Mueller SENTRY II Installation And Operation Manual

Page 1
SENTRY II
WITH AUTO-DOSING ASSEMBLY
INSTALLATION AND OPERATION
MANUAL
PART NO. 8823644
EFFECTIVE 4/1/00
®
THE MILK COOLING SYSTEMS SPECIALISTS
®
Page 2
Page 3
®
Table of Contents
SENTRY
®
II WITH AUTO-DOSING ASSEMBLY
INSTALLATION AND OPERATION MANUAL
Section 1.0 - Introduction Page
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.3 Regulatory Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Figure 1 - Sentry II Control Cabinet and Milk Cooler Components . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Section 2.0 - Installation
2.1 Crate Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.2 Skid Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 2—Skid Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.3 Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.4 Hot Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.5 Water Supply Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.6 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.7 Foundation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Formula 1—Gross Weight of Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 3—Foundation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.8 Leveling the Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Figure 4—Leveling the Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.9 Bulk Head Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 5—Agitator Weather Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 6—Basic Bulk Head Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.10 Milk Room Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Figure 7—Milk Room Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.11 Agitator Assembly Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Figure 8—Agitator Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.12 Pump Assembly and Electric Drain Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Figure 9—Pump Assembly and Electric Drain Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.13 Instructions for Mounting the Sentry II Control Box Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.14 Water Line Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Figure 10—Sentry II Control Box Installation and Water Connections . . . . . . . . . . . . . . . . . . . . . . . .11
2.15 Chemical Line Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.16 Manway Wash Tube Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 11—Manway Wash Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.17 Spray Dish Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 12—Spray Dish Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Figure 13—Spray Dish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.18 Milk Cooler Vent Assembly Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 14—Milk Cooler Vent Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Section 3.0 - Electrical Wiring
3.1 Field Electrical Connections at Milk Cooler’s Rear Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 15—Milk Cooler Electrical Terminal Strip (Rear Junction Box) . . . . . . . . . . . . . . . . . . . . . . . . .16
Part No. 8823644
Page 4
Section 3.0 - Electrical Wiring -
Continued
Figure 16—Electrical Schematic - Wash Pump Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 17—Electrical Schematic - Agitator Motor(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 18—Electrical Schematic - Rear Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 19—Internal Conduit Raceways - Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 20—Electrical Schematic - Field Wiring (enlarged schematic in back of manual) . . . . . . . . . . .19
Figure 21—Electrical Schematic - Factory Wiring (enlarged schematic in back of manual) . . . . . . . . .20
Figure 22—Sentry II Relay and Switch Contact Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.2 PLC Electrical Troubleshooting (Input and Output Data) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Table 1—PLC Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 23—Electrical Schematic - PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Figure 24—Electrical Schematic - Peristaltic Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Section 4.0 - Sentry II Temperature Control
4.1 Sentry II Temperature Control and Thermocouple Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.2 Sentry II Thermocouple Sensor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Figure 25—Sentry II Thermocouple Sensor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.3 Sentry II Thermocouple Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Figure 26—Sentry II Thermocouple Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
4.4 Important Thermocouple Splicing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 27—Sentry II Thermocouple - Temperature Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.5 Sentry II Temperature Control Calibration Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.6 Sentry II Temperature Control Lock and Unlock Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 28—Sentry II Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
4.7 Sentry II Temperature Control Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
4.8 Sentry II Temperature Control Set Point Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
4.9 Sentry II Temperature Control Unit of Measure (Fahrenheit or Celsius) . . . . . . . . . . . . . . . . . . . . . . .30
Section 5.0 - Automatic Chemical Dosing
5.1 Initial Start-Up Procedures for Automatic Dosing and Chemical Usage . . . . . . . . . . . . . . . . . . . . . . . .31
5.2 Peristaltic Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.3 Chemical Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.4 Peristaltic Pump Priming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Figure 29—Peristaltic Pump Priming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5.5 Adjusting Peristaltic Pump Timers for Proper Chemical Concentration . . . . . . . . . . . . . . . . . . . . . . . .33
Figure 30—Peristaltic Pump Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Table 2—Timer Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Table 3A—Peristaltic Pump Timing for Specific Chemical Concentrations (2-240 Seconds) . . . . . . . . .34
Table 3B—Peristaltic Pump Timing for Specific Chemical Concentrations (240-478 Seconds) . . . . . . .35
Table 3C—Peristaltic Pump Timing for Specific Chemical Concentrations (478-726 Seconds) . . . . . . .36
5.6 Determining Water Usage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Figure 31—PLC Fill-Time Potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Table 4—Minimum Water Requirements (Per Cycle) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
5.7 Determining Actual Water Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Table 5—Calculated Water Usage (Fill-Time/Supply Pressure) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
5.8 Wash Cycle Timing Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Chart 1—Detergent Wash or Complete Wash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Chart 2—Acid Cycle or Sanitize Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Table of Contents -
Continued
Page 5
Section 6.0 - Sentry II PLC Programming
6.1 Sentry II Programmable Features, Options, and Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . .41
6.2 Sentry II - MTA to PLC Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
6.3 Sentry II Service Reference Form, Programmable Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Section 7.0 - Operating Instructions
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Figure 32—Sentry II Operating Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
7.2 “Cool-Off-Wash” Rotary-Selector Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
7.3 Cooling Bottoms Units Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
7.4 Cooling All Units Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
7.5 Pre-Start Cooling Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
7.6 Pre-Start Agitator Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
7.7 Detergent Cycle Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
7.8 Acid Cycle Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
7.9 Sanitize Cycle Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
7.10 Agitate Sample Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
7.11 Alarm Lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
7.12 Milk Temperature Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
7.13 Cooling Override Switch (Emergency Use Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Section 8.0 - Weights and Dimensions
8.1 English Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
8.2 Metric Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Section 9.0 - Sentry II Replacement Parts
9.1 Sentry II Replacement Parts Drawing, Main Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
9.2 Sentry II Replacement Parts List, Main Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
9.3 Sentry II Replacement Parts Kit, Dosing and Manifold Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.4 Sentry II Replacement Parts List, Dosing and Manifold Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
9.5 Sentry II Replacement Parts Kit, Pump Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
9.6 Sentry II Replacement Parts List, Pump Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Section 10.0 - Sentry II Equipment Markings
10.1 Label No. 8822229, Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10.2 Label No. 8820482, Caution - Disconnect Power and Retain Latch . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10.3 Label No. 8820623, Warning Symbol - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10.4 Label No. 8805616, Manual - Run Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10.5 Label No. 8820248, Auto - Automatic Run Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.6 Label No. 8823064, Acid - Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.7 Label No. 8823063, Detergent - Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.8 Label No. 8823065, Sanitize - Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.9 Label No. 8822584, Pump Motor - Wire Marker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.10 Label No. 8802375, Agitator(s) - Wire Marker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.11 Label No. 3791, Hot - Water Valve Marker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
10.12 Label No. 8823609, Warning - Manifold Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
10.13 Label No. 8823013, Warning - Disconnect Power Before Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . .66
10.14 Label No. 8801150, Warning - Disconnect Power Before Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . .66
10.15 Label No. 8822225, CE Data Tag (U.K. Models Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
10.16 Label No. 8820410, Data Tag (U.K. Models Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
10.17 Label No. 30612, Notice - Chart Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Table of Contents -
Continued
Page 6
Table of Contents -
Continued
Section 10.0 - Sentry II Equipment Markings -
Continued
10.18 Label No. 8820454, Dry Nitrogen Holding Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
10.19 Label No. 8805299, Warning - HCFC Class II Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
10.20 Label No. 30737, Bottom Temp-Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
10.21 Label No. 8822972, Transformer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
10.22 Label No. 8822705, Canadian and U.S. Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
10.23 Label No. 8822948, 24 VAC Component List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
10.24 Label No. 8820409, Mueller Name Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
10.25 Label No. 8822980, Programmable Controller Name Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
10.26 Label No. 8822558, Mueller Milk Cooler Data Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
10.27 Label No. 30890, Mueller Data Tag - Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
10.28 Label No. 8820677, Ground Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
10.29 Label No. 3792, Cold - Water Valve Marker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
10.30 Label No. 30397, Stainless Steel Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
10.31 Label No. 30166, Caution - Vent Must Be Over Milk Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
10.32 Label No. 8820508, Hot - Tube Marker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
10.33 Label No. 8802777, Caution - Do Not Sanitize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
10.34 Label No. 8823146, Terminal Block - 24 VAC - 240 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
10.35 Label No. 8823263, Terminal Block - 24 VAC - 240 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Section 11.0 - Safety
11.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
11.2 Manway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Section 12.0 - Disposal
12.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
12.2 Chemical Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
12.3 Solid Component Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Page 7
SECTION 1.O - INTRODUCTION
1.1 General
The Mueller®Sentry®II refrigeration and cleaning control with auto-dosing feature is custom designed and manufactured to provide programmable and automated push-button timing of the cleaning, cooling, and agitation cycles. A large digital temperature display and automatic temperature alarm system informs the operator of safe milk temperatures.
Durable construction and enhanced control circuitry ensures maximum cooling and energy efficiencies, superior automation, and long-term reliability.
1.2 Technical Support
This manual provides the basic installation and operating information to ensure safe and optimum performance of the Sentry II control system. Please contact your local Mueller Sales and Service Representative if you require additional technical assistance pertaining to installation or operating procedures.
Manufacturer’s support is available by contacting:
Paul Mueller Company Dairy Farm Equipment Service Department P.O. Box 828 Springfield, Missouri 65801 Telephone: (417) 831-3000 • 1-800-MUELLER (683-5537)
1.3 Regulatory Requirements
It is the responsibility of the purchaser and installer to seek the necessary regulatory pre-approval of an installation, ensuring that the site and method of installation meets all regulations for the locality.
Local, state, and/or county regulations pertaining to the installation, operation, and service of the equipment may vary and must be followed accordingly.
Installation and service must be performed by authorized service technicians who have the proper training and certification to install and service refrigeration and electrical equipment.
Sentry II with Auto-Dosing Assembly Operating Instructions 1 Effective April 1, 2000
Page 8
Figure 1 - Sentry II Control Cabinet and Milk Cooler Components
Sentry II with Auto-Dosing Assembly Operating Instructions 2 Effective April 1, 2000
A. Sentry II Control Box B. Alarm Indicator C. Detergent Switch/Indicator D. Acid Switch/Indicator E. Sanitize Switch/Indicator F. Sample Agitation Switch/Indicator G. Cool/Off/Wash Selector Switch H. Digital Temperature Indicator I. Cooling Switch/Indicator (Bottom Units) J. Cooling Switch/Indicator (All Units) K. Pre-Start Switch/Indicator (Cooling) L. Pre-Start Switch/Indicator (Agitate)
M. Peristaltic Pump Priming Switch N. Priming Selector Switch O. Peristaltic Pump (Sanitize) P. Peristaltic Pump (Acid) Q. Peristaltic Pump (Detergent) R. Chemical Line Priming Disconnect S. Fill Line Disconnect T. Pressure Switch (No Water Alarm) U. Manifold Assembly V. Water Solenoid Valve (Dual) W. Electric Drain Valve X. Wash Pump Assembly
Page 9
SECTION 2.0 - INSTALLATION
2.1 Crate Removal
CAUTION: Equipment used to move or lift the milk cooler must be rated for the weight of the milk cooler. Approximate weights are provided in Section 8.
1. Remove any open-type crating and the packaged parts. Do not remove the skids attached to the milk cooler legs at this time.
2. Inspect the milk cooler and report any damage to the transportation carrier. File a claim immediately if the milk cooler is damaged.
3. Move the milk cooler into the milk house and position it to meet all regulatory requirements for the locality.
4. Once in place, the skids can be removed.
2.2 Skid Removal
1. Raise one end of the milk cooler with the floor jack placed beneath the skid’s cross brace. Securely block the skid to ensure safety and stability while removing the self-tapping screws from the bottom of each leg.
2. Lower the milk cooler and repeat the procedure on the opposite end.
3. Remove cross-bracing members, leaving the two skids under the milk cooler’s legs.
4. Raise one end of the milk cooler with a floor jack and wooden-cradle block. Pivot the skids away from the milk cooler. Lower the milk cooler and repeat the procedure for the other end.
Figure 2 - Skid Removal
!
Sentry II with Auto-Dosing Assembly Operating Instructions 3 Effective April 1, 2000
Page 10
2.3 Site Requirements
It is the responsibility of the installer and/or purchaser to provide adequate electrical service, water supply, floor drains, and footer foundations for the installation. Failure to do so can cause non­warranted structural damage to the milk cooler and/or costly service problems for the user.
