MTS Sensors Temposonics T Operation Manual

TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval /
Safety SIL 2 capable
Operation Manual
Temposonics
®
Magnetostrictive Linear Position Sensors
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
Table of contents
1. Introduction .......................................................................................................................................................3
1.1 Purpose and use of this manual .................................................................................................................................................................... 3
1.2 Used symbols and warnings .........................................................................................................................................................................3
2. Safety instructions ...............................................................................................................................................3
2.1 Intended use ..................................................................................................................................................................................................3
2.2 Forseeable misuse .........................................................................................................................................................................................4
2.3 Installation, commissioning and operation ....................................................................................................................................................4
2.4 Safety instructions for use in explosion-hazardous areas .............................................................................................................................5
2.5 Warranty........................................................................................................................................................................................................6
2.6 Return ........................................................................................................................................................................................................... 6
3. Identification......................................................................................................................................................7
3.1 Order code of Temposonics
®
TH ....................................................................................................................................................................7
3.2 Nameplate (example) ....................................................................................................................................................................................9
3.3 Approvals ...................................................................................................................................................................................................... 9
3.4 Scope of delivery ........................................................................................................................................................................................... 9
4. Product description and commissioning ................................................................................................................... 10
4.1 Functionality and system design .................................................................................................................................................................10
4.2 Styles and installation of Temposonics
®
TH ................................................................................................................................................ 11
4.3 Magnet installation ...................................................................................................................................................................................... 17
4.4 Electrical connection ...................................................................................................................................................................................19
4.5 Frequently ordered accessories .................................................................................................................................................................. 25
5. Operation........................................................................................................................................................ 28
5.1 Getting started .............................................................................................................................................................................................28
5.2 Programming and configuration .................................................................................................................................................................28
6. Maintenance and troubleshooting .......................................................................................................................... 35
6.1 Error conditions, troubleshooting ................................................................................................................................................................35
6.2 Maintenance ................................................................................................................................................................................................ 35
6.3 Repair ..........................................................................................................................................................................................................35
6.4 List of spare parts .......................................................................................................................................................................................35
6.5 Transport and storage .................................................................................................................................................................................35
7. Removal from service / dismantling ........................................................................................................................ 35
8. Technical data Temposonics
®
TH SIL 2 ..................................................................................................................... 36
9. Technical data Temposonics
®
TH standard ................................................................................................................ 39
10. Declaration of conformity of standard version ........................................................................................................... 41
11. Declaration of conformity of SIL 2 version ............................................................................................................... 42
12. Appendix ....................................................................................................................................................... 43
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
1/ The term qualied technical personnel characterizes persons who:
are familiar with the safety concepts of automation technology applicable to the particular project
are competent in the eld of electromagnetic compatibility (EMC)
have received adequate training for commissioning and service operations
are familiar with the operation of the device and know the information required
for correct operation provided in the product documentation
1. Introduction
1.1 Purpose and use of this manual
Before starting the operation of Temposonics® position sensors, read this documentation thoroughly and follow the safety information. For further details on SIL 2 refer to MTS Sensors SIL 2 safety manual (part number: 551504). Keep the manual for future reference!
The content of this technical documentation and of its appendix is intended to provide information on mounting, installation and com­missioning by qualied automation personnel
1
or instructed service technicians who are familiar with the project planning and dealing with Temposonics
®
sensors.
1.2 Used symbols and warnings
Warnings are intended for your personal safety and for avoidance of damage to the described product or connected devices. In this doc­umentation, safety information and warnings to avoid dangers that might affect the life and health of operating or service personnel or cause material damage are highlighted by the preceding pictogram, which is dened below.
Symbol Meaning
NOTICE
This symbol is used to point to situations that may lead to material damage, but not to personal injury.
2. Safety instructions
2.1 Intended use
This product must be used only for the applications dened under item 1 to item 4 and only in conjunction with the third-party devices and components recommended or approved by MTS Sensors. As a prerequisite of proper and safe operation, the product requires correct transport, storage, mounting and commissioning and must be operat­ed with utmost care.
