MULTI MEASURING INSTRUMENTS CO.,LTD. MCL-4000F Instruction Manual

3CT METHOD LEAKAGE CURRENT METER
MCL-4000F
INSTRUCTION MANUAL
Thank you very much for selecting our model MCL-4000F
Leakage Current Meter.
completely and familiarize yourself thoroughly with all
functions.
Keep this instruction manual carefully to take out
whenever you need.
MULTI MEASURING INSTRUMENTS CO.,LTD.
Akihabara Murai Bldg. 7F 1-26, Kanda Sakuma-cho,
Chiyoda-ku, Tokyo, Japan, 101-0025
TEL : +81-3-3251-7013 FAX : +81-3-3253-4278
Home Page : http://www.mutimic.com/
E-mail : multi@multimic.com
SAFETY SUMMARY observe by all means
To use this instrument safely, read this "SAFETY SUMMARY" carefully and apply the instrument correctly.
The CAUTIONs and WARNINGs which appear on the following pages are stated to prevent the operator & other people from the dangers and their properties from the damages beforehand.
WARNING : This symbol indicates the contents "Possibilities of the death or the serious wound can be supposed" caused from mis-operations. CAUTION : This symbol indicates the contents "Possibilities of the injury or
only the material damage can be supposed" caused from mis- operations.
OPERATION ENVIRONMENT
CAUTION
Do not use or storage this instrument under the condition of direct rays of the
sun high temperature & humidity and or condensation, as it may cause the
deformation and or the isolation defect of the instrument.
Do not use this instrument in the environment influenced by acids, alkalis, organic solutions. corrosive gas, etc.
Do not use or storage this instrument where the mechanical vibration can be directly transmitted, as it may cause defect of the instrument.
Do not use this instrument nearby the appliances which generate strong magnetic field and or electric field, as it may cause mis-movement of the instrument.
This instrument does not have the water / dust-proof structure. Do not use this instrument in the environment with a lot of dust and drops of water, as it may cause defect of the instrument.
OPERATION CONDITION & CONNECTION
WARN IN G
POSSIBLE ELECTRICAL SHOC
K
This instrument is for the use of low voltage circuit. Do not make measurements of power lines carrying more than AC 500V. Before use, check and confirm the voltage of circuit to be measured.
Apply only the coated cables and do not clamp bare cables.
POSSIBLE ELECTRICAL SHOCK OR ACCIDENT
Do not handle the instrument in the rain, at humid place, with a drop of water and or with wet hands.
Do not use the instrument if the CT or CT case are damaged and if something is wrong with the CT cables.
If excessive current is applied to the CT, the instrument will be heated and
damaged. Use the CT according to the rating current.
1. GENERAL
3CT/4CT Method Leakage Current Meter (Model MCL-4000F) measures the leakage current and or the line current in low voltage circuit. The ordinary clamp can measure the leakage current by clamping CT to the conductors en bloc but the actual measuring fields where CT can be clamped en bloc are very limited. This model MCL-4000F can measure the leakage current by clamping CTs respectively to each phase of conductors.
2. SPECIFICATIONS
2-1 Current Detection CT Inside Diameter of CT :φ36mm Remanence Current : less than 10mA at 100A of 3P/3W in balance Withstanding Voltage : AC2000V, 1 minute between CT core and outer case Dimension & Weight : 96(W)x120(H)x42(D)mm, 430g
2-2 Measuring Part Measuring Function :Leakage Current (4CT/3CT/2CT & grounding line) and
Line Current Measuring Method : Clamp CT Method Measuring Range : 0~20mA/2000mA (Leakage) 0~800A (Line Current) Range Switch : 3 range manual AC Conversion : Average Rectification AD Conversion : Double Integration Method Sampling Rate : 2 times/second Display : LCD, max. reading 1999 with annunciator Over Range Indication : Blanking of all digit except MSD 1 (except 800A range) Data Hold Function : "DH" sign on the display Low Battery Indication : "B" sign on the display Output Signal for Recorder: DC100mV full scale to each range except 800A (DC40mV to 800A range) Output Impedance : Less than 10KΩ High Frequency Cut : Low Pass Filter (130Hz)
1
2-3 General Specification Limitation of Circuit Voltage : Low Voltage Circuit less than AC500V Withstanding Voltage : AC2000V, 1 minute Operating Temperature : 0~40℃, less than 80%RH ( non-condensing) Storage Temperature : -10~60℃, less than 80%RH ( non-condensing) Power Supply : UM-4 (1.5V) x2 Consumption Current : 2mA (approx. 200h continuous) Dimension & Weight : 130(W)x172(H)x38(D)mm, 380g Standard Accessories : Battery/2, Carrying Case/1, Detection CT/3,
Instruction Manual/1
Option : CT for 3P/4W ( Model No. MCL-4000F-NCT )
2-4 Accuracy
Function Range Resolution
Accuracy(4565Hz)
Leakage Current
200mA 0.1mA
1.0%±5dgt
2000mA 1mA
Line Current 800A 1A
1.0%±5dgt
Output Signal for Recorder
±1.5% F.S.
