multimatic MD-1000I, MD-2000I, MD-3000I User Manual

UPS
Uninterruptible Power Supply
MD-1000I / MD-2000I / MD-3000I
V 1.0 User Manual
Authentic Manua
l
MD-1000I / MD-2000I / MD-3000I Imprint
Imprint
multimatic Vertriebs GmbH
This document is protected by copyright held by multimatic Vertriebs GmbH, 78667 Villingendorf, Germany.
This document is intended solely for the operator and operator's personnel. Any reproduction, distribution, commercial or competitive use of its contents (text, graphic representations, including figures, drawings, images schematics, etc.), or making of them available to a third party, whether in part or in their en­tirety, without the express written permission of multimatic Vertriebs GmbH is strictly prohibited.
multimatic Vertriebs GmbH
Im Wasen 2 D – 78667 Villingendorf Germany
Phone: + 49 (0) 74 1 / 9292-0 Fax: + 49 (0) 74 1 / 9292-22 E-mail: kundenservice@multimatic-usv.de Internet: www.multimatic-usv.de
Manual Language: English Issued: 10/2012
MD Series 2
MD-1000I / MD-2000I / MD-3000I Imprint
MD Series 3
multimatic Vertriebs GmbH reserves the right to make cosmetic or technical design changes that may serve to improve the system, manufacturing process or the product.
MD-1000I / MD-2000I / MD-3000I Table of Contents
MD Series 4
Table of Contents
1. Introduction ................................................................................................................ 6
1.1 Forward ........................................................................................................................ 6
1.2 Scope of Application .................................................................................................... 7
1.3 Availability of Manual ................................................................................................... 7
1.4 Symbols Used in Manual ............................................................................................. 7
1.5 Information Liability .................................................................................................... 11
1.6 Warranty Terms ......................................................................................................... 11
1.7 Transport and Storage ............................................................................................... 13
1.8 Installation Site........................................................................................................... 14
2. Safety Instructions................................................................................................... 16
2.1 Introduction ................................................................................................................ 16
2.2 Compliant Use............................................................................................................ 16
2.3 Avoiding Personal Injury and Property Damage ........................................................ 17
2.4 Environmental Protection ........................................................................................... 17
2.5 Power Connection...................................................................................................... 18
2.6 Operation ................................................................................................................... 19
2.7 Handling Batteries...................................................................................................... 19
2.8 Maintenance, Service and Malfunction ...................................................................... 20
3. Explanation of USB Function.................................................................................. 22
3.1 Front Panel................................................................................................................. 24
3.2 Rear Panel ................................................................................................................. 29
3.3 Installation Changes................................................................................................... 40
3.4 Operational Modes and Voltage Settings................................................................... 46
4. Storage and Unpacking ........................................................................................... 50
4.1 UPS Storage .............................................................................................................. 50
4.2 Unpacking the UPS.................................................................................................... 50
5. System Function ...................................................................................................... 52
5.1 UPS Schematic Diagram ........................................................................................... 52
5.2 UPS Operating Mode - Normal .................................................................................. 54
5.3 Overload..................................................................................................................... 56
5.4 Inverter ....................................................................................................................... 57
5.5 Inverter - Excessive Internal Temperature ................................................................. 58
6. UPS Installation and Hook-Up ................................................................................ 60
6.1 UPS Connection......................................................................................................... 60
6.2 UPS Communication Interfaces ................................................................................. 62
6.3 Equipment Connection Sequence.............................................................................. 63
MD-1000I / MD-2000I / MD-3000I Table of Contents
MD Series 5
7.
System Operation and Display ................................................................................64
7.1 UPS Modes and Display Messages ...........................................................................64
7.2 USP User Instructions.................................................................................................64
7.3 Replacing Batteries.....................................................................................................72
8. Trouble Shooting Guide ...........................................................................................77
9. Software.....................................................................................................................81
10. Maintenance and Service .........................................................................................82
10.1Determining the Back-up Capacity .............................................................................82
10.2Service Log .................................................................................................................84
10.3Service Hotline............................................................................................................85
10.4Maintenance and Service Contracts...........................................................................85
11. Technical Information...............................................................................................86
11.1Included Components and Accessories .....................................................................89
11.2Wear Parts ..................................................................................................................91
12. Declaration of Conformity........................................................................................92
MD-1000I / MD-2000I / MD-3000I Introduction
1. Introduction
1.1 Forward
Dear User,
You will find this manual to be of great assistance. For this reason, we urge you to read it carefully before operating the unit. It will provide you with information and instructions necessary to effectively and responsibly operate the uninterruptible power supply. It also offers advice on what to do in the event of malfunction. In addition, you'll find transport, storage and installation information here.
Guidelines presented in this document solely concern the supply of uninter­rupted power. The installation and personnel performing the installation are subject to applicable national and local electrical codes and regulations.
Modification to contents of this manual may be necessary from time to time to accommodate technical changes. We have gone to great lengths to ensure the contents' accuracy and ease of comprehension. However, we would be grateful if you notify us of any errors or inaccuracies you find.
We accept no liability for errors or consequential damages resulting from those errors.
The uninterruptible power supply unit has been designed and built to protect sensitive electrical equipment against failure caused by poor power quality or power failure.
Read this manual carefully and completely, while paying careful attention to the safety guidelines!
Your company's technical support or a member of our team will be glad to as­sist you with your questions concerning this unit.
Sincerely, multimatic Vertriebs GmbH
MD Series 6
MD-1000I / MD-2000I / MD-3000I Introduction
MD Series 7
1.2 Scope of Application
al
al
The explanations found in this manual apply exclusively for the
uninterruptible power supply
as described in the Technical Information section as an entire system and for modules, subsystems and individual parts designed and built by multimatic Vertriebs GmbH.
( 11. Technical Information)
1.3 Availability of Manu
Make sure this manual is always in proximity to the UPS to ensure it is there when and where needed.
1.4 Symbols Used in Manu
The abbreviation UPS appearing in this manual stands for uninterruptible power supply.
Read this document carefully to become familiar with the product before using it.
Keep the manual handy at all times, so you can reference it when needed.
Pass the manual on to future users of the product.
1.4.1 Warning levels
Text in which "DANGER!" appears warns you of dangers. If you neglect preventative measures, serious (irreversible), life-threatening injuries or death will occur!
MD-1000I / MD-2000I / MD-3000I Introduction
Text in which "WARNING!" appears warns you of dangers. If you neglect preventative measures, serious (irreversible), life-threatening injuries or death may occur!
Text in which "CAUTION!" appears warns you of dangers. If you neglect precautionary measures, slight or moderate injuries may occur!
Text in which "ATTENTION!" appears contains very important information about situations in which neglecting preventative measures can result in damage to the product, its function or objects in its vicinity.
This symbol indicates information that is especially useful or important.
MD Series 8
MD-1000I / MD-2000I / MD-3000I Introduction
1.4.2 Warning pictograms
1.4.2.1 Hazard vicinity warning
Generally hazardous area!
1.4.2.2 Specific warnings
Hazardous voltage!
Battery hazard!
1.4.3 Mandatory action symbols
Take action as stated in information and instructions provided in docu­ments and by pictograms.
Disconnect via all-pole disconnect prior to beginning work!
MD Series 9
MD-1000I / MD-2000I / MD-3000I Introduction
1.4.4 General symbols
This symbol indicates actions that you are required to perform.
- This hyphen introduces items in a list.
This arrow indicates a cross reference.
To keep things easily understandable, you'll find cross references directing you to other chapters on occasion. Example: UM, 2 Safety Instructions This tells you to refer to User Manual,
Chapter 2 in the manual. If the cross reference refers to a page, figure or item number, it will appear at the end of the cross reference. Example: Fig. 4 - 4, Item 1 This directs you to Chapter 4 in the User Manual, Figure 4, Item 1.