1. The sensor systems of all Temposonics
®
series are intended exclusively for measurement tasks encountered in industrial, commercial and laboratory applications. The sensors are consid­ered as system accessories and must be connected to suitable evaluation electronics, e.g. a PLC, IPC, indicator or other electron­ic control unit.
2. The sensor’s surface temperature class is T4.
3. The EU-Type Examination Certicates and Certicates of Compli-
ance have to be taken into account including any special condition dened therein.
4. The position sensor may be used in zones (ATEX, IECEx) and Classes, Zones and Divisions (CEC, NEC) according to chapter 8 and chapter 9. Any use of this product outside of these approved areas will void the warranty and all manufacturer’s product re­sponsibilities and liabilities. For non-hazardous areas MTS Sen­sors recommends to use the version N (not approved).
Class and Division Concept
Ex-Atmosphere Class Division Group
Gas-Ex Class I Div. 1 A*, B, C, D
Gas-Ex Class I Div. 2 A, B, C, D
Dust-Ex Class II/III Div. 1 E, F, G
Dust-Ex Class II/III Div. 2 E, F, G
*Cl. I Div. 1 Gr. A not valid for Canada
Zone Concept
Ex-Atmosphere Zone Category Explosion
group
Gas-Ex In the bafe between Zone 0 Up to IIC
(at the rod)
Gas-Ex Zone 1 2G IIA, IIB, IIC
Gas-Ex Zone 2 3G IIA, IIB, IIC
Dust-Ex Zone 21 2D IIIA, IIIB, IIIC
Dust-Ex Zone 22 3D IIIA, IIIB, IIIC
Gas-Ex In the bafe between Zone 0
and
Up to IIC (at the rod)
Zone 1 or Zone 2 Up to IIC
(at the connection chamber)
Gas-Ex In the bafe between Zone 0
and
Up to IIC (at the rod)
Dust-Ex Zone 21 or Zone 22 Up to IIIC
(at the connection chamber)
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
2.2 Forseeable misuse
Forseeable misuse Consequence
Lead compensating currents through the enclosure
The sensor will be damaged
Use sensor without external fuse in Zone 0 or as SIL 2 version (in Zone 0, Zone 1 / 21)
In case of failure, the sensor might overheat
Use a fuse with more than 125 mA
In case of failure, the sensor might overheat
Wrong sensor connection The sensor will not work
properly or will be destroyed
Operate the sensor out of the operating temperature range
No signal output The sensor can be damaged
Power supply is out of the dened range
Signal output is wrong / no signal output /
the sensor will be damaged Position measurement is inuenced by an external magnetic eld
Signal output is wrong
Cables are damaged Short circuit – the sensor can
be destroyed / sensor does not
respond Spacers are missing / are installed in a wrong order
Error in position measurement
Wrong connection of ground / shield
Signal output is disturbed
The electronics can be damaged
Use of a magnet that is not certied by MTS Sensors
Error in position measurement
Do not step on the sensor. The sensor might be damaged.
Do not alter the sensor afterwards. The sensor might be damaged.
2.3 Installation, commissioning and operation
The position sensors must be used only in technically safe condi­tion. To maintain this condition and to ensure safe operation, installa­tion, connection and service, work may be performed only by qualied technical personnel, according to IEC 60079-14, TRBS 1203, Canadi­an Electrical Code (CEC) and National Electrical Code (NEC) and local regulations. If danger of injury to persons or of damage to operating equipment is caused by sensor failure or malfunction, additional safety measures such as plausibility checks, limit switches, EMERGENCY STOP systems, protective devices etc. are required. In the event of trouble, shut down the sensor and protect it against accidental operation.
Safety instructions for commissioning
To maintain the sensor’s operability, it is mandatory to follow the instructions given below.
1. Follow the specications given in the technical data.
2. Ensure that equipment and associated components used in a
hazardous environment are selected and installed in compliance with regulations governing the geographical location and facility. Only install equipment that complies with the types of protection relevant to the applicable Classes, Zones, Divisions and Groups.
3. In explosive atmospheres use only such auxiliary components that meet all requirements of the local and national standards.
