2.1 Intended use .............................................................................................................................................. 6
4.2 System description ................................................................................................................................. 11
6.1 Function description ............................................................................................................................... 16
6.2 Description of the input of machine data .............................................................................................. 16
6.2.5.1 Impulses per litre input .............................................................................................................................. 18
6.2.5.2 Tank method .............................................................................................................................................. 18
6.2.6.1 Manifold type ............................................................................................................................................. 19
6.2.6.2 Control constants ....................................................................................................................................... 20
6.5.1 Short SPRAYDOS version ........................................................................................................................ 23
6.5.2 Long SPRAYDOS version ......................................................................................................................... 23
6.7.2 Calibrating the boom control ...................................................................................................................... 25
6.7.3 Calibrating the drawbar steering ................................................................................................................ 26
7.2 Flow meter ................................................................................................................................................ 28
8.1 Technical data .......................................................................................................................................... 29
8.1.1 Long SPRAYDOS version ......................................................................................................................... 29
8.1.2 Short SPRAYDOS version ........................................................................................................................ 29
9 LIST OF DIAGRAMS ................................................................................................................................ 30
The SPRAYDOS board computer is a new development on the basis of the well tried and tested SPRAY-Control board
computer. The SPRAYDOS has up to 9 boom section switches with a main switch, the manual or automatic regulation of
the spray rate and up to 4 hydraulic functions (the long version allows a further 10 hydraulic functions as soon as foam
marker and corner nozzles). The current speed and the current spray rate are displayed simultaneously.
If an automatic pressure sensor is installed, the pressure is displayed instead of the speed. The speed appears on the
display when the km/h key is pressed for about 5 seconds. Specific applications can be carried out by pressing the +/- 10%
key. The pre-set rate resets by means of the l/ha key. The spray rate is adhered to accurately even when the speed varies.
This signal word identifies medium-risk hazards, which could potentially cause death or serious
physical injury, if not avoided.
CAUTION
This signal word identifies low-risk hazards, which could potentially cause minor or moderate
physical injury or damage to property, if not avoided.
2 Safety instructions
2.1 Intended use
The SPRAYDOS is specified exclusively for agricultural use and in wine, fruit and hop growing. The manufacturer
takes no responsibility for any installation or application outwith this area.
The manufacturer does not accept liability for damage to persons or property resulting from unspecified use. In
such cases all risks are the responsibility of the user.
Specified implementation also includes adhering to the operation and maintenance requirements stipulated by the
manufacturer.
Relevant accident prevention regulations as well as other generally recognised safety, industrial, health and road
traffic rules are to be adhered to. In addition the manufacturer accepts no liability in cases where arbitrary
modifications have been made to the device.
2.2 Basic safety instructions
Observe the following recommended precautions and safety instructions:
Do not remove any safety devices or labels.
Before using the SPRAYDOS read and understand this guide. It is of equal importance that others operating this
device also read und understand the manual.
During maintenance or when using a battery charger, switch off the power supply.
Never service or repair the device while the job computer is switched on.
Before welding on the tractor or on an attached machine, interrupt the power supply to the SPRAYDOS.
Only use a soft damp cloth with clear water or a little glass cleaning agent to clean the SPRAYDOS.
Operate the keys with your finger tips but avoid using fingernails.
Should any part of this guide remain incomprehensible after reading, contact the dealer or Mueller-Elektronik
Service for further clarification before using the SPRAYDOS.
Read carefully all safety instructions in the manual.
Learn how to operate the SPRAYDOS correctly. Nobody is to operate the machine without exact instructions.
Keep the SPRAYDOS and the spare parts in good condition. Unspecified alterations can impair the function and/or
safety and affect the life span of the machine.
2.3 Layout and meaning of warnings
All safety instructions found in these Operating Instructions are composed in accordance with the following pattern:
This signal word identifies actions which could lead to operational malfunctions if performed
incorrectly.