2
3. NAME OF PART & EXPLANATION
Power On/Off Switch : Switch to supply the power to the instrument LINE/LEAK Switch : “LINE” for line current measurement and
“LEAK” for leakage current measurement
Range Switch : Manual range switch to select 200mA/2000mA FL (Filter) Switch : Switch to cut high frequency component Data Hold Switch : Switch to hold the displayed value LCD Display : Display of measured value, symbol and sign Battery Cover : To replace the battery, remove this part Terminal Stand : For connection of CT, according to wiring method
Wiring Method
Leakage of
Grounding Line : Connect “R” phase CT
and Line Current to “N” phase terminal
3P/3W Leakage Current : Connect each “R”, “S” &
”T” phase CT to the respective terminals
1P/2W Leakage Current : Connect each “R”&“S”
phase CT to the respective terminals
3
1P/3W Leakage Current : Connect each “R”, “S”&”T” phase CT to the respective
terminals
3P/4W Leakage Current : Connect each “R”, “S”, ”T”&”N” phase CT to the
respective terminals
MCL-4000FCT
4. OPERATION PROCEDURE
4-1 Measurement of Line Current
Set power switch "ON".
Connect
"R" phase CT to “N” terminal.
Set LINE/LEAK switch to “LINE”.Clamp CT to one of conductors to be
measured.
Red “R” phase CT
4-2 Measurement of Leakage Current (Grounding Line)
Set power switch "ON".Connect "R" phase CT to “N” terminal.Set LINE/LEAK switch to “LEAK”.Clamp CT to the grounding line and measure leakage current.If necessary, change the measuring range by range switch.Where the circuit contains many high-frequency waves, use filter switch.
CAUTION
It may cause damage to the instrument.
In case of applying the excessive current to CT at the time of line current measurement, it may cause damage to the instrument by heating. Do not apply more than AC 800A to CT.
4
4-3 Measurement of Leakage Current (3P/3W) Connect each "R" phase, “S” phase &
“T” phase CT to the respective terminals.
Set LINE/LEAK switch to “LINE”.Set power switch "ON".Clamp CTs to one of conductors
respectively (make “K” side of CT toward power supply side).
Set LINE/LEAK switch to “LEAK” to
measure the leakage current.
Where the circuit contains many
high-frequency waves, use filter switch. In case of the field where the measured value hardly can be seen, use data hold switch.
After finished the measurement, set LINE/LEAK
switch to “LINE” and remove CTs from the conductors.
4-4 Measurement of Leakage Current (1P/2W) Connect "R" phase CT and “S” phase
CT to the respective terminals.
Set LINE/LEAK switch to “LINE”.Set power switch "ON" and clamp
CTs to the conductors (“R” phase CT to L
1
and “S” phase CT to N).
Measure the leakage current in
the same manner as ⑤~⑦ of 3P/3W.
5
4-5 Measurement of Leakage Current (1P/3W) Connect "R" phase, “S” phase &
“T” phase CT to the respective terminals.
Set LINE/LEAK switch to “LINE”.Set power switch "ON" and clamp
CTs to the conductors (“R” phase CT to L
1,
“S” phase CT to N, “T” phase CT to L2 ) and make “K” side of each CT toward power supply side.
Measure the leakage current in
the same manner as ⑤~⑦ of 3P/3W.
4-6 Measurement of Leakage Current (3P/4W) Connect each "R" phase, “S” phase,
“T” phase & “N” phase CT to the respective terminals.
Set LINE/LEAK switch to “LINE”.
Set power switch "ON" and clamp
CTs to the conductors (“R” phase CT to “R” Line, “S” phase CT to “S” Line, “T” phase CT to “T” Line, “N phase CT to “N” Line) and make “K” side of each CT toward power supply side .
Measure the leakage current in
the same manner as ⑤~⑦ of 3P/3W.
RECORDER Analog DC
Output
CAUTION
1. In case that the phase balance is wrong in 1P/3W, there may be an error in the measurement.
2. Be sure to set LINE/LEAK switch to LINE whenever clamping or removing CTs. In case of clamping or removing CTs leaving LINE/LEAK switch to LEAK at the measurement of 2CT4CT method, it may cause the internal resister burning.
6
4-7 Signal Output for Recorder This instrument has the signal output function for recorder which enables the long period measurement. As to the recorder, use one with the input impedance more than 1MΩ.
4-8 Change of Batteries
Confirm the power switch is “OFF” and remove the screws by + driver and take off the battery cover.
Take out the exhausted batteries and
install new ones, not to mistake the polarity. the battery
cover and tighten the screws.
When th
e batteries are exhausted and the voltage gets lower than operation, “B”
sign appears on LCD.
Replace the batteries to new ones immediately but do not mix the new and old
one and or different kinds.
WARN IN G
POSSIBLE ELECTRICAL SHOCK OR ACCIDENT
Do not use the instrument absolutely, keeping the battery cover off.
CAUTION
In case of not using the instrument for a long period, keep it without batteries
installed. It may cause liquid leakage of batteries and may cause the damage to the instrument.
Do not lose the screw for battery cover and not mistake to put them into the instrument.
7
5. REPAIR SERVICE
When requesting for repair service, please bring the instrument directly to the dealer where you bought. When mailing the instrument, always pack it in its original or equivalent packing materials to avoid any damage during the transportation and also put together with documents showing your name, address, phone number and defect point.
6. WARRANTY
This instrument is sent out from our factory after the sufficient internal inspections but if you find any defect due to the fault in our workmanship or the original parts, please contact the dealer where you bought the instrument.
The warranty period is 12 months from the date of purchase and the instrument shall be repaired at free of charge, provided that we judge the cause of defect is obviously resulted from our responsibility.
GURANTEE REGULATIONS
1. This instrument is warranted for the operation under normal use for 12 months from the date of purchase.
2. This warranty does not cover the following defects: a. Defect caused from the improper use and operation. b. Defect caused from the use, operation and storage beyond the original
specifications, designs and conditions.
c. Defect caused from the renovations or repairs done by someone else than us or our representatives. d. Defect not caused from our responsibilities.
8