(3) Numbers in parentheses refer to items found in figures.
Must be recycled
Indicates components or assemblies that are subject to electronic waste dis­posal ordinances and regulations.
Indicates assemblies or parts that you are prohibited from disposing of as or in regular household rubbish.
Prerequisite or something you must do:
The DC disconnect switch is switched to OFF.
MD Series 10
MD-1000I / MD-2000I / MD-3000I Introduction
1.5 Information Liability
This manual must be read by everyone, including
– users
– maintenance and cleaning personnel
– those responsible for disposal and recycling
of the device. They must understand and follow every instruction and all guide­lines provided therein.
multimatic Vertriebs GmbH accepts no liability for damages caused by uninstructed or insufficiently instructed personnel!
1.6 Warranty Terms
Your receipt is your proof for your initial purchase. Make sure you keep in a safe place, because you will require it for warranty claims. In the event you transfer the product to the possession of another user, the warranty shall re­main in effect. The new user requires the receipt and this explanation.
We guarantee the product you have purchased to be in good functioning order and technically as described in the enclosed documents when it left our prem­ises.
The warranty period for custom-built or -configured units complies with the leg­islatively-regulated minimum.
This warranty does not apply in the following instances:
Defects caused by shipping, accident, natural catastrophes, abuse, vandalism, improper use, inappropriate maintenance or improper repair by an unqualified third party.
Modifications performed by unauthorized persons, incorrect operation,
other devices or equipment, improper installation or any modifications not authorized by multimatic Vertriebs GmbH
Improper use, for example plugging the device into unsuitable sources of
electrical power, attempts to overload the UPS, use in an unsuitable envi­ronment.
Disregard of the instructions in provided documents.
MD Series 11
MD-1000I / MD-2000I / MD-3000I Introduction
Incompatibility of product due to technical changes or regulations that oc-
cur after purchase.
Incompatibility or malfunction caused by product components not installed
by multimatic Vertriebs GmbH.
Effects caused by normal product wear and tear.
Defects caused by external apparatuses or devices.
Warranty periods for parts repaired or replaced under the unit's original war­ranty expire when the unit's warranty expires.
Units returned without accessories will be replaced without accessories. To be accepted, products returned must be shipped in their original packages.
In general, the warranty does not cover shipping costs.
The customer is responsible for repair and replacement costs and multimatic Vertriebs GmbH is not liable for damages, whether direct, accidental, unique or consequential damage, even if caused by negligence or other acts.
multimatic Vertriebs GmbH gives neither explicit nor implicit guarantees on this product, its quality, performance, saleability or suitability for a specific pur­pose. In some countries, the exclusion of implicit guarantees is not permitted by law. In such instances, the validity of all express and implicit guarantees is limited to the warranty period. When the warranty expires, all guarantees lose their validity. In some countries, law does not permit a limit of the period of va­lidity of implicit guarantees, so that the limitation described above does not take effect.
MD Series 12
MD-1000I / MD-2000I / MD-3000I Introduction
MD Series 13
1.6.1 Liability limitations
Claims for compensation are excluded, unless based on wrongful intent or gross negligence on the part of multimatic Vertriebs GmbH or its employees. Liability as per product liability laws remains unaffected. Under no circum­stances are we liable for:
Third-party claims filed against you the purchaser for losses or damages.
Loss of or damages to your records or data or the costs for the recovery of
these data.
Economic damages (including profit or savings losses) or other related
damages, even if we were informed in advance of the possible occurrence of such damages.
Under no circumstances, is multimatic Vertriebs GmbH liable for any acci­dental, indirect, unique, consequential damages or any other damages (without exception, whether loss of profit, business activity or business, business re­cords, data or information or any other losses) that occur through the use of this product or in any conjunction with the product, whether due to a contract, damage claim, negligence, strict liability of claims, even if multimatic Ver- triebs GmbH was informed in advance of the possibility of such an occur­rence. This exclusion also includes any liability that could occur due to third­party claims on the original purchaser.
In some countries, law does not permit the limitation of accompanying or re­lated damages or consequential damages, so that the explanation above does not take effect.
1.7 Transport and Storage
The UPS appliance shall be packed in its original packaging when transported to its site of operation, when returned to the seller or in the event it is moved to another site of operation.
The original package offers no protection in the event the package falls or is dropped. For this reason, products that have fallen must be examined by mul- timatic Vertriebs GmbH prior to operation.
Do not store or transport this device with its top upside down.
MD-1000I / MD-2000I / MD-3000I Introduction
1.8 Installation Site
Do not install in an area where flammable vapours are present, for exam­ple, petrol/gasoline, storerooms, areas in which combustion-driven mo­tors operate, etc.
The UPS appliance is designed for operation in ventilated rooms with ambient temperatures of 0 to 40° C.
If the UPS is subject to significant and quick temperature changes, condensa­tion may develop. Should this be the case, it is necessary to give the unit at least 2 hours to acclimate.
Never place, install or operate the UPS in a damp environment. Keep fluids at a suitable distance away from the unit.
Do not place, install or operate the UPS near a source of heat.
You may install the UPS in either a horizontal or a vertical position. Vertical in­stallation requires you use the feet; horizontal requires the use of a 19-inch rack.
Install and maintain a minimum distance of 10 cm from the appliance's back and front to other objects to ensure the UPS has enough air circulation to pre­vent high temperatures. Make sure the air vents are free of blockage through paper or other materials that might be stuck in the intake openings.
MD Series 14
MD-1000I / MD-2000I / MD-3000I Introduction
MD Series 15
MD-1000I / MD-2000I / MD-3000I Safety Instructions
2. Safety Instructions
2.1 Introduction
The UPS is designed and built in accordance with technical guidelines and regulations for uninterruptible power supply equipment. It and its components, modules and assemblies individually and as an entire sys­tem meet the current safety code requirements and comply with the EU 2006/42/EG Machinery Directive.
The UPS is operationally safe, provided the user uses this appliance pur­suant to said codes and regulations and the safety instructions, guide­lines and precautions stated in this user manual.
2.2 Compliant Use
Use the UPS and its components solely for their intended purpose, which is the temporary supply of electrical power to electrical devices (230 V AC) while, together, not exceeding the total nominal capacity.
Any other use or use that exceeds said use is not in accordance with the intended purpose and may lead to personal injury or equipment damage!
Improper uses
The UPS is not intended for use:
in explosive,
dust-laden,
radioactively or
biologically or chemically contaminated atmospheres.
The
UPS is Class A equipment. This product may produce electromag­netic interference. If this is the case in living areas, the user may be re­quired to implement appropriate corrective measures.
MD Series 16
MD-1000I / MD-2000I / MD-3000I Safety Instructions
MD Series 17
2.3 Avoiding Personal Injury and Property Damage
n
Read the user manual carefully, making sure you understand the product.
Pay careful attention to the information and instructions concerning the installa­tion, pre-operation and initial operation of the unit.
Operate this product only properly and in accordance with the intended use and the technical specifications provided.
Perform only the service and maintenance work that is described in the pro­vided documents. Follow the stipulated actions and steps as described. Use only original parts obtained from multimatic Vertriebs GmbH.
2.4 Environmental Protectio
When your product has reached the end of its service life, send it back to mul­timatic Vertriebs GmbH and we'll dispose of it compliant with environmental
protection laws.
MD-1000I / MD-2000I / MD-3000I Safety Instructions
2.5 Power Connection
Use only an outlet socket with earthed/grounding contact or, if using a terminal block, connect protective conductor. Under no circumstances, operate the UPS without an earth/ground connection.
The socket you use must be readily accessible and close to the UPS unit. If using a permanent connection, keep the cable length as short as pos­sible.