4. The potential equalisation of the system has to be established according to the regulations of erection applicable in the respective country of use (VDE 0100 part 540; IEC 364-5-54).
5. Sensors from MTS Sensors are approved only for the intended use in industrial environments (see chapter “2.1 Intended use” on page 3). Contact the manufacturer for advice if aggressive substances are present in the sensor environment.
6. Measures for lightning protection have to be taken by the user.
7. The user is responsible for the mechanical protection of the sensor.
8. The sensor may be used only for xed installations with permanently wired cables. The user shall ensure that cables and cable glands correspond to the risk assessment of the hazardous application as well as to thermic, chemical and mechanical environmental conditions. The user is also responsible for the required strain relief. When selecting the sealing, the maximum thermal load of the cables must be taken into account.
9. The user is responsible for meeting all safety conditions as outlined by:
Installation instructions
Local prevailing standards and regulations
Safety manual (document part no. 551504) for SIL 2 capable
sensor version
10. Any parts of the equipment which got stuck (e.g. by frost or corrosion) may not be removed by force if potentially explosive atmosphere is present.
11. The surface temperatures of equipment parts must be kept clearly below the ignition temperature of the foreseeable air/ dust mixtures in order to prevent the ignition of suspended dust.
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
How to ensure safe commissioning
1. Protect the sensor against mechanical damage during installation and operation.
2. Do not use damaged products and secure them against uninten­tional commissioning. Mark damaged products as being defective.
3. Prevent electrostatic charges.
4. Do not use the sensor in cathodic systems for corrosion
protection. Do not allow parasitic currents on the sensor housing.
5. Switch off the supply voltage prior to disconnecting or connecting the connectors.
6. Connect the sensor very carefully and pay attention to the polarity of connections, power supply as well as to the shape and duration of control pulses.
7. Cable entry temperature and branching point temperature may reach 104 °C (219 °F) and 116 °C (241 °F) respectively. Select suitable cable and entry device.
8. For eld wiring, use cables suitable for the service temperature range of −40 °C (−40 °F) to +116 °C (241 °F).
9. Do not open when energized. Open the sensor only as shown in Fig. 7 on page 13.
10. A seal shall be installed within 18" of the enclosure (for NEC / CEC only).
11. Use only approved power supplies of Category II according to IEC 61010-1.
12. Ensure that the specied permissible limit values of the sensor for operating voltage, environmental conditions, etc. are met.
13. Make sure that:
the sensor and associated components were installed
according to the instructions
the sensor enclosure is clean
all screws (only those of quality 6.8, A2-50 or A4-50 are
allowed) are tightened according to specied fastening torque in Fig. 7
the cable glands certied according to the required
hazardous area classication and IP protection are tightened according to the manufacture’s specications
surfaces limiting the joint shall not be machined or painted
subsequently (ameproof enclosure)
surfaces limiting the joint have not been provided with a seal
(ameproof enclosure)
the magnet does not grind on the rod. This could cause
damage to the magnet and the sensor rod. If there is contact between the moving magnet (including the magnet holder) and the sensor rod, make sure that the maximum speed of the moving magnet is less or equal 1 m/s.
14. Ground the sensor via one of the two ground lugs. Both the sensor and the moving magnet including magnet holder must be connected to protective ground (PE) to avoid electrostatic discharge (ESD).
15. Before applying power, ensure that nobody’s safety is jeopardized by starting machines.
16. Check the function of the sensor regularly and provide documentation of the checks (see chapter “6.2 Maintenance” on page 35).
2.4 Safety instructions for use in explosion-hazardous areas
The sensor has been designed for operation inside explosion-hazard­ed areas. It has been tested and left the factory in a condition in which it is safe to operate. Relevant regulations and standards have been observed. According to the marking (ATEX, IECEx, CEC, NEC, KCs, EACEx, Japanese approval) the sensor is approved only for operation in dened hazardous areas (see chapter “2.1 Intended use” on page
3). The SIL 2 version cannot be adjusted by the customer.
When do you need an external fuse?