These actions require that you operate in a precise and cautious manner in order to produce
optimum work results.
2.4 Safety notice for the subsequent installation of electrical and electronic devices
and /or components
Present-day agricultural machines are equipped with electronic components and devices, whose function can be affected
by electromagnetic emission from other devices. These influences can lead to endangerment for individuals when the
following safety measures are not adhered to.
When subsequently installing electrical and electronic devices and/or components in a machine with a connection to the
electrical system, the user must take sole responsibility for testing the installation for interference of the vehicle electronics
or other components. This applies in particular to the electronic controls of:
EHR
Front lifting gear
Power take-off shafts
Motor
Gears
Above all it must be ensured that all subsequently installed electrical and electronic components comply with the current
version of the EMC directive 89/336/EWG and carry the CE symbol.
In addition the following requirements must be fulfilled when upgrading with mobile communication systems (e.g. radio,
telephone):
Only approved devices complying to national regulations (e.g. BZT approval in Germany) are to be installed;
The device must be securely installed;
The use of portable or mobile devices inside the vehicle is permissible only via a connection to a permanently
installed outside antenna;
The transmitting unit is to be installed in a position away from the vehicle electronics;
An antenna should only be installed professionally ensuring that there is a good earth connection between the
antenna and the vehicle chassis.
Please refer to the manufacturer's installation instructions for cabling and installation as well as the maximum current
consumption.
This product has been manufactured in conformity with the following national and harmonised standards as specified in the
current EMV Directive 2004/1008/EG:
Dieses Produkt ist in Übereinstimmung mit folgenden nationalen und harmonisierten Normen im Sinne der EMV-Richtlinie
2004/108/EG hergestellt:
If the SPRAYDOS is being used on a trailed field sprayer, no speed sensor is to be connected to
the SPRAYDOS. In this case the speed is measured at the wheel of the field sprayer.
CAUTION
During transport the SPRAYDOS must be switched off.
If available, the drawbar or axle steering must be set to centre position during transport.
4.2 System description
The SPRAYDOS can be installed on the field sprayer as a fully automatic control instrument. The device carries out an
area-related control of the spray rate regardless of the current speed, the working width and the pre-set rate.
The calculation of the current spray rate, speed, working area, total area, quantity spray as well as the total quantity and the
working time is carried out continuously.
The device consists of the computer [1] and the console [2-5].
A wheel/cardan speed sensor [9] can be connected directly to SPRAYDOS in order to determine the speed.
The SPRAYDOS can be connected directly to the signal socket [10] on the tractor using a connecting cable. By means of a
switch integrated in the connecting cable it is possible to switch between wheel/cardan and a radar device.
The field sprayer is connected by means of the machine plug (circulation, hydraulic) on the SPRAYDOS.
Please ensure that the computer casing [1] has a lead connection to the tractor's chassis above the
console [2-5]. When mounting, remove the paint from the mounting points.
Brown cable core
Blue cable core
Free end of the butt connector
Loose ring tongue – ground/0V
Ring tongue +12V
WARNING
Risk of injury caused by short circuit
Connecting the positive terminal and the vehicle mass when working on the battery terminals can
cause a short circuit. This can cause burn injuries to persons.
◦ When working on the battery terminals, ensure that no connection is created between the
vehicle battery and the vehicle mass.
◦ Remove metallic items such as watches and rings before starting work.
◦ When disconnecting the terminals, always begin with the negative terminal.
◦ Always begin reconnecting the terminals with the positive terminal.
5 Installation instructions
5.1 Console and computer
The basic console [5] must be mounted vibration-free and electroconductive to the cabin on the driver's right-hand side
and within his visual range and reach. The distance to the radio or to the radio antenna should be at least 1 m.
Attach the bracket [4] to the tube of the basic console.
Mount the cap profile rail [2] on to the bracket. Push the SPRAYDOS computer [1] from above on to the profile and
secure using the wing nuts [3].
