insERtion instRUctions ManUaL
®
MUELLER
Improved, Centurion Series, Modern Improved,
®
Centurion Series Fire Hydrant – Adding an Extension 2-3
Improved Fire Hydrant – Inserting Extension Section (All Models Prior to 1962) 4-5
Improved Fire Hydrant – Inserting Extension Section (Sealed Oil Reservoir 1962 Style) 6-7
Improved Fire Hydrant – Inserting Extension Section with Steel Stem Coupling (Sealed Oil Reservoir 1962 Style) 8-9
Modern Improved Fire Hydrant – Inserting Extension Section 10-11
107 Inserting Extension Section 12-13
TABLE OF CONTENTS PAGE
®
Fire Hydrant –
and 107
Inserting Extension Sections – Notes 14-15
Fire Hydrants
Reliable Connections
Inserting Extension Sections
moreinfo@muellercompany.com
!
WARNING: Before working on, or disassembling the Hydrant (including removing any bolts(s) holding the Hydrant together), shut off gate valve to isolate
Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant - bleed off any pressure, then
remove nozzle cap completely. Open Hydrant main valve completely. A continuous ow of water, no matter how slight, indicates Hydrant is not properly isolated from
the main water supply, and that problem must be corrected before any Hydrant disassembly can proceed. Disassembly of Hydrant with pressurized water acting against the main valve could result in unexpected ejection of Hydrant parts, debris or high-pressure water stream, which could cause serious bodily injury.
Customer Service Center
Decatur, Illinois
800.423.1323
www.muellercompany.com
TM
Page 2
MUELLER
®
Centurion
®
Series Fire Hydrant
Adding an Extension
!
WARNING: Before removing any bolt(s) holding the Hydrant together, shut off gate valve to isolate Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant
– bleed off any pressure, then remove nozzle cap completely. Open Hydrant main valve completely. A continuous ow
of water, no matter how slight, indicates Hydrant is not properly isolated from the main water supply, and that problem must be corrected before any Hydrant disassembly can proceed. Disassembly of Hydrant with pressurized water acting against the main valve could result in unexpected ejection of Hydrant parts, debris or high-pressure water stream, which could cause serious bodily injury.
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-311 operating wrench, pliers.
1.
Remove Hold-Down Nut, Anti-Friction Washer and Operating Nut from Bonnet. Lubricate outside of Brass Sleeve and slide over threaded stem end to prevent O-ring damage. Unbolt Bonnet from Upper Barrel and remove. Remove Brass Sleeve.
4.
Attach Extension Barrel to Lower Barrel with solid Flange halves (without groove) and Bolts, being sure O-ring is in place.
2.
Unbolt Trafc Flange. Remove Upper
Barrel. Remove Upper Stem and Stem Coupling by removing the lower stainless steel Cotter Pin and stainless steel Clevis Pin.
5.
Assemble Upper Stem and Stem Cou­pling onto Extension Stem and retain it with stainless steel Clevis Pin and stain­less steel Cotter Pin.
NOTE: Make sure Stem Coupling is installed with “This End Up” towards the Upper Stem.
3.
Place Extension Stem and Extension Coupling on Lower Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin.
2
Page 3
MUELLER
®
Centurion
®
Series Fire Hydrant
Adding an Extension
!
CAUTION: Always ll the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is lled with lubricant under any other circumstances, excess lubricate can overll the Bonnet and create a pressure lock. This could result in damage to the seals or Bonnet or prevent proper
Hydrant operation.
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrenches, A-311 operating wrench.
6.
Attach Upper Barrel with Trafc Flange
Halves (with bevel on outer edge
downward) and Bolts; being sure Trafc
Flange O-ring* is in groove in Upper Barrel. Tighten Bolts to 60 ft-lbs.
9.
Torque Bonnet Bolts to 40-80 ft-lbs. Torque Hold-Down Nut to 200-300 ft-lbs. after Bonnet Bolts are tight. Open Gate Valve. Unscrew one Hose Nozzle Cap slightly to bleed air. Open Hydrant fully. Tighten Hose Nozzle Cap when
water starts owing and check all ange
connections for leaks. Turn Operating Nut to fully closed position and remove Hose Nozzle Cap to allow Barrel to drain. Replace Hose Nozzle Cap.