If operating with a generator, make sure not to reverse the connection's polarity.
Use only a VDE- and CE-approved power cable between the socket and the UPS. If wiring the UPS via permanent/direct connection, use a cable with suitable approval rating.
Use only a VDE- and CE-approved power cable to connect the protected equipment to the UPS. If wiring protected equipment via permanent/direct connection, use a cable with suitable approval rating.
Make sure the circuit breaker to protect the connected equipment always comes right before the connected/protected equipment; never rely on a central fuse placed in front of the UPS.
Do not use the UPS to power household appliances and power tools, such as portable heaters, vacuum cleaners, drills, hair dryers, toasters, etc.
Never connect to the UPS unit electrical equipment that could overtax it (laser printer, etc.).
Make sure the total current amperage of all the equipment connected to the UPS does not exceed 3.5 mA.
Keep power cables as short as possible and make sure they are installed code-compliant, including installation that avoids stumbling, exposure to heavy weight or sharp objects, etc.
Use only a VDE- and CE-approved power cable with suitable gauge to connect the protected equipment to the UPS. Make sure the circuit breaker to protect the connected equipment always comes right before the connected/protected equipment; never rely on a central fuse placed in front of the UPS. Never con­nect to the UPS unit electrical equipment that could overtax it (monitor inrush current).
MD Series 18
MD-1000I / MD-2000I / MD-3000I Safety Instructions
2.6 Operation
Before connecting equipment to the UPS outlet, you must perform the initial configuration. Very important here is the output voltage going to the connected equipment.
The UPS device contains an energy storage facility (battery), which means the outlet can carry electricity even if the USP is not connected to a power supply.
To switch the UPS off completely, first, hold the OFF button for longer than 3 seconds and wait for the UPS to shut down. Next, disconnect the power supply connector from the device. Make sure no liquids or foreign materials gain ac­cess to the UPS' interior. To protect the UPS, it is best to avoid lasting output loads greater than 80%. The output load shown on the display is only a guide. To determine the actual output load, extra measurements with a suitable de­vice are necessary.
2.7 Handling Batteries
Attention! Danger of shock and burns
Batteries can produce electrical shock and short circuit currents that are capable of burning tissue.
Keep unqualified persons away from batteries.
Do not place batteries in or around sources of heat, e.g. fire, because they may explode!
Do not open or destroy batteries. The electrolyte is extremely hazardous for persons and the environment (danger of burns to eyes and skin; poi­son).
MD Series 19
MD-1000I / MD-2000I / MD-3000I Safety Instructions
MD Series 20
Defective batteries must be disposed of compliant with environmental
protection regulations.
Under no circumstances ever dispose of batteries with regular household garbage.
Follow local disposal regulations.
2.8 Maintenance, Service and Malfunction
Attention! Danger of shock
Even after, you have turned off the power switch or broken the circuit to the battery, UPS components may still carry high voltage.
Only qualified persons with the required knowledge of precautionary measures are to perform and supervise work on batteries.
Keep unqualified persons away from batteries.
The following precautionary measures are necessary when working on UPS devices and batteries:
Remove wristwatches, rings and other metal objects
Use only insulated tools that are compliant with electrical regulations
and guidelines
Wear protective glasses/goggles, gloves, face protection
Do not dismantle the UPS
MD-1000I / MD-2000I / MD-3000I Safety Instructions
MD Series 21
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3. Explanation of USB Function
This manual will provide you with fundamental information about single-phase online UPS systems, specifically how they function, use of the various func­tions and what you are to do in the event of malfunction. In addition, this man­ual contains information about transport, storage, handling and installation of UPS systems.
Guidelines presented in this document solely concern UPS requirements. The installation and personnel performing the installation are subject to applicable national and local electrical codes and regulations. Modification to the contents of this manual may be necessary from time to time to accommodate technical changes. We have gone to great lengths to ensure the contents' accuracy and ease of comprehension. However, we would be grateful if you notify us of any errors or inaccuracies you find.
We accept no liability for errors in this user manual or consequential damages resulting from those errors.
The UPS system (uninterruptible power supply) has been designed and built to protect sensitive electrical equipment, such as computers, workstations, elec­tronic money handling machines, important business devices, telecommunica­tion systems, process controls, etc., against failure caused by poor power qual­ity or power failure. Such sensitive systems require comprehensive protection against electrical failure. Often, the failure may be caused by events outside the system (e.g. thunderstorm, breakdown of operations) or interference caused by nearby equipment (such as motors, air conditioners, machinery, welding, etc.).
Power supply malfunctions are typically:
Quick and slow line voltage peaks, fluctuation
Power failures
Fast or slow frequency peaks and fluctuations
Power line interference or transients
The UPS s
ystem monitors the abovementioned power supply parameters and protects the connected devices via suitable actions (e.g. switch over in the event of power surges, over voltage or drops).
The UPS' mode of installation modifies easily from upright, using the provided legs, to horizontal in a 19" rack and vice versa.
You'll find instructions for changing the installation mode in the chapter dedi­cated to this subject ( 3.3 Changing Installation Mode).
MD Series 22
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
The advanced in
sulated-gate bipolar transistor (IGBT) technology and indus­trial quality design ensure the UPS will operate efficiently and dependably, even under tough conditions.
A powerful CPU integrates all the power stages, control and communication functions required to provide maximum protection and UPS function, including monitoring of the energy saving management, remote control and self­diagnostics. The unit's cleverly designed CPU communication system permits remote computer control with full functionality from any computer environment via standard RS-232 port.
The UPS' wide input voltage tolerance (120V~288V) permits under or over voltage correction without use of the battery, helping to extend the battery's operating life.
The cold start function ensures the UPS will start even in the event of a power outage.
A battery management system monitors the battery's charge to determine when the battery draw will cease, another feature that prolongs the battery's life span.
Advanced input voltage control minimizes the reactive power factor and in­creases efficacy. The unit's active power factor correction (PFC) delivers a power factor (PF) of greater than 0.99, which translates into superb energy ef­ficiency.
The adjustable bypass input voltage tolerance (low/high) prevents the unit from switching to the bypass mode in the event of low or over voltage.
Large choices of output voltages (200/208/220/230/240) permit the use of dif­ferent voltage systems.
This UPS device was designed and built to comply with international electro­magnetic standards.
MD Series 23
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.1 Front Panel
You'll find all the display and control elements you need for normal use on the UPS' front panel.
1 Status LEDs
2 LCD display
3 Buttons
Fig. 3-1 - 1 MD-1000I / MD-2000I / MD-3000I front view
MD Series 24
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.1.1 LCD display (optional)
1 LCD display
2 LED input voltage
3 Programmable output 1 LED
4 Programmable output 2 LED
5 Bypass LED
6 UPS system fault LED
7 Select
8 Scroll up
9 Scroll down
10 Other functions
11 UPS off
12 UPS on; mute alarm
Fig 3-1 - 2 Front panel interfaces
MD Series 25
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.1.2 Keypad
UPS On / Alarm mute (12) functions:
Turns UPS on.
Deactivates audible alarm.
UPS off (11) functions:
Turns UPS off.
Other functions (10) functions:
Buzzer on/off
Battery test
Bypass power
Output frequency synchronization window
Inverter output voltage
UPS operating mode
Output voltage fine adjustment
Scroll down (9) functions:
Scrolls down menu by pages
Scroll to previous page / Change UPS settings (8) functions:
Scrolls up menu by pages
Changes UPS settings
Select (7) functions:
Verifies selection
MD Series 26
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
Manual bypass
To activate the manual bypass, proceed as follows:
Press buttons 12 and 8 simultaneously for about 3 seconds, to change from normal operation to bypass mode.
