MTS Systems Level Plus Interface Manual

Level Plus
®
HART® Interface Manual
LP Series
Magnetostrictive Liquid Level Transmitters with Temposonics
®
Technology
2
HART® Interface Manual
LP Series
Table of contents
1. Contact information ....................................................................3
2. Terms and denitions .................................................................4
3. Introduction .................................................................................6
4. Safety instructions ......................................................................6
5. Quick start-up guide ...................................................................6
5.1 Before you begin ................................................................... 6
5.2 Quick start-up procedure ...................................................... 6
6. Display Menu ..............................................................................6
6.1 Operation Modes ................................................................... 6
6.1.1 Run Mode ...................................................................... 6
6.1.1 Program Mode ............................................................... 6
6.2 Display Diagram .................................................................... 7
6.3 Menu Structure ..................................................................... 7
7. Alarms .........................................................................................7
7.1 Software fault alarms ............................................................ 7
7.2 Hardware fault alarms ........................................................... 7
8. Error Codes (Faults) ....................................................................8
9. HART
®
interface ..........................................................................8
9.1 Analog setup software .......................................................... 8
9.1.1 Installing setup software ................................................ 8
9.1.2 General parameters ........................................................ 9
9.1.3 Process data ................................................................ 10
9.1.4 Output setup ............................................................... 10
9.1.4.1 Output ................................................................. 10
9.1.4.2 Calibrate .............................................................. 10
9.2 Handheld programming ...................................................... 10
9.3 Programming from the display ........................................... 10
9.3.1 Data from the device .................................................... 10
9.3.2 Calibrate ....................................................................... 11
9.3.3 Factory ........................................................................ 11
3
HART® Interface Manual
LP Series
1. Contact information
United States
General
Tel: +1-919-677-0100 Fax: +1-919-677-2343 E-mail: info.us@mtssensors.com
http://www.mtssensors.com
Mailing and shipping address
MTS Systems Corporation Sensors Division 3001 Sheldon Drive Cary, North Carolina, 27513, USA
Customer service
Tel: +1-800-633-7609 Fax: +1-800-498-4442 E-mail: info.us@mtssensors.com
Technical support and applications
24 Hour Emergency Technical Support Tel: +1-800-633-7609 e-mail: levelplus@mts.com
Germany
General
Tel.: +49-2351-9587-0 Fax: +49-2351-56491 e-mail: info.de@mtssensors.com
http://www.mtssensors.com
Mailing and shipping address
MTS Sensor Technologie, GmbH & Co. KG Auf dem Schüffel 9 D - 58513 Lüdenscheid, Germany
Technical support and applications
Tel.: +49-2351-9587-0 e-mail: info.de@mtssensors.com
http://www.mtssensors.com
Japan
General
Tel.: +81-42-775-3838 Fax: +81-42-775-5512 e-mail: info.jp@mtssensors.com
http://www.mtssensors.com
Mailing and shipping address
MTS Sensors Technology Corporation 737 Aihara-machi, Machida-shi Tokyo 194-0211, Japan
Technical support and applications
Tel.: +81-42-775-3838 Fax: +81-42-775-5512
4
HART® Interface Manual
LP Series
2. Terms and denitions
6A Heavy Oils
‘Generalized Crude Oils’, Correction of Volume to 60 °F against API Gravity.
6B Light Oils
‘Generalized Products’, Correction of Volume to 60 °F against API Gravity.
6C Chemical
‘Volume Correction Factors (VCF)’ for individual and special applica­tions, volume correction to 60 °F against thermal expansion coef­cients.
6C Mod
An adjustable temperature reference for dening VCF.
A
API Gravity
The measure of how heavy or light a petroleum liquid is compared to
water. Allowable values are 0 to 100 degrees API for (6A) and 0 to 85 degrees API for (6B).
D
DDA
‘Direct Digital Access’ – The proprietary digital protocol developed by
MTS for use in intrinsically safe areas.
Density
Mass divided by the volume of an object at a specic temperature. The
density value should be entered as lb / cu. ft..
E
Explosion proof
Type of protection based on enclosure in which the parts which can
ignite an explosive gas atmosphere are placed within, and which can withstand the pressure developed during an internal explosion of an ex­plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.