The console can be swivelled to allow the display to be adjusted to the optimal angle of vision which lies between 45° and
90° from below.
Danger of injury from explosion of the vehicle battery
If the battery terminals are loose fitting, starting the vehicle can cause the vehicle battery to
overheat. The vehicle battery may then explode.
◦ Always tighten the battery terminals firmly after assembly.
CAUTION
Damage to the vehicle’s electrical system
Switching the polarity of the cables can cause damage to the vehicle’s electrical system.
◦ Pay attention to the polarity of the cable cores and the terminals.
CAUTION
The negative pole on the battery must be connected to the tractor's chassis.
> Ensure that the vehicle is switched off.
> Insert the blue cable core into the 0V ring tongue .
> Insert the brown cable core into the free end of the butt connector .
> Pinch with a crimping tool.
>
Shrink both of the butt connectors with a heat source (e.g. hot air gun) until the adhesive emerges.
> Connect the ring tongues to the battery terminals of the vehicle battery. Pay attention to the polarity, beginning with
the positive terminal.
> Fasten the battery cable with cable ties. Ensure that there is sufficient distance from moving parts and parts
generating large amounts of heat.
Operating voltage is 12 V and must be taken directly from the battery or from the 12-volt starter. Care should be taken
when laying the cable [6] and it should be shortened if necessary. The crimpon ring terminal for the ground line (blue) and
the end sleeve for strands for the + line (brown) should be fitted using suitable pliers. The end sleeve for strands for the +
line are in the connection clamp of the fuse holder.
If an X sensor is connected in the machine distributor, no sensor is to be connected to the
SPRAYDOS.
5-10 mm
Diagram 5-1 Sensor X at the cardan
shaft
Magnet (rote Seite)
5 - 10 mm
Sensor-X
Diagram 5-2 Sensor X on the tractor's wheel
5.3 Sensor X (calculation of the distance)
Mounting on four-wheel drive tractors:
Mount the hose clamp with a magnet to the cardan shaft.
The sensor must point in the direction of the magnets at a distance
between 5 – 10 mm. It is to be mounted vibration-free.
Mounting on tractors without without four-wheel drive:
Install the magnets in the wheel shell using V4A screws
provided, distributing them evenly over the circumference.
The number of magnets depends on the size of the wheel.
The distance travelled from impulse to impulse must not
exceed 60 cm.
Calculation:
Wheel circumference ÷ 60 cm = number of magnets
e.g.: 256 cm ÷ 60 cm = 4.27 = min. 5 magnets
Mount the sensor to the steering knuckle using the bracket
provided so that the end of the sensors is pointing towards the
magnets. The distance should be 5-10mm
Mounting on the wheel of the trailed sprayer
Mount the sensor on the wheel of the field sprayer in the same
way as on the wheel of the tractor (see diagram 5.2). In this
case the electrical connection is in the machine distributor
manifold.
5.4 Adapter cable for tractors with signal socket
In this case it is not necessary to install the X sensor. The SPRAYDOS is connected to the tractor's signal socket using the
adapter cable [10].
The attached or trailed field sprayer is connected via a 39 channel machine plug manifold. With the SPRAYDOS long
version the machine plug – hydraulic must be connected in addition.
During normal operation, the operating mode is always displayed on the monitor. There are two alternatives:
1. Pressure sensor is not connected
on the left hand side of the monitor the speed is displayed and an arrow appears above. The current spray
rate is shown on the right hand side of the monitor.
2. Pressure sensor is connected
on the left hand side of the monitor the current spraying pressure in bar is displayed. The current spray rate in l/ha is
displayed on the right hand side. If the spray rate exceeds 1000 l/ha, the rate is displayed with four digits and the
pressure with just two digits.
With both display alternatives, an arrow on the left shows that the sprayer is switched on. Below this a circle flashes when
impulses are being measured by the speed sensor.
The operating mode is interrupted for 10 seconds when a key is pressed to display another value. For each further key
pressed, the time counter is extended again for 10 seconds.