2.4 Hot Water Requirements
A water heating device with adequate storage and temperature recovery capacity must be provided to wash the milk cooler and milking equipment simultaneously. The water heater should be capable of supplying water temperatures of 160-170°F (71-76.6°C) during the detergent wash cycle.
CAUTION: To prevent non-warranted expansion damage to the milk cooler, the maximum wash water temperature shall not exceed 170°F (76.6°C). Installation sites that require water temperatures in excess of 170°F (76.6°C) should install a tempering valve, Mueller Part No. 8820276, to regulate the milk cooler wash water temperature at 170°F (76.6°C) or below.
2.5 Water Supply Pressure
Water supply pressure to the milk coolers wash system must be maintained between 20 and 60 psig.
2.6 Electrical Requirements
The Sentry II Control System requires a 240/50-60/1 power supply, fused at 15 amps maximum. See Section 3 for detailed wiring schematics.
NOTE: International markets may request optional transformer, Mueller Part No. 8823060, for power supplies providing 195/50/1.
Electrical installation requirements for the refrigeration units should be obtained from the Installation and Operation Manual specific to the refrigeration unit(s) being installed.
NOTE: All wiring to be performed in accordance with the National Electrical Code and/or regulatory agency for the installation locality. All wiring that enters the Sentry II control box must be sealed with cord grips or liquid-tight conduit connectors.
Sentry II with Auto-Dosing Assembly Operating Instructions 4 Effective April 1, 2000
!
Page 11
2.7 Foundation Requirements
IMPORTANT: Due to varying geographical soil conditions, contact a local civil engineer for footer, concrete, and foundation requirements that will adequately support the weight of the milk cooler when filled to maximum capacity.
The following information is required to determine the foundation requirements:
1. A drawing showing the layout location of the milk cooler’s legs. See Section 8.
2. A drawing describing the proposed installation layout.
3. Gross weight of the milk cooler when filled to maximum capacity.
Formula 1 - Gross Weight of Milk Cooler
Net Weight (lb)* + (Capacity in US Gallons x 8.6) = Gross Weight (lb) Net Weight (kg)* + (Capacity in Liters x 1.0305) = Gross Weight (kg)
*Section 8 provides approximate net weights of Mueller milk coolers.
Example: 2,000 gallon Mueller milk cooler filled to maximum capacity.
2,356 lbs. + (2,000 x 8.6) = 19,556 lbs. 1,069 kg. + (7,570 x 1.0305) = 8,870 kg.
IMPORTANT NOTE: Mueller warrants to the original purchaser/user that the Mueller factory calibration of a Mueller milk cooler will not be affected (i.e. exceed the tolerances prescribed by the National Institute of Standards and Technology) by distortion or structural change for a period of five (5) years from the date of installation or sixty-six (66) months from the date of shipment from the Company factory, whichever occurs first. The Company’s obligation shall be limited to the correction of the calibration only, and does not cover reimbursement of product loss. This warranty will not apply if distortion is caused by changes in the floor or foundation on which the milk cooler is installed. Refer to the Mueller Milk Cooler Warranty Card for complete warranty information.
Figure 3 - Foundation Requirements
Sentry II with Auto-Dosing Assembly Operating Instructions 5 Effective April 1, 2000
Page 12
2.8 Leveling the Milk Cooler
With the assistance of a floor jack and protective wooden-cradle block, level the milk cooler as described in the following steps:
1. Adjust the inner legs off the floor until the proper pitch is obtained with the four corner legs.
2. Place a carpenter’s level across the brim of the manway opening and level the milk cooler by adjusting the corner legs with a nylon strap wrench. Legs may be extended by turning the legs counterclockwise, and retracted by turning the legs clockwise.
3. Using the levels located on the side of the cooler, adjust each end of the milk cooler until the proper height and pitch is obtained. (The milk cooler should pitch 1/4" per foot towards the outlet valve.)
4. Using a certified seraphin, add the exact volume of water indicated for the “Set-Up Reading” on the calibration chart.
5. Adjust the final pitch of the milk cooler, matching the calibration gauge reading with the “Set-Up Reading” on the calibration chart.
6. When the front and back corner legs are positioned properly, the inner legs should be extended firmly against the floor.
7. Ensure that the final location and position complies with all regulations for the installation locality, including the proper height of the milk outlet and the proper dimensions beneath and around the milk cooler.
Figure 4 - Leveling the Milk Cooler
Sentry II with Auto-Dosing Assembly Operating Instructions 6 Effective April 1, 2000
Page 13
2.9 Bulk Head Installations
If the milk cooler is bulkheaded through a wall, the wall must be free-standing and not load bearing against the milk cooler. Mueller offers an optional steel-formed structural support channel that may be installed in masonry walls to prevent the wall from bearing load on the milk cooler. Contact Mueller’s Sales Department for availability and pricing.
A weather shield kit, Part No. 93750, is required for agitator(s) that are located exterior of the milk house wall. See Figures 5 and 8, and Section 2.11 for additional installation instructions.
Figure 5 - Agitator Weather Shield
Figure 6 - Basic Bulk Head Installation
Sentry II with Auto-Dosing Assembly Operating Instructions 7 Effective April 1, 2000
Page 14
2.10 Milk Room Installations
Ensure proper clearances between the milk cooler and other obstacles or equipment as required by the regulations in your locality. Special attention should be placed on floor drain locations, high-traffic and working areas, and ease of access for the operators.
The milk cooler parts box includes two stainless steel brackets to secure the water/chemical fill line to the rear head of the milk cooler, Part Nos. 8823254 (top) and 8823253 (bottom). Each bracket is supplied with 1.125" rubber grommets, which provides a method to support the water/chemical fill hose inside of .75" PVC conduit. See Figure 7.
Figure 7 - Milk Room Installations
Sentry II with Auto-Dosing Assembly Operating Instructions 8 Effective April 1, 2000
Page 15
2.11 Agitator Assembly Installation
1. Remove the protective plastic shipping wrap and position the agitator shaft (Item 7) up through the opening in the top of the milk cooler. Slip the neoprene shield (Item 8) over the end of the agitator shaft. Be careful not to damage the internal and external finishes of the cooler during this procedure.
2. Position the spacer sleeves (Item 3) on the studs located on the top of the cooler. Apply Never­Seez®to the shaft end (Item 7) and threads of the cap screws (Item 1). Slip the agitator shaft through the agitator drive and secure in place with cap screws (Item 1), lock washers (Item 2), and spacer sleeves (Item 3).
3. Align the hole in the agitator shaft with the hole in the output shaft of the agitator drive and insert the roll-pin (Item 5).
4. Place the blue plastic cap (Item 6) over the top of the output shaft after assembly.
5. Thread the 90° liquid-tight conduit fitting (Item 10) through the plastic nut (Item 11) with the flat­washer flange facing the motor. Slip the cut gasket (Item 12) over the threads and thread the assembly into the agitator motor. Insert the 3-wire cable through the straight conduit fitting, conduit, and 90° fitting installed in the motor. Thread the straight liquid-tight conduit fitting into the full coupling attached to the milk cooler. Connect L1 and L2 as shown in the wiring schematic, secure the ground wire under the grounding screw in the motor housing. Ensure clockwise rotation as viewed from the top of the drive.
6. The optional agitator weather shield (Item 13) must be installed on all agitators that are located exterior of the milk room.
Figure 8 - Agitator Installation
Sentry II with Auto-Dosing Assembly Operating Instructions 9 Effective April 1, 2000
Page 16
2.12 Pump Assembly and Electric Drain Installation
1. Bolt the pump assembly and electric motor to the left front corner of the milk cooler as shown in
Figure 9.
2. Trim the rubber elbow (Item 1) for proper fit and connect between the discharge fitting on the
pump assembly and the wash line in the milk cooler.
3. Install the straight, liquid-tight conduit fitting (Item 2) in the stainless steel cover plate located on
the left side of the milk cooler.
4. Thread the 3-wire cord (marked pump motor) through the conduit fitting and conduit (Item 3).
5. Thread the plastic nut (Item 4) with the flat flange facing the motor onto the 90° liquid-tight fitting
(Item 5).
6. Slip the neoprene gasket (Item 6) over the threads of the 90° liquid-tight fitting and thread the
assembly into the pump motor.
7. Thread the 3-wire cord and conduit into the 90° liquid-tight fitting and secure with the liquid-tight
compression fitting.
8. Wire the motor per the electrical schematic attached to the motor.
9. Install the stainless steel screen (Item 7) in the rubber adapter (Item 8) and clamp the electric drain
valve in position with the two stainless steel hose clamps.
10. Install the cord grip (Item 9) in the stainless steel cover plate located on the left side of the milk
cooler.
11. Thread the cord (marked drain valve) through the cord grip and wire to terminal numbers 1 and 2
at the 24-vac electric drain valve coil.
12. Reattach the stainless steel cover plate and tighten all cord grips and liquid-tight conduit fittings.
Figure 9 - Pump Assembly and Electric Drain Installation
Sentry II with Auto-Dosing Assembly Operating Instructions 10 Effective April 1, 2000
Page 17
2.13 Instructions for Mounting the Sentry II Control Box Enclosures
1. Install the Sentry II control box in a location where it is easily accessible for the operator and protected from excessive wash down.
2. Install the peristaltic pump box and manifold box in an area protected from freezing and within easy access to the chemical storage drums.
NOTE: The maximum length for the chemical supply hose is 28 feet (8 meters).
2.14 Water Line Connections
1. Connect the hot and cold water fill hoses to the water solenoid valves located in the right side of the manifold box. See Figure 10.
2. Some localities may require the installation of high hazard back-flow preventors in the water supply plumbing if the installation is connected to chemical supply drums larger than 1 gallon. Contact your local regulatory agencies for proper direction and compliance.
Figure 10 - Sentry II Control Box Installation and Water Connections
Sentry II with Auto-Dosing Assembly Operating Instructions 11 Effective April 1, 2000
Page 18
2.15 Chemical Line Connections
1. Locate the chemical supply drums in an area protected from freezing, direct sunlight, and unauthorized access.
2. Connect the chemical supply hoses between the chemical drums, peristaltic pumps, and manifold box as follows:
a. Insert the clear-colored chemical supply hose to the bottom of the detergent drum. Route and
connect the opposite end to the inlet of the peristaltic pump marked detergent.
b. Connect a second piece of clear-colored chemical supply hose to the outlet of the detergent
pump. Route and connect the opposite end to the quick-disconnect and check valve located on the bottom of the manifold box.
c. Repeat the procedure for the acid and sanitize connections, connecting the red hose to acid
and the blue hose to sanitize. See Figure 10.
NOTE: The maximum total length of the chemical supply hoses must not exceed 28 feet (8 meters).
CAUTION: Wear protective clothing and eye protection when handling caustic chemicals! Always observe the chemical manufacturer’s precautions, warnings, and usage recommendations! Store all chemicals in a location protected from freezing, unauthorized access, and direct sunlight.
Sentry II with Auto-Dosing Assembly Operating Instructions 12 Effective April 1, 2000
!
CAUTION
WEAR EYE PROTECTION,
RUBBER GLOVES, AND
APRONS WHEN HANDLING
CHEMICALS
CORROSIVE
POISON
Page 19
2.16 Manway Wash Tube Installation
The manway wash tube provides positive wash of the manway opening and cover. The tube is inserted in the stainless steel nipple in the top of the milk cooler and held in place with a stainless steel pin. Refer to the drawing in Figure 11 for detailed installation procedures.
Figure 11 - Manway Wash Tube
Sentry II with Auto-Dosing Assembly Operating Instructions 13 Effective April 1, 2000
Page 20
2.17 Spray Dish Installation
The spray dishes connect to the internal or external CIP wash line with a stainless steel keeper pin. Check for proper spray dish installation and orientation during the installation and start-up inspection. The rectangular notch cut across the bottom of the spray dish tube must face the front and rear heads of the milk cooler and the slot cut in the bottom of the dish must point towards the center of the agitator shaft. See Figures 12 and 13.
Figure 12 - Spray Dish Orientation
Figure 13 - Spray Dish
Sentry II with Auto-Dosing Assembly Operating Instructions 14 Effective April 1, 2000
Rectangular notch must face front and rear heads of the milk cooler.
Orient slot towards the center of the agitator shaft.
Page 21
2.18 Milk Cooler Vent Assembly Installation
Install the milk cooler vent assembly by rotating the vent assembly clockwise and allow the retaining straps to engage in the retaining lugs. See Figure 14.
