MTL Instruments WWIP-N Specifications

Technical data
MTL surge protection
MTL WWIP-N range
October 2015 EPS WWIP-N rev1
Transmitter protection for water/wastewater industries
Corrosion resistant water/wastewater field
instrument protection
Protects 2 wire instruments
Easy and direct mounting — screws into
spare conduit entry
Parallel connection avoids introduction of any
resistance into loop
High Performance low cost protection
10 year product warranty
The WWIP-N range of surge protection devices uniquely provide a
level of protection for 2 wire field-mounted instruments that is far in excess of the optional transient protection facilities available from the transmitter manufacturers - without involving any additional wiring, conduit modifications or other expensive extras.
The WWIP-N range consists of high-power, solid-state electronics and a gas-filled discharge tube (GDT) capable of diverting 10kA impulses. Specially designed for the water/wastewater industry with the whole unit encased in a corrosion resistant ANSI 316 stainless steel housing. The units are threaded for the common conduit entries used on field instruments. The WWIP-N is available for 1/2” NPT threaded entries.
Installation can easily be carried out retrospectively to existing installations. The WWIP-N is screwed into any unused conduit entry on the field instrument case and flying leads are connected to the terminal block (+ve, -ve) and the internal earth stud. The WWIP-Ns operate without in any way affecting normal operation - passing ac or dc signals without attenuation while diverting surge currents safely to earth and clamping output voltages to specific levels.
The all-important earthing connection is made to the local casing of the transmitter with no separate earth connection or ground stake at the transmitter being needed. In operation, the WWIP-N makes sure that the transmitter electronics are never exposed to damaging transients between lines or between lines and casing/earth. Any surge current appearing as a series-mode or common-mode transient is converted into a common-mode voltage - whereupon the transmitter electronics are temporarily raised to some higher voltage level before ‘floating’ down automatically (and without damage) to resume normal operation.
Measurement Technology Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2015 MTL All Rights Reserved Publication No. EPS WWIP-N rev1 131015 October 2015
1
MTL WWIP-N range
October 2015
SPECIFICATION
Maximum surge current
10kA peak current (8/20μs waveform)
Leakage current
Less than 10μ A at max. working voltage
Working voltage
24- 48VDC
Bandwidth 1MHz Resistance No resistance introduced into loop Ambient temperature limits
-40°C to +8 5°C (-40°F to +185°F) (working)
-40°C to +8 5°C (-40°F to +185°F) (storage)
Model WWIP-N
Nominal Voltage
Rated Voltage (MCOV)
Nominal Current
Nominal Discharge Current (8/20µs)
Max. Discharge Current (8 /20µs)
Lightning Impulse Current (10/350µs)
Residual Voltage @ i
Voltage Protection Level @ 1kV/µs
Bandwidth
Capacitance
Series Resistance
Operation Temperature Range -40ºC to +85º C
Category Tested A2, B2, C1, C2, C3, D1
Overstressed Fault Mode in=3kA 12k A
Impulse Durability (8/20µs) 10k A
Degree of Protection IP66
AC Durability 1Arms, 5 T
Service Conditions 80kPa -160kPa, 5%-95% RH
sn
U
U
i
I
max
I
imp U
U
f
I
sn
Humidity
5% to 95% RH (non-condensing) Electrical connections
3 flying leads (line1, line 2 & earth) Wire size: 32/0.2 (1.0mm2, 18 AWG) Lead length: 250mm (minimum)
Casing
ANSI 316 stainless steel hexagonal bar stock, male thread
Threads
1/2” NPT
Weight
175 g ( 6. 2oz)
Dimensions
See figure 1
n
c
n
24- 48V
58V
N/A
3kA
10k A
1.2kA
p
p
G
C
R
95V, L-G 500V
<76V
1MHz
100 pF
N/A
TO ORDER SPECIFY: WWIP-N
2
Measurement Technology Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com
© 2015 MTL All Rights Reserved Publication No. EPS WWIP-N rev1 131015 October 2015
Figure 1: Dimensions
EUROPE (EMEA):
+44 (0)1582 723633 mtlenquiry@eaton.com
THE AMERICAS:
+1 800 835 7075 mtl-us-info@eaton.com
ASIA-PACIFIC:
+65 6 645 9888 sales.mtlsing@eaton.com
The given d ata is only intended as a p roduct descrip tion and shoul d not be regarde d as a legal warrant y of properties or gu arantee. In the int erest of further technical developments, we reserve the right to make de sign changes.