F
Flame proof
Type of protection based on enclosure in which the parts which can
ignite an explosive gas atmosphere are placed within and which can withstand the pressure developed during an internal explosion of an ex­plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.
FOUNDATION™ eldbus
An all digital, serial, two-way communications system that serves as
the base-level network in a plant or factory automation environment.
Developed and administered by the eldbus FOUNDATION™.
G
GOVI
‘Gross Observed Volume of the Interface’ – The total volume of the tank
occupied by the interface liquid. The GOVI is only given when mea­suring two liquids and is calculated by subtracting the volume of the product from the total volume of liquid in the tank (GOVT – GOVP).
GOVP ‘Gross Observed Volume of the Product’ – The total volume of the tank
occupied by the product liquid. When measuring only one liquid, it is also the total volume of liquid in the tank (GOVT). When measuring two liquids it is the total volume of liquid in the tank minus the volume of the interface liquid (GOVT – GOVI).
GOVT ‘Total Gross Observed Volume’ – The total volume of liquid in the tank.
When measuring only one liquid it is equal to the volume of the product (GOVP). When measuring two liquids it is equal to the volume of the product and interface liquids (GOVP + GOVI).
GOVU ‘Gross Observed Volume Ullage’ – the difference in volume between the
working capacity of a tank and the total volume in the tank (Working Capacity – GOVT).
H
HART
®
A Bidirectional communication protocol that provides data access
between intelligent eld instruments and host systems.
I
Interface
Noun; The measurement of the level of one liquid when that liquid is
below another liquid.
Interface Adj.; The Software Graphical User Interface (GUI) that allows the user
to access software protocols (HART®, DDA, MODBUS).
Intrinsic safety ‘Intrinsically safe’ - Type of protection based on the restriction of
electrical energy within apparatus of interconnecting wiring exposed to potentially explosive atmosphere to a level below that which can cause ignition by either sparking or heating effects.
5
HART® Interface Manual
LP Series
M
Mass
The property of a body that causes it to have weight in a gravitational
eld, calculated by density at the reference temperature multiplied by
the volume correction factor (Density * VCF).
MODBUS A serial communications protocol published by Modicon in 1979 for use
with its programmable logic controllers (PLCs). It has become a de fac­to standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices.
N
NEMA Type 4X
A product Enclosure intended for indoor or outdoor use primarily to
provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water; and to be undamaged by the formation of ice on the enclosure. They are not intended to provide protection against conditions such as internal condensation or internal icing.
NPT U.S. standard dening tapered pipe threads used to join pipes and
ttings.
NSVP ‘Net Standard Volume of the Product’ – The temperature corrected
volume for the product liquid in the tank, requires the transmitter to be ordered with temperature measurement capabilities. The NSVP is calculated by multiplying the volume of the product liquid by a volume correction factor based on temperature (GOVP * VCF).
R
Reference Temperature
The temperature at which the density measurement is given, the allow-
able values are 32 °F to 150 °F (0 °C to 66 °C).
S
Specic Gravity The density ratio of a liquid to the density of water at the same condi-
tions.
Sphere Radius The internal radius of the sphere that contains the liquid, the value is
used to calculate the volume along with the Sphere Offset.
Sphere Offset
An offset value that accounts for additional volume in a sphere from
non-uniform sphere geometry, the value is used to calculate the volume along with the Sphere Radius.
Strap Table
A table of measurement correlating the height of a vessel to the volume that is contained at that height. The transmitter can contain up to 100 points.
T
TEC
‘Thermal Expansion Coefcient’ - a value correlating the change in tem-
perature for an object with the change in its volume. Allowable values are 270.0 to 930.0. TEC units are in 10 E-6/Deg F.
Temperature Correction Method One of ve product correction methods used to correct the product
volume in the tank due to changes in temperature from 60 °F including (6A, 6B, 6C, 6C Mod, and Custom Table.
V
Volume Calculation Mode
One of two methods use to calculate volume measurements from level
measurements, including Sphere and Strap Table.