How to install a T-Series sensor in Zone 0 according to the guide­lines (ATEX, IECEx, CEC, NEC, EAC Ex, KCs Japanese approval)
1. Install an external fuse in compliance with IEC 127 outside the Ex-atmosphere. Connect it upstream to the equipment. Current: 125 mA
2. Install the sensor housing in Zone 1, Zone 2, Zone 21 or Zone 22. Only the rod section (for version D, G, and E) can extend into Zone 0.
3. Follow the safety regulations detailed in IEC/EN 60079-26, ANSI/ISA 60079-26 (12.00.03), ANSI/ISA/IEC/EN 60079-10-1 and JNIOSH-TR-46-2 to ensure isolation between Zone 0 and Zone 1.
4. When installing the TH sensor in the boundary wall for Zone 0, the corresponding requirements in ANSI/ISA/IEC/EN 60079-26 and ANSI/ISA/IEC/EN 60079-10-1 have to be noticed. Thereby the screw-in thread is to be sealed gas tightly (IP67) according to ANSI/ISA/IEC/EN 60079-26 and ANSI/ISA/IEC/EN 60079-10-1.
Zone / Div. T-Series standard sensor T-Series SIL 2 sensor
Zone 0 (rod only)
External fuse required External fuse required
Zone 1 / 21 No additional fuse External fuse required
Zone 2 / 22 No additional fuse No additional fuse
Div. 1 External fuse
recommended
External fuse recommended
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
2.5 Warranty
MTS Sensors grants a warranty period for the Temposonics
®
position sensors and supplied accessories relating to material defects and faults that occur despite correct use in accordance with the intended application
2
. The MTS Sensors obligation is limited to repair or replacement of any defective part of the unit. No warranty can be provided for defects that are due to improper use or above average stress of the product, as well as for wear parts. Under no circumstances will MTS Sensors accept liability in the event of offense against the warranty rules, no matter if these have been assured or expected, even in case of fault or negligence of the company. MTS Sensors explicitly excludes any further warranties. Neither the company’s representatives, agents, dealers nor employees are authorized to increase or change the scope of warranty.
2.6 Return
For diagnostic purposes, the sensor can be returned to MTS Sensors. Any shipment cost is the responsibility of the sender
2
. For a corre-
sponding form, see chapter “12. Appendix” on page 43.
2/ See also applicable MTS Sensors terms of sales and delivery on
www.mtssensors.com
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
3. Identication
3.1 Order code of Temposonics® TH
T H 1 N
a b c d e f g h i
a Sensor model
T H
Rod
b Design
Enclosure Type 3: TH rod sensor with housing material stainless steel 1.4305 (AISI 303) and rod material stainless steel 1.4306 (AISI 304L)
M
Threaded ange with at-face (M18×1.5-6g)
N
Threaded ange with raised-face (M18×1.5-6g)
S
Threaded ange with at-face (¾"-16 UNF-3A)
T
Threaded ange with raised-face (¾"-16 UNF-3A)
Enclosure Type 3X: TH rod sensor with housing material stainless steel 1.4404 (AISI 316L) and rod material stainless steel 1.4404 (AISI 316L)
F
Threaded ange with at-face (¾"-16 UNF-3A)
G
Threaded ange with raised-face (¾"-16 UNF-3A)
W
Threaded ange with at-face (M18×1.5-6g)
d Connection type
C 0 1
Side connection with thread ½"-14 NPT (All versions)
C 1 0
Top connection with thread ½"-14 NPT (All versions)
M
0 1
Side connection with thread M16×1.5-6H (Version E & N)
M
1 0
Top connection with thread M16×1.5-6H (Version E & N)
N
0 1
Side connection with thread M20×1.5-6H (All versions)
N
1 0
Top connection with thread M20×1.5-6H (All versions)
N
F 1
Side connection with thread M20×1.5-6H (Version E & N)
Note: Not available for SIL 2 version!
See next page
e
*/ Non standard stroke lengths are available; must be encoded in 5 mm / 0.1 in. increments
c Stroke length
X X X X M
0025…1500 mm (SIL 2)
X X X X
U
001.0…060.0 in. (SIL 2)
.