IMPORTANT: The vent for the milk cooler must be in place at all times. The vent prevents contaminates from entering the milk cooler and provides proper air flow to prevent internal damage resulting from vacuum or pressurization when the milk cooler is washed or emptied. Mueller Model “O,” “OE,” “OH,” and “OHF” milk coolers are designed for operation at normal atmospheric pressure only.
Figure 14 - Milk Cooler Vent Assembly
Sentry II with Auto-Dosing Assembly Operating Instructions 15 Effective April 1, 2000
VENT ASSEMBLY MUST BE OVER MILK INLET AT ALL TIMES!
EL ENSAMBLAJE DE VENTEO DEBE ESTAR SOBRE LA ENTRADA DE LA LECHE EN TODO MOMENTO.
30166
CAUTION
!
CUIDADO
!
Page 22
SECTION 3.0 - ELECTRICAL WIRING
3.1 Field Electrical Connections at Milk Cooler's Rear Junction Box
The rear junction box is factory equipped with a quick-connect terminal strip for simple field electrical connections. See Figure 15.
Figure 15 - Milk Cooler Electrical Terminal Strip (Rear Junction Box)
To make electrical connections to the quick-connect terminal strip:
1. Disconnect all power supplies.
2. Strip .375-inches (10 mm) of insulation off each conductor.
3. Open the quick-connect terminal connection by inserting a 3-mm screwdriver into the bottom of socket “A”.
4. Following the electrical schematics, insert the correct conductor into terminal connection “B” and remove the screwdriver, allowing the quick-connect terminal to close on the conductor.
Sentry II with Auto-Dosing Assembly Operating Instructions 16 Effective April 1, 2000
Page 23
Figure 16 - Electrical Schematic - Wash Pump Motor
Figure 17 - Electrical Schematic - Agitator Motor(s)
Figure 18 - Electrical Schematic - Rear Junction Box
Sentry II with Auto-Dosing Assembly Operating Instructions 17 Effective April 1, 2000
Page 24
Figure 19 - Internal Conduit Raceways - Milk Cooler
Sentry II with Auto-Dosing Assembly Operating Instructions 18 Effective April 1, 2000
Page 25
Figure 20 - Electrical Schematic - Field Wiring (Enlarged Schematic Attached in Back)
Sentry II with Auto-Dosing Assembly Operating Instructions 19 Effective April 1, 2000
Page 26
Figure 21 - Electrical Schematic - Factory Wiring (Enlarged Schematic Attached in Back)
Sentry II with Auto-Dosing Assembly Operating Instructions 20 Effective April 1, 2000
Page 27
Figure 22 - Sentry II Relay and Switch Contact Positions
Sentry II with Auto-Dosing Assembly Operating Instructions 21 Effective April 1, 2000
Page 28
3.2 PLC Electrical Troubleshooting (Input and Output Data)
The LED lights on the top cover of the PLC provide a quick and simple visual aid for troubleshooting the inputs and outputs. Compare the PLC input and output terminology from Table 1 with the illuminated LED lights on the PLC for accurate troubleshooting of each individual circuit. Figure 23 provides an exploded view of the PLC electrical connections.
Table 1 - PLC Inputs and Outputs
Service Note: Inputs “X” are 24 VDC, outputs “Y0 - Y11” are 24 VAC, and “Y12 - Y15” are 240 VAC.
Sentry II with Auto-Dosing Assembly Operating Instructions 22 Effective April 1, 2000
Inputs Input Description Outputs Output Description
Not Used 24V 24 VDC (+) Output L (Line) L1 of 240 VAC Supply OV 24 VDC (-) Output Ground Electrical Ground COM0 (24VAC) Power for Y0, Y1, and COM1
N L2 of 240 VAC Supply Y0 (24VAC) Condensing Unit 1 (or) Hot Solenoid
S/S 24 VDC (-) Y1 (24VAC) Condensing Unit 2 (or) Cold Solenoid
Not Used Not Used
S/S 24 VDC (-) COM1 (24VAC) 24V Power for Y2-Y5 and COM2
X0 Agitator Sampling Switch Y2 (24VAC) Alarm Lamp X1 Pre-Start Agitator Switch Y3 (24VAC) Agitator Lamp X2 Pre-Start Cooling Switch Y4 (24VAC) Pre-Start Agitator Lamp X3 Cooling Bottom Unit Switch Y5 (24VAC) Pre-Start Cooling Lamp X4 Cooling All Units Switch Not Used X5 Wash Cycle Start Switch COM2 (24VAC) 24V Power for Y6-Y11 X6 Acid Cycle Start Switch Y6 (24VAC) Cooling Bottom Unit Lamp (or) Drain Valve
X7 Sanitize Cycle Start Switch Y7 (24VAC) Cooling All Units Lamp (or) Detergent Wash X10 Cooling Selector Switch Y10 (24VAC) Acid Cycle Lamp X11 Wash Selector Switch Y11 (24VAC) Sanitize Cycle Lamp X12 Temperature Control Set Point Not Used X13 High/Low Temp. Alarm Input COM3 (240VAC) L1 of 240VAC/Power for Y12-Y15 X14 Not Used Y12 (240VAC) Agitator Coil (or) Wash Pump Coil X15 Water Level Pressure Switch Y13 (240VAC) Detergent Chemical Pump X16 Not Used Y14 (240VAC) Acid Chemical Pump
X17 Not Used Y15 (240VAC) Sanitize Chemical Pump
Page 29
Figure 23 - Electrical Schematic - PLC
Sentry II with Auto-Dosing Assembly Operating Instructions 23 Effective April 1, 2000
Page 30
Figure 24 - Electrical Schematic - Peristaltic Pumps
Sentry II with Auto-Dosing Assembly Operating Instructions 24 Effective April 1, 2000
Page 31
SECTION 4.0 - SENTRY II TEMPERATURE CONTROL
4.1 Sentry II Temperature Control and Thermocouple Sensor
The Sentry II control uses an electronic temperature control with digital display and a Type “T” thermocouple sensor. The following installation and calibration procedures are very important to ensure accurate sensing of the milk temperature.
4.2 Sentry II Thermocouple Sensor Installation
Install the thermocouple sensor in the front-sensor raceway of the milk cooler as follows:
1. Fabricate an insertion rod from a 5-foot piece of 10-gauge solid wire by forming a 3/8" open loop on one end. See Figure 25.
2. Align the flat side of the “T” shaped sensor with the inner shell of the milk cooler.
3. Slip the loop of the insertion rod over the thermocouple wire and push the sensor down the raceway until it seats into the spring-clip at the end of the sensor raceway.
4. Being careful not to pull the thermocouple from the spring clip, withdraw the insertion rod from the sensor raceway. See Figures 25 and 26.
Figure 25 - Sentry II Thermocouple Sensor Installation
Sentry II with Auto-Dosing Assembly Operating Instructions 25 Effective April 1, 2000
Page 32
4.3 Sentry II Thermocouple Sensor Wiring
1. Route the thermocouple cable from the right-hand access opening through the internal conduit to the left-hand access opening in the milk cooler.
2. Route the thermocouple cable from the left-hand access opening through the internal conduit to the top-rear junction box of the milk cooler.
3. Mating copper (+) to copper (+) and constantan (-) to constantan (-), splice the thermocouple cable to the thermocouple extension cable in the top-rear junction box of the milk cooler with non-metallic wire nuts. See “Important Thermocouple Splicing Information” in Section 4.4.
4. Cut and insulate the foil shield and drain wire of the thermocouple extension cable at the top-rear junction box. The drain wire should be grounded (one end only) at the Sentry II control cabinet.
5. Route the thermocouple extension cable from the rear junction box to the wall-mounted Sentry II.
Avoid routing this cable in conduit that contains high-voltage conductors.
6. Connect the copper (+) thermocouple conductor to Terminal No. 11 and the constantan/silver (-)
to Terminal No. 10 of the temperature control. Connect the drain wire to the electrical ground in the Sentry II enclosure. See Figure 27.
Figure 26 - Sentry II Thermocouple Sensor Wiring
Sentry II with Auto-Dosing Assembly Operating Instructions 26 Effective April 1, 2000
Page 33
4.4 Important Thermocouple Splicing Information
If it is necessary to splice the thermocouple cable, always mate copper to copper and constantan (silver) to constantan (silver).
The thermocouple sensor must be wired continuously with Type “T” thermocouple cable. Do not use ordinary copper wire.
Use non-metallic wire nuts, Mueller Part No. 8822361, to make all spliced thermocouple connections.
If thermocouple extension cable is required, Mueller Part No. 8820166, connect the drain wire to the electrical ground at the Sentry II enclosure and cap and insulate the foil shield and drain wire at the opposite end.
Figure 27 - Sentry II Thermocouple-Temperature Control Wiring
4.5 Sentry II Temperature Control Calibration Accuracy
Once the installation wiring is completed for the Sentry II control box, check the calibration accuracy of the temperature control as outlined below:
1. Cover the bottom evaporator and agitator paddle with water or milk to check the temperature calibration.
2. Allow the product temperature to stabilize for a minimum of 15 minutes.
3. Using an accurate electronic thermometer, determine the actual temperature of the water or milk in the milk cooler.
4. If the known product temperature does not correspond with the temperature display, the temperature control will require an input program correction. See Sections 4.6 and 4.7.
Sentry II with Auto-Dosing Assembly Operating Instructions 27 Effective April 1, 2000
Page 34
4.6 Sentry II Temperature Control Lock and Unlock Features
The temperature control is equipped with a locking feature to prevent unauthorized adjustments to the calibration, temperature set points, and unit of measure.
Unlock - To unlock the temperature control for adjustment, press and hold the and keys (see Figure 28) simultaneously for two seconds. When released the display will blink once indicating a successful unlock, otherwise repeat the process.
Lock - To lock the temperature control, press and hold the and keys simultaneously for 4 seconds. When released the display will blink once indicating a successful lock, otherwise repeat the process. To validate a locked condition, press the key once, when released the display will momentarily display “Lock.”
Note: The temperature control should be locked during normal operating conditions to prevent unauthorized or accidental setting alterations.
Figure 28 - Sentry II Temperature Control
Sentry II with Auto-Dosing Assembly Operating Instructions 28 Effective April 1, 2000
Factory Temperature Control Settings:
Refrigeration On - 39°F (3.9°C) Programmed Set Point - 38°F (3.3°C) Refrigeration Off - 37°F (2.8°C)
Temperature Alarms:
High Alarm - 41°F (5.0°C) Low Alarm - 35°F (1.7°C)
See Section 4.8.
Page 35
4.7 Sentry II Temperature Control Calibration
1. Unlock the temperature control as instructed in Section 4.6.
2. Press and hold the key until the display stops blinking, then release.
3. The display will show “SHIF” alternating with the current calibration setting.
NOTE: If display reverts to temperature, repeat step 2.
4. Press and release either the or key, the display will show 3 digits and 1 decimal (000.0).
5. Press and release either the or key to cycle to the decimal point or digit you wish to change.
The selected digit will be highlighted. Example (000.0)
6. Adjust the temperature calibration offset for the digit selected in step 5, by pressing and holding
the key to increase, or the key to decrease. Example: (001.0)
7. Note: For a negative calibration offset, select the first digit (X00.0) then press and hold the key until “-” negative is displayed (-00.0). If “-100.0” is displayed, press the key until “-00.0” is displayed. Example: (-01.0)
8. Press the key once to enter the change.
9. Press the key a second time to return to the temperature display.
10. Lock the temperature control by pressing and holding the and keys simultaneously for 4 seconds. When released the display will blink once indicating a successful lock, otherwise repeat the process. To validate a locked condition, press the key once, when released the display will momentarily display “Lock.”
EXAMPLE:
If the known product temperature was 37°F and the temperature control displayed 39°F, a correction factor of -2°F would be required for calibration.
Starting at step 5 of the above instructions, you would perform the following procedure:
Press and release the or key to cycle to the second digit (000.0)
Press and hold the key until “2” (002.0) is displayed.
Press and release either the or key to cycle to the first digit (002.0).
Press and hold the key until “-” negative is displayed (-02.0).
Press the key once to enter the change.
Press the key a second time to return to the temperature display.
Lock the temperature control by pressing and holding the and keys simultaneously for 4
seconds. When released the display will blink once indicating a successful lock, otherwise repeat the process.