VCF ‘Volume Correction Factor’ – A table of measurements correlating
temperature points with correction factors for the liquids expansion/ contraction. The transmitter can contain up to 50 points.
W
Working Capacity
The maximum volume of liquid that the user desires for their vessel to
hold, typically 80% of the vessels maximum volume before overll.
6
HART® Interface Manual
LP Series
3. Introduction
3.1 Purpose and use of this manual
The content of this technical documentation and of its various annexes is intended to provide information on the HART® Interface of
the LP Series. All safety related information is in the product specic
operation manual.
3.2 Used symbols and warnings
Warnings are intended for your personal safety and for avoidance of damage to the described product or connected devices. In this documentation, safety information and warnings to avoid dangers that might affect the life and health of personnel or cause material damage
are highlighted by the preceding pictogram, which is dened below.
4. Safety instructions
4.1 Intended use
The purpose of this document is to provide detailed information on the protocol interface. All safety related information is in the product
specic operation manual. Consult the operation manual before
connecting to the level transmitter.
5. Quick start-up guide
5.1 Before you begin
Tools needed:
• 24 Vdc linear regulated power supply
• Current meter
5.2 Quick start-up procedure
1. Connect 24 Vdc power supply to Loop 1.
2. Turn on power supply.
3. Connect Current Meter to test pins on interconnect board.
4. Move the oat towards the tip of the pipe and verify 4 mA set point.
5. Move the oat towards the top of the pipe and verify 20 mA set point.
6. If using two oats, repeat steps 4 and 5 for second oat. Note both oats must be present or else the level transmitter will go into alarm.
Before starting the operation of the equipment read this documentation thoroughly and follow the safety information.
Symbol Meaning
NOTICE
This symbol is used to point to situations that may lead to material damage and/or personal injury.
7. Turn off power and disconnect power supply and current meter.
8. Install in tank.
6. Display Menu
All LP-Series liquid level transmitters are shipped with a Stylus (MTS Part # 404108) to be used for manipulating the display. For single and dual cavity housings, the Stylus is designed to allow for programming of the unit without removing the housing. When using the Stylus make sure to align the Stylus with the shape outline around the buttons in the same orientation. Failure to correctly align the Stylus can cause the display to not function properly.
Note:
Do not use any device other than the MTS Stylus to operate the display on the LP Series.
Note:
Improper use of the Stylus can cause the display to not function properly.
6.1 Operation Modes
The LP Series level transmitter runs in one of the following modes of operation. You can use these modes to calibrate and set up various operating parameters.
6.1.1 Run Mode
Run mode is the primary mode of operation. This mode will perform measurements, display data, and respond to HART
®
commands.
6.1.2 Program Mode
Program mode is the primary mode for commissioning and trouble­shooting the level transmitter. The full menu and available functions are shown in section 6.3 Menu Structure. To enter program mode use the Stylus and press the Enter Key as shown in section 6.2 Display Diagram. Program Mode is protected by a password to keep unwarranted chan­ges from occurring. The factory default password is 27513. When in program mode, remote communications are not functional. An automa­tic timeout feature is provided so that the transmitter does not remain inadvertently in program mode. The timeout is set for 1 minute before prompted for additional time. Total timeout is 2 minutes.
Note:
Whenever program mode is exited from the display the unit will reset itself to insure all changes have been accepted. The reset will take approximately 5 seconds before the level transmitter is able to respond to commands.
Note:
In program mode, the transmitter will not respond to incoming HART
®
commands. A busy error will be sent to the controller to notify the unit is in program mode. This function will prevent a user at a remote terminal from programming the unit while a user is accessing program mode from the display.
Note:
Output will vary depending on the location of the 4 and 20 mA set points.