Standard stroke length (mm)* Ordering steps
25 … 500 mm 5 mm
500 … 750 mm 10 mm
750…1000 mm 25 mm
1000…1500 mm 50 mm
Standard stroke length (in.)* Ordering steps
1 …20 in. 0.2 in.
20 …30 in. 0.4 in.
30 …40 in. 1.0 in.
40 …60 in. 2.0 in.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
c Stroke length (continued)
X X X X M
0025…7620 mm (standard)
X X X X
U
001.0…300.0 in. (standard)
.
Standard stroke length (mm)* Ordering steps
25 … 500 mm 5 mm
500 … 750 mm 10 mm
750…1000 mm 25 mm
1000…2500 mm 50 mm
2500…5000 mm 100 mm
5000…7620 mm 250 mm
Standard stroke length (in.)* Ordering steps
1 … 20 in. 0.2 in.
20 … 30 in. 0.4 in.
30 … 40 in. 1.0 in.
40…100 in. 2.0 in.
100…200 in. 4.0 in.
200…300 in. 10.0 in.
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
NOTICE
Use magnets of the same type (e.g. 2 ring magnets with part no. 201 542-2 ) for multi-position measurement.
e Operating voltage
1
+24 VDC (−15 / +20 %)
f
Version
(see chapter 8 and chapter 9 for further information)
D
Ex db and Ex tb (A/F 55)
E
Ex db eb and Ex tb (A/F 55) US & CA approval: Ex nA /NI (for Zone 2 and 22)
(Note: US & CA approval is only available for SIL 2 version)
G
Ex db and Ex tb (A/F 60) US & CA approvals: Explosionproof (XP)
(Note: Group A is not available for Canada)
N
Not approved
g Functional safety type
N
Not approved
S
SIL 2 (with certicate and manual)
h Additional option type
N
None
i Output
1 output with 1 position magnet Output 1 (position magnet 1) (Available outputs for SIL 2: A01 and A11)
A
0 1
4…20 mA
A
1 1
20…4 mA
A 2
1
0…20 mA
A 3
1
20…0 mA
2 outputs with 1 position magnet Output 1 (position magnet 1) + output 2 (position magnet 1) Notice: Not available for SIL 2 version!
A
0
3
4…20 mA 20…4 mA
2 outputs with 2 position magnets Output 1 (position magnet 1) + output 2 (position magnet 2) Notice: Not available for SIL 2 version!
A
0
2
4…20 mA 4…20 mA
A
1
2
20…4 mA 20…4 mA
A 2 2
0…20 mA 0…20 mA
A 3 2
20…0 mA 20…0 mA
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
3.2 Nameplate (example)
3.3 Approvals
See chapter “8. Technical data Temposonics
®
TH SIL 2” on page
36ff and chapter “9. Technical data Temposonics
®
TH standard” on
page 39 ff..
3.4 Scope of delivery
TH (rod sensor):
Sensor
Fig. 1: Example of a nameplate of a TH sensor (SIL 2 version)
Fig. 2: Example of a nameplate of a TH sensor (standard version)
Fig. 3: Label for japanese approval
NOTICE
For a detailed overview of the certications, see www.mtssensors.com
CML 17JPN1072X
MTS Sensors
労(平297月)検
THN0080MC011DSNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T130 °C Ga/Db
18-KA4BO-0247X 18-KA4BO-0248X
−40 °C ≤ Ta ≤ 85 °C IP66 / IP67
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db IIC T4 X Da/Db Ex tb IIIC T130 °C X
THN0080MC011ESNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db eb IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T130 °C Ga/Db
18-KA4BO-0249X 18-KA4BO-0250X
Class I, Div. 2, Groups A, B, C, D T4 Class II/III, Div. 2, Groups E, F, G T130 °C
Ex nA / AEx nA IIC T4 Gc
Ex tc / AEx tc IIIC T130 °C Dc
−40 °C ≤ Ta ≤ 80 °C IP66 / IP67
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db eb IIC T4 X Da/Db Ex tb IIIC T130 °C X
THN0080MC011GSNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T 130 °C Ga/Db
18-KA4BO-0247X 18-KA4BO-0248X
Class I, Div. 1, Groups A, B, C, D T4 Class II/III, Div. 1, Groups E, F, G T130 °C Class I, Zone 0/1 AEx d / Ex d IIC T4 Class II/III, Zone 21 AEx tb / Ex tb IIIC T130 °C Group A is not approved for Canada