Keyboard
The keyboard is divided into different areas.
- Operating data
This block of keys is used to recall required data. By pressing the simultaneously, the order is
started. All counters except ha and l are set to 0.
- Machine data
This block of keys is used to communicate the machine data to the computer. Using the keys it is
possible to vary the spray rate in degrees of 10% in relation to the set rate.
- Input keys
to enter and alter machine data, the keys and are used.
6.2 Description of the input of machine data
Before the device can put into operation, the machine-specific data must be entered:
> Press the „working width " key
> > Enter the value using the keys and
> > Press to transfer the new value
6.2.2 "Impulses/100m" key
With this key the number of impulses which the speed sensor records to the computer is entered.
There are two possibilities to enter the data:
1. The impulses/100m value is known
> Press
> Enter the value using the keys and
> Press to transfer the new value
2. The impulses/100m value is not known
> Measure out and mark a distance of 100m on the field
> Bring the vehicle to the start position
> Press and simultaneously
> Travel a distance of 100m and stop. The computer counts the impulses during the journey
> Press to transfer the new value
6.2.3 "Number of boom sections" key
This key is used to enter the number of boom sections (max. 9) and the number of nozzles for each boom section.
The boom sections are numbered from left to right as seen from the direction of driving.
During input, the boom sections are displayed on the left hand side and the number of nozzles on the left hand side.
Procedure:
> Press
on the left a 1 (boom section 1) is displayed and on the right the number of nozzles.
> To alter the number of nozzles, enter the new value using the keys and.
> Press
the value is now stored in the memory. On the left hand side of the display a 2 (boom section 2) appears. If the
value – number of nozzles – on the right hand side of the display is correct, press to transfer the value and
select boom section 3. This process can be carried on until the 9th boom section is reached. Subsequently the total
number of boom sections and nozzles will be displayed.
> If e.g. the field sprayer has 5 boom sections, enter a 0 when the 6
sets the boom sections 7-9 automatically to 0. In this case the computer operates on the basis of 5 boom sections
and displays the number of boom sections and the total number of nozzles as 5:30.
th
boom section is displayed. The computer then
6.2.4 "Pre-set rate - l/ha" key
The required spray rate is communicated to the computer using this key. If the switch is in automatic position the
electronics control the pressure and subsequently the spray rate automatically.
If, due to a fault (e.g. tank empty) the pre-set rate is not achieved, an alarm is set off.
Input value
> Press
> Enter the value using the keys and
> Press to transfer the new value
The value entered is controlled by pressing again.
6.2.5 "Impulses / litre" key
Direct input of impulses per litre or a calibration of the flow meter can be carried out here. The various possibilities are
described in the chapters 6.2.5.1 - 6.2.5.3.
6.2.5.1 Impulses per litre input
If the number of flow meter impulses per litre is known, the value can be entered directly.
1. The value impulses/litre is known:
> Press
> Enter the value using the keys and
> Press to transfer the new value
6.2.5.2 Tank method
With the tank method calibration is carried out by weighing the entire field sprayer before and after spraying. The procedure
is as follows:
> Fill the tank with water and determine the quantity (weigh).
> Press and simultaneously
> While stationary, switch on the field sprayer using and spray a few hundred litres.
(The computer now counts the flow meter impulses). All sections must be open.
> Switch off the sprayer using
> Determine the amount sprayed (reweigh).
> Set the value using the keys and
> Press to transfer the new value
> The computer calculates the "impulses / litres"
The flow meter impulse number should be checked several times a year especially before each season.
6.2.5.3 Nozzle method
With the nozzle method the quantity sprayed is measured at a nozzle and projected to the total number of nozzles. The
procedure is as follows:
> Fill the tank with water.
> Secure a measuring jug below a nozzle.
Balanced pressure manifold without reflux measurement
1.15
Manifold without balanced pressure function.