7
HART® Interface Manual
LP Series
6.2 Display Diagram
Fig. 1 Display
UP Arrow – Used to move cursor on screen up and to increment num­ber DOWN Arrow – Used to move cursor on screen down and to decrease number SCROLL Arrow – Used to move cursor on screen to the right, cursor will cycle back ENTER Key – Used to Enter Program Mode, select Highlighted Item, and
Conrm Selection
EXIT Key – Hidden key in the middle of the display that is used to exit menu at any time MEASURED VARIABLE – The process variable that is selected to display. The display will automatically scroll between selected variables. MEASUREMENT – The numerical value for the MEASURED VARIABLE shown on the display. UNITs – Unit of measurement for the MEASURED VARIABLE shown on the display. TEMPERATURE – Average temperature for the product in the tank. Only shown if the level transmitter was purchased with temperature. NOTIFICATIONS – Four squares with letters. Top left square is blank. Top right square, A, will only show when there is an alarm. Toggle the UP Arrow key to view alarms. Bottom right square, F, will only show when there is a fault. Toggle the DOWN Arrow key to view error codes. Bottom left square, P, will only show when the units is being program­med remotely.
6.3 Menu Structure
Go to section 9.3 for more information about how to program the unit from the display.
• Data From Device  Display  Units
` Length Units ` Temp Units
 Set Points
` Prod LVR (4 mA) ` Prd URV (20 mA) ` Prd Current LRV ` Prd Current URV ` Int LRV (4 mA) ` Int URV (20 mA)
` Int Current LRV
` Int Current URV  Alarm Select  Signal Strength
` Prod Trig Lvl
` Int Trig Lvl
• Calibrate  Product Level
` Current Level ` Offset
 Interface Level
` Current Level ` Offset
• Factory  Settings
` Gradient ` Serial Number ` HW Revision ` SW Revision ` SARA Blanking ` Magnet Blanking ` Gain
` Min Trig Level  Temp Setup  Temp Enable
 No of Temp Float Cong
` Loop 1
` Loop 2  Damping
` Loop 1
` Loop 2  Auto Threshold  Reset to Factory
7. Alarms
MTS has two separate types of alarms featuring both a software fault alarm and a hardware fault alarm.
7.1 Software Fault Alarm
MTS offers a software fault alarm that will force the 4-20 mA output into an either a low or high alarm state. The default setting from the factory
is a low alarm state. The low alarm state is ≤ 3.6 mA and the high alarm state is ≥ 21 mA. The software fault alarm follows the recommendations
set forth by NAMUR NE 43. Typical faults that will cause a software fault
alarm are a missing oat, the oat in the inactive range, and the level transmitter looking for the wrong number of oats.
7.2 Hardware Fault Alarm
MTS offers a hardware fault alarm that will force the 4-20 mA output into a low alarm. The hardware low alarm is 3.2 mA. The hardware low alarm is triggered when the internal diagnostics of the level transmitter have detected a hardware issue with the 4-20 mA output.
8
HART® Interface Manual
LP Series
101 Missing
Magnet
• Verify Float Conguration is correct for the number of oats installed
• Verify Float(s) are not in inactive zone.
• Verify Auto Threshold is enabled.