7.
Check Bonnet O-ring* for proper position and condition. Attach Brass Sleeve to Upper Stem and lubricate outside to protect O-ring Seals from thread damage. Place Bonnet onto Upper Barrel and assemble Bonnet Bolts only hand-tight. Remove Brass Sleeve. Reassemble Operating Nut, Anti-Friction Washer, and Hold-Down Nut (snug-tighten). Be sure O-ring Seals are in good condition at thread shoulder on outside of Hold-Down Nut and on inside where contact is made with Operating Nut.
8.
Remove Oil Filler Plug in side of Bonnet. Pour MUELLER Hydrant Lubricant into Oil Reservoir until it is level with Oil Filler Plug Hole. Replace Oil Filler Plug (see Lubrication section on page 8).
10.
Turn Operating Nut in closing direction to make sure Main Valve is closed tightly, then turn in opening direction approximately 1/4 turn to relieve tension on operating mechanism.
*To determine correct O-rings for Bonnet and Ground Line anges, which are similar in appearance: smaller diameter O-ring is used at Bonnet ange; larger at Ground line ange.
3
Page 4
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section (All Models Prior to 1962)
EQUIPMENT & TOOLS NEEDED – PPE: Safety shoes, safety vest, safety glasses, work gloves.
1
Tools:
/4” hex-head wrench, A-51 lubricating oil, A-311 operating wrench, A-367 brass sleeve.
1.
Remove four Bonnet Bolts and turn operating nut in the opening direction until free of stem. Remove Bonnet.
4.
Screw Extension Stem into Extension Coupling until it contacts Lower Stem. Align tongue and groove of stems with hole in Extension Stem Coupling. Screw Extension Stem Coupling upward until tongue and groove of
stems rmly lock together. Tighten with
wrench, then, screw in Set Screw in Extension Stem Coupling.
2.
Remove four bolts in stufng box.
Lubricate A-366 Brass Sleeve. Slide Sleeve over threaded area of stem to protect O-rings from damage by
threads. Lift stufng box off carefully.
Remove Brass Sleeve.
5.
Place new Stem Coupling Sleeve part onto Upper Stem. Screw new Stem Coupling part onto Lower Stem as far as threads permit.
Screw Upper Stem into Stem Coupling until it contacts the Lower Stem. Turn Stem Coupling and Upper Stem so that slot in Thimble aligns with the tongue and groove of stems. Hold Upper Stem in alignment and screw Stem Coupling upward until
tongue and groove of stems rmly lock
together. Tighten with wrench. With Stem Coupling in place, slide Sleeve downward so that lower end of sleeve surrounds upper end of Stem Coupling. Be sure
Sleeve projections t into Stem Coupling
slots. With Sleeve in place, tighten set screw in Sleeve.
3.
Unbolt Trafc Flange and remove Upper
Barrel.
Unscrew set screw in Sleeve. Screw Stem Coupling down against shoulder. Slide Sleeve up and unscrew Upper Stem from Stem Coupling. Unscrew Stem Coupling from Lower Stem. Screw Extension Stem Coupling down on Lower Stem against shoulder.
4
Page 5
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section (All Models Prior to 1962)
EQUIPMENT & TOOLS NEEDED – PPE: Safety shoes, safety vest, safety glasses, work gloves.
1
Tools:
/4” hex-head wrench, A-51 lubricating oil, A-311 operating wrench, A-367 brass sleeve.
6.
Attach Extension Barrel to Lower Barrel with solid Flange Halves (without groove) and bolts, being sure Flange Gasket is in place.
7.
Attach Upper Barrel to Extension Barrel
with Trafc Flange Halves (with groove)
and bolts, being sure Flange Gasket is in place.
Turn Operating Nut in the
10.
closing direction to make sure
Main Valve is closed, then turn in the opening direction approximately 1/4 turn to relieve tension on the operating mechanism.