−40 °C ≤ Ta ≤ 85 °C IP66 / IP67
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db IIC T4 X Da/Db Ex tb IIIC T130 °C X
Variant with flameproof connection chamber Version D
Variant with increased safety connection chamber Version E
Variant with flameproof / explosionproof connection chamber Version G
THN0080MC011DNNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T130 °C Ga/Db
18-KA4BO-0247X 18-KA4BO-0248X
−40 °C ≤ Ta ≤ 75 °C IP66 / IP67
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db IIC T4 X Da/Db Ex tb IIIC T130 °C X
THN0080MC011ENNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db eb IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T130 °C Ga/Db
18-KA4BO-0249X 18-KA4BO-0250X
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db eb IIC T4 X Da/Db Ex tb IIIC T130 °C X
−40 °C ≤ Ta ≤ 75 °C IP66 / IP67
THN0080MC011GNNA11
In: 24 VDC 100 mA YofC: 26/2018 Out: 20-4 mA Enclosure type 3 S/N: 18260255
CML ATEX1090X IECEx CML 16.0039X
II 1/2G Ex db IIC T4 Ga/Gb II 1G/2D Ex tb IIIC T 130 °C Ga/Db
18-KA4BO-0247X 18-KA4BO-0248X
Class I, Div. 1, Groups A, B, C, D T4 Class II/III, Div. 1, Groups E, F, G T130 °C Class I, Zone 0/1 AEx d / Ex d IIC T4 Class II/III, Zone 21 AEx tb / Ex tb IIIC T130 °C Group A is not approved for Canada
−40 °C ≤ Ta ≤ 75 °C IP66 / IP67
Датчик серии Т ОС ВО ЗАО ТИБР №TC RU С-DE.ГБ08.B.01976 Ga/Gb Ex db IIC T4 X Da/Db Ex tb IIIC T130 °C X
Variant with flameproof connection chamber Version D
Variant with increased safety connection chamber Version E
Variant with flameproof / explosionproof connection chamber Version G
10
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
4.1 Functionality and system design
Product designation
Position sensor Temposonics® T-Series
Sensor model
Temposonics® TH (rod sensor)
Stroke length
Stroke length SIL 2 version: 25…1500 mm (160 in.)
Stroke length standard version: 25
7620 mm (1300 in.)
Output signal
Analog
Application
Temposonics® position sensors are used for measurement and conver­sion of the length (position) variable in the elds of automated systems and mechanical engineering. The T-Series sensors are designed for installation in a raised or at­face anged hydraulic cylinder, for use as an open-air position sensor or as a liquid level sensor with the addition of a oat.
Principle of operation and system construction
The absolute, linear position sensors provided by MTS Sensors rely on the company’s proprietary Temposonics
®
magnetostrictive technology, which can determine position with a high level of precision and robustness. Each Temposonics
®
position sensor consists of a ferromagnetic waveguide, a position magnet, a strain pulse converter and supporting electronics. The magnet, connected to the object in motion in the application, generates a magnetic eld at its location on the waveguide. A short current pulse is applied to the waveguide. This creates a momentary radial magnetic eld and torsional strain on the waveguide. The momentary interaction of the magnetic elds releases a torsional strain pulse that propagates the length of the waveguide. When the ultrasonic wave reaches the end of the waveguide it is converted into an electrical signal. Since the speed of the ultrasonic wave in the waveguide is precisely known, the time required to receive the return signal can be converted into a linear position measurement with both high accuracy and repeatability.
