Multi-Link ConnectFloor, AD-600 User Manual

AD-600
Installation Guide

Installation Guide

AD-600

General Information

Installation Time

The following estimates do not include material preparation and handling time. For open space: Trained installer: 900-1200 sq. feet (80-110 sq. meters) per man-day. Newly trained or amateur: 600-800 sq. feet (55 – 75 sq. meters) per man-day.
Small rooms and irregular floor plans: may call for 20 to 30 percent more installation time. Good preparation and job site planning are very influential to installation costs.

Recommended Tools Application

Electric Drill & Driver Perimeter & wall finish Chalk line Marking straight line for large rooms Pencils General Markings Steel rule Measuring Cutting Knife Cut UniPanel into Sub-Panels Scroll saw Cut Wall Rail, Edge Rail at corners Tape measures Measuring
1. Before installation
The following Instructions should be read before installation:
a. ConnectFloor systems are for in-door use only. b. Modular carpet is the standard finish flooring for the AD-600 (3’X3’ carpet tiles are recommended). c. Condition: UniPanel (AD-611) and adhesive should be conditioned at room temperature, not lower
than 40°F(5°C).
d. Floor Preparation: Sub-Floor must be free of grease, oil, wax, and moisture or any other foreign
material. All holes, cracks, and depressions should be filled with floor patching compound.
e. Sub-floor of the job site should be generally level. Elevation variation shall be no more than 3/8”(1
CM) within 3.3 feet (1 meter).
1
2. Starting Line – laying instructions
To maximize usage of full panels at the borders, it is recommended that you select the longest walls or the entrance wall as starting point.
Note: Properly selecting the starting line is important. It saves labor time and materials. Other factors that may affect choice of the starting line include: door, ramp, entry wall, other long walls and so on.
General Office Example – (Drawing D605)
Use the longer wall as the primary starting wall. Starting from the corner, test sequence no. 1 and no. 2 UniPanels along both walls, connected by half-Connector. If extension is not obstructed, move on to sequence no. 3. Be aware that any two walls might not be perfectly perpendicular to each other. If the second wall is at an angle less than 90° to the primary starting wall, the first UniPanel laid will need to be strategically offset from both walls to allow for extension of UniPanels in both directions. The resulting gaps to both
walls will then with appropriate accessories. If the gaps are greater than 1/5”(5 mm) in width, Edge Rail should work well.
Lay out entire floor with complete UniPanels until the remaining walls cannot allow complete UniPanels up against them. Cutting or trimming pieces will be required for the remaining walls to finish the UniPanel matrix. There will also be removal of some panels that have been laid down to apply the ramping required at the entranceways. In figure D605A, note that in cases where doors swing inside the room their must be a 25 sq. ft. entrance area to maintain ADA compliancy. The actual ramping area can easily be added by removing one UniPanel in front of the door plus an additional half of a UniPanel to account for the length of the ramps.
be filled up
D605A
D605
2
Loading...
+ 6 hidden pages