• Cycle power to sensor. If proper operation is not restored, Contact Factory
102 Internal
Fault 1
Cycle power to sensor. If proper operation is not restored, Contact Factory
103 Internal
Fault 2
Cycle power to sensor. If proper operation is not restored, Contact Factory
104 Internal
Fault 3
Cycle power to sensor. If proper operation is not restored, Contact Factory
105 Lobe Fault 1 • Verify Auto Threshold is enabled
• Cycle power to sensor
• If proper operation is not restored, Con­tact Factory
106 Lobe Fault 2 • Verify Auto Threshold is enabled
• Cycle power to sensor
• If proper operation is not restored, Contact Factory
107 Delta Fault Contact Factory to discuss application.
108 Internal
Fault 4
Cycle power to sensor. If proper operation is not restored, Contact Factory
109 Peak Fault • Verify Auto Threshold is enabled
• Cycle power to sensor
• If proper operation is not restored, Contact Factory
110 Hardware
Fault 1
Cycle power to sensor. If proper operation is not restored, Contact Factory
111 Power Fault • Cycle power to sensor
• Verify Power Supply rating
• Verify wiring
• If proper operation is not restored, Contact Factory
112 Hardware
Fault 2
Cycle power to sensor. If proper operation is not restored, Contact Factory
113 Hardware
Fault 3
Cycle power to sensor. If proper operation is not restored, Contact Factory
114 Hardware
Fault 4
Cycle power to sensor. If proper operation is not restored, Contact Factory
115 Timing
Fault 1
Cycle power to sensor. If proper operation is not restored, Contact Factory
116 Timing
Fault 2
Cycle power to sensor. If proper operation is not restored, Contact Factory
117 Timing
Fault 3
Cycle power to sensor. If proper operation is not restored, Contact Factory
118 DAC Fault 1 Cycle power to sensor. If proper operation
is not restored, Contact Factory
119 DAC Fault 2 Cycle power to sensor. If proper operation
is not restored, Contact Factory
120 DAC Fault 3 Cycle power to sensor. If proper operation
is not restored, Contact Factory
Fault Code
Description Corrective Action Fault
Code
Description Corrective Action
121 DAC Fault 4 Cycle power to sensor. If proper operation
is not restored, Contact Factory
122 SPI Fault 1 Cycle power to sensor. If proper operation
is not restored, Contact Factory
123 SPI Fault 2 Cycle power to sensor. If proper operation
is not restored, Contact Factory
124 Setpoint
Fault
The analog setpoints are too close. Mini­mum distance is 150 mm (6 in.) for analog and 290 mm (11.5 in.) for SIL. Adjust programmed setpoints as needed. (Analog only) If proper operation is not restored, Contact Factory
125 Loop 1 Out
of Range
Verify that magnets are positioned within expected measuring range. Adjust pro­grammed setpoints as needed. (Analog only) If proper operation is not restored, Contact Factory
126 Loop 2 Out
of Range
Verify that magnets are positioned within expected measuring range. Adjust pro­grammed setpoints as needed. (Analog only) If proper operation is not restored, Contact Factory
127 EEPROM
Fault 1
Cycle power to sensor. If proper operation is not restored, Contact Factory
128 EEPROM
Fault 2
Cycle power to sensor. If proper operation is not restored, Contact Factory
129 Flash Failure Cycle power to sensor. If proper operation
is not restored, Contact Factory
130 Internal
Error
Cycle power to sensor. If proper operation is not restored, Contact Factory
8. Error Codes (Faults)
9. HART® Interface
MTS has tested and is compliant to HART® ITK 7.2. The device driver le is available for download from HART
®
Communication Protocol website at http://www.hartcomm.org or from MTS at
http://www.mtssensors.com. Programming via HART
®
can be done
either using the MTS Analog Setup Software via a HART
®
modem or a
handheld programmer.
9.1 Analog Setup Software
9.1.1 Installing Setup Software
Adjustments to the calibration and setup parameters of the HART® interface can be performed using the MTS LP Dashboard. The software can be run from any Windows 7 or newer OS using a HART
®
to USB
converter (MTS part # 380068).
Perform the following steps to install the setup software and establish communication:
1. Install setup software from the USB stick that came with the level transmitter or go to http://www.mtssensors.com to download the latest version.
9
HART® Interface Manual
LP Series
2. Connect level transmitter to HART® to USB converter, connect 24 Vdc power to the level transmitter, and connect the HART
®
to
USB converter to the PC. Example setup shown below.
Note:
Power must be on Loop 1 for HART
®
communication to work. Power does not have to be applied on Loop 2 for HART® to work. Power must be applied to Loop 2 to check current output.
Note:
HART
®
requires a load resistor to work correctly. Add a 250 Ohm resistor for proper communication. Some PLC cards will have built in load resistors.
Fig. 2 Example setup
3. Open setup software. Select HART
®
Protocol.
4. Select COM Port. Software will show active components. If you do not know which COM port to select, right click Computer on the desktop and select Properties. On the left hand side menu you can click Device Manager. In Device Manager click on the + sign next to Ports (COM & LPT) to view list. An error message will appear if HART
®
does not successfully connect.
9.1.2 General Parameters
The General Parameters selection in the Setup Software shows the basic setup for the level transmitter.
Manufacturer ID Code
The Manufacturer ID Code is a unique numerical code that is supplied to each HART
®
certified manufacturer. This parameter cannot be changed.
Device Code
The Device Code is a unique numerical code assigned to each HART® certified product. This parameter cannot be changed.