Sentry II with Auto-Dosing Assembly Operating Instructions 29 Effective April 1, 2000
Page 36
4.8 Sentry II Temperature Control Set Point Adjustment
The temperature control is factory programmed at 38°F (3.3°C) with a 1°F differential on rise and fall of temperature. This setting turns the refrigeration off at 37°F (2.8°C) and on at 39°F (3.9°C).
The High and Low-Temperature Alarms are activated at 3°F above and 3°F below the programmed temperature set point.
NOTE: The minimum and maximum set-point adjustments are regulated between 36-41°F (2.2-5.0°C).
1
Factory setting.
To change the factory settings:
1. Unlock the temperature control as instructed in Section 4.6.
2. Press either the or key once to display the current temperature set point.
3. Press and release either the or key to select the digit to be changed.
4. Adjust the temperature set point for the digit selected in step c, by pressing and holding the key to increase, or the key to decrease.
5. Press and hold the key until the display stops blinking, then release to enter the change.
6. Press and release the key twice to return to the temperature display.
7. Lock the temperature control by pressing and holding the and keys simultaneously for 4 seconds. The display will blink once when the keys are released, informing you that the control was successfully locked. See Section 4.6.
4.9 Sentry II Temperature Control Unit of Measure (Fahrenheit or Celsius)
1. Unlock the temperature control as instructed in Section 4.6.
2. Press and hold the key until the display stops flashing.
3. When the key is released “SHIF” will be displayed.
4. Press and release the key until “UNIT” is displayed.
5. Press and hold the to select °F or the key to select °C.
6. Press and hold the key until the display stops blinking, when released the temperature will be displayed.
7. Lock the temperature control by pressing and holding the and keys simultaneously for 4 seconds. The display will blink once when the keys are released, informing you that the control was successfully locked. See Section 4.6.
Sentry II with Auto-Dosing Assembly Operating Instructions 30 Effective April 1, 2000
Programmed Refrigeration Refrigeration High-Temp Low-Temp
Set Point ON OFF Alarm Alarm
36°F (2.2°C) 37°F (2.8°C) 35°F (1.7°C) 39°F (3.9°C) 33°F (0.6°C) 37°F (2.8°C) 38°F (3.3°C) 36°F (2.2°C) 40°F (4.4°C) 34°F (1.2°C) 38°F (3.3°C)
1
39°F (3.9°C)
1
37°F (2.8°C)
1
41°F (5.0°C)
1
35°F (1.7°C)
1
39°F (3.9°C) 40°F (4.4°C) 38°F (3.3°C) 42°F (5.5°C) 36°F (2.2°C) 40°F (4.4°C) 41°F (5.0°C) 39°F (3.9°C) 43°F (6.0°C) 37°F (2.8°C) 41°F (5.0°C) 42°F (5.5°C) 40°F (4.4°C) 44°F (6.6°C) 38°F (3.3°C)
Page 37
SECTION 5.0 - AUTOMATIC CHEMICAL DOSING
5.1 Initial Start-Up Procedures for Automatic Dosing and Chemical Usage
The chemical usage will vary depending on the make and manufacturer, the amount of water required for each cycle, and the water quality. It is very important to have your Chemical Supplier test the water supply and determine the proper usage and concentrations of each specific chemical. This information should be posted on a cleaning chart near the milk cooler.
IMPORTANT NOTE: Improper chemical usage can cause non-warranted and non-repairable damage to your stainless steel milk cooler. Chemicals should be purchased from a reputable source that specializes in the proper application and usage of dairy cleansers for clean-in-place (CIP) applications.
5.2 Peristaltic Pumps
The peristaltic pumps are controlled by electronic timers and designed to deliver 2.6 milliliters (.0879 oz.) of liquid chemical per second of operation. See Section 5.5 and Tables 3A - 3C.
5.3 Chemical Cautions
Proper safety precautions must be followed when handling chemicals.
Read and abide by all Material Safety Data Sheets (MSDS), labels, instructions, warnings,
and health hazard information provided by the Chemical Manufacturer.
Eye, face, and skin protection should be worn at all times!
Prime peristaltic pumps in a glass jar only. Do not prime the pumps into the milk cooler.
Without proper dilution, chemicals can damage the stainless steel milk cooler.
Never mix chemicals—a deadly gas may be created.
Ensure that all drains are properly trapped to prevent mixed chemical gasses from re-
entering the workplace.
Store chemicals in an area protected from freezing and out of direct sunlight.
Store chemicals in an area that prevents access by children or unauthorized individuals.
Sentry II with Auto-Dosing Assembly Operating Instructions 31 Effective April 1, 2000
WEAR EYE PROTECTION,
RUBBER GLOVES, AND
APRONS WHEN HANDLING
CHEMICALS
!
CAUTION
WEAR EYE PROTECTION,
RUBBER GLOVES, AND
APRONS WHEN HANDLING
CHEMICALS
CORROSIVE
CAUTION
Page 38
5.4 Peristaltic Pump Priming
The peristaltic chemical pumps will require priming upon the initial installation and each time the chemical supply drums are emptied and replaced thereafter. The following procedure provides the proper method of priming each pump:
1. While holding the female barbed fitting stationary, separate the in-line disconnect by pulling the quick-connect down and turning it a 1/2turn counterclockwise.
2. Select the pump to be primed with the priming selector switch located on the top-left corner of the chemical dosing box.
3. Hold a clean glass jar beneath the pump’s discharge line and press the momentary priming switch located on the top-right corner of the chemical dosing box until a solid column of chemical is discharged from the pump into the glass jar.
4. Reconnect the quick-connect fitting by inserting the male end into the female socket and turning
1
/2turn clockwise to lock it into position.
5. Safely dispose of the small amount of chemical in the glass jar.
6. Thoroughly wash all chemical traces from the glass jar and repeat the procedure for the remaining peristaltic chemical pumps.
Figure 29 - Peristaltic Pump Priming
Sentry II with Auto-Dosing Assembly Operating Instructions 32 Effective April 1, 2000
Page 39
5.5 Adjusting Peristaltic Pump Timers for Proper Chemical Concentration
1. Each peristaltic pump is connected to a timer that must be adjusted to provide the proper
concentration of each specific chemical. The peristaltic pumps are designed to deliver 2.6 milliliters (.0879 oz.) of chemical per second.
IMPORTANT: The timers must be readjusted for the proper chemical concentration anytime the type or manufacture of chemical is changed!
2. The timer has 10 switches that will select a predetermined operating time (seconds x 10) for each
peristaltic pump. Multiple switches may be selected for an additive run time to obtain the exact concentration of chemical recommended by the Chemical Supplier. See Figure 30 and Table 2.
Figure 30 - Peristaltic Pump Timer Table 2 - Timer Selections
NOTE: Time is additive when multiple switches are selected in the on position. Multiply the seconds labeled for each switch by 10.
EXAMPLE:
Switch Number 8 and 9 on, all others off.
Switch 8 (12.8 x 10 = 128 seconds) + Switch 9 (25.6 x 10 = 256 seconds).
The peristaltic pump will operate for 384 seconds.
Referencing the Table 3B, 384 seconds will deliver 998.4 ml (33.75 oz.).
SERVICE NOTE: Peristaltic pump hoses should be inspected on a regular basis. Replace every two years or at any time they show signs of cracking or collapsing, or if they become non-pliable.
Using the Chemical Supplier’s concentration recommendations, select the required run time in seconds for each of the cleaning chemicals from Tables 3A - 3C.
Sentry II with Auto-Dosing Assembly Operating Instructions 33 Effective April 1, 2000
Switch Number Seconds of Operation
10 51.2 x 10 = 512 sec.
9 25.6 x 10 = 256 sec.
8 12.8 x 10 = 128 sec.
7 6.4 x 10 = 64 sec.
6 3.2 x 10 = 32 sec.
5 1.6 x 10 = 16 sec.
4 0.8 x 10 = 8 sec.
3 0.4 x 10 = 4 sec.
2 0.2 x 10 = 2 sec.
1 0.1 x 10 = 1 sec.
Page 40
Table 3A - Peristaltic Pump Timing for Specific Chemical Concentrations
(2 - 240 seconds)
Sentry II with Auto-Dosing Assembly Operating Instructions 34 Effective April 1, 2000
Page 41
Table 3B - Peristaltic Pump Timing for Specific Chemical Concentrations
(240 - 478 seconds)
Sentry II with Auto-Dosing Assembly Operating Instructions 35 Effective April 1, 2000
Page 42
Table 3C - Peristaltic Pump Timing for Specific Chemical Concentrations
(478 - 726 seconds)
Sentry II with Auto-Dosing Assembly Operating Instructions 36 Effective April 1, 2000
Page 43
5.6 Determining Water Usage Requirements
The PLC in the Sentry II is supplied with a potentiometer that allows the volume of fill water to be adjusted for each specific installation. As the timer is turned clockwise to increase the volume of wash water, it automatically increases the electric drain time to ensure adequate drainage at the end of each cycle. See Figure 31.
There are two factors that must be considered when determining the amount of water required during the wash cycle:
a. The first requirement is to ensure there is sufficient water to prevent cavitation of the wash pump.
See Table 4 for minimum water requirements.
b. The second requirement is to ensure that there is sufficient water to maintain a minimum drain
temperature of 115°F (46°C) at the end of the hot-detergent wash cycle. The volume of water required to satisfy the minimum drain temperature will vary depending on the surface area and temperature of the milk cooler and the inlet supply water temperature. The installation technician will need to adjust the fill water volume until the minimum drain temperature is achieved for the hot-detergent cycle.
Figure 31 - PLC Fill-Time Potentiometer
Sentry II with Auto-Dosing Assembly Operating Instructions 37 Effective April 1, 2000
The fill-time potentiometer increases or decreases the amount of water admitted for each cleaning cycle.
Turned to the far counterclockwise position, the fill-time is regulated at 3 minutes.
Turned to the far clockwise position, the fill-time is regulated at 15 minutes.
Time the actual fill cycle and refer to Table 5 for calculated water usage.
NOTE: The maximum adjustment rotation for the fill-time potentiometer is less than one turn. Do not force it beyond stops!
Page 44
Table 4 - Minimum Water Requirements (Per Cycle)
5.7 Determining Actual Water Usage
To estimate the actual water usage:
1. Measure the customer’s water supply pressure.
2. Record the actual fill-time of the wash cycle after adjusting the fill-time potentiometer.
3. Refer to the calculated water usage provided in Table 5.
Table 5 - Calculated Water Usage (Fill-Time/Supply Pressure)
Sentry II with Auto-Dosing Assembly Operating Instructions 38 Effective April 1, 2000
Cooler Model Liters U.S. Gallons
400 - 1000 37.9 10.0
1,350 - 2,000 56.8 15.0
2,700 - 3,000 60.6 16.0
4,000 - 5,000 75.7 20.0
6,000 - 8,000 113.6 30.0
Measured Measured Water Supply Pressure (psig)
Fill-Time 15 psig 20 psig 30-50 psig 60 psig
(Minutes) Liters Gallons Liters Gallons Liters Gallons Liters Gallons
3.00 35.89 9.48 42.59 11.25 48.83 12.90 51.10 13.50
4.00 47.85 12.64 56.78 15.00 65.11 17.20 68.14 18.00
5.00 59.81 15.80 70.98 18.75 81.39 21.50 85.17 22.50
6.00 71.77 18.96 85.17 22.50 97.66 25.80 102.21 27.00
7.00 83.73 22.12 99.37 26.25 113.94 30.10 119.24 31.50
8.00 95.70 25.28 113.56 30.00 130.22 34.40 136.27 36.00
9.00 107.66 28.44 127.76 33.75 146.50 38.70 153.31 40.50
10.00 119.62 31.60 141.95 37.50 162.77 43.00 170.34 45.00
11.00 131.58 34.76 156.15 41.25 179.05 47.30 187.38 49.50
12.00 143.54 37.92 170.34 45.00 195.33 51.60 204.41 54.00
13.00 155.50 41.08 184.54 48.75 211.60 55.90 221.45 58.50
14.00 167.47 44.24 198.73 52.50 227.88 60.20 238.48 63.00
15.00 179.43 47.40 212.93 56.25 244.16 64.50 255.52 67.50
Page 45
5.8 Wash Cycle Timing Sequence
The Sentry II provides several programming options for the wash cycles. See Section 6 for detailed information.