8.
Check Stufng Box Gasket. Lubricate
A-366 Brass Sleeve. Slide Sleeve over threaded area of stem to protect O-rings from damage by threads.
Place Stufng Box in position and bolt
to barrel. Remove Brass Sleeve. Pour Mueller Hydrant Lubricant into Oil Reservoir until
3
/4” from top.
9.
Replace bonnet. Turn Operating Nut in closing direction to engage stem. If Bonnet has Filler Plug, make sure that the Filler Plug Hole is aligned with the offset portion of the Oil Reservoir. Bolt in place.
5
Page 6
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section (Sealed Oil Reservoir 1962 Style)
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
1.
Remove Weather Cap, Hold Down Nut and Operating Nut from Bonnet. Lubricate A-366 Brass Sleeve and slide over threaded stem end to prevent O-ring damage. Unbolt Bonnet from Upper Barrel and remove. Remove Brass Sleeve.
4.
Place new Stem Coupling Sleeve part onto Upper Stem. Screw new Stem Coupling part onto Lower Stem as far as threads permit. Screw Upper Stem into Stem Coupling until it contacts the Lower Stem. Turn Stem Coupling and Upper Stem so that slot in Thimble aligns with the tongue and groove of stems. Hold Upper Stem in alignment and screw Stem Coupling upward until tongue and groove
of stems rmly lock together. Tighten with
wrench. With Stem Coupling in place, slide Sleeve downward so lower end of sleeve surrounds upper end of Stem
Coupling. Be sure Sleeve projections t
into Stem Coupling slots. With Sleeve in place, tighten set screw in Sleeve.
2.
Unbolt Trafc Flange and remove
Upper Barrel. Unscrew set screw in Sleeve.
Screw Stem Coupling down against shoulder. Slide Sleeve up and unscrew Upper Stem from Stem Coupling. Unscrew Stem Coupling from Lower Stem. Screw Extension Stem Coupling down on Lower Stem against shoulder.
5.
Attach Extension Barrel to Lower Barrel with solid Flange Halves (without groove) and bolts, being sure Flange Gasket is in place.
3.
Screw Extension Stem into Extension Coupling until it contacts Lower Stem. Align tongue and groove of stems with hole in Extension Stem Coupling. Screw Extension Stem Coupling upward until tongue and groove of
stems rmly lock together. Tighten with
wrench, then screw in set screw in Extension Stem Coupling.
6.
Attach Upper Barrel to Extension Barrel
with Trafc Flange Halves (with groove)
and bolts, being sure Flange Gasket is in place.
6
Page 7
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section (Sealed Oil Reservoir 1962 Style)
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-367 brass sleeve, A-359 seat wrench, A-311 operating wrench.
Turn Operating Nut in the
9.
closing direction to make sure
Main Valve is closed, then turn in the opening direction approximately 1/4 turn to relieve tension on the operating mechanism.
7.
Check Bonnet Gasket. Attach the A­24099 Brass Sleeve, if it had been removed, to Upper Stem and lubricate outside to protect O-ring seals from thread damage. Place Bonnet onto Upper Barrel and assemble Bonnet Bolts only hand tight. Remove Brass Sleeve. Reassemble Operating Nut and remove Oil Plug in side of Bonnet. Pour Mueller Hydrant Lubricant into Oil
Reservoir until it is lled to the level of
the Oil Plug. Replace Oil Plug.
8.
Replace Hold Down Nut* being sure O-ring seals are in good condition at thread shoulder on outside of Hold Down Nut and on inside where contact is made with Operating Nut. Replace Weather Cap. Tighten Bonnet Bolts. Check gasket tightness by opening one hose cap slightly before opening Hydrant to bleed air. Open Hydrant
until barrel lls with water, tighten
Hose Cap, open Hydrant fully. Check gaskets, and then turn Operating Nut to fully closed position.
*Tighten hold down nut to 200-300 ft-lbs of torque. If torque wrench is not available, use a 3 lb hammer to strike the end of the A-311
wrench rmly two times to assure the nut is
properly tightened.
