MULTI MEASURING INSTRUMENTS CO.,LTD. MCL-500IRV Instruction Manual

Io/Ior CLAMP LEAKER
MCL-500IRV
INSTRUCTION MANUAL
Thank you very much for selecting our Io/Ior clamp leaker
This model is complex instrument and employs a very reliable
mechanical/electronic design.
Before you use your new instrument, read this instruction
manual completely and familiarize yourself thoroughly with
all functions and keep this instruction manual carefully to
take out whenever you need.
MULTI MEASURING INSTRUMENTS CO.,LTD.
Akihabara Murai Bldg., 7F, 1-26 Kanda Sakuma-cho,
Chiyoda-ku, Tokyo, 101-0025 Japan
TEL : 81-3-3251-7013 FAX : 81-3-3253-4278
Home Page : http://www.multimic.com/
E-mail : multi@multimic.com
SAFETY SUMMARY observe by all means
To use this instrument safely, read this SAFETY SUMMARY carefully and apply the instrument correctly.
The CAUTIONs and WARNINGs which appear on the following pages are stated to prevent the operator & other people from the dangers and their properties from the damages beforehand.
△! WARNING : This symbol indicates the contents "Possibilities of the death or
the serious wound can be supposed" caused from mis-operations.
△! CAUTION : This symbol indicates the contents "Possibilities of the injury or
only the material damage can be supposed" caused from mis- operations.
△! WARNING
POSSIBLE ELECTRICAL SHOCK
This instrument is for the use of low voltage circuit.
Do not make measurements in the circuit more than AC 600V.
Before use, check and confirm the voltage of circuit to be measured.
Apply only the coated cables and do not clamp the bare cables.
POSSIBLE ELECTRICAL SHOCK OR ACCIDENT
Do not handle the instrument in the rain, at humid place, with a drop of water and or with wet hands.
Do not use the instrument if the CT or CT case are damaged and if the battery cover is off, do not operate this instrument.
Do not give a shock to the tip of CT.
Do not disassemble this instrument.
Replace the batteries after took off test probe, etc. from the circuit.
SPECIFICATIONS
1. CURRENT DETECTION ZCT
Inside diameter : Φ40mm Method : Split core type ZCT Withstanding voltage : AC 2200V/1 minute between CT core and grip
2. MEASURING PART
Measuring function : Leakage current (Io), Line current (I),
Resistive leakage current (Ior), AC Voltage (V)
Measuring method : Clamp CT (in case of Ior, based on voltage standard
to be inputted directly or by non-contact voltage
sensor) Measuring range : Io, Ior: 40mA/400mA/4A I: 40mA/400mA/4A/40A/500A V: 500V Input frequency range : 50Hz/60Hz (auto) AC current detection : I,Io,V: True RMS by analog operation
Ior: RMS by synchronous dual integration mode AD conversion : Successive approximation method Display change : By rotary switch Display : LCD, max.9999 reading with annunciator Data hold indication : DH mark on LCD Sampling rate : 2 times/sec. Overrange indication : OL mark on LCD Low battery indication : "B" mark on LCD Auto power off :Approx. 10 minutes after power on Filter/V Input Switch :When pressing this switch once at I, Io current
measurement, “FL” mark on LCD and high
frequencies are cut off. By pressing once again, this
function will be released. In case of Ior measurement,
this switch is ineffective. By pressing this switch at Ior measurement, “Direct
Voltage Input” or “Non-contact Voltage Input” can be
selected. [Ld] mark on the right upper side of display
means direct voltage input and [no] display shows
non-contact voltage input. Ior Switch : In case of measuring Ior current, press this switch
and then, set the circuit condition to be measured by
Ior SELECT switch. Circuit voltage : less than 600V (isolated wire) Operating temperature : 0~40oC < 85%RH (without condensation) Storage temperature : 1060 oC < 70%RH (without condensation) Consumption current : 13mA (approx. 48h for continuous use) Power supply : AAA alkali battery LR03×3 Dimension/Weight : 70(W)×223(H)×34(D)mm, approx. 440g Accessories : Battery LR-03 (installed into the instrument)/3pcs. Carrying Case/1pce., Instruction Manual/1pce. Test Lead for direct voltage input/1set
Non-contact voltage input sensor/1pce.
Accuracy (23
o
C±5 oC, less than 85%RH)
Leakage current (Io), Line current (I), Resistive leakage current (Ior), Voltage (V)
Range
Resolution
Display
Accuracy
I, Io
40mA
0.01mA
0.40mA~39.99mA
±1.0%rdg±10dgt
400mA
0.1mA
40.0mA~399.9mA
±1.0%rdg±10dgt
4A
0.001A
0.4A~3.999A
±1.0%rdg±10dgt
40A
0.01A
4.0A~39.99A
±1.0%rdg±10dgt
500A
0.1A
40.0A~499.9A
±1.0%rdg±3.0%FS
Ior (direct)
40mA
0.01mA
0.40mA~39.99mA
±1.5%rdg±15dgt
400mA
0.1mA
4.0mA~399.9mA
±1.2%rdg±15dgt
4A
0.001A
0.04A~3.999A
±1.2%rdg±15dgt
40mA
0.01mA
0.40mA~3.99mA
±3.0%rdg±20dgt
4.00mA~39.99mA
±1.5%rdg±15dgt
Ior
400mA
0.1mA
4.0mA~39.9mA
±3.0%rdg±20dgt
(non-
40.0mA~399.9mA
±1.5%rdg±15dgt
contact)
4A
0.001A
0.040A~0.399A
±3.0%rdg±20dgt
0.400A~3.999A
±1.5%rdg±15dgt
V
500V
0.1V
10.0V~499.9V
±1.0%rdg±8dgt
The conductor must be located at the center of CT. Input voltage for Ior measurement.
The accuracy of Ior is based on the phase angle with 0°between the voltage
and current at the standard voltage of AC100V in case of single phase. In case of 3P/3W, it is based on the phase angle with 300°between the voltage and current at wiring and the standard voltage of AC200V.
The accuracy of non-contact Ior is based on the inputted voltage by standard
non-contact voltage sensor.
At each range, the value less than 9 count becomes “0” display compulsively
(zero suppression).
The specifications, dimensions, etc. subject to change due to product
improvement, etc.