Chart 1 - (Detergent Wash or Complete Wash)
NOTE: Fill and drain times are charted with the PLC potentiometer turned to the far counterclockwise position. See Section 5.6 and Figure 31.
Sentry II with Auto-Dosing Assembly Operating Instructions 39 Effective April 1, 2000
Page 46
Chart 2 - (Acid Cycle or Sanitize Cycle)
NOTE: Fill and drain times are charted with the PLC potentiometer turned to the far counterclockwise position. See Section 5.6 and Figure 31.
Sentry II with Auto-Dosing Assembly Operating Instructions 40 Effective April 1, 2000
Page 47
SECTION 6.0 - SENTRY II PLC PROGRAMMING
6.1 Sentry II Programmable Features, Options, and Recommendations
The Sentry II offers the following programming options, allowing the cooling and washing procedures to be customized for each specific installation:
Note 1: Standard program only, not available with Japan program. Note 2: Japan program is programmable for cold or warm sanitize cycle only. Acid cycle temperature is not adjustable.
Sentry II with Auto-Dosing Assembly Operating Instructions 41 Effective April 1, 2000
Programming Selectable Reference
Feature Description and Recommendations Options Section
Cooling Delay Allows the user to initiate a delayed start of the bottom refrigeration 0-120 min. Sec. 6.2
Bottom Unit(s) unit(s) at the onset of the first milking. (1-10)
Select a time delay that will delay the start of the bottom refrigeration unit(s) until an adequate amount of milk has entered the cooler and made contact with the agitator blade.
Cooling Delay Allows the user to initiate a delayed start of the side refrigeration unit(s) 0-120 min. Sec. 6.2
Side Unit(s) at the onset of the second, third, or fourth milking. (11-15)
Select a time delay that will delay the start of the side refrigeration unit(s) until a sufficient amount of milk has entered the cooler to cover 1/3of the side evaporator(s). NOTE: Time starts after bottom unit delay.
Pre-Start Allows the user to pre-start the agitator(s) and refrigeration 30 min. Sec. 6.2 Cooling unit(s) at the onset of the second, third, or fourth milking. Pre-Start or (16-20)
Cooling is disabled at 34°F (1.1°C) for freeze protection. 60 min. Dependent upon fill rate into milk cooler.
Pre-Start Allows the user to pre-start the agitator(s) to blend incoming milk at the 30 min. Sec. 6.2
Agitate Only onset of the second, third, or fourth milking. or (21-25)
Dependent upon fill rate into milk cooler. 60 min.
Interval Allows the user to select an interval agitation time period to ensure proper On-3 min. Sec. 6.2
Agitation agitation of the milk. every 18 min. (26-30)
Timer or
Select 3 minutes every 30 minutes for 1,600 gallon and smaller milk coolers On-3 min. and 3 minutes every 18 minutes for 2,000 gallon and larger milk coolers. every 30 min.
Sample Allows the user to select a time period that ensures adequate agitation for 2, 5, or 10 Sec. 6.2
Agitation proper milk sampling. min. (31-37)
Timer Select 5 minutes for 1,600 gallon and smaller milk coolers and 10 minutes
for 2,000 gallons and larger milk coolers.
Pre-Rinse Allows the user to select the fill water temperature for the Pre-Rinse Cycle. Cold Sec. 6.2
Fill or (38-42)
Temperature Follow your chemical supplier’s recommendations. Warm
Automatic Allows the user to select the option of an automatic Fifth-Cycle at the end On Sec. 6.2
Fifth-Cycle of a complete wash. or (43-47)
(See Note 1). Off (See Note 1).
Cycle Sequence: Pre-Rinse, Rinse, Wash, Post-Rinse, Selectable Fifth Cycle. Normally programmed “On” for acid rinse. Follow your chemical supplier’s recommendations.
Fifth-Cycle Allows the user to select Acid or Sanitizer for the chemical injection during the Acid Sec. 6.2
Acid or Fifth-Cycle. or (48-52) Sanitize Normally programmed for Acid Rinse. Follow your chemical supplier’s Sanitizer (See Note 1).
(See Note 1). recommendations.
Fifth-Cycle Allows the user to select the fill water temperature for the Fifth-Cycle, Acid, Cold Sec. 6.2
Fill Temperature or Sanitize. or (53-57)
(See Note 2). Follow your chemical supplier’s recommendations. Warm (See Note 2).
Full Allows the user to select a 45-minute delayed start for the complete None Sec. 6.2
Wash Automatic Wash Cycle. or (58-62)
Delay Recommended for installations where the milk cooler and milking 45 min.
equipment are normally washed at the same time. The 45-minute delay will allow adequate time for the water heating device to recover, and generate sufficient hot water for washing the milk cooler.
Page 48
6.2 Sentry II - MTA to PLC Programming Procedures
1. Open the hinged door on the PLC.
2. Energize the power supply to the Sentry II Control before proceeding to Step 3.
3. Plug the MTA into the PLC.
CAUTION: Be careful not to touch any terminals, power is applied!
4. The MTA will display:
SENTRY 1 2
5. Press the key twice to select Sentry 2.
The MTA will display:
SENTRY ➞ 1 ■ 2
6. Press the key to enter the selection for the Sentry II Model.
The MTA will display:
SENTRY II
Sentry II with Auto-Dosing Assembly Operating Instructions 42 Effective April 1, 2000
!
Page 49
PROGRAMMING NOTE:
If RETURN TO MENU is displayed at any time, press the ✚ key to return to SENTRY II, and use the to scroll back to the desired programmable option.
7. Press the key to scroll to the first programmable selection, “Bottom Refrigeration Unit Time Delay.”
NOTE: If you scroll past a programming selection, use the key to scroll back to the desired selection.
The MTA will display:
Cond Bottm Unit
8. Press the ✚ key to display the current time delay setting—0-120 minutes.
The MTA will display:
xx Minute Delay
9. Press the ✚ key to increase or the key to decrease the “Bottom Unit Time Delay.”
Sentry II with Auto-Dosing Assembly Operating Instructions 43 Effective April 1, 2000
Page 50
10. Press the key to enter the selected “Bottom Unit Time Delay.”
The MTA will display:
RETURN TO MENU
11. Press the key to return to the main menu.
The MTA will display:
SENTRY II
12. Press the ▼ key, scrolling past the previous programmable selection, to the next option, “Side Unit(s) Delay.”
The MTA will display:
Cond Side Units
13. Press the ✚ key to display the current time delay setting—0-120 minutes.
The MTA will display the current time delay selection:
xx Minute Delay
Sentry II with Auto-Dosing Assembly Operating Instructions 44 Effective April 1, 2000
Page 51
14. Press the key to increase or the key to decrease the “Side Unit(s) Time Delay.”
15. Press the key to enter the selected “Side Unit(s) Time Delay.”
The MTA will display:
RETURN TO MENU
16. Press the key to return to the main menu.
The MTA will display:
SENTRY II
17. Press the key, scrolling past the previous programmable selection, to the next option, “Pre-Start Cooling.”
The MTA will display:
Pre-Start Cool
Sentry II with Auto-Dosing Assembly Operating Instructions 45 Effective April 1, 2000
Page 52
18. Press the ✚ key to display the current settings, 30 or 60 minutes.
19. Press the key to select 60 minutes or the key to select 30 minutes.
20. Press the key to enter the selection.
21. Press the key to return to the main menu.
22. Press the key to scroll to the next option, "Pre-Start Agitation.”
23. Press the ✚ key to display the current settings—30 or 60 minutes.
24. Press the key to select 60 minutes or the key to select 30 minutes.
25. Press the key to enter the selection.
26. Press the key to return to the main menu.
27. Press the key to scroll to the next option, "Agitation Interval Timer.”
28. Press the ✚ key to display the current settings—3 out of every 30 minutes or 3 out of every 18 minutes.
Sentry II with Auto-Dosing Assembly Operating Instructions 46 Effective April 1, 2000
Page 53
29. Press the key to select 3 out of every 30 minutes or the key to select 3 out of every 18 minutes.
30. Press the key to enter the selection.
31. Press the key to return to the main menu.
32. Press the key to scroll to the next option, "Sample Agitation Time.”
33. Press the ✚ key to display the current setting—2, 5, or 10 minutes.
34. Press the key a second time to change the current setting.
35. Press the ▲ or ▼ keys to select the desired time—2, 5, or 10 minutes.
36. Press the key to enter the new setting.
37. Press the key to enter the selection.
38. Press the key to return to the main menu.
Sentry II with Auto-Dosing Assembly Operating Instructions 47 Effective April 1, 2000
Page 54
39. Press the key to scroll to the next option, "Pre-Rinse Temperature.”
40. Press the key to display the current setting, Cold or Warm.
41. Press the key to select Warm or the key to select Cold.
42. Press the key to enter the selection.
43. Press the key to return to the main menu.
44. Press the key to scroll to the next option, "Fifth Cycle On or Off.”
NOTE: This allows the Fifth-Cycle, Acid or Sanitize, to be turned off for specific International requirements.
Pre-Rinse, Rinse, Wash, Rinse, Fifth-Cycle—
On or Off
45. Press the key to display the current setting, On or Off.
46. Press the ✚ key to turn the Fifth-Cycle On, or the key to turn it Off.
47. Press the key to enter the selection.
48. Press the key to return to the main menu.
Sentry II with Auto-Dosing Assembly Operating Instructions 48 Effective April 1, 2000
Japan Program: Skip to Step 53.
Page 55
49. Press the key to scroll to the next option, "Fifth Cycle Acid or Sanitize.”
NOTE: This selects Acid or Sanitize Chemicals for the automatic Fifth Cycle, if selected in the previous programming step.
50. Press the key to display the current setting, Sanitize or Acid.
51. Press the ✚ key to introduce Sanitizer, or the
key to introduce Acid chemicals in the
Fifth-Cycle.
52. Press the key to enter the selection.
53. Press the key to return to the main menu.
54. Press the key to scroll to the next option, "Acid/Sanitize Cycle Fill Temperature.”
Japan Program: “Sanitize Temp.”
55. Press the ✚ key to display the current settings, Cold or Warm.
56. Press the key to select Warm or the key to select Cold.
57. Press the key to enter the selection.
58. Press the key to return to the main menu.
Sentry II with Auto-Dosing Assembly Operating Instructions 49 Effective April 1, 2000
▲▲
Page 56
59. Press the key to scroll to the next option, "Full Wash Delay.”
NOTE: This option allows the Full Automatic Wash Cycle to be delayed for 45 minutes to allow adequate recovery time of the water heating device in specific installations.
60. Press the key to display the current setting, no delay or 45 minute delay.
61. Press the key to select a 45 minute delay or the key to select no delay.
62. Press the key to enter the selection.
63. Press the key to return to the main menu.
64. Press the key to scroll to the next option, "Service Contact.”
65. Press the key to select “Paul Mueller Company.”
66. Consecutively press the key, scrolling through the "Service Contact” information and telephone numbers until “Return to Menu” is displayed.
67. Press the key to return to the main menu.
68. Programming is complete, unplug the MTA from the PLC.
Note: De-energize the power supply to the Sentry II for 5
minutes after making any programming changes.
This will ensure that the changes are stored to the E.Prom of the PLC.
Sentry II with Auto-Dosing Assembly Operating Instructions 50 Effective April 1, 2000
Page 57
6.3 Sentry II Service Reference Form, Programmable Features
Please complete for future service reference:
Mueller Authorized Dealer: End User/Owner:
Name: Name:
Address: Address:
Phone: Phone:
Contact: Contact:
Please check the selected program options:
Description: Options and Selection
Bottom Unit(s) Cooling Delay 0-120 minutes ________ minutes
All Units Cooling Delay 0-120 minutes ________ minutes
Pre-Start Cooling ______ 30 minutes ______ 60 minutes
Pre-Start Agitation ______ 30 minutes ______ 60 minutes
Interval Agitation ______ 3 out of 18 min. ______ 3 out of 30 min.
Sample Agitation ______ 2 minutes ______ 5 minutes ______ 10 minutes
Pre-Rinse Temperature ______ Cold ______ Warm
Fifth-Cycle for Complete Wash ______ On ______ Off ______ n/a Japan Program
Fifth-Cycle (Acid or Sanitize) ______ Acid ______ Sanitize ______ n/a Japan Program
Acid/Sanitize Temperature* ______ Cold ______ Warm
Delayed Start - Complete Wash ______ None ______ 45 minutes
*Selects sanitize temperature only with Japan program.