The LED bypass indicator will blink constantly and an audible signal will sound.
Press buttons 12 and 8 simultaneously for about 3 seconds, to change
from bypass mode to normal operation.
MD Series 27
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.1.3 LCD display panel symbols
Item Symbol Description
1 Power supply (utility) or bypass source
2 Battery low
3 Battery problem
4 Output overload
5 Local wire problem
6 UPS shut off
7 Abnormal UPS lock
8 UPS flow
9 4-digit display
10 Indicates which item to be measured
22 Weak or dead battery
23 Output short circuit
24 Inverter overload
25 UPS overheated
26 UPS output overload
27 Other faults
MD Series 28
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.2 Rear Panel
123546
789
10
3.2.1 MD-1000I
1 USB port
2 Battery pack connector
3 Power input
4 Communication interface
5 Two programmable outputs
6 UPS output
7 Input circuit breaker
8 Fan
9 Emergency power off (EPO) port
10 RS-232 port
Fig. 3-2 - 3 MD-1000I rear panel
MD Series 29
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
When the USP output and power input sockets are in connected states, they are capable of transmitting power.
Even if disconnected, dangerous electrical charges may be present in­side the unit that could discharge hazardous high voltage at the connec­tions.
As soon as the unit is connected to a source of power, the charger becomes active. That means without turning the UPS on, the battery charges.
MD Series 30
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
12345
666677889
10
3.2.2 MD-2000I
1 USB port
2 Battery pack connector
3 Input circuit breaker
4 Power input
5 Communication interface
6 UPS output (non-programmable)
7 UPS output (programmable)
8 Fan
9 Emergency power off (EPO) port
10 RS-232 port
Fig. 3-2 - 4 MD-2000I rear panel
MD Series 31
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
When the USP output and power input sockets are in connected states, they are capable of transmitting power.
Even if disconnected, dangerous electrical charges may be present in­side the unit that could discharge hazardous high voltage at the connec­tions.
As soon as the unit is connected to a source of power, the charger becomes active. That means without turning the UPS on, the battery charges.
MD Series 32
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
12 2 3455678
999101011
12
3.2.3 MD-3000I
1 USB port
2 Fan
3 Battery pack connector
4 Circuit breaker for two programmable outputs
5 Circuit breaker for two non-programmable outputs
6 Power input circuit breaker
7 Power input
8 Communication interface
9 UPS output (non-programmable)
10 UPS output (programmable)
11 Emergency power off (EPO) port
12 RS-232 port
Fig. 3-2 - 5 MD-3000I rear panel
MD Series 33
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
When the USP output and power input sockets are in connected states, they are capable of transmitting power.
Even if disconnected, dangerous electrical charges may be present in­side the unit that could discharge hazardous high voltage at the connec­tions.
As soon as the unit is connected to a source of power, the charger becomes active. That means without turning the UPS on, the battery charges.
MD Series 34
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.2.4 UPS output
IEC 10 A socket for equipment connection
The protective earth conductor must be connected!
Make sure you observe the input voltage requirements that appear on the identification label and in the technical information provided in this man­ual.
3.2.5 Emergency power off (EPO) port
The emergency power off port permits the connected equipment to shut down in emergencies. This function is available for use in the event of connected equipment emergency.
Make sure to isolate this electrical circuit from hazardous electrical cir­cuits.
Do not connect the EPO to electrical circuits that connect directly to the power mains.
Make sure power mains lines are heavily insulated.
The EPO switch must have snap-action and at least 24 V DC / 20 mA capacity and install without connection to another electrical circuit.
To function properly, the EPO signal must remain active for a minimum of 20 ms.
MD Series 35
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.2.6 Relay card (potential-free)
Fig. 3-2 - 6 Relay card (potential-free)
Pin configuration:
1 2 3 4 4 5 6 7 8 9 10
1 UPS in bypass mode (Bypass) 2 Normal power source (normal: closed contact) 3 Normal power source (normal: open contact) 4 Inverter on 5 Battery low 6 Battery bad or abnormal 7 UPS alarm 8 General 9 UPS positive (+) signal 10 UPS negative (-) signal
MD Series 36
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
The shutdown function activates after +6~+25VDC between PIN 9 and Pin 10 is applied for 5 seconds. Each relay contact has a load capacity of 40VDC/25mA. Installation: random insert. Flexible output for N.C. (normal closed) or N.O. (normal open) Sets via the repositioning of Jumper Pin1-2 or Pin2-3 from JP1-5. The shutdown function activates within a minute after the flow of current ceases when Pin1-2 of both jumpers CN1 and CN6 are connected. The shut­down function activates only from C3 via PIN9-10 when Pin2-3 of both CN1 and CN6 are closed.
3.2.7 SNMP cards (Web card)
Fig. 3-2 - 7 SNMP cards (Web card)
For information about installing SNMP cards, please see the SNMP card man­ual enclosed with the UPS documents.
3.2.8 USB port
The UPS port allows you to connect the UPS to a PC.
MD Series 37
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.2.9 Fan
Fan cools UPS.
3.2.10 Power input
IEC power plug
MD-1000/2000 - C13/10A MD-3000 - C19/16A
The unit connects to the power supply by means of the enclosed power cable with Schuko plug.
The protective earth conductor must be connected!
Make sure you observe the input voltage requirements that appear on the identification label and in the technical information provided in this man­ual.
MD Series 38
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.2.11 RS-232 port
PIN 3: RS-232 Rx
PIN2: RS-232Tx
PIN5: Earth/Ground
Fig. 3-2 - 8 RS-232 ports
MD Series 39
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.3 Installation Changes
The UPS features placement versatility to accommodate specific needs:
Vertical standing on feet
Horizontal in 19" rack
Depending on your chosen means of installation, you will need to turn the LCD display (tower) or mount brackets to the unit (19" rack).
3.3.1 Tower
Fig. 3-3 - 1 Tower configuration
Proceed as described in the following:
Turn the display, so you can read it when the unit is standing.
Install the feet.
MD Series 40
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
Make sure the floor under the UPS is even and level. The floor must have sufficient weight-bearing capacity. For specific weight-bearing requirements, you'll find the UPS weight in the technical information ( Chapter 11 Technical Information)
Turning the display:
Fig. 3-3 - 2 Turning of display
The display is capable of turning 90°.
MD Series 41
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
3.3.2 Rack installation
Fig. 3-3 - 3 Rack installation
Proceed as described in the following:
Turn the display, so you can read it when the unit is in the rack.
Mount the brackets to the housing.
Insert the UPS into its compartment in the 19"-rack.
MD Series 42
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
Fig. 3-3 - 4 Rack brackets
Mount the brackets to both sides of the housing.
MD Series 43
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
Fig. 3-3 - 5 19"-rack
Insert the UPS into the 19"-rack.
MD Series 44
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
1 Screws
Fig. 3-3 - 6 Fixing the UPS in the 19"-rack
Use the screws (1) to fasten the UPS to the rack.
Upon completion, you may connect the UPS and put it into operation.
MD Series 45
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
MD Series 46
3.4 Operational Modes and Voltage Settings
Download the UPS Setting Tool software and open the software, so that you have the window shown below open.
System configuration settings
1. Selecting power supply voltage: Select the input voltage 230V.
2. Next, select the output voltage from: 200V/208V/220V/230V/240V.
3. UPS mode: Select normal mode /CF50*/CF60*.
4. Output voltage fine tuning: output voltage 0 - ±3%
5. Bypass voltage: low or high
Low High
220V-system 184V260V 194V~260V
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
6. Syn-Frequency Window: Select 3Hz/1Hz inverter frequency
range
7. Com. port: Select the PC’s communication port
8. Click Write to confirm the configuration settings. The UPS sounds two audi-
ble tones to indicate you have successfully made the settings.
