MTL Instruments ZoneSentinel Specifications

• Enhanced redundancy built into each
module
• Thermal and short circuit fusing
• Replaceable bolt-in modules
• UL 1449 3rd Edition Listed
• Type 1 and Type 2 Models
• 15 year product warranty
technical datasheet
ZoneSentinel Series
100kA surge capacity for distribution boards and small service entrance locations
The ZoneSentinel Series is engineered specifically for application at distribution boards and small service entrance locations. ZoneSentinel devices provide cost effective, high capacity power surge protection and, when used at a local panel in combination with a ZoneMaster at the service entrance, provide the lowest suppression voltages available today.
ZoneSentinel units offer a 100kA surge handling capability with protection be-tween
Line to Neutral, Line to Ground, Line to Line and Neutral to Ground and no restriction to the amount of load current. Thermal and short circuit fusing mechanisms are also included as an additional safety feature.
ZoneSentinel is modular in construction with individual modules bolted to a large surge return plate to minimize transient impedance. These modules, with a UL 94-5 rated plastic casing, are supplied mounted within a durable, corrosion resistant, NEMA 4X rated enclosure which can easily be drilled for cable access. ZoneSentinel units are easy to wall mount and flush mounting is also an option, should this be required. Individual modules are available upon request.
LED status indication is supplied with ZoneSentinel units as standard - normally open/normally closed contacts change state to indicate a fault. These contacts can be employed in a variety of applications from turning on lights remote from the surge protector, to interfacing with intelligent building management systems.
An optional remote monitoring unit is available for the ZoneSentinel range, capable of monitoring the status of all panel mounted surge protectors in the facility. This unit provides audio and visual indication of protector status in one compact wall mounting case. Other features of the remote monitoring unit include a test switch which checks the monitoring circuitry and an audio alarm silence switch.
The optional power filter, for the Type 2 ZoneSentinel range, which is tested to ANSI/ IEEE C62.41 and is UL 1283 listed, has a noise attenuation of just 75dB at 100KHz to 100MHz. The filter module will attenuate 6kV transients down to a mere 200V without the support of other surge components.
All ZoneSentinel units are UL 1449 3rd Edition Listed. Models with 20kA I
meet UL96A Master Label requirements.
ratings
n
901-132 Rev N 041011
www.mtl-inst.com enquiry@mtl-inst.com
SPECIFICATION
All figures typical at 77°F (25°C) unless otherwise stated
Maximum continuous operating voltage
120V — 140Vac 277V — 320Vac
Lines protected
L-N 50kA , L-G 50kA, L-L 100kA, N-G 50kA
Duty cycle performance (8/20µs)
50,000A >4 impulses 10,000A >6,000 impulses 100A infinite
Impulse current for class I (I
20kA (10/350µs)
Long duration current pulse (10/1,000µs) capability
3,600A (tested)
Ambient temperature limits
-40°F to +185°F (working)
-40°C to +85°C (working)
Humidity
95% RH (non-condensing)
Enclosure
NEMA 1, 2, 3, 3S, 4, 4X, 12 & 13 (IP66)
Terminals
2 AWG (32mm2)
Mounting
Surface mount by 0.31” (8mm) diameter holes
Indication
Continuous visual status monitoring Green LED Lit = Full protection Red LED Lit = Reduced (Standby) OR
No protection
Green LED out = No power to protector
Remote contacts
NO/NC
Weight
4 lbs (1.8Kg)
Dimensions
Enclosure – see Figure 1
EMC compliance
BS EN 60950: 1992 BS EN 61000-6-2: 1999
imp
)
Maximum
Model
ZS12100 100 120/240 Split Type 1 20kA 200kA 600 456V 550V Split phase 3-wire
ZS12101 100 120/208 Type 1 20kA 200kA 600 456V 550V Three phase 4-wire
ZS12102 100 120/240 HL Type1 20kA 200kA 600
ZS12104 100 277/480 Type 1 10kA 200kA 1200 825V 950V Three phase 4-wire
ZS12107 100 220/380 Type 1 10kA 200kA 1200 825V 950V Three phase 4-wire
ZS12108 100 240/415 Type 1 10kA 200kA 1200 825V 950V Three phase 4-wire
ZS12100X 100 120/240 Split Type 2 10kA 100kA 600 456V 550V Split phase 3-wire
ZS12101X 100 120/208 Type 2 10kA 100kA 600 456V 550V Three phase 4-wire
ZS12102X 100 120/240 HL Type2 10kA 100kA 600
ZS12104X 100 277/480 Type 2 10kA 100kA 1200 825V 950V Three phase 4-wire
ZS12107X 100 220/380 Type 2 10kA 100kA 1200 825V 950V Three phase 4-wire
ZS12108X 100 240/415 Type 2 10kA 100kA 1200 825V 950V Three phase 4-wire
* Tested as per ANSI/IEEE C62.45; IEC 61643-1 U Filter option not available with Type 1 models
surge
current
I
(kA)
max
Working
Voltage (V)
UL1449 Product
Type
= 6kV
oc
Short
UL 3rd
Circuit
Current
Rating (SCCR)
Edition
VPR
(V)
1200
1200
I
n
Limiting
Voltage
@3kA @10kA
456V
550V
825V
950V
456V
550V
825V
950V
Phase Types
Three phase 4-wire
High Leg Delta
Three phase 4-wire
High Leg Delta
EMI/RFI POWER FILTER - TYPE 2 MODELS ONLY
Limiting voltage
200V (@ 3kA 8/20µs)
Maximum attenuation (typical)
-75dB (100kHZ to 100MHz)
OPTIONAL REMOTE MONITORING UNIT
ZM11101 — Battery operated
TO ORDER SPECIFY -
Model number - as per table
Add suffix F for flush mount options
(The X suffix indicates an EMI/RFI filter - standard on Type 2 models - not available on Type 1 models)
EUROPE (EM EA): +44 ( 0)1582 723633 THE AMER ICAS: +1 800 835 7075 ASIA-PACIF IC: +65 6 64 5 9888
enquiry@mtl-inst.com csinfo@mtl-inst.com sales.mtlsing@cooperindustries.com 901-132 Rev N 041011
Figure 1 Dimensions
APPROVALS
Country Standard/Authority Approved for Product
United States UL1449 3rd Edition / UL AC power product ZS12100,
United States &
UL1449 3rd Edition / UL AC power product ZS12100X,
Canada
The given data is only in tended as a product des cription and should not b e regarded as a legal warranty o f properties or guarantee. I n the interest of further te chnical deve lopments, we rese rve the right to m ake design chan ges.
ZS12101,ZS12102, ZS12104, ZS12107, ZS12108
ZS12101X,ZS12102X, ZS12104X, ZS12107X, ZS12108X