2.15
Balanced pressure manifold with reflux measurement
3.15
Spraying devices without balanced pressure function
Manifold type (number before the comma)
> Press and simultaneously
> While stationary switch on the field sprayer using until the measuring jug has been filled with e.g. 2 litres (the
computer counts the flow meter impulses). All sections must be open.
> Switch off the sprayer using
> Determine the amount sprayed
(read the quantity in the measuring jug and multiply by the number of nozzles)
> Set the value calculated using the keys and
> Press to transfer the new value
> The computer has now calculated the "impulses / litres"
6.2.6 "Type" key
This key is used to enter 2 functions. The number before the comma determines the manifold type. The 2 positions after
the comma determine the control constant.
> Press
> Set the value using the keys and
> Press to transfer the new value
6.2.6.1 Manifold type
The manifold type is communicated to the computer via the number before the comma.
The following manifold types are taken into account (in the example a control constant of 15 is assumed):
The valves on the balanced pressure manifold must be set accurately.
Balanced pressure manifold without reflux measurement
The manifold is equipped with electrovalves and separate balanced pressure valves (e.g. Tecnoma-Elektra). The spraying
fluid which flows back to the tank via the balanced pressure valves when the boom section is switched off is not recorded
by the flow meter.
Manifold without balanced pressure function
The manifold is equipped with motor or electromagnetic valves.
Only the quantity sprayed via the spray bar is measured by the flow meter even when the boom section is switched off.
If, at the end of the field with the sprayer switched off, one or more boom sections are switched off, the computer takes a
pre-setting via the control valve. Fine-tuning then takes place once the field sprayer has been switched on.
Balanced pressure manifold with reflux measurement
The manifold can be equipped with either motor or electromagnetic valves. When boom sections are switched off the flow
meter also measures the amount which flows back to the tank. The computer takes this into account when calculating the
quantity sprayed depending on the number of nozzles per boom section.
Example: Field sprayer with 5 boom sections
One boom section is switched off; only 4/5 of the total quantity is recorded
(1/5 flows back into the tank).
Spraying devices without balanced pressure function
This setting takes into account the specific features of spraying devices for use in fruit, wine and hops production. In this
case the quantity and not the working width is altered when the upper nozzle segments are switched off. If one side of the
device is completely switched off, the working width is halved.
6.2.6.2 Control constants
Depending on the fabrication and the size of the sprayer different control times are required when there is a certain
deviation from the pre-set value.
The computer calculates the control time with which the control valve is driven. The control time is determined by the
control constant.
> Regulation too sluggish -> enter a highter value
> Regulation overdrive -> enter a lower value
The control constant is optimally selected, when, in the case of a deviation from the pre-set value, one control process is
sufficient for the computer to get to the proximity of the pre-set value and then fine tune by means of a few small processes.
Regulation can be seen in the display l/ha.
Control constants can be within the range of 1 to 99.
During operation the sprayed rate can be adjusted in degrees of 10% in relation to the pre-set rate by using the keys
and. An arrow in the display above shows that a manual adjustment of the spray rate has been
carried out.
By pressing the key, a manual adjustment of the spray rate by means of the keys is cancelled out
again. The value entered with the key is once again set as the pre-set value. The file above disappears
again.
6.3 Description of the operating data keys
6.3.1 "Start function"
The start function is activated by pressing the keys, i.e. the memory for the area, spraying fluid and time is
set to "0". Time starts automatically when this key is pressed. This function is to be carried out before each job.
6.3.2 "Area / total area"
This key has a dual function. When the key is pressed for the first time, the area covered since activating the start function
is displayed for 10 seconds. In addition an arrow appears at the bottom of the display above. If, within 10 seconds the
key is pressed a second time, the total area is displayed. This value is not deleted by the start function. This enables the
total area for a season to be determined. At the beginning of the season the counter is set to "0" by pressing the keys
and simultaneously.
The area calculation adapts to current conditions. Switched-off boom sections are automatically taken into account.
