5-4 Harmonics Current Measurement
① Set the POWER switch to “ON”.
② Set the range selector switch to a range appropriate to the current to be
measured.
If the current of the circuit is not known, set the switch to highest range and
reduce setting until satisfactory reading is obtained.
When the range is set incorrectly, “OL” mark will be displayed.
③ Clamp the conductor of the circuit under test.
Be sure the clamp jaws are securely closed.
④ Press the SELECT switch once, “HARMONIC NO. XX” is displayed and the tester
is activated to the harmonics mode.
“HARMONIC NO. 1” is the fundamental current.
⑤ Select a harmonic number by pressing UP and DOWN switch.
If you make measurements in a dark place or in a place where it is difficult to see
the readings, disconnect clamp and press UP and DOWN switches to select a
harmonic number.
⑥ Read the displayed value.
⑦ When the displayed value is less than 100 counts in harmonics mode, use “X10”
switch to read the measured value at 10 times.
Please note this value is 10 times of the actual value. In “X10” mode, even if the
least significant digit is fluctuated, this is not abnormal.
Note: In harmonics mode, it is impossible to change the range. If necessary, press to
release the harmonics mode with the SELECT switch once again and set the
range selector switch again to a range appropriate to the current to be
measured. To start the harmonics current measurement, press the SELECT
switch again. If the input current is relatively small, it will take the
reasonable time to get the sable reading.
5-5 Compensation for The Influence by The Harmonic Component of
The Neighboring Frequency
The accuracy of this tester is influenced by the harmonic component of the
neighboring frequency, as the synchronous filter method is used to measure the
harmonic current. For more accurate measurement, the following compensation
calculation is recommended.
Measured harmonic value Compensating
Measured value - of neighboring frequency X percentage (%)
= Compensated value
For example:
If the 5th harmonics = 2.00A (Measured harmonics value)
6th harmonics = 1.00A (Measured harmonics value)
The compensating calculation should be made as below.
5th harmonics = 2.00A - (1.00A x 0.15) = 1.985A
6th harmonics = 1.00A - (2.00A x 0.15) = 0.97A
Compensation percentage (1.5%)
Note: Refer to item 3-3-3 for the value of compensating percentage.
- P7 -