7
Page 8
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section with Steel Stem Coupling (Sealed Oil Reservoir 1962 Style)
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
1.
Remove Weather Cap, Hold Down Nut and Operating Nut from Bonnet. Lubricate A-366 Brass Sleeve and slide over threaded stem end to prevent O-ring damage. Unbolt Bonnet from Upper Barrel and remove. Remove Brass Sleeve.
4.
Assemble Upper Stem and Stem Coupling onto Extension Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin. Make
sure Stem Coupling is installed with notches towards the Lower Stem, words “THIS END UP” towards the Upper Stem.
2.
Unbolt Trafc Flange and remove Upper
Barrel. Remove Upper Stem and Stem Coupling by removing the lower stainless steel Cotter Pin and stainless steel Clevis Pin.
5.
Attach Extension Barrel to Lower Barrel with solid Flange Halves (without groove) and bolts, being sure Flange Gasket is in place.
3.
Place Extension Stem and Extension Coupling on Lower Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin.
6.
Attach Upper Barrel to Extension Barrel
with Trafc Flange Halves (with groove)
and bolts, being sure Flange Gasket is in place.
8
Page 9
®
MUELLER
Improved Fire Hydrant
Inserting Extension Section with Steel Stem Coupling (Sealed Oil Reservoir 1962 Style)
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-366 brass sleeve, A-359 seat wrench, A-311 operating wrench.
Turn Operating Nut in the
9.
closing direction to make sure
Main Valve is closed, then turn in the opening direction approximately 1/4 turn to relieve tension on the operating mechanism.
7.
Check Bonnet Gasket. Attach the A-366 Brass Sleeve, if it had been removed, to Upper Stem and lubricate outside to protect O-ring seals from thread damage. Place Bonnet onto Upper Barrel and assemble Bonnet Bolts only hand tight. Remove Brass Sleeve. Reassemble Operating Nut and remove Oil Plug in side of Bonnet. Pour Mueller Hydrant Lubricant into Oil Reservoir
until it is lled to the level of the Oil Plug.
Replace Oil Plug.
8.
Replace Hold Down Nut* being sure O-ring seals are in good condition at thread shoulder on outside of Hold Down Nut and on inside where contact is made with Operating Nut. Replace Weather Cap. Tighten Bonnet Bolts. Check gasket tightness by opening one hose cap slightly before opening Hydrant to bleed air. Open Hydrant
until barrel lls with water, tighten
Hose Cap, open Hydrant fully. Check gaskets, and then turn Operating Nut to full closed position.
*Tighten hold down nut to 200-300 ft-lbs of torque. If torque wrench is not available, use a 3 lb hammer to strike the end of the A-311
wrench rmly two times to assure the nut is
properly tightened.
9
Page 10
®
MUELLER
Modern Improved Fire Hydrant
Inserting Extension Section
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
1.
Remove Weather Cap, Hold Down Nut, Lock Washer and Operating Nut. Put on Brass Sleeve and lubricate to protect O-rings in operating housing.
4.
Place Extension Stem and Extension Coupling on Lower Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin.
2.
Unbolt Trafc Flange Clips and lift
hydrant over stem.
5.
Assemble Upper Stem and Stem Coupling onto Extension Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin. Make sure Stem Coupling is installed with notches towards the Lower Stem.
NOTE: “THIS END UP” stamped on coupling.
3.
Remove Upper Stem and Stem Coupling by removing the lower stainless steel Cotter Pin and stainless steel Clevis Pin.
6.
Attach Extension Barrel to Lower Barrel
with solid ange halves and bolts,
being sure Flange Gasket is in place (tighten bolts to 1,000 in-lbs).
10
Page 11
®
MUELLER
Modern Improved Fire Hydrant
Inserting Extension Section
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
7.
With lubricated Brass Sleeve on threads of Upper Stem and Upper Barrel Seal in position, lift Upper Barrel over Upper Stem and onto extension section
Attach Trafc Flange Clips and Trafc
Flange Clip Bolts loosely, face nozzles
in desired position and tighten Trafc
Flange Clip Bolts uniformly to 1,000 in-lbs.