Measurement is interrupted as soon as the field sprayer is switched off at the main switch.
6.3.3 "Time" key
Operating time since activating the "start function" (6.3.1) is displayed when this key is pressed. An arrow appears
above .
If the computer is switched off, the input of time data is stopped. It restarts once the device has been switched on again.
The clock can also be stopped during operation. After the key has been pressed, it can be pressed once again to
stop the clock. To restart it press yet again.
6.3.4 "Spraying fluid l/min" key
Displays the flow meter litres per minute. An arrow appears above.
6.3.5 "Spraying fluid l and l" key
This key has a dual function. When the key is pressed for the first time, the quantity spray since activating the start
function (6.3.1 ) is displayed for 10 seconds. In addition an arrow appears at the bottom of the display above. If, within
10 seconds the key is pressed a second time, the total number of litres is displayed. This value is not deleted by the start
function. This enables e.g. monitoring the tank content. After filling, the counter is set to "0" by pressing the keys
and simultaneously. The quantity of spraying fluid sprayed can be read during operation.
6.3.6 "Speed" key
When the sprayer is switched off, the current speed being travelled is displayed by pressing and also an arrow
appears above.
When a sprayer with an installed pressure sensor is switched on, the speed is displayed on the left-hand side of the
monitor by pressing this key for 5 seconds. In addition an arrow appears above. This key has no function when
there is no pressure sensor as, in this case, the speed is displayed permanently in the job display.
6.3.7 "Tank content" key
If a Tank-Control is connected, the tank content can be called up by pressing. The value is displayed for 10
seconds.
6.4 Spraying function switch
6.4.1 Boom section main switch
The boom section main switch switches the sprayer's main valve. When switched on, spraying begins with all switched-on
boom sections.
6.4.2 Manual/automatic switch
This switch can be used to switch between automatic and manual operation. In "Auto" position the computer controls the
spray rate automatically. If the switch is set at "Manual" the correct spraying pressure must be set manually by means of
the key.
6.4.3 Spraying pressure +/- key
This key is for manual adjustment of the spraying pressure in manual operation mode. Manual operation is selected by
The function of the boom section switch is to switch the individual boom sections. If a switch is off, then the corresponding
boom section is also switched off and cannot be switched on by means of the boom section main switch.
6.4.5 Configuring the section switches
If you connect a Spraydos with nine section switches to a sprayer with five sections, you can set that only every second
switch is used. In doing so, please note that the LEDs above unused switches are also illuminated as soon as they are
switched up.
Diagram 6-2 Section switches
On the left: Every second switch controls one valve (Configuration 1:0); on the right, the first five switches control
the valves (Configuration 1:1)
> Reboot the computer.
> Press the and keys (in this sequence) simultaneously.
> The current configuration appears on the display:
> Set the value using the and keys.
> Press the key to adopt the new value.
> Reboot the computer.
6.5 Hydraulic functions switch
6.5.1 Short SPRAYDOS version
The short SPRAYDOS version supports a maximum of 4 hydraulic functions. For this purpose up to 4 switches can be
mounted on the top right-hand area of the computer. The function of each of these switches is illustrated by the pictograms
on the tactile keyboard.
6.5.2 Long SPRAYDOS version
The long SPRAYDOS version has an additional row of switches underneath the section switches. Here, up to 10 hydraulic
functions as well as foam markers and corner nozzles can be accommodated. Pictograms illustrate their function.
6.6 Operating procedure
Once the machine data have been entered (6.2.1- 6.2.6), only the start function (6.3.1) has to be activated before
operation can begin. During operation all values can be called up.
Before initial operation fill the sprayer with water (without spraying fluid). Start the field sprayer.
Subsequently check the values measured and displayed.
Magnet
The calibration mode is activated by applying a magnet onto the casing. The
magnet must be positioned exactly above the left edge of the display.
LED
Is switched off in calibration mode, and flashes to indicate completion. The
same LED is used for all of the calibrations.