Fig. 4: Time-of-ight based magnetostrictive position sensing principle
4. Product description and commissioning
T-Series models
The T-Series is available in four variations, three of which are hazardous classications:
Flameproof housing with ameproof connection chamber (version D)
Flameproof (explosionproof) housing with ameproof (explosion-
proof) connection chamber (version G)
Flameproof housing with increased safety connection chamber (version E)
Non-hazardous (version N)
All of these variations are available in two types of hardware / software, SIL 2 compliant and standard, both in 4…20 mA and 20…4 mA out­put. The sensor assembly is offered in 1.4305 (AISI 303) stainless steel and in 1.4404 (AISI 316L). Associated with hazardous rating the sensor meets IP66 / IP67. For non-hazardous environments the sensor meets IP66, IP67, IP68, IP69K and NEMA 4X.
5
Sensing element
(Waveguide)
Position magnet (Magnetic fi eld)
Torsional strain pulse converter
4
Current pulse generates magnetic fi eld
Interaction with position magnet fi eld generates torsional strain pulse
Torsional strain
pulse propagates
Strain pulse detected by converter
Time-of-fl ight converted
into position
1
2
3
11
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
Fig. 5: Temposonics® TH with ring magnet
4.2 Styles and installation of Temposonics® TH
Threaded ange with raised-face
Version D & G
2.5
(0.1)
(2.01)
Null zone
51
Sensor electronics housing
132.5 (5.22)
Magnet
Ø 10 ± 0.13
(Ø 0.39 ± 0.01)
Refer to “Table 1” for
“TH rod sensor threaded flange type references”
A
B C
Version D
77 (3.03)
83.8 (3.29) 55 (2.17)
Version G
82 (3.23)
89.2 (3.51) 60 (2.36)
A
B
C
Version D: A/F 55 Version G: A/F 60
See order code section “d” for connection types
M18×1.5-6g:
Ø 23.8 ± 0.2 (Ø 0.94 ± 0.01)
¾"-16 UNF-3A:
Ø 25.4 ± 0.2 (Ø 1 ± 0.01)
22.5
(0.89)
Stroke length
Standard: 25…7620 (1…300)
SIL 2: 25…1500 (1…60)
Dead zone
63.5 (2.5) / 66* (2.6)*
* Stroke length > 5000 mm (196.9 in.)
on page 12
Version E & N
2.5
(0.1)
83.8
(3.29)
73
(2.87)
55
(2.17)
Null zone
51
(2.01)
Sensor electronics housing
112.5 (4.43)
Magnet
Ø 10 ± 0.13
(Ø 0.39 ± 0.01)
Refer to “Table 1” for
“TH rod sensor threaded flange type references”
A/F 55
See order code section “d” for connection types
M18×1.5-6g:
Ø 23.8 ± 0.2 (Ø 0.94 ± 0.01)
¾"-16 UNF-3A:
Ø 25.4 ± 0.2 (Ø 1 ± 0.01)
22.5
(0.89)
Stroke length
Standard: 25…7620 (1…300)
SIL 2: 25…1500 (1…60)
Dead zone
63.5 (2.5) / 66* (2.6)*
* Stroke length > 5000 mm (196.9 in.)
Threaded ange with at-face
Version D & G
Null zone
51
(2.01)
Sensor electronics housing
132.5
(5.22)
83.8
(3.29)
55
(2.17)
73
(2.87)
Sensor electronics housing
112.5 (4.43)
Null zone
51
(2.01)
Refer to “Table 1” for
“TH rod sensor threaded flange type references”
Refer to “Table 1” for
“TH rod sensor threaded flange type references”
Ø 10 ± 0.13
(Ø 0.39 ± 0.01)
Ø 10 ± 0.13
(Ø 0.39 ± 0.01)
A
B C
Version D
77 (3.03)
83.8 (3.29) 55 (2.17)
Version G
82 (3.23)
89.2 (3.51) 60 (2.36)
A
B
C
Version D: A/F 55 Version G: A/F 60
A/F 55
Magnet
Magnet
See order code section “d” for connection types
See order code section “d” for connection types
22.5
(0.89)
22.5
(0.89)
Stroke length
Standard: 25…7620 (1…300)
SIL 2: 25…1500 (1…60)
Stroke length
Standard: 25…7620 (1…300)
SIL 2: 25…1500 (1…60)
Dead zone
63.5 (2.5) / 66* (2.6)*
Dead zone
63.5 (2.5) / 66* (2.6)*
* Stroke length > 5000 mm (196.9 in.)