10.
Remove Oil Filler Plug and add Mueller® Hydrant Lubricant until level with Filler Plug hole. Replace Oil Filler Plug and replace Weather Cap.
8.
With extension section and Hydrant securely bolted in place, remove Brass Sleeve, replace Operating Nut, Lock Washer, and Hold Down Nut.
Open Hydrant fully and loosen
11.
one Hose Nozzle Cap, to bleed
air. When barrel is lled with water,
tighten Nozzle Cap and check gaskets. Turn Operating Nut to fully closed position, loosen one nozzle cap to allow barrel to drain.
9.
Tighten Hold Down Nut to 100 ft-lbs and bend Lock Washer Ears over Hold
Down Nut ats in two places and over
Operating Housing in two places.
Turn Operating Nut in the
12.
closing direction to make sure
Main Valve is closed, then turn in the opening direction approximately 1/4 turn to relieve tension on the operating mechanism.
11
Page 12
®
MUELLER
107® Fire Hydrant
Inserting Extension Section
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
1.
Remove Bonnet Bolts and Nuts. Rotate Operating Nut in opening direction to fully opened position. This lifts Bonnet off the Upper Barrel. Rotate bonnet assembly counter-clockwise to detach Bonnet from Upper Stem threads. Lift off Bonnet, remove Bonnet Gasket.
4.
Assemble Upper Stem and Stem Coupling onto Extension Stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin. Make
sure Stem Coupling is installed with notches towards the Lower Stem, words “THIS END UP” towards the Upper Stem.
2.
Unbolt Trafc Flange and remove Upper
Barrel. Remove Upper Stem and Stem Coupling by removing the lower stainless steel Cotter Pin and stainless steel Clevis Pin.
5.
Attach Extension Barrel to Lower
Barrel with solid ange halves (without groove) and bolts, being sure ange
gasket is in place.
3.
Place Extension Stem and Extension Coupling on lower stem and retain it with stainless steel Clevis Pin and stainless steel Cotter Pin.
6.
Attach Upper Barrel to Extension Barrel
with Trafc Flange halves (with groove) and bolts, being sure Trafc Flange
Gasket is in place.
12
Page 13
®
MUELLER
107® Fire Hydrant
Inserting Extension Section
EQUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, brass hammer.
Turn Operating Nut in the
8.
closing direction to make sure
Main Valve is closed, then turn in the opening direction approximately 1/4 turn to relieve tension on the operating mechanism.
7.
Check Bonnet Gasket on top of Upper Barrel, replace if damaged. Check to see that Upper Stem threads are lubricated and Upper Stem Seal (O-ring) is not damaged. Check to be sure that the Operating Nut is in the fully open position, which is with the Stem Nut fully extended. Reassemble Bonnet Assembly to Upper Stem by rotating clockwise as far as possible, then back up only enough to align bolt holes, if needed. Rotate Operating Nut in closing direction, which lowers Bonnet Assembly onto Upper Barrel and allows bolts to be replaced. With all bolts in Bonnet, rotate Operating Nut using the same torque as normally used to close the Hydrant. Tighten all Bonnet Bolts and Nuts.
13
Page 14
Inserting Extension Sections
Notes
14
Page 15
Inserting Extension Section
Notes
15
Page 16
Water (U.S.)
1.800.423.1323
Reliable Connections
Copyright © 2016 Mueller Co., LLC. All Rights Reserved.
The trademarks, logos and service marks displayed in this document herein are the property of Mueller Co., LLC, its afliates or other third parties.
Products marked with a section symbol ( § ) are subject to patents or patent applications. For details, visit www.mwppat.com. These products are intended for use in potable water applications. Please contact your Mueller Sales or Customer Service Representative concerning any other application(s).
TM
www.muellercompany.com moreinfo@muellercompany.com
Water (Canada)
1.705.719.9965 www.muellercanada.com more-info@muellercanada.com
International
1.423.490.9555 www.mueller-international.com international@muellercompany.com
Form 10923 - Rev 09/17
Loading...