The automatic mode guarantees accurate dosage. Please ensure that the pressure in connection with the drop formation
for the nozzle type in operation is maintained.
At times when the field sprayer is switched on and off, the same speed should be driven if possible to avoid brief underdosage or over-dosage after switching on the field sprayer.
If regulation is to be carried out manually, set the switch to manual. The quantity is controlled using the key.
Once the job is completed all values can be called up. A new job begins with the "start function" (6.3.1).
6.7 Calibrating hydraulic functions
If the following hydraulic functions are available, they can be calibrated by the user:
> Boom control
> Drawbar steering
Calibration serves to adapt the controller to the characteristics of the implement.
Diagram 6-3 Operating elements that are required for calibration
The implement component (boom/drawbar) will be moved to the left, until it
reaches a resistance (ground/stop).
- Control dial to the right
The implement component (boom/drawbar) will be moved to the right, until it
reaches a resistance (ground/stop).
- Control dial at the centre
The implement component is not moved.
6.7.1 Activating calibration mode
> Apply the magnet onto the casing, as shown in the figure above.
The LED is illuminated.
> -Within one second, turn the control dial or first 90°
to the left, then 90° to the right and then back to the centre.
The LED flashes several times. If the LED does not flash, it means that the computer was not put into
calibration mode and that you must repeat the steps.
The LED is turned off.
> Leave the magnet on the casing until the calibration is completed, unless you are prompted to lift it briefly.
> If you remove the magnet prematurely for longer than 1 second, the LED flashes briefly. The calibration will be
cancelled and the values determined during calibration are discarded.
In calibration mode, the control dials are used differently than normally:
6.7.2 Calibrating the boom control
Use the control dial for the calibration.
To calibrate the boom control:
> Activate calibration mode. See: p. 25
> First, you must teach the computer the direction in which the control dial must be turned to slope the boom to the
right. This direction depends on the electrical connection of the actuators. To do so, follow the next two steps.
> or - Slope the boom a few degrees to the right. It does not have to be sloped down to the
ground.
The boom was sloped a little to the right.
> Lift the magnet briefly and apply it again.
The LED flashes briefly.
You have taught the computer where the right side is.
> - Turn the control dial to the centre position.
> Lift the magnet briefly and apply it again.
The LED flashes briefly.
You have calibrated the horizontal position.
> - Slope the boom as far as possible to the right.
The boom touches the ground on the right.
> - Turn the control dial to the centre position.
> Lift the magnet and apply it again.
The LED flashes briefly.
You have calibrated the slope to the right.
> - Slope the boom as far as possible to the left.
The boom touches the ground on the left.
> - Turn the control dial to the centre position.
> Lift the magnet briefly and apply it again.
The LED is illuminated.
You have calibrated the slope to the left.
The calibration is complete.
> Lift the magnet.
LED is off.
Calibration mode is terminated.
6.7.3 Calibrating the drawbar steering
Use the control dial for calibration.
To calibrate the drawbar steering:
> Put the switch to the position.
> Activate calibration mode. See: p. 25
> First, you must teach the computer direction in which the control dial must be turned to move the drawbar to the
right. This direction depends on the electrical connection of the actuators. To do so, follow the next two steps.
> or - Move the drawbar to the right.
The drawbar was moved a little to the right.
> Lift the magnet briefly and apply it again.
The computer is maintenance-free. It has an internal safety fuse. During the winter it should be stored at room temperature
and protected from dampness.
7.2 Flow meter
Rinse the flow meter with water each time after use. At the end of the season check the run of the impeller wheel and
replace if necessary. At the beginning of each season carry out a calibration process (see 6.2.5).
Diagram 5-1 Sensor X at the cardan shaft ........................................................................................................................ 14
Diagram 5-2 Sensor X on the tractor's wheel .................................................................................................................... 14
Diagram 6-3 Operating elements that are required for calibration .................................................................................... 24