* Stroke length > 5000 mm (196.9 in.)
on page 12
Version E & N
83.8
(3.29)
55
(2.17)
73
(2.87)
Sensor electronics housing
112.5 (4.43)
Null zone
51
(2.01)
Refer to “Table 1” for
“TH rod sensor threaded flange type references”
Ø 10 ± 0.13
(Ø 0.39 ± 0.01)
A/F 55
Magnet
See order code section “d” for connection types
22.5
(0.89)
Stroke length
Standard: 25…7620 (1…300)
SIL 2: 25…1500 (1…60)
Dead zone
63.5 (2.5) / 66* (2.6)*
* Stroke length > 5000 mm (196.9 in.)
on page 12
on page 12
Controlling design dimensions are in millimeters and measurements in ( ) are in inches
12
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
Table 1: TH rod sensor threaded ange type references
Fig. 6: Temposonics
®
TH connection options
Threaded ange type
Description
Threaded ange
F
Threaded ange with at-face Stainless steel 1.4404 (AISI 316L)
¾"-16 UNF-3A
G
Threaded ange with raised-face Stainless steel 1.4404 (AISI 316L)
¾"-16 UNF-3A
M
Threaded ange with at-face Stainless steel 1.4305 (AISI 303)
M18×1.5-6g
N
Threaded ange with raised-face Stainless steel 1.4305 (AISI 303)
M18×1.5-6g
S
Threaded ange with at-face Stainless steel 1.4305 (AISI 303)
¾"-16 UNF-3A
T
Threaded ange with raised-face Stainless steel 1.4305 (AISI 303)
¾"-16 UNF-3A
W
Threaded ange with at-face Stainless steel 1.4404 (AISI 316L)
M18×1.5-6g
Side connection C01 / N01 / NF1 (with adapter) / M01 (without adapter)
Magnet
Connection length 22 mm (0.87 in.) for version D & G 18 mm (0.7 in.) for version E & N
Side connection
C01 / N01:
Connector on 6 different positions at 60° each
NF1:
Connector on 4 different positions at 60° each
Top connection C10 / N10 (with adapter) / M10 (without adapter)
Top connection
Top connection
Magnet
Connection length 22 mm (0.87 in.) for version D & G 18 mm (0.7 in.) for version E & N
13
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
Fig. 7: Temposonics® TH exploded view drawing
NOTICE
Connect cable to sensor
See page 22 ff. for more details.
Change orientation of cable bushing (C01, M01, N01, NF1)
Loosen the ve hexagonal screws M4 (A/F 3) and remove the upper lid (Fig. 7). Then loosen the six hexagonal screws M4 (A/F 3) of the connection adapter (Fig. 7). Change the orientation of the connector on six different positions at 60° each. Note the example on page
22 ff..
Part Fastening torque
Screw M4×10
1.2 Nm
Screw M4×40
1.2 Nm
Earthing connection: M5×8 for mounting
2.5 Nm
Version D & G
Connection adapter
O-ring
Upper lid
Version E & N
Connection adapter
Upper lid
O-ring
14
Temposonics® TH Analog ATEX / IECEx / CEC / NEC / KCs / EAC Ex certied / Japanese approval / Safety SIL 2 capable
Operation Manual
Fig. 8: Temposonics® TH Zone classication
NOTICE
Seal sensor according to ingress protection IP67 between Zone 0 and Zone 1.
Version D & G (example: Threaded fl ange with raised-face) Flameproof (explosionproof) housing with fl ameproof (explosionproof) connection chamber Version D: ATEX / IECEx / EAC Ex / Japanese Approval Version G: ATEX / IECEx / CEC / NEC / EAC Ex / Japanese Approval
Zone 1 Zone 0
Magnet
Version E (example: Threaded fl ange with raised-face) Flameproof housing with increased safety connection chamber SIL 2: ATEX / IECEx / CEC / NEC / EAC Ex / Japanese Approval Standard: ATEX / IECEx / EAC Ex / Japanese Approval
Zone 1 Zone 0
Magnet
Loading...
+ 30 hidden pages