9. After you have completed the configuration, shut the UPS down to make
sure the system saves all the settings in the EEPROM. To activate the new setting, restart the UPS.
NOTE: *
CF50/CF60 = Frequency inverter mode 50 to 60Hz or vice versa.
MD Series 47
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
Programmable output settings
To meet the power needs of less critical equipment, the UPS comes with 2 programmable outputs. You can deactivate these outputs to shut down less critical equipment while the UPS is running on the battery or to reduce the load in order to ensure the critical equipment will continue to receive power.
Click Programmable Outlet Scheme to make the following settings:
MD Series 48
MD-1000I / MD-2000I / MD-3000I Explanation of USB Function
MD Series 49
1. "Outlet turn on, after UPS on" allows you to set the time delay. Set the delay between the time when the UPS turns on and the time when the output automatically activates. Select "0" if you want the outlet to activate immedi­ately when the UPS powers up.
2. "Outlet turn off, after AC failure" permits you to make setting for power fail­ure events. Select this option to shut the output off automatically within the predetermined time frame in the event of a power outage, in order to shut down less critical equipment to allow the more critical equipment more bat­tery time for back-up, etc.
3. "Outlet turn on after AC recovery." Use this option to set the time when the output will automatically reactivate after regular power has been restored.
4. "Outlet turn off when UPS overload" Select this option to turn off the outlet automatically when the battery has a specified remaining capacity, which you specify here. This permits you to shut down less critical equipment in order to allow the more critical equipment more battery time for back-up, etc.
5. "Outlet turn off, when UPS overload": This item allows you to specify that the outlet automatically switches off (bypass mode) during an overload event, in order to provide more critical equipment with power as described in the following: Continuously via bypass, or via return to normal operation, if the shutdown of less critical equipment has successfully remedied the over­loaded status.
6. To perform further configurations, you need to click Setting. Consider new settings successfully completed when the UPS emits two audio signal tones. After you have completed the configuration, shut the UPS down to make sure the system saves all the settings in the EEPROM. To activate the new setting, restart the UPS.
7. Manual Control Switch: Click On or Off to activate or deactivate program­mable outputs and overwrite all previous settings.
MD-1000I / MD-2000I / MD-3000I Storage and Unpacking
MD Series 50
4. Storage and Unpacking
4.1 UPS Storage
If you don't put the UPS into operation immediately, you need to follow the in­structions below:
Always store the unit and any accessories in their original packaging.
Suggested ambient storage temperature is 0 to +40° C.
Protect this product and the packaging against moisture.
If you are storing the UPS longer than 4 months, it is necessary, when you reach 4 months, to connect the UPS and the external battery string (optional) to a power source for about 8 hours to avoid extensively expending the charge.
4.2 Unpacking the UPS
Remove the box in which the product came and the packing materials.
Always keep the UPS in a horizontal position.
Compare the packing list to the package contents to determine if anything
is missing. Notify the vendor immediately if something is missing or if you have received something you did not order.
In addition, inspect the contents for any damage. Report any shipping or
handling damages immediately:
– Save the boxes and packing materials completely for potential claims.
– Notify the manufacturer immediately and/or your vendor.
– Notify the shipping company immediately.
MD-1000I / MD-2000I / MD-3000I Storage and Unpacking
MD Series 51
MD-1000I / MD-2000I / MD-3000I System Function
MD Series 52
5. System Function
The UPS operates continuously employing double conversion online topology. It processes the power provided by the power source, providing uninterrupted, clean, single-phase power for the critical equipment.
Besides furnishing the connected equipment with power, the UPS charges the internal battery, keeping it charged to its capacity. In the event of a power fail­ure or disturbance, the UPS continues to provide uninterrupted, clean power to the UPS output, supplied by the battery.
5.1 UPS Schematic Diagram
Fig. 5-1 - 1 Block diagram
The block diagram depicts the individual UPS modules and displays their inter­action roughly.
MD-1000I / MD-2000I / MD-3000I System Function
Important
UPS components are:
AC to DC power converter (rectifier)
AC to DC high frequency power inverter
Smart battery charger
String consisting of durable maintenance-free batteries
DC to DC push-pull inverter
Static bypass lead
Input and output EMI filter
The following table contains a summary of the UPS' power input and battery workings.
Power Supply (utility) Status
UPS Operating Mode LED Display
Normal power Power converter (rectifier)
converts AC to DC, battery charges, inverter converts DC to AC, providing clean stable power
, ,
LEDs illuminate
Power supply (utility) abnormal (over or under voltage) / unavail­able
Power converter and charger cease operating, Battery discharges via DC~DC pro­tective circuit and delivers power to the inverter. Load continues to receive power from the inverter. Audible alarm sounds, the UPS is operating in battery mode.
LED off,
LED illuminates
Power supply (utility) abnormal / unavailable, bat­tery almost dis­charged
Power converter and charger cease operating, Battery discharges via DC~DC pro­tective circuit and delivers power to the inverter. Audible alarm sounds with fast and short intervals, indicating battery charge is becoming critical and the inverter will soon cease to deliver power.
LED off, &
LED illuminates
MD Series 53
MD-1000I / MD-2000I / MD-3000I System Function
MD Series 54
5.2 UPS Operating Mode - Normal
Normal UPS operation is as shown below:
Fig. 5-2 - 1 During normal power supply
The inverter converts DC into clean, stable AC. Output LEDs 2 and 4 light.
MD-1000I / MD-2000I / MD-3000I System Function
Abnormal UPS operation is as shown below:
Fig. 5-2 - 2 During abnormal power supply
If the power supply is abnormal, the UPS battery automatically transmits power to the inverter, shuts off the charger and the AC-DC power converter (rectifier). The inverter converts the DC to AC, in order to supply the connected equip­ment with uninterrupted energy.
As soon as the power coming from the supply returns to normal, the UPS opens the AC-DC power converter (rectifier), shuts off the DC-DC converter and turns the charger on.
During a power outage, the UPS operates as shown in ( Fig. 5-2 - 1 During normal power supply). When battery level becomes too low, the audible alarm signal begins and continues until the battery shuts down. The UPS automati­cally stops battery-supplied power when battery capacity reaches a certain limit in order to prevent complete discharging. The UPS starts automatically when the mains is again available.
MD Series 55
MD-1000I / MD-2000I / MD-3000I System Function
5.3 Overload
UPS operation when overloaded is as shown below:
Fig. 5-3 - 1 Overloaded situation
Generally, modern electronics and IT equipment produce inrush current when they start. The magnitude of the inrush current varies depending on the equip­ment. Sometimes the current can be 6 times as high as measured capacity, while other devices generate inrush that is insignificant.
The UPS has an overload protection that protects it from inrush current. If the overload exceeds 105~120% of its capacity, it automatically switches to bypass within 30 seconds, in order to protect the inverter. As soon as the overload drops below <105%, the UPS returns to the inverter mode. If the UPS load ex­ceeds 150%, the inverter automatically shuts down.
MD Series 56
MD-1000I / MD-2000I / MD-3000I System Function
5.4 Inverter
Fig. 5-4 - 1 Inverter malfunction
Output short circuit If a short circuit occurs in the output while the connected equipment is receiv­ing current from the inverter, the UPS automatically shuts down the inverter and ceases supplying the equipment with power. LEDs indicate malfunction and the audible alarm goes off. Once the short circuit has been remedied, the UPS does not automatically start, but requires manual action to restart.
MD Series 57
MD-1000I / MD-2000I / MD-3000I System Function
MD Series 58
5.5 Inverter - Excessive Internal Temperature
Raised temperatures in the UPS automatically set off the bypass mode. The UPS switches back over to normal operation, once the temperature has re­turned to normal. If excessive termperatures occur while the energy supply is abnormal, the audible alarm sounds and the LEDs indicate malfunction. The UPS ceases to supply the equipment with power.
