixture should supply 100 PPM available chlorine (1/4 oz. bleach to 1 gallon water).
2. Disconnect all product and water lines from product tanks and remove carbonator.
3. Locate the Figal syrup tank for the circuit to be sanitized. Remove both quick disconnects from the Figal syrup tank. Rinse quick disconnects in tap water.
4. Connect rinse tank to the syrup line. Draw clean rinse water through the valve until syrup is flushed from the system.
5. Connect detergent tank to the syrup line and draw detergent through the valve for two minutes. Then, allow remaining detergent to stay in the system for five minutes.
6. Connect rinse tank to the syrup line. Draw clean rinse water through the valve until detergent is flushed from the system.
7. Remove valve nozzle and diffuser as shown in Daily Cleaning instructions. Using a plastic brush or a soft cloth and warm water, scrub the nozzle, diffuser, bottom of the dispensing valve and cup lever, if applicable.
8. Place removable valve parts (EXCEPT solenoids) in sanitizing solution for 15 minutes.
9. Replace valve diffuser and nozzle on the beverage valve.
10. Connect sanitizer tank to the syrup line and draw sanitizer through the valve for two minutes. Allow sanitizer to remain in the system for a minimum of 15 minutes.
11. Reconnect syrup and carbonated water lines.
12. Draw syrup through the lines to rinse the system. Discard drinks until at least two cups of satisfactory tasting beverage are dispensed through the valve.
4-2
Part Number 020001552 5/11
Section 4 Maintenance

Back-flow Preventer Maintenance

The integral carbonator in this unit is equipped with a back-flow preventer designed to protect the potable water supply from CO2 contamination.
Important
The back-flow preventer must be checked at least once every year to confirm that it is functioning properly.
1. Shut OFF power to unit.
2. Shut OFF potable water supply to unit. Do not shut OFF CO
3. Remove top cover panel of unit and disconnect inlet fitting from back-flow preventer.
NOTE: The carbonator tank is still pressurized.
4. Observe inlet of backflow preventer #1 check for any discharge. If there is no discharge, #1 check is OK. Proceed to step 5. If there is discharge, proceed to step 6.
5. Disconnect and carefully remove #1 check assembly. Avoid losing any internal parts.
6. Observe inlet of #2 check for any discharge. If there is no discharge, #2 check is OK. Proceed to step 7. If there is discharge, proceed to step 5.
7. Shut OFF CO2 supply and relieve pressure from carbonator tank.
8. Remove back-flow preventer and install new backflow preventer. Turn ON CO2 supply and check for leaks.
9. Check water supply strainer upstream of backflow preventer. Clean out and/or replace as required.
10. Reconnect water lines and turn water supply ON.
11. Turn ON power to unit.
supply.
2

Shipping, Storage and Relocation

Caution
!
Before shipping, storing, or relocating this unit, syrup systems must be sanitized. After sanitizing, all liquids (sanitizing solution and water) must be purged from the unit. A freezing environment causes residual sanitizing solution or water remaining inside the unit to freeze, resulting in damage to internal components.
Part Number 020001552 5/11 4-3
Maintenance Section 4
THIS PAGE INTENTIONALLY LEFT BLANK
4-4
Part Number 020001552 5/11

Section 5 Before Calling for Service

Section 5
Before Calling for Service

Checklist

Warning
If a problem arises during operation of your post mix soda refrigeration unit, follow the checklist below before calling service. Routine adjustments and maintenance procedures are not covered by the warranty.
Problem Possible Cause To Correct
Water only dispensing:
No pressure
Syrup and CO
Syrup and plain water only dispensing:
One valve will not dispense anything:
Is there power to the valve?
Beverage dispensed is too sweet:
Is the ratio (brix) of the drink correct?
Beverage is not sweet enough:
Is the ratio (brix) of the drink correct?
Drinks are foaming:
Are system pressures correct?
only dispensing:
2
Carbonator
No pressure
Regulator(s) out of adjustment Check/adjust regulator(s).
Out of CO
Defective regulator(s) Check/repair/replace regulator(s).
CO
line pinched, kinked, or obstructed Check/repair/replace CO2 line.
2
No power Check poser supply. Plug in carbonator
Water supply Make sure water is turned ON.
Defective carbonator Check/repair/replace carbonator pump,
Out of CO
HP regulator out of adjustment Adjust HP regulator to the proper setting.
Defective HP regulator Check/repair/replace HP regulator.
CO
line pinched, kinked, or obstructed Check/repair/replace CO2 line.
2
Broken wire or loose connection Replace/repair wire or connector.
Bad microswitch Replace microswitch.
Flow control out of adjustment Adjust the flow control.
Insufficient soda flow due to low
carbonator pressure
Low CO
Obstruction in the water or soda line Clean out the lines.
Flow control out of adjustment Adjust the flow control.
pressure due to leaks Repair CO2 leaks.
2
Soda flow too high Reset CO
Obstruction in syrup line Clean out the syrup line.
Over carbonation Check CO
Dirty lines/valves Clean sanitize entire system.
Only trained and certified electrical and plumbing technicians must service this unit. All wiring and plumbing must conform to national and local codes.
2
2
!
Install fresh tank.
or reset breaker.
Replace water filter.
Check/clean/replace pump strainer.
Check/clean/repair water check valve.
Check for frozen water line.
Internal Carbonator unit only.
motor, electrode or liquid level control.
Install fresh tank.
Adjust CO
pressure or change the tank.
2
pressure or replace regulator
2
if necessary.
supply. Reset pressure or
2
replace regulator is necessary.
Part Number 020001552 5/11 5-1
Before Calling for Service Section 5
THIS PAGE INTENTIONALLY LEFT BLANK
5-2
Part Number 020001552 5/11
© 2011 Manitowoc Continuing product improvements
may necessitate change of specifications without notice.
Part Number 020001552 5/11