Device Serial Number
The Device Serial Number is the unique identifier for the unit from MTS and should not be changed. The serial number is used for tracking and determining spare parts.
Gradient
The gradient is a calibration factor that is unique for each transmitter. Typical values are between 8.9 and 9.2 µs/in.
Display Units
The Display Units has a drop down menu where the user can select Nor­mal, mA, or percent. Normal changes the display to show the enginee­ring units selected. mA changes the display to show the output in mA. Percent changes the display to show the output in percentage full.
Float 2
Float 2 allows the user to turn on or off the option of looking for a second float. Do not Enable this option if a second float is not present on the level transmitter or else the level transmitter will enter alarm. Float 2 does not enable a second loop unless the level transmitter was ordered with a second loop. Both float positions can be viewed via HART
®
over a
one loop transmitter.
Temperature
Temperature allows the user to turn on or off the option of measuring temperature. Temperature will not work if a temperature element was not ordered with the level transmitter from the factory. The Temperature will show on the display but will not change from 32° F (0° C).
Damping
Damping slows the rate of change for the output signal. It does not change the output but dampens how quickly the output follow the change in the float position. The standard rate of change would have the Damping set to 0.400 seconds.
Others
Length, Head Adder, and Display are not used by the LP Series. These are shown for backwards compatibility and should not be changed.
Fig. 3 General Parameters window
10
HART® Interface Manual
LP Series
9.1.3 Process Data
Fig. 4 Process data window
The Process Data section of the setup software allows the user to view the current output of the level transmitter in the engineering units and log data to a file.
9.1.4 Output Setup
The Output Setup section of the setup software allows the user to change the engineering units, mapping of variables to Loops, and set the 4 and 20 mA set points.
9.1.4.1 Output
Fig. 5 Ouput window
The Output allows the user to select the Temperature Units and Length Units. The Temperature units will only work if the level transmitter was ordered with temperature sensing capability. The Temperature and Length units will change on the display and over HART
®
communication. The Output Mapping can be changed by changing the selected variable for PV, SV, and TV. PV is mapped to Loop 1 and the selected process variable will modulate the Loop 1 current when selected. SV is mapped to Loop 2 and the selected process variable will modulate the Loop 2 current when selected. TV is not mapped to a Loop and is only viewable via HART
®
.
9.1.4.2 Calibrate
Fig. 6 Calibrate window
Calibrate allows the user to change the set points for levels and tempe­rature. The user can Read and Write the 4 mA (Zero or LRV) and 20 mA (Span or URV) independently for each variable. The values need to stay within the active range of the level transmitter or else the 4 and 20 mA set points cannot be reached and a tank can overflow or run dry. Do not modify the Offset field.
9.2 Handheld Programming
MTS is working on creating a handheld DD file. Once it is released this section will be updated with more information. Please contact Technical Support with any questions.
9.3 Programming from the Display
The factory password for entering the display is 27513.
9.3.1 Data from Device
Display
Allows the user to select if the display shows engineering units, mA, or percent full.
Units
Allows the user to change the selected Length Units and/or Temperature Units.
Set Points
Allows the user to change the 4 and 20 mA set points in two ways. The user can select Prd LRV (4 mA), Prd URV (20 mA), Int LRV (4 mA), and or Int URV (20 mA) to enter the desired location for the set points in engineering units. Alternatively the user can use Prd Current LRV, Prd Current URV, Int Current LRV, and/or Int Current URV and move the float to the desired location of the set points while setting the 4 and 20 mA locations.
Alarm Select
Allows the user to choose between a High Alarm (>21 mA) and a Low Alarm (<3.6 mA) for software alarm faults. The default setting is Low Alarm. MTS complies with NAMUR NE 43.
Signal Strength
Allows the user to view the strength of the return signal for the product
11
HART® Interface Manual
LP Series
float (Prod Trig Lvl) and the Interface float (Int Trig Lvl). If the Interface float is not active no signal can be viewed.
9.3.2 Calibrate
Product Level
Allows the user to change the level in engineering units if needed. Typically this is not needed for analog output units. The user should use the Current Level selection and enter the current position of the float. The user is advised not to use the Offset feature without help from Technical Support.