If a power outage exceeds the duration of the UPS' power supply, the UPS will shut down to protect the battery from deeply discharging. When the mains comes back on, the UPS kicks back on, energises connected equipment and controls the recharging of the battery/battery string.
The UPS has many outstanding features:
Absolutely no interruptions or change in signal if a primary power source
outage occurs
Pure sine wave output. The quality of the output voltage is significantly bet-
ter than that of the mains input.
Processor-controlled bypass
Input Power Factor Correction (> 0.95).
LCD status and operating display
Excellent Power Factor of 0.8
Powerful and extensive communication interfaces
– RS-232 is standard
– USB is standard
– Programmable switch contacts are standard.
– NOT-HALT EPO contact is standard.
MD-1000I / MD-2000I / MD-3000I System Function
MD Series 59
MD-1000I / MD-2000I / MD-3000I UPS Installation and Hook-Up
6. UPS Installation and Hook-Up
All instructions in technical information pertaining to the operating environment and operating conditions are mandatory and necessary to the proper function and operation of the UPS.
For the installation of the UPS in a tower or rack configuration, the following in­structions apply:
Avoid extreme temperatures and relative humidity.
Follow the instructions provided for the horizontal rack installation.
Make sure the unit has adequate ventilation with sufficient unhindered air-
flow.
Be careful when integrating the UPS in other systems, e.g. machines or
switch gear cabinets. Make sure the UPS' environment remains within the specified temperature requirements. If heat is prone to accumulate in the environment, you must act to provide suitable ventilation.
Only a base plate is suitable to anchor the unit.
6.1 UPS Connection
These models come equipped with plug-and-socket connectors.
The UPS system contains components with high voltage and amperage. Improper use or handling can lead to electrical shock, injuries with death and/or property damage.
The protective earth conductor must be connected! If it is not grounded, the connected equipment is also not earthed.
If operating with a generator, make sure not to reverse the connection's polarity.
If the UPS is in an emergency stop (NOT-HALT) cycle, the UPS output will still carry power. The connected equipment receives electricity for the duration while the UPS' electricity backup function is operating.
MD Series 60
MD-1000I / MD-2000I / MD-3000I UPS Installation and Hook-Up
1 Power mains
2 16 A
3 1.5 mm
2
4 Load 1
5 Load 2
Fig. 6-1 - 1 UPS and connected equipment connections
MD Series 61
MD-1000I / MD-2000I / MD-3000I UPS Installation and Hook-Up
MD Series 62
6.2 UPS Communication Interfaces
The UPS has convenient communication features for data transfer.
Only a single communication port can be active. The USB port has priority over the RS-232 port.
If a communication cable is connected, the software can exchange data with the UPS. The software gathers information from the UPS about the power sup­ply status. In the event of a power emergency, the software backs up the data and shuts down the equipment properly.
6.2.1 RS-232 port
Use only those cables specified in the Chapter "Accessories" (1 : 1).
Pin Configuration
2 RS-232 Tx Receiving line Rx or shut down SD
3 RS-232 RX Transmitting line Tx
5 Ground GND
The communication interface is completely isolated via galvanic means.
6.2.2 SNMP communication interface
The UPS can be ordered or fit with a SNMP interface.
MD-1000I / MD-2000I / MD-3000I UPS Installation and Hook-Up
6.3 Equipment Connection Sequence
Connect the UPS to source of power, but make sure the power source and
the UPS are both reliably shut down.
Before connecting equipment to the UPS outlet, you must perform the ini-
tial configuration.
Connect the equipment to the UPS, making sure that all the equipment is
turned off.
6.3.1 EPO connection configuration
Function Connection wire gauge Suggested gauge
EPO 4 - 0.32 mm2
(12 - 22 AWG )
0.82 mm2 (18 AWG)
MD Series 63
Leave the EPO p
lug installed on the UPS' EPO port, even if you don't plan to
use the EPO function.
Fig. 6-3 -
1 EPO plug
Follow
the instructions for the EPO port as stated in Chapter 3.2.5 EPO port.
MD-1000I / MD-2000I / MD-3000I System Operation and Display
MD Series 64
7. System Operation and Display
7.1 UPS Modes and Display Messages
s
Operating this system involves different operational modes and control com­munications.
7.2 USP User Instruction
The user of this UPS system must invariably follow and adhere to the in­structions and guidelines provided in this manual at all times. The user may perform only those actions described in the following and the user must perform them with great care:
Controls: energizing the UPS and switching it on and off
Reading the display and interpreting audible warnings
Activating the test operation
Use the communication interface, but if the UPS installation includes a
permanent connection, the connection to a PC or other systems should be already present.
Thanks to comprehensive protective and safety functions that the UPS performs in conjunction with the connected equipment, the UPS's opera­tion is completely automatic. The user need only energize and turn the unit on and off. In addition, communication interfaces allow the transfer of data via SNMP adapter, which, however, is not necessary for the regu­lar operation of the system.
MD-1000I / MD-2000I / MD-3000I System Operation and Display
7.2.1 Turning on the UPS
Connect the power cable to the UPS.
The UPS starts.
Fig. 7-2 - 1 UPS power cable connected
Hold the button USV Ein down ( Fig. 3-1 - 2, Item 12) until the unit emits an audible alarm. The UPS will perform a self test during initialisation.
Fig. 7-2 - 2 Self test
If the initialisation was successful, the input voltage will appear on the LCD dis­play.
MD Series 65
MD-1000I / MD-2000I / MD-3000I System Operation and Display
Fig. 7-2 - 3 Main display
If the system fails the self test, it will indicate failure on the LCD display.
Figure. 7-2 - 4 Failure
7.2.2 Turning off the UPS
Hold the button USV Aus down ( Fig. 3-1 - 2, Item 11) until the unit emits an audible alarm. The UPS shuts down.
Fig. 7-2 - 5 UPS is off
Please remember that the UPS shuts down only the outputs. To completely shut down the UPS, you must disconnect the power cable. Bear in mind that the connected equipment will no longer have power.
MD Series 66
MD-1000I / MD-2000I / MD-3000I System Operation and Display
7.2.3 Menu
7.2.4 Readings
With the Scroll Down ( Fig. 3-1 - 2, Item 9) Scroll Up ( Fig. 3-1 - 2, Item 8) keys, you can view the various values monitored by the system.
Menu structure:
Fig. 7-3 - 1 Input voltage
Fig. 7-3 - 2 Input frequency
Fig. 7-3 - 3 Output voltage
MD Series 67
MD-1000I / MD-2000I / MD-3000I System Operation and Display
Fig. 7-3 - 4 Output frequency
Fig. 7-3 - 5 Capacity in use
Fig. 7-3 - 6 Battery charging voltage
Fig. 7-3 - 7 Temperature inside UPS
MD Series 68
MD-1000I / MD-2000I / MD-3000I System Operation and Display
7.2.5 Menu functions
Press Other Functions ( Fig. 3-1 - 2, Item 10) to view the menu.
Menu structure:
Fig. 7-3 -
8 Audible signal ON / OFF
Fig. 7-3 - 9 Run self test
Fig 7-3 - 10 Bypass voltage
Fig. 7-3 - 11 Bypass frequency
MD Series 69
MD-1000I / MD-2000I / MD-3000I System Operation and Display
Fig. 7-3 - 12 Inverter output voltage
Fig. 7-3 - 13 UPS operating mode: Online, 50Hz or 60Hz at output
Fig. 7-3 - 14 Inverter output settings:
+1% -1%, +2% -2%, +3% -3%
MD Series 70
MD-1000I / MD-2000I / MD-3000I System Operation and Display
Consult your dealer or specialist before you change the settings in this menu. Wrong settings may cause the system to malfunction or even damage the UPS irreparably.