Sentry Information: Milk Cooler Information:
Part Number/Model: Part Number/Model:
Serial Number: Serial Number:
Comments:
Sentry II with Auto-Dosing Assembly Operating Instructions 51 Effective April 1, 2000
Page 58
SECTION 7.0 - OPERATING INSTRUCTIONS
7.1 General
The Sentry II control system is designed for easy, touch-of-a-button operation with simple visual notification of each operational mode with bright, illuminated indicators.
Please locate the enclosed plastic laminated reference chart, Part No. 8823066, near the Sentry II control. This will provide unfamiliar operators with a quick reference to the basic operation and features of the Sentry II control system.
Figure 32 - Sentry II Operating Controls
7.2 “Cool-Off-Wash” Rotary-Selector Switch
Select “Cool” for cooling modes, “Off” for sample agitation or when the milk cooler is not in use, and “Wash” for cleaning modes.
7.3 Cooling Bottom Units Switch
1. With the rotary selector switch in the “Cool” position, press the “Cooling Bottom Units” switch once to initiate the time-delayed start of the bottom refrigeration unit(s). The lamp will flash until the programmable time-delay expires. After the time delay expires, the lamp will remain on, and the bottom refrigeration unit(s) will energize if the temperature control is calling for cooling. The programmable time delay may be adjusted between 0-120 minutes. See Sections 6.1 and 6.2 (1-10).
2. Pressing the “Cooling Bottom Units” selector switch a second time will by-pass the programmable time delay and immediately start the bottom refrigeration unit(s).
3. To cancel the bottom or all refrigeration unit(s), turn the “Cool-Off-Wash” rotary switch to the “Off” position.
Sentry II with Auto-Dosing Assembly Operating Instructions 52 Effective April 1, 2000
Page 59
7.4 Cooling All Units Switch
1. With the rotary selector switch in the “Cool” position, press the “Cooling All Units” switch once to initiate the time-delayed start of the side refrigeration unit(s). The lamp will flash until the programmable time-delay expires. The programmable time delay may be adjusted between 0-120 minutes. See Sections 6.1 and 6.2 (11-15).
NOTE: The time delay for “Cooling All Units” will not start timing until the “Cooling Bottom Units” time delay expires.
2. After the “Cooling All Units” time delay expires, the lamp will remain on, and the side refrigeration unit(s) will energize if the temperature control is calling for cooling.
3. Pressing the “Cooling All Units” selector switch a second time will by-pass the programmable time delay and immediately start the bottom and side refrigeration units.
4. To cancel all refrigeration units, turn the “Cool-Off-Wash” rotary switch to the “Off” position.
7.5 Pre-Start Cooling Switch
1. With the rotary selector switch in the “Cool” position and “Cooling Bottom Units” and/or “Cooling All Units” in the automatic cool position, press the “Pre-Start Cooling” switch once to initiate an automatic override of the agitator(s) and refrigeration unit(s). The “Pre-Start Cooling” mode may be programmed for 30 or 60 minutes. See Sections 6.1 and 6.2 (16-20).
2. After the programmed time period expires, the refrigeration unit(s) will return to the normal cooling mode.
3. This feature will pre-cool and blend the milk to 34°F (1.1°C) at the onset of the second, third, or fourth milkings.
4. To cancel “Pre-Start Cooling” press the switch a second time.
7.6 Pre-Start Agitator Switch
1. With the rotary selector switch in the “Cool”position and “Cooling Bottom Units” and/or “Cooling All Units” in the automatic cool position, press the “Pre-Start Agitator” switch once to initiate manual agitation for programmed period of 30 or 60 minutes. See Section 6.1 and 6.2 (21-25).
2. This feature blends the warm incoming milk at the onset of the second, third, or fourth milkings.
3. To cancel “Pre-Start Agitation” press the switch a second time.
Sentry II with Auto-Dosing Assembly Operating Instructions 53 Effective April 1, 2000
Page 60
7.7 Detergent Cycle Switch
1. With the rotary selector switch in the “Wash” position, press the “Detergent Cycle” switch once to start the automatic wash cycle.
2. The “Detergent Cycle” offers two programmable-cycle options:
• “Pre-Rinse—Rinse—Detergent—Post-Rinse” (Standard and Japan program)
• “Pre-Rinse—Rinse—Detergent—Post-Rinse—Acid/Sanitize” (Standard program only) See Sections 5.8, 6.1, and 6.2 (43-57).
3. The Pre-Rinse and Acid/Sanitize Cycles may be programmed for warm or cold fill water temperature. See Sections 5.8, 6.1, and 6.2 (38-57).
4. A programmable 45-minute delayed start is available to allow sufficient recovery time for the water-heating device. See Sections 6.1 and 6.2 (58-62).
5. To cancel and reset the “Wash Cycle,” turn the “Cool-Off-Wash” rotary switch to the “Off” position.
7.8 Acid Cycle Switch
1. With the rotary selector switch in the “Wash” position, press the “Acid Cycle” switch once to start a “Rinse—Acid” cycle. (Japan program starts a “Pre-Rinse—Hot Acid—Post-Rinse” cycle.) See Section
5.8, Chart 2.
2. To cancel and reset the “Acid Cycle,” turn the “Cool-Off-Wash” rotary switch to the “Off” position.
7.9 Sanitize Cycle Switch
1. With the rotary selector switch in the “Wash” position, press the “Sanitize Cycle” switch once to
start a “Sanitize” cycle. See Section 5.8, Chart 2.
2. To cancel and reset the “Sanitize Cycle,” turn the “Cool-Off-Wash” rotary switch to the “Off”
position.
7.10 Agitate Sample Switch
1. With the rotary selector switch on the “Off” position, press the “Agitate Sample” switch once to
start the agitator(s) for milk sampling. The agitator(s) will operate for the programmed period of 2, 5, or 10 minutes, and shut off automatically. See Sections 6.1 and 6.2 (31-37).
2. To cancel “Agitate Sample” press the switch a second time.
7.11 Alarm Lamp
1. The “Alarm Lamp” provides visual aid of the following alarm conditions:
a. Flashing at 11/2second intervals—The milk temperature is above a safe holding temperature.
b. Flashing at 1/2second intervals—The milk temperature is below a safe holding temperature
and near freezing. (Call a Mueller Authorized Service Technician.)
c. Constant illumination—Wash water did not enter the milk cooler within 2 minutes of a fill
cycle. (Call a Mueller Authorized Service Technician.)
2. To test the “Alarm Lamp,” turn the rotary selector switch to the “OFF” position and press the
“Detergent Cycle” switch.
Sentry II with Auto-Dosing Assembly Operating Instructions 54 Effective April 1, 2000
Page 61
7.12 Milk Temperature Display
The milk temperature display provides a digital readout of the product temperature. To ensure calibration accuracy and safe product holding temperatures, check and compare the actual product temperature with an accurate secondary thermometer on a regular basis. See Sections 4.6 - 4.10.
7.13 Cooling Override Switch (Emergency Use Only)
1. The Sentry II has an emergency override switch located inside the enclosure. This will override the temperature control and several other components and engage the bottom refrigeration unit(s) and agitator(s) in an emergency situation.
2. To access and activate this switch, turn the power off to the Sentry II control box, open the door and move this switch to the “Manual” position. Close the door, turn selector switch to the “Cool” position, and reapply power.
IMPORTANT NOTE: There will be no automatic temperature control in the “Manual Over-Ride Position.” When the product temperature is at a safe holding temperature, turn the power supply off to the Sentry II control. (This is for emergency cooling only and an authorized Mueller Technician should be contacted for immediate service.)
Sentry II with Auto-Dosing Assembly Operating Instructions 55 Effective April 1, 2000
Page 62
SECTION 8.0 - WEIGHTS AND DIMENSIONS
8.1 English Weights and Dimensions
Dimensions not to be used for construction unless certified.
1
Actual calibration capacity may exceed certified capacity
2
Minimum and maximum clearance under the milk cooler with standard adjustable legs.
3
Approximate weight measured in pounds (includes agitator(s), pump assembly, and controls).
Sentry II with Auto-Dosing Assembly Operating Instructions 56 Effective April 1, 2000
Revised February 5, 2001
Capacity
1
ABCDE F GH2J No. of Weight
3
Model (gallons) (inches) (inches) (inches) (inches) (inches) (inches) (inches) (inches) (inches) Legs (Empty)
O-500 500 78 61 37.25 51 63.75 18 42 4-5 8.25 4 934
O-600 600 90 61 37.25 51.25 64 18 54 4-5 8.25 4 1,044
O-800S 800 80 71.25 50 60.75 73.5 18 44 4-8 8.25 4 1,284
O-1000S 1,000 102 71.25 50 61.25 74 18 33 4-8 8.25 6 1,530
O-1000D 1,000 102 71.25 50 61.25 74 18 33 4-8 8.25 6 1,576
O-1350 1,350 102 80 48.25 69.125 82 18 33 7-9 8.25 6 1,770
O-1600 1,600 120 80 48.25 69.5 82.25 18 42 7-9 8.25 6 1,988
O-2000 2,000 155 80 48.25 70.25 83 17.5 40 7-9 8.25 8 2,432
O-2700 2,700 155 90.5 48.25 70.25 83 17.5 40 7-9 8.25 8 3,220
O-3000 3,000 176 90.5 55 79.375 92.25 18 35 7-9 8.25 10 3,792
O-4000 4,000 196 97.625 58 86.25 99 18 32 7-9 8.25 12 5,982
O-5000 5,000 196 108 62 93.675 106.25 18 32 7-9 5.375 12 6,282
O-6000 6,000 196 119 72 99.375 112.25 12.25 24.5 7.9 5.375 16 6,792
O-7000 7,000 196 127 78 106.5 119.25 12.25 24.5 7-9 5.375 16 6,912
O-8000 8,000 228 126.3125 78 107.125 119.25 12 25.5 7-9 5.375 18 7,744
Page 63
8.2 Metric Weights and Conversions
Dimensions not to be used for construction unless certified.
1
Actual calibration capacity may exceed certified capacity
2
Minimum and maximum clearance under the milk cooler with standard adjustable legs.
3
Approximate weight measured in kilograms (includes agitator(s), pump assembly, and controls).