Interface Level
Allows the user to change the level in engineering units if needed. Typically this is not needed for analog output units. The user should use the Current Level selection and enter the current position of the float. The user is advised not to use the Offset feature without help from Technical Support.
9.3.3 Factory
Settings
Menu section that contains factory parameters. Do not edit these para­meters without talking to Technical Support.
Gradient
The gradient is a calibration factor that is unique for each transmitter. Typical values are between 8.9 and 9.2 µs/in.
Serial Number
The Serial Number is the unique identifier for the unit from MTS and should not be changed. The serial number is used for tracking and determining spare parts.
SARA Blanking
Initial blanking distance from the head of the level transmitter. Do not change.
Magnet Blanking
Blanking distance between two floats. Do not change.
Gain
Measurement of how large an interrogation signal is used. Do not change without Technical Support.
Min Trig Level
Threshold level for return signal to qualify as a valid signal and not noise.
Temp Setup
Allows the user to turn the temperature measurement on or off. Turning it on will not cause the temperature to work if no temperature measure­ment was ordered.
No. of Temp
Change the number of temperature points the level transmitters is looking for. Changing this number does not change the number of temperature measurement points that were ordered or whether or not temperature measurement was ordered.
Float Cong
Allows the user to enable or disable the product float (Loop 1) and/or the interface float (Loop 2). The first float measured by the electronics will be used as the product float. If the interface float is turned on and there is no second float both loops will go into alarm.
Damping
Damping slows the rate of change for the output signal. It does not change the output but dampens how quickly the output follow the change in the float position. The standard rate of change would have the Dam­ping set to 3276. Loop 1 and Loop 2 can be dampened independently
Auto Threshold
Do not disable.
Reset to Factory
Allows the user to reset the electronics to the original factory settings. This should be used to return the electronics to a known good state when troubleshooting.
12
Document Part Number:
551699 Revision A (EN) 10/2016
Reg.-No. 003095-QN
LOCATIONS
LEGAL NOTICES
USA MTS Systems Corporation Sensors Division
3001 Sheldon Drive Cary, N.C. 27513, USA Tel. +1 919 677-0100 Fax +1 919 677-0200 info.us@mtssensors.com www.mtssensors.com
JAPAN MTS Sensors Technology Corp.
737 Aihara-machi, Machida-shi, Tokyo 194-0211, Japan Tel. + 81 42 775-3838 Fax + 81 42 775- 5512 info.jp@mtssensors.com www.mtssensors.com
FRANCE MTS Systems SAS
Zone EUROPARC Bâtiment EXA 16 16/18, rue Eugène Dupuis 94046 Creteil, France Tel. + 33 1 58 4390-28 Fax + 33 1 58 4390-03 info.fr@mtssensors.com www.mtssensors.com
GERMANY MTS Sensor Technologie GmbH & Co. KG
Auf dem Schüffel 9 58513 Lüdenscheid, Germany Tel. + 49 2351 9587-0 Fax + 49 2351 56491 info.de@mtssensors.com www.mtssensors.com
CHINA MTS Sensors
Room 504, Huajing Commercial Center, No. 188, North Qinzhou Road 200233 Shanghai, China Tel. +86 21 6485 5800 Fax +86 21 6495 6329 info.cn@mtssensors.com www.mtssensors.com
ITALY MTS Systems Srl. Sensor Division
Via Camillo Golgi, 5/7 25064 Gussago (BS), Italy Tel. + 39 030 988 3819 Fax + 39 030 982 3359 info.it@mtssensors.com www.mtssensors.com
MTS, Temposonics and Level Plus are registered trademarks of MTS Systems Corporation in the United States; MTS SENSORS and the MTS SENSORS logo are trademarks of MTS Systems Corporation within the United States. These trademarks may be protected in other countries. All other trademarks are the property of their respective owners. Copyright © 2016 MTS Systems Corporation. No license of any intellectual property rights is granted. MTS reserves the right to change the information within this document, change product designs, or withdraw products from availability for purchase without notice. Typographic and graphics errors or omissions are unintentional and subject to correction. Visit www.mtssensors.com for the latest product information.
Loading...