MTL Instruments ZoneMaster Operating Manual

CONNECTING LEADS
Connect the suppressor as shown in the installation diagram. Refer to page 5 for recommended cable dressing. Connect the terminals within the suppressor to the load side of 60A breakers within the panel.
RECOMMENDED WIRE GAUGE
Minimum of 8 AWG Maximum of 4 AWG ( for ease of dressing)
LENGTH OF CONNECTING LEADS
The longer the connecting leads between the the ZoneMaster and power panel, the higher the residual transient voltage.
RECOMMENDED MAXIMUM: 19” (500mm) IDEALLY: 10” (250mm)
RECOMMENDED CABLE DRESSING
Each 10” (250mm) increase in cable length; increases clamping volt­age by 25V per 1000A surge current discharged.
• BIND THE PHASE NEUTRAL AND GROUND CONDUCTORS TIGHTLY, OVER THE ENTIRE RUN FROM THE SUPPRESSOR TO THE SERVICE PANEL.
• ALWAYS USE THE SHORTEST LENGTH OF CONNECTING CABLE POSSIBLE.
4 5
DIMENSIONS
INTRODUCTION
60A
N
L2
L1
L1 L2
G
N
This document explains how to install the ZoneMaster Series of AC Panel Surge Protective Devices.
INSTALLATION INSTRUCTIONS
Warning: T erminals marked L1, L2, L3, N, GND (where relevant) must
be connected respectively to phase(s) neutral and ground. Failure to comply may result in danger or damage. See corresponding diagrams for proper connections.
INSTALLATION DESCRIPTION
ZoneMaster units are connected in parallel (or in “shunt” across) the supply to be protected. The connecting cable does not carry the sup­ply current, only the current associated with suppressing the transient overvoltage.
MOUNTING
The units should be mounted as close as possible to the panel to be protected. See (page 4) on Connecting Lead lengths. Conduit, preferably metallic, is to be installed from the suppressor to the panel. Drill holes in the ZoneMaster enclosure only in the designated areas as shown in recommended cable dressing illustrations (page 5). Mount the unit in the appropriate location using the mounting holes provided on the enclosure.
ZONEMASTER
Confi guration
and Schematic Connection Diagrams
120/240V SPLIT PHASE 3W
INCORRECT INSTALLATION WILL IMPAIR THE EFFECTIVENESS OF THE AC PANEL PROTECTORS.
Particularly important is the length of the connecting leads (see page 4).
2
7
Loading...
+ 2 hidden pages