Sentry II with Auto-Dosing Assembly Operating Instructions 57 Effective April 1, 2000
Capacity1ABCDE FGH2J No. of Weight
3
Model (liters) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) Legs (Empty)
O-500 1,893 1981.2 1549.4 946.2 1295.4 1619.3 457.2 1066.8 101-127 209.6 4 424
O-600 2,271 2286.0 1549.4 946.2 1301.8 1625.6 457.2 1371.6 101-127 209.6 4 474
O-800S 3,028 2032.0 1809.8 1270.0 1543.1 1866.9 457.2 1117.6 101-203 209.6 4 582
O-1000S 3,785 2590.8 1809.8 1270.0 1555.8 1879.6 457.2 838.2 101-203 209.6 6 694
O-1000D 3,785 2590.8 1809.8 1270.0 1555.8 1879.6 457.2 838.2 101-203 209.6 6 715
O-1350 5,110 2590.8 2032.0 1225.6 1755.8 2082.8 457.2 838.2 178-229 209.6 6 803
O-1600 6,057 3048.0 2032.0 1225.6 1765.3 2089.2 457.2 1066.8 178-229 209.6 6 902
O-2000 7,571 3937.0 2032.0 1225.6 1765.3 2108.2 444.5 1016.0 178-229 209.6 8 1,103
O-2700 10,221 3937.0 2298.7 1397.0 2006.6 2333.6 444.5 1016.0 178-229 209.6 8 1,461
O-3000 11,356 4470.4 2298.7 1397.0 2016.1 2343.2 457.2 889.0 178-229 209.6 10 1,720
O-4000 15,142 4978.4 2479.7 1473.2 2190.8 2514.6 457.2 812.8 178-229 209.6 12 2,713
O-5000 18,927 4978.4 2743.2 1574.8 2371.7 2698.8 457.2 812.8 178-229 136.5 12 2,849
O-6000 22,712 4978.4 3022.6 1828.8 2524.1 2851.2 311.2 622.3 178-229 136.5 16 3,081
O-7000 26,498 4978.4 3225.8 1981.2 2705.1 3029.0 311.2 622.3 178-229 136.5 16 3,135
O-8000 30,283 5791.2 3208.3 1981.2 2721.0 3029.0 304.8 647.7 178-229 136.5 18 3513
Page 64
SECTION 9.0 - SENTRY II REPLACEMENT PARTS
9.1 Sentry II Replacement Parts Drawing, Main Control
Sentry II with Auto-Dosing Assembly Operating Instructions 58 Effective April 1, 2000
Page 65
9.2 Sentry II Replacement Parts List, Main Control
Sentry II with Auto-Dosing Assembly Operating Instructions 59 Effective April 1, 2000
ITEM PART NO. DESCRIPTION
1 8822971 TRANSFORMER, 240/24 VAC, 75 VA (SEE ITEM 2 FOR 195 VAC)
2 8823060 TRANSFORMER, 195/24 VAC, 150 VA
3 8823007 RELAY, DPST, 240 VAC COIL, 30 AMP, NO
4 8822995 TEMPERATURE CONTROLLER, THERMOCOUPLE INPUT, 2 RELAY OUTPUT
5 8822988 INDICATOR LIGHT, 24 VAC, RED
6 8822989 PUSH-BUTTON SWITCH, LIGHTED, 24 VAC, GREEN
7 8822990 PUSH-BUTTON SWITCH, LIGHTED, 24 VAC, AMBER
8 8822991 PUSH-BUTTON SWITCH, LIGHTED, 24 VAC, BLUE
9 8822992 RELAY, 4PDT, 24 VAC, 14 PIN
10 8822993 RELAY, SOCKET, 14 PIN
11A 8823313 PROGRAMMABLE CONTROLLER, PLC, FACTORY PROGRAMMED (US)
11B 8823314 PROGRAMMABLE CONTROLLER, PLC, FACTORY PROGRAMMED (JAPAN)
12 8822985 TERMINAL STRIP, FUSED
13 8822983 FUSE CARTRIDGE, 1 AMP, 250V BUSS MDL-1
14 8822984 FUSE CARTRIDGE, 2 AMP, 250V BUSS MDL-2
15 8820704 FUSE CARTRIDGE, 3 AMP, 250V BUSS AGC-3
16 8800086 TOGGLE SWITCH, DPST, 10 AMP
17 8822981 SELECTOR SWITCH, 3 POSITION ROTARY
18 8823011 SPACER, .375" OD X 1.50" LG, NYLON
19 8822927 TERMINAL BLOCK, INSULATOR
20 8808268 REPLACEMENT BULB, 24 VAC
21 8820165 THERMOCOUPLE, 50 FEET
22 8822013 CABLE, PLC TO MTA HAND-HELD INTERFACE PROGRAMMER
23 8822179 MTA, HAND-HELD INTERFACE PROGRAMMER WITH CABLE (U.S. PROGRAM)
24 8823315 MTA, HAND-HELD INTERFACE PROGRAMMER WITH CABLE (JAPAN PROGRAM)
25 8820166 THERMOCOUPLE EXTENSION WIRE, 20/2 TYPE “T” (PURCHASED BY THE FOOT)
26 8822361 NUT, WIRE, ALL PLASTIC FOR THERMOCOUPLE CONNECTIONS
Page 66
9.3 Sentry II Replacement Parts Kit, Dosing and Manifold Box
Sentry II with Auto-Dosing Assembly Operating Instructions 60 Effective April 1, 2000
Page 67
9.4 Sentry II Replacement Parts List, Dosing and Manifold Box
Sentry II with Auto-Dosing Assembly Operating Instructions 61 Effective April 1, 2000
ITEM PART NO. DESCRIPTION
1A 8823002 BOX ASSEMBLY DOSING, SENTRY II (INCLUDES ITEMS 1-14), STANDARD LABEL
1B 8823365 BOX ASSEMBLY DOSING, SENTRY II (INCLUDES ITEMS 1-14), JAPANESE LABEL
2 8822996 TIMER, 230 VAC, 1-1023 SECONDS, DIP SWITCH SELECTABLE
3 8822997 SWITCH, TOGGLE, SPST, OFF/ON/MOMENTARY
4 8822998 SWITCH, TOGGLE, SPTT, ON/ON/ON
5 31381 WASHER, LOCK, TOGGLE SWITCH
6 31382 RING, LOCK, TOGGLE SWITCH
7 3995 BOOT, RUBBER, TOGGLE SWITCH
8 8822978 TERMINAL STRIP, 8 POLE
9 8822976 GEAR MOTOR, 230-VAC, 50/60-HZ, 58-RPM INTERMITTENT DUTY
10A 8822977 KIT, PERISTALTIC PUMP (INCLUDES HOUSING, COVER, ROLLER BRACKET, & .25" NORPRENE HOSE)
10B 8823710 .25" X 9" NORPRENE HOSE
11 8823011 SPACER, .375" OD X 1.5" LG. X .171" ID, NYLON
12 3200128 SCREW, MACHINE, .25-20NC X 1", 18-8 S/S
13 8822974 SCREW, MACHINE, 8-32 NC X 2.25", 18-8 S/S
14 8823030 TERMINAL BLOCK INSULATOR
15 8823021 ADAPTER, BARBED MALE
16 8823019 ELBOW, POLYPROPYLENE, 90 DEGREE X .25" BARB X .25" BARB
17 8823041 TUBE, .375" OD X .25" ID (CLEAR PVC)
18 8823042 TUBE, .375" OD X .25" ID (BLUE PVC)
19 8823043 TUBE, .375" OD X .25" ID (RED PVC)
20 8823068 HOSE CLAMP, PLASTIC, RYAN
21 8823236 BOX ASSEMBLY, MANIFOLD SOLUTION (INCLUDES ITEMS 22 - 33)
22 8823071 VALVE, SOLENOID, DUAL, 24-VAC
23 505263 CORD GRIP
24 3690 NUT LOCK CONDUIT
25 8823239 MANIFOLD, SOLUTION
26 8823614 SWITCH, PRESSURE, 5 PSI
27 8823602 ADAPTER HOSE, .5" MPT X .5" HOSE BARB
28 8823240 VALVE, CHECK, .25" MPT X .25" FPT
29 8823709 REDUCER, .25-18 NPT TO .25 UNF
30 8823241 COUPLING, QUICK CONNECT, BODY, .5" NPT
31 8823244 ADAPTER, THREADED, FEMALE
32 8823070 HOSE, .5" ID
33 30423 CLAMP, HOSE, S/S
34 30581 HOSE, .375" ID
35 93590 HOSE ASSEMBLY, WATER (INCLUDES HOT AND COLD HOSE, AND BACK FLOW PREVENTER)
36 8823243 COUPLING, QUICK CONNECT, INSERT, BARBED
37 8823301 COIL, SOLENOID, 24 VAC (REPLACEMENT ONLY)
Page 68
9.5 Sentry II Replacement Parts Kit, Pump Assembly
Sentry II with Auto-Dosing Assembly Operating Instructions 62 Effective April 1, 2000
Page 69
9.6 Sentry II Replacement Parts List, Pump Assembly
Sentry II with Auto-Dosing Assembly Operating Instructions 63 Effective April 1, 2000
ITEM QTY PART NO. DESCRIPTION
1A 1 30455 MOTOR, ELECTRIC, .75 HP, 208-230/50-60/1
1B 1 8823665 MOTOR, ELECTRIC, .75 HP, STAINLESS STEEL, 208-230/50-60/1
1C 1 30456 MOTOR, ELECTRIC, 1.5 HP, 208-230/50-60/1
1D 1 8823666 MOTOR, ELECTRIC, 1.5 HP, STAINLESS STEEL, 208-230/50-60/1
2 1 3909 SEAL, SHAFT
3A 1 31195 IMPELLER, 4.25" OD (.75 HP)
3B 1 8802751 IMPELLER, 5" OD (1.5 HP)
4 1 8823074 VALVE, DRAIN, 24 VAC, COIL
5 1 8823300 COIL, DRAIN, VALVE, 24 VAC
6 1 30419 ADAPTER, OUTLET, NEOPRENE, 2" X 2"
7 1 8823058 SCREEN, DRAIN VALVE
8A 1 8822415 SEAL, RETAINER (.75 HP)
8B 1 8822202 SEAL, RETAINER (1.5 HP)
9A 1 30690 GASKET, PUMP HOUSING, 6.625" OD (.75 HP)
9B 1 30691 GASKET, PUMP HOUSING, 8.125" OD (1.5 HP)
10A 1 8823672 PUMP, SUCTION HOUSING (300- TO 600-GALLON MILK COOLER)
10B 1 8823673 PUMP, SUCTION HOUSING (800- TO 1,600-GALLON MILK COOLER)
10C 1 8823678 PUMP, SUCTION HOUSING (2,000- TO 8,000-GALLON MILK COOLER)
11 1 8823232 CONNECTOR, CONDUIT, .375", 90°
12 1 8820593 WASHER, NEOPRENE
13 1 8822085 NUT, LOCK, CONDUIT, .5", NYLON
14 1 8823233 CONNECTOR, CONDUIT, .375", STRAIGHT
15 2LF 8823337 CONDUIT, FLEX, .375", LIQUID TIGHT
16 1 505263 CORD, GRIP, .25" - .375"
17 1 8823231 ELBOW, RUBBER, 45°, 1" ID X 1.375" OD
18 2 30420 CLAMP HOSE, STAINLESS STEEL
Page 70
SECTION 10.0 - SENTRY II EQUIPMENT MARKINGS
10.1 Label No. 8822229, Lock Out
10.2 Label No. 8820482, Caution - Disconnect Power and Retain Latch
10.3 Label No. 8820623, Warning Symbol - Electrical
10.4 Label No. 8805616, Manual - Run Position
Sentry II with Auto-Dosing Assembly Operating Instructions 64 Effective April 1, 2000
LOCK OUT
HERE
BEFORE ENTERING TANK
DISCONNECT POWER TO AGITATOR. REMOVE AND
RETAIN COVER LATCH.
8820482
CAUTION
!
MANUAL
8805616
Page 71
10.5 Label No. 8820248, Auto - Automatic Run Position
10.6 Label No. 8823064, Acid - Timer
10.7 Label No. 8823063, Detergent - Timer
10.8 Label No. 8823065, Sanitize - Timer
10.9 Label No. 8822584, Pump Motor - Wire Marker
10.10 Label No. 8802375, Agitator(s) - Wire Marker
10.11 Label No. 3791, Hot - Water Valve Marker
Sentry II with Auto-Dosing Assembly Operating Instructions 65 Effective April 1, 2000
AUTO
8820248
Acid
8823064
Detergent
8823063
Sanitize
8823065
PUMP MOTOR
8822584
HOT
3791
AGITATOR(S)
8802375
Page 72
10.12 Label No. 8823609, Warning - Manifold Box
10.13 Label No. 8823013, Warning - Disconnect Power Before Servicing
10.14 Label No. 8801150, Warning - Disconnect Power Before Servicing
Sentry II with Auto-Dosing Assembly Operating Instructions 66 Effective April 1, 2000
DISCONNECT SENTRY II
®
CONTROL CABINET FROM
MAIN POWER SUPPLY
BEFORE SERVICING.
8908 8823013
WARNING
!
Disconnect both condensing unit and Mueller Matic
®
control cabinet from main power supply before servicing.
Antes de empezar a dar servicio o reparar la unidad condensadora o el gabinete de control del Mueller Matic
®
, es indispensable desconectarios del suministro de corriente eléctrica.
Separez l’unité réfrigérant et la cabine de contrôle du systéme Mueller Matic
®
du câble de
distribution avant de réparer.
8801150
WARNING
!
PELIGRO
!
ADVERTISSEMENT
!
Page 73
10.15 Part No. 8822225, CE Data Tag (U.K. Models Only)
10.16 Label No. 8820410, Data Tag (U.K. Models Only)
10.17 Label No. 30612, Notice - Chart Accuracy
Sentry II with Auto-Dosing Assembly Operating Instructions 67 Effective April 1, 2000
PAUL MUELLER COMPANY
MILK COOLER
MODEL PART NO. SERIAL NO.
NOMINAL CAPACITY WEIGHT, EMPTY
VOLTS HERTZ PHASE F.L.A.
Note: For electrical characteristics of condensing unit, refer to
condensing unit data plate.
ISO PERFORMANCE CLASS REFRIGERANT
8820410
litres
kg.
®
Paul Mueller Company • 1600 W. Phelps • P.O. Box 828 • Springfield, Missouri 65801-0828, U.S.A.
Year of Construction Model Number Serial Number Noise Level Weight
6911 8822225
Notice
The accuracy of these charts depends upon the proper installation of the cooler.