You'll find a description of the parameters in the following table.
Parameters Possible Settings Standard
Value
MD Series 71
MD-1000I / MD-2000I / MD-3000I System Operation and Display
1
1
7.3 Replacing Batteries
Risk of electrical shock
Battery replacement must be performed by QUALIFIED SERVICE PER­SONNEL ONLY!
Even when the UPS is turned off, the batteries and UPS components carry hazardous electrical charges.
To replace batteries, please proceed as described in the following:
1 Covers
Fig. 7-4 - 1 Removing covers
Remove the covers (1) on the UPS' front panel.
MD Series 72
MD-1000I / MD-2000I / MD-3000I System Operation and Display
1
1
1 Screws
Fig. 7-4 - 2 Screws
Remove both screws (1)
MD Series 73
MD-1000I / MD-2000I / MD-3000I System Operation and Display
1
1 Front panel cover
Fig. 7-4 - 3 Front panel cover
Slide the front panel cover (1) to the left out of the housing.
MD Series 74
MD-1000I / MD-2000I / MD-3000I System Operation and Display
1
Model MD-1000I
1 Connector
Fig. 7-4 - 4 MD-1000I
Unplug the connector (1)  Pull the battery out of the housing.
MD Series 75
MD-1000I / MD-2000I / MD-3000I System Operation and Display
1
1
Model MD-2000I and MD-3000I
1 Connector
Fig. 7-4 - 5 MD-2000I and MD-3000I
Unplug the connector (1)  Pull both batteries out of the housing.
MD Series 76
MD-1000I / MD-2000I / MD-3000I Trouble Shooting Guide
8. Trouble Shooting Guide
Only authorised qualified service personnel are to perform repairs or cor­rective actions to remedy UPS system malfunctions.
Situation Description Audible Signal Description
UPS malfunction, serious problem
Long continuous audible signal
UPS malfunction, power still provided via inverter or bypass
Single continuous audible signal with ~2­second interval
Battery mode Single short audible signal with ~1-
second interval
Battery low Very fast and short continuous signal
Verify/RS-232 connection 2 short, fast audible signal tones
Service mode ok 1 faster and shorter audible signal tone
UPS starts first with self-test 2 continuous fast and short audible
signal tones repeating in ~2-second intervals.
MD Series 77
MD-1000I / MD-2000I / MD-3000I Trouble Shooting Guide
Situation Malfunction Message
/ Meaning
Solution
UPS failure LED
Read the failure code indicated by LEDs.
1. Er05 battery weak or defective
1. Check if the battery is properly connected. Check battery voltage to determine if the batteries are charged and free of defect. If neces­sary, charge the batteries 8 hours.
2. Er12 Overload
2. Disconnect the uncritical equip­ment from the UPS outputs until the overload has subsided. Check to see if insufficient cable insulation has caused a short circuit. If neces­sary, replace the cable(s).
3. Er11 (UPS Exces­sive temperature)
3. Clean plugged up vents. Check to make sure the fan is working prop­erly. If necessary, ask your local dealer to replace the fan.
4. Local cable or earthing problem
4. Check to see if the "L" and "N" phases of the AC power lead are wrongly wired or if the earth neutral wire voltage exceeds the limit.
5. Er14 (Fan defec­tive)
5. Check to see if the fan is operat­ing properly. Do not attempt to replace the fan. Contact your local distributor.
6. Other faults codes 6. Contact your local dealer for
assistance.
MD Series 78
MD-1000I / MD-2000I / MD-3000I Trouble Shooting Guide
UPS doesn't p
rovide interval time or time is shorter than expected.
If the back-up time is still shorter than
required after charging for 8 hours, please contact your local dealer for technical assistance.
UPS appears to be nor­mal, but there is absence of output voltage.
Check to see if all power cables are prop­erly connected.
If the problem persists, contact your local dealer for technical assistance.
Unusual sounds or smells Shut down the entire system immedi-
ately. Turn off the power supply and contact your technical customer ser­vice.
UPS cannot run battery Check the battery connections. If the
batteries are weak, let them charge for a while. If the problem persists after you have charged the batteries, re­place them. If the problem still per­sists, contact your local dealer for technical assistance.
MD Series 79
MD-1000I / MD-2000I / MD-3000I Trouble Shooting Guide
MD Series 80
Malfunction code:
Code Meaning
Er05 Battery weak or defective
Er06 Output short circuit
Er07 EPO mode
Er11 UPS under excessive temperature
Er12 Inverter overload
Er14 Fan defective
Er18 EEPROM data error
Er24 Power supply low (<85/170V) and battery not
connected
Er28 Bypass overload
Er31 EEPROM data doesn't match. Settings of
control and driver boards don't match.
If you don't find the failure in the table, please contact our service department. You'll need to provide the following information when you talk to them.
1 Model number, serial number
2 Date on which the problem first occurred
3 Detailed description of the problem
MD-1000I / MD-2000I / MD-3000I Software
9. Software
Connect the RS-232 or USB cable connector to the UPS communication
port.
Connect the RS-232 or USB cable socket to a suitable RS-232/USB com-
puter port.
A suitable software package can monitor and process UPS settings and opera­tional status via communication port.
Software is available from the manufacturer, distributor or the provided hotline, where you'll receive useful information for selecting the most suitable software based on your needs and UPS.
Visit our Web site for further information:
http://www.edelstrom-usv-systeme.de
The follo
wing basic functions are supported by any software package:
Identification and display of UPS power source status
Display of UPS output status
Identification and display of the battery string charge status
Shutting down open applications if power fails
Shutting down operating system
Generating log files
General monitoring of UPS data and conditions (diagnostics)
You'll find more detailed information about the individual software packages, such as installation, operation and scope in the software manual.
In Chapte
r "Included Components and Accessories," you'll find a suitable,
tested software package.
MD Series 81
MD-1000I / MD-2000I / MD-3000I Maintenance and Service
MD Series 82
10. Maintenance and Service
With just a little maintenance, you will have the uninterrupted use of your UPS system for a long time.
Please note that the dependability of the UPS is very much affected by its envi­ronment. Temperature and relative humidity must be kept at reasonable levels. In addition, the area around the UPS should be kept as clean and dust-free as possible.
At the optimum ambient temperature of 22° C, the typical battery life span is approx. 4 years. Special-purpose, high-performance batteries will significantly increase longevity, reaching around 8-10 years.
Regularly, (every 6-12 months), you should check to make sure the system back-up capacity suffices for the intended purpose. If this is not the case, it is necessary to replace the batteries.
10.1 Determining the Back-up Capacity
Before you begin this procedure, make sure all open documents and data are backed up/saved. Also, be sure to inform all personnel who may be affected.
There are two methods of determining the back-up capacity.
Method a) is suitable for measuring the actual duration of time until the connected equipment loses power.
Method b) Permits determination of the remaining power capacity after a run using a specified back-up time. Connected equipment usually does not lose power in this instance.
To use one of these methods, it is necessary for you to simulate a situa­tion that forces the UPS into battery back-up operation (e.g. turning off building circuit breaker). Do not disconnect the power cable, as this will break the earthing (neutral) connection. Once you have completed the test, switch the circuit breaker back on and start the UPS as usual with the ON button.
MD-1000I / MD-2000I / MD-3000I Maintenance and Service
Remember that after the test the batteries are low. The UPS system will need to run several hours (min. 5 hr) on the mains before it reaches about 80% ca­pacity.
If you fail to perform a battery back-up test regularly, we suggest, for the sake of prevention, replacing the batteries every two years in order to safeguard the availability of your system against failure caused by battery degradation.
MD Series 83
MD-1000I / MD-2000I / MD-3000I Maintenance and Service
MD Series 84
10.2 Service Log
Always record all maintenance and service work performed on the UPS system in the Service Log.
Date Work Performed Performed By
MD-1000I / MD-2000I / MD-3000I Maintenance and Service
MD Series 85
10.3 Service Hotline
If contrary to expectations, you experience problems with the UPS or if you re­quire assistance with safety-related information, please use our Service Hot­line, either phone or fax:
Phone: 0049 / (0) 741 – 9292-0 Fax: 0049 / (0) 741 – 9292-33
If for whatever reason, telephone service is unavailable to you, you may use the following e-mail:
E-mail: kundenservice@multimatic-usv.de
10.4 Maintenance and Service Contracts
multimatic Vertriebs GmbH provides maintenance and service that guarantee
the best possible dependability and availability of your UPS system.
MD-1000I / MD-2000I / MD-3000I Technical Information
11. Technical Information
Model MD-1000I MD-2000I MD-3000I Output
Output in VA 1000 VA 2000 VA 3000 VA Output in W 800 W 1600 W 2400 W Power factor 0.8 Topology Online double-conversion Placement Tower or 19"-rack Safety CE
Input
Voltage range 120/140/160 - 288 VAC
Basis charge percent (0~33/33~66/66~100%) Under voltage 120/140/160Vac Under voltage start 170Vac Over voltage 288 VAC
Voltage
Over voltage start 278 VAC
Frequency 50/60 Hz auto-select, ± 5Hz Phases Single-phase with earth PF > 0.99 at full measured linear load Typical transfer time 0 ms. Leakage current 3.5 mA Surge protection 300 Joule
Output
Voltage 230V, adjustable to 200/208/220/230/240 Voltage setting ± 1% until weak battery warning Frequency (synchro­nised range)
3Hz or 1Hz (setting via software)
Frequency (battery mode)
±0.1% (0.05~0.06Hz) if not synchronised with
line Crest factor 3:1 Total harmonic distor­tion
3% THD (linear l ad) o
7% THD (non-linear load)
Dynamic response (ms)
<=60ms/5%
Output (INV. mode)
Wave form type True sine wave
Efficiency AC mode (full load) 85% 85% 88% Battery mode (full
load)
83% 83% 85%
Battery system
Type 12V/7.2Ah 12V/7.2Ah 12V/9Ah Number of batteries 3 6 6 Back-up time (full load) >7min. >7min. >5min. Recharge time 4 hours to 90% Charge current (max.) 1.1A 2.16A 2.7A Charge voltage VDC (DC high) 41.0Vdc±0.5 82.0Vdc±0.5 82.0Vdc±0.5V
MD Series 86
MD-1000I / MD-2000I / MD-3000I Technical Information
V V Hot swappable battery Yes Internal battery Yes DC leakage current 30uA (±10uA) with AC not in use and the unit
off
Battery type Sealed, maintenance-free, lead battery
Transfer time
AC to DC None Inverter to bypass 2.5ms (typically) None DC start Yes Self diagnostics Switch located on panel or software
Front panel
LED Load level/Battery level/ Battery mode/ Normal
mode/Bypass mode/ Self test/ Weak/Bad bat­tery/Local cable failure/ Failure/ Overload/ Programmable output 1/Programmable output 2
Keypads ON key/ OFF key/ (Test/Alarm reset key)
Protection
(AC mode)
105 unlimited 106%~120 for 30 seconds, then bypass
mode
121%~150 for 10 seconds, then bypass 150 immediate transfer to bypass
Continuous audible signal (tone) (Battery mode)
105 unlimited 106%~120 for 30 seconds, then shut down 121%~150 for 10 seconds, then shut down 150 for immediate shut down
Continuous audible signal (tone)
Overload
(Bypass mode)
105 unlimited 106%~120 for 250 seconds, then shut
down 121%~130 for 125 seconds, then shut down
131%~135 for 50 seconds, then shut down 136%~145 for 20 seconds, then shut down 146%~148 for 5 seconds, then shut down 149%~157 for 2 seconds, then shut down 158%~176 for 1 seconds, then shut down 177%~187 for 0.32 seconds, then shut
down 188 for 0.16 seconds, then shut down Continuous audible signal (tone)
Short circuit Bypass mode: input circuit breaker
Normal mode: output circuit breaker
MD Series 87
MD-1000I / MD-2000I / MD-3000I Technical Information
Battery mode: output circuit breaker
EPO UPS shuts down immediately
Normal mode Transfer to bypass mode Excessive
temperature
Battery mode UPS shuts down immediately
Audible alarm
Battery mode Audible signal every 1.5 seconds once Weak battery Audible signal every 0.2 seconds once Overload Audible signal every 3 seconds once Failure Continuous audible signal
(or every 3 seconds once
Physical
Dimensions (HxWxD in mm) 88(2U)x440x
405
88(2U)x440x
650
88(2U)x440x
650 Weight 15.7kg 29.4kg 29.7kg Input connector 10A, IEC
320-C14
10A, IEC 320-
C14
16A, IEC
320-C20
Output connector (6) 10A,IEC 320-C13 (4) 10A,IEC
320-C13
(1) 16A,IEC
320-C19
Environmental
Operating temperature 0-40 Noise level <50dBA Relative humidity 0 to 90% (without condensation)
Interfaces
Type 1 *USB port and 1*RS-232 port SNMP (optional) Energy management by SNMP manager and
Web browser
Operating systems Windows 95/98/NT/2000/XP Novell NetWare,
Linux, etc.
Standards and certification
Safety IEC/EN 62040-1-1,IEC 60950-1 Performance IEC/EN 62040-3 EMC IEC/EN62040-2 Class A, FCC Part 15
Safety CE,UL, cUL, FCC
MD Series 88
MD-1000I / MD-2000I / MD-3000I Technical Information
MD Series 89
11.1 Included Components and Accessories
In the following, you will find a list of components that multimatic Vertriebs GmbH has carefully selected, specified and tested for use in this UPS. Please
check to make sure that nothing is missing.
11.1.1 Components
Qt y.
Name Function / Graphic Article No. In-
cluded
1 UPS electronics,
incl. battery
MD-1000I
MD-2000I
MD-3000I
X
1 User Manual Printed in German X
Software package
multimatic Man­agement Software
CD-ROM Power supply shutdown and diagnostics software
1 License Windows/Novell
1 License UNIX, LINUX, MAC
multimatic Man­agement Software
X
LAN/RS-232-
connector
Interface cable X
USB cable X
Connecting lead
(IEC 10 A, straight)
X
Output cable
MD-1000I
MD-2000I
(IEC 10 A, straight)
X
Output cable X
MD-1000I / MD-2000I / MD-3000I Technical Information
MD-3000I
(IEC 16 A, straight)
2 Brackets Brackets for 19"-rack X
2 Feet Feet for tower variant X
MD Series 90
MD-1000I / MD-2000I / MD-3000I Technical Information
MD Series 91
11.1.2 Communication ports (optional accessories)
Name Article Number
Relay card 222302000434
SNMP card AR1041, AR1042
11.2 Wear Parts
The components listed below are parts that need replacement because of wear caused by regular operation of the UPS. These parts are not covered by war­ranty.
Wear Parts Function Article Number
XXXX XX XX ** Battery 12 V xx Ah
Energy storage (elec­tricity)
Subject to specific model and UPS con­figuration. See acces­sories or consult mul­timatic Vertriebs GmbH.
** For battery replacement, see current battery part number or consult multimatic Vertriebs GmbH.
12. Declaration of Conformity
MD Series 92
MD Series 93
MD Series 94
Loading...