Follow the detailed “leveling” instructions carefully. Check the level indicator and test gauge reading before use. Improper installation could result in claims by the buyer or seller of the milk against the party making the installation.
6911 30612
®
Page 74
10.18 Label No. 8820454, Dry Nitrogen Holding Charge
10.19 Label No. 8805299, Warning - HCFC Class II Refrigerant (To Be Applied After Installation)
10.20 Label No. 30737, Bottom Temp-Plate
Sentry II with Auto-Dosing Assembly Operating Instructions 68 Effective April 1, 2000
THIS EQUIPMENT CONTAINS R-22 HYDROCHLOROFLUOROCARBON (HCFC CLASS II)
A SUBSTANCE THAT, IF RELEASED INTO THE ENVIRONMENT, WILL CONTRIBUTE TO A SERIOUS PUBLIC HEALTH AND ENVIRONMENTAL PROBLEM BY DEPLETING THE OZONE LAYER. OZONE LAYER DEPLETION INCREASES THE RISK OF SKIN CANCER AND OTHER DISEASES IN HUMANS AND IS HARMFUL TO PLANT AND ANIMAL LIFE.
THIS EQUIPMENT SHALL BE SERVICED AND DISPOSED OF ONLY IN ACCORDANCE WITH THE
OZONE DEPLETING
SUBSTANCES REGULATION - CLEAN ENVIRONMENT ACT.
N.B. This regulation is consolidated to September 30, 1992.
LE PRÉSENT ÉQUIPMENT CONTIENT R-22 HYDROCHLOROFLUOROCARBON (HCFC CLASS II)
UNE SUBSTANCE QUI, LORSQU’ÉMISE DANS L’ENVIRONNEMENT, CONSTITUE UN SÉRIEUX DANGER `A LA SANTÉ PUBLIQUE ET
`
A L’ENVIRONNEMENT EN APPAUVRISSANT LA COUCHE D’OZONE. L’APPAUVRISSEMENT DE LA COUCHE D’OZONE
AUGMENTE LES RISQUES DE CANCER DE LA PEAU ET D’AUTRES MALADIES CHEZ LES HUMAINS ET CONSTITUE UN DANGER
`
A LA VIE VÉGÉTALE ET ANIMALE.
LE PRÉSENT ÉQUIPEMENT EST MIS EN SERVICE ET N’EST ÉLIMINÉ QU’EN CONFORMITÉ DU
RÉGLEMENT SUR LES
SUBSTANCES APPAUVRISSANT LA COUCHE D’OZONE - LOI SUR L’ASSAINISSEMENT DE L’ENVIRONNEMENT.
N.B. Le présent réglement est refondu au 30 septembre 1992.
ESTE EQUIPO CONTIENE FLUOROCARBURO HIDROCLORADO R-22 (HCFC CLASS II)
(Escriba el nombre de la substancia empobrecedora de la capa de ozono.) UNA SUBSTANCIA QUE, SI SE SUELTA AL MEDIO AMBIENTE, CONSTITUIRA UN SERIO PELIGRO PARA EL AMBIENTE Y LA
SALUD PUBLICA AL EMPOBRECER LA CAPA DE OZONO. EL EMPOBRECIMIENTO DE LA CAPA DE OZONO AUMENTA EL RIESGO DE CANCER A LA PIEL Y OTRAS ENFERMEDADES EN LOS SERES HUMANOS Y ES TAMBIEN DAÑINO PARA LA VIDA DE LAS PLANTAS Y LOS ANIMALES.
EL MANTENIMIENTO Y LA ELIMINACION DE ESTE EQUIPO SOLO SE PODRA REALIZAR EN CUMPLIMIENTO CON
LAS NORMAS SOBRE LAS SUBSTANCIAS EMPOBRECEDORAS DE LA CAPA DE OZONO - LEY PARA LA CONSERVACION DEL AMBIENTE LIMPIO.
N.B. La presente norma se ha consolidado hasta el 30 de septiembre de 1992.
8805299
WARNING
!
IMPORTANT
THIS EQUIPMENT CONTAINS A HOLDING CHARGE OF DRY NITROGEN GAS. SLOWLY RELEASE PRESSURE THROUGH SERVICE PORTS OR SCHRADER VALVES BEFORE REMOVING FITTINGS.
EVACUATE THE SYSTEM TO 500 MICRONS BEFORE CHARGING WITH REFRIGERANT. DISCARD THIS TAG UPON CHARGING SYSTEM WITH REFRIGERANT AND APPLY A SYSTEM REFRIGERANT SPECIFICATION DECAL.
NOTE: IT IS THE TECHNICIAN’S RESPONSIBILITY TO COMPLY WITH ALL CURRENT REFRIGERANT USAGE REGULATIONS.
(11/94) 8820454
BOTTOM TEMP-PLATE
30737
®
Page 75
10.21 Label No. 8822972, Transformer Wiring
10.22 Label No. 8822705, Canadian and U.S. Certification
10.23 Label No. 8822948, 24 and 240 VAC Component List
Sentry II with Auto-Dosing Assembly Operating Instructions 69 Effective April 1, 2000
LR67608
NPI 8822705
240V 208V COM
X4 X2 X3 X1
H1 H2
®
DAIRY FARM EQUIPMENT
®
DAIRY FARM EQUIPMENT
9910 8822972
Standard Transformer
Part No. 8822971 (240V)
Japanese Transformer
Part No. 8823060 (195V)
24V
195V
240V
24V
3 Remote Alarm Lamp (24 VAC) 4 Remote Cool Lamp (24 VAC) 5 Remote Wash Lamp (24 VAC) 6 Condensing Unit 1 (24 VAC) 7 Condensing Unit 2 (24 VAC) 8 Drain Valve (24 VAC) 9 Hot Water Solenoid (24 VAC)
10 Cold Water Solenoid (24 VAC)
2 Neutral (24 VAC) 11 Pressure Switch (N.O.) 12 Pressure Switch (N.O.) 13 Detergent Pump (240 VAC) 14 Acid Pump (240 VAC) 15 Sanitize Pump (240 VAC) 16 Pump Motor (240 VAC) 17 Pump Motor (240 VAC) 18 Agitator Motor (240 VAC) 19 Agitator Motor (240 VAC) L1 Main Power (240 VAC) L2 Main Power (240 VAC)
0003 8822948
Page 76
10.24 Label No. 8820409, Mueller Name Tag
10.25 Label No. 8822980, Programmable Controller Name Tag
10.26 Label No. 8822558, Mueller Milk Cooler Data Tag
Sentry II with Auto-Dosing Assembly Operating Instructions 70 Effective April 1, 2000
8820409
PLC Part No. 8823313
(9907) 8822980
Page 77
10.27 Label No. 30890, Mueller Data Tag - Control Box
10.28 Label No. 8820677, Ground Symbol
10.29 Label No. 3792, Cold - Water Valve Marker
10.30 Label No. 30397, Stainless Steel Symbol
Sentry II with Auto-Dosing Assembly Operating Instructions 71 Effective April 1, 2000
®
PRODUCT
MODEL NUMBER PART NUMBER SERIAL NUMBER
VOLTS HERTZ PHASE FLA
DISCONNECT MAIN POWER SUPPLY BEFORE SERVICING.
6911 ROMPRE LE CABLE DE DISTRIBUTION AVANT DE REPARER 30890
COLD
3792
®
®
Stainless
Steel
Page 78
10.31 Label No. 30166, Caution - Vent Must Be Over Milk Inlet
10.32 Label No. 8820508, Hot - Tube Marker
10.33 Label No. 8802777, Caution - Do Not Sanitize
VENT ASSEMBLY MUST BE OVER MILK INLET AT ALL TIMES.
EL ENSAMBLAJE DE VENTEO DEBE ESTAR SOBRE LA ENTRADA DE LA LECHE EN TODO MOMENTO.
30166
CAUTION
¡
CUIDADO!
Sentry II with Auto-Dosing Assembly Operating Instructions 72 Effective April 1, 2000
!
!
HOT
8820508
Do not sanitize your cooler with solutions containing
in excess of 200 parts per million of chlorine.
Do not mix sanitizers or any chlorine containing
substances with acid as this will result in damage to
the stainless steel surface and can generate a gas
that is lethal to your health.
Do not exceed 170°F(76°C) during the wash cycles.
8905 8802777
CAUTION
!
Page 79
10.34 Label No. 8823146, Terminal Block - 24 VAC - 240 VAC
10.35 Label No. 8823263, Terminal Block - 240 VAC
Sentry II with Auto-Dosing Assembly Operating Instructions 73 Effective April 1, 2000
13 Detergent Pump (240v AC) 14 Acid Pump (240v AC) 15 Sanitize Pump (240v AC) L1 Main Power (240v AC) L2 Main Power (240v AC) 20 Used for Internal Wiring (240v AC) 21 Used for Internal Wiring (240v AC) 22 Used for Internal Wiring (240v AC)
9904 8823263
Page 80
SECTION 11.0 - SAFETY
Note: See all safety, warning, and caution labels displayed in Section 10.
11.1 General
1. The Mueller milk cooler and Sentry II control system should be operated by qualified personal who are familiar with the equipment and instructions.
2. Improper handling, operation, or service of the equipment, cleaning chemicals, and/or electricity can create a health hazard and possible non-warranted damage to the equipment.
3. An authorized Mueller Service Representative who is trained and certified in electrical and refrigeration work must perform all service.
4. The equipment can start automatically! Use extreme caution when servicing. All guards and covers must be in place during operation to prevent mechanical and electrical hazards.
11.2 Manway
1. The Mueller milk cooler manway is supplied with a lock-out cover to prevent entry during operation. Ensure that this is securely locked during operation.
2. Disconnect the power supply before entering the milk cooler. Follow “Confined Entry” laws and regulations when entering the milk cooler.
Sentry II with Auto-Dosing Assembly Operating Instructions 74 Effective April 1, 2000
Page 81
SECTION 12.0 - DISPOSAL
12.1 General
If the milk cooler and controls are removed from the installation site, ensure the materials, refrigerants, and chemicals are handled and/or disposed of according to applicable codes and regulations.
12.2 Chemical Disposal
All detergents, acids, sanitizers, refrigerants, and oils can be harmful and toxic to the environment if not properly disposed of. Consult each chemical label and comply with all local environmental regulations and agencies.
12.3 Solid Component Disposal
The milk cooler’s basic components consist of steel, copper, rubber, and plastics which may be separated and recycled. The “CFC-Free” foam insulation should be disposed of according to local environmental regulations and agencies.
Sentry II with Auto-Dosing Assembly Operating Instructions 75 Effective April 1, 2000
Page 82
Sentry II Service Reference Form, Programmable Features
Please detach, complete, and leave in Sentry II control box for future reference.
Mueller Authorized Dealer: End User/Owner:
Name: Name:
Address: Address:
Phone: Phone:
Contact: Contact:
Please check the selected program options:
Description: Options and Selection
Bottom Unit(s) Cooling Delay 0-120 minutes ________ minutes
All Units Cooling Delay 0-120 minutes ________ minutes
Pre-Start Cooling ______ 30 minutes ______ 60 minutes
Pre-Start Agitation ______ 30 minutes ______ 60 minutes
Interval Agitation ______ 3 out of 18 min. ______ 3 out of 30 min.
Sample Agitation ______ 2 minutes ______ 5 minutes ______ 10 minutes
Pre-Rinse Temperature ______ Cold ______ Warm
Fifth-Cycle for Complete Wash ______ On ______ Off ______ n/a Japan Program
Fifth-Cycle (Acid or Sanitize) ______ Acid ______ Sanitize ______ n/a Japan Program
Acid/Sanitize Temperature* ______ Cold ______ Warm
Delayed Start - Complete Wash ______ None ______ 45 minutes
*Selects sanitize temperature only with Japan program.
Sentry Information: Milk Cooler Information:
Part Number/Model: Part Number/Model:
Serial Number: Serial Number:
Comments:
Sentry II Operating Instructions Effective April 1, 2000
Page 83
P.O. Box 828 • Springfield, Missouri 65801-0828, U.S.A. Phone: (417) 831-3000 • 1-800-MUELLER • Fax: 1-800-436-2466 www.muel.com • E-mail: dairyfarm@muel.com
International Inquiries - Fax: (417) 831-6906 • E-mail: international@muel.com
®
(2